0100 br 0801

Upload: flores-jesus

Post on 04-Apr-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 0100 Br 0801

    1/3

    Selective CoordinationStreamlining System Design

    Make the most of your energySM

  • 7/29/2019 0100 Br 0801

    2/3

    22

    Smart design and expert guidance for

    meeting regulatory requirements

    Schneider Electric offers an online Selective Coordination Analysis Tool

    that assists users in selecting coordinated breakers on two- or three-tier

    systems. Visit www.schneider-electric.us/go/consultantsand look for

    the Selective Coordination Analysis Tool under Resources.

    Achieving Selective CoordinationDesigning a coordinated electrical distribution system requires knowledge

    about the application and circuit breakers being specied. Considering selective

    coordination early in the design phase will make the process easier and more

    cost-eective.

    Conducting a comprehensive short-circuit current study and an overcurrent

    coordination study o the electrical power system is the only true method o

    achieving selective coordination and equipment protection. The ollowing actions

    help simpliy the creation o compliant systems that meet NEC requirements orselective coordination.

    Step One: Short-Circuit Current StudyShort-circuit current studies consist o determining the prospective short-circuit currents available at all points in the system, when ed rom both

    the normal and alternate power sources. It is helpul to label the nodes othe system with prospective current levels to aid in proper selection o the

    circuit breakers.

    Step Two: OvercurrentCoordination StudyThe overcurrent coordination study is a comparison o the time it takes the

    individual devices to operate when certain levels o normal or abnormal current

    pass through the protective devices. The objective o a coordination study isto determine the characteristics, ratings, and settings o overcurrent protective

    devices that help ensure the minimum unaulted load is interrupted when

    the protective devices isolate a ault or overload anywhere in the system. At

    the same time, the devices and settings selected should provide satisactory

    protection against overloads on the equipment and interrupt short circuits asrapidly as possible.

    Step Three: Short-CircuitCoordination TablesTime-current curves graphically represent the trip time compared to currentlevels or a si ngle protective device. In an electrical system, each circuit is ed by

    two or more circuit breakers rom the source to the branch (load). During a ault

    which causes a circuit breaker to operate in its instantaneous tripping region,

    the circuit breaker adds a dynamic impedance to the circuit. This can aect the

    tripping times o upstream circuit breakers and it is impossible to chart theseinteractions on a single time-current curve.

    Much like the use manuacturers use ratio tables, Schneider Electric publishes

    short-circuit coordination tables to provide advanced inormation on the

    interaction o circuit breakers to allow appropriate selection.

    These tables should be consulted when ove

    the instantaneous trip characteristics o twobreakers is observed on their time-current c

    Short-circuit coordination tables provide the

    levels o coordination between two circuit b

    in a series. Taking into account dynamic imp

    where circuit breakers limit the prospective fcurrent that upstream circuit breakers regist

    downstream ault, the level o coordination b

    two circuit breakers in series may be greater

    what their individual time-current characterist

    indicate. By using our coordination tables, ahigher levels o selective coordination is pos

    Additional Design Resources

    From the expertise o our ConsultingEngineer Specialists to downloadable w

    papers rom our Design Resource Cente

    www.schneider-electric.us/go/consulta

    Schneider Electric can provide expert

    technical advice to aid in the developmo compliant system designs. Additiona

    we provide our circuit breaker tested

    combinations to electrical engineer

    sotware manuacturers, making them

    available on time-current curve overlayseasier device selection and system des

    FPO

    Dynamic Impedance Effect Between Circuit Breakers

    FPO

    Certain electrical power system

    designs need to ensure that the

    selection and setting o protective

    devices be done in such a manner as

    o cause the smallest possible portion

    o the system to be de-energized

    due to an abnormal condition. In

    a selectively coordinated system,

    only the circuit breaker that directly

    supplies the overloaded/aulted part

    o the system will trip, limiting the

    service interruption to only the circuitexperiencing the problem and not

    shutting down the larger portion o the

    power system.

    CB B1, CB PM1Coordination through 2.0 kA

    21.6 kA

    1CB PM

    CB B1

    Actual Tested Combination

    CB B1 and

    CB PM1coordinate

    up to theavailable

    fault currentof 25 kA,

    despite whattime-currentcurves show,

    due todynamic

    impedanceeffects.

    10 100

    1K

    10K

    100K

    TIMEINSECONDS

    100

    1K

    10

    K

    100K10

    0.01

    0.10

    1

    10

    100

    1000

    0.01

    0.10

    1

    10

    100

    1000

    CURRENT IN AMPERES

  • 7/29/2019 0100 Br 0801

    3/3

    Meeting Selective Coordination

    Code RequirementsSchneider Electric delivers the industry experience, technical knowledge,application expertise, market-ocused products, and expert servicesupport to meet your selective coordination design needs.

    For more information

    Contact us today or your next selective coordination design project at

    www.schneider-electric.us/go/consultants

    November 2012

    2 0 1 2 S c h n e i d e r E l e c t r i c

    A l l R i g h t s R e s e r v e d

    S c h n e i d e r E l e c t r i c a n d M a k e t h e m o s t o f y o u r e n e

    r g y a r e t r a d e m a r k s o w n e d b y S c h n e i d e r E l e c t r i c I n d u s t r i e s S A S o r i t s a f f i l i a t e d

    Document Number 0100BR0801R10/12

    Schneider Electric USA

    1415 S. Roselle Road

    Palatine, IL 60067

    Tel: 847-397-2600

    Fax: 847-925-7500

    www.schneider-electric.com/us