0100 br 0801
TRANSCRIPT
-
7/29/2019 0100 Br 0801
1/3
Selective CoordinationStreamlining System Design
Make the most of your energySM
-
7/29/2019 0100 Br 0801
2/3
22
Smart design and expert guidance for
meeting regulatory requirements
Schneider Electric offers an online Selective Coordination Analysis Tool
that assists users in selecting coordinated breakers on two- or three-tier
systems. Visit www.schneider-electric.us/go/consultantsand look for
the Selective Coordination Analysis Tool under Resources.
Achieving Selective CoordinationDesigning a coordinated electrical distribution system requires knowledge
about the application and circuit breakers being specied. Considering selective
coordination early in the design phase will make the process easier and more
cost-eective.
Conducting a comprehensive short-circuit current study and an overcurrent
coordination study o the electrical power system is the only true method o
achieving selective coordination and equipment protection. The ollowing actions
help simpliy the creation o compliant systems that meet NEC requirements orselective coordination.
Step One: Short-Circuit Current StudyShort-circuit current studies consist o determining the prospective short-circuit currents available at all points in the system, when ed rom both
the normal and alternate power sources. It is helpul to label the nodes othe system with prospective current levels to aid in proper selection o the
circuit breakers.
Step Two: OvercurrentCoordination StudyThe overcurrent coordination study is a comparison o the time it takes the
individual devices to operate when certain levels o normal or abnormal current
pass through the protective devices. The objective o a coordination study isto determine the characteristics, ratings, and settings o overcurrent protective
devices that help ensure the minimum unaulted load is interrupted when
the protective devices isolate a ault or overload anywhere in the system. At
the same time, the devices and settings selected should provide satisactory
protection against overloads on the equipment and interrupt short circuits asrapidly as possible.
Step Three: Short-CircuitCoordination TablesTime-current curves graphically represent the trip time compared to currentlevels or a si ngle protective device. In an electrical system, each circuit is ed by
two or more circuit breakers rom the source to the branch (load). During a ault
which causes a circuit breaker to operate in its instantaneous tripping region,
the circuit breaker adds a dynamic impedance to the circuit. This can aect the
tripping times o upstream circuit breakers and it is impossible to chart theseinteractions on a single time-current curve.
Much like the use manuacturers use ratio tables, Schneider Electric publishes
short-circuit coordination tables to provide advanced inormation on the
interaction o circuit breakers to allow appropriate selection.
These tables should be consulted when ove
the instantaneous trip characteristics o twobreakers is observed on their time-current c
Short-circuit coordination tables provide the
levels o coordination between two circuit b
in a series. Taking into account dynamic imp
where circuit breakers limit the prospective fcurrent that upstream circuit breakers regist
downstream ault, the level o coordination b
two circuit breakers in series may be greater
what their individual time-current characterist
indicate. By using our coordination tables, ahigher levels o selective coordination is pos
Additional Design Resources
From the expertise o our ConsultingEngineer Specialists to downloadable w
papers rom our Design Resource Cente
www.schneider-electric.us/go/consulta
Schneider Electric can provide expert
technical advice to aid in the developmo compliant system designs. Additiona
we provide our circuit breaker tested
combinations to electrical engineer
sotware manuacturers, making them
available on time-current curve overlayseasier device selection and system des
FPO
Dynamic Impedance Effect Between Circuit Breakers
FPO
Certain electrical power system
designs need to ensure that the
selection and setting o protective
devices be done in such a manner as
o cause the smallest possible portion
o the system to be de-energized
due to an abnormal condition. In
a selectively coordinated system,
only the circuit breaker that directly
supplies the overloaded/aulted part
o the system will trip, limiting the
service interruption to only the circuitexperiencing the problem and not
shutting down the larger portion o the
power system.
CB B1, CB PM1Coordination through 2.0 kA
21.6 kA
1CB PM
CB B1
Actual Tested Combination
CB B1 and
CB PM1coordinate
up to theavailable
fault currentof 25 kA,
despite whattime-currentcurves show,
due todynamic
impedanceeffects.
10 100
1K
10K
100K
TIMEINSECONDS
100
1K
10
K
100K10
0.01
0.10
1
10
100
1000
0.01
0.10
1
10
100
1000
CURRENT IN AMPERES
-
7/29/2019 0100 Br 0801
3/3
Meeting Selective Coordination
Code RequirementsSchneider Electric delivers the industry experience, technical knowledge,application expertise, market-ocused products, and expert servicesupport to meet your selective coordination design needs.
For more information
Contact us today or your next selective coordination design project at
www.schneider-electric.us/go/consultants
November 2012
2 0 1 2 S c h n e i d e r E l e c t r i c
A l l R i g h t s R e s e r v e d
S c h n e i d e r E l e c t r i c a n d M a k e t h e m o s t o f y o u r e n e
r g y a r e t r a d e m a r k s o w n e d b y S c h n e i d e r E l e c t r i c I n d u s t r i e s S A S o r i t s a f f i l i a t e d
Document Number 0100BR0801R10/12
Schneider Electric USA
1415 S. Roselle Road
Palatine, IL 60067
Tel: 847-397-2600
Fax: 847-925-7500
www.schneider-electric.com/us