1 . occurrence of discharge

13
1 . Occurrence of Discharge 1.1 Partial discharge 1.2 Inception of internal discharge 1.3 Inception of surface discharge 1.4 Inception of corona discharge 1.5 Discharge by electrical

Upload: ursa-griffith

Post on 03-Jan-2016

64 views

Category:

Documents


0 download

DESCRIPTION

1 . Occurrence of Discharge. 1.1 Partial discharge 1.2 Inception of internal discharge 1.3 Inception of surface discharge 1.4 Inception of corona discharge 1.5 Discharge by electrical treeing. 1.1 Partial discharge. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: 1 . Occurrence of Discharge

1 . Occurrence of Discharge

1.1 Partial discharge1.2 Inception of internal discharge1.3 Inception of surface discharge1.4 Inception of corona discharge1.5 Discharge by electrical treeing

Page 2: 1 . Occurrence of Discharge

1.1 Partial discharge

Electric discharge that do not completely bridge the electrodes are called partial discharges.

방전크기는 작지만 점진적으로 발전하면 ultimate failure 로 유발가능 비파괴시험으로 방전의 진행을 detect 하는게 필수적이다 .

1.1.1 Classification 1) Internal discharge (Figures 1.1 and 1.2) 2) surface discharge (Figures 1.3) 3) Corona discharge (Figures 1.4) 4) Discharge in electrical trees (Figures 1.5)

Page 3: 1 . Occurrence of Discharge

1.1.2 Terminology Partial discharge 대신에 미국 , 영국 (ionization) 프랑스 (ionisation gazeuse) 독일 (Ionisationsvorgange) 라고함 . 파생어로는 ionization point , ionization livel Corona 의 파생어

1.2 Inception of internal discharge 1.2.1 Gas-filled cavities Figure(1.2(a)- 고체 절연체 전계 배 , (b) 배 ( c) 유전체와 동일한 크기 ( 전계가 집중되는 위험이있음 )

)21/(3

Page 4: 1 . Occurrence of Discharge

Breakdown strength of the cavities (dimensions , type of gas , gas pressure) Ex)a flat cavity of 0.1mm 인 폴리에틸렌의 , =2.2 1atm 일때 f

ig 1.7 에서 의 breakdown stress 는 6.8kV/mm 이다 . inception stress 는 6.8/2.2 ~~3kV/mm 부분방전 전계는 설계전계보다 낮아도 일어난다 .(3.5 to 7kV/mm) Breakdown voltage 에 미치는 여러가지 요소중 예측치보다 낮은 B

DS 를 보이는데 그 예로 static charge in wall of cavity 에 의해 예측치는 20% 만큼 감소한다 . 그의 방안으로 the wall 을 도전성을 갖게한다 .

Page 5: 1 . Occurrence of Discharge

1.2.2 Inclusions Extruded plastics of cast resin 에는 various inclusions : dirt, paper of textile fibres and other foreign particles inclusions 에 의해 BDS 는 감소하고 breakdown gas is forme

d and gas discharges occur. Gooding and slade 의 metal splinters embedded in the dielectric

local field concentration

1.2.3 oil-filled cavities Oil-impregnated paper insulation 의 stress 는 gas-filled cavities

와 유사하다 .

Page 6: 1 . Occurrence of Discharge

1.3 Inception of surface discharge Surface discharge may occur of there exists a stress component p

arallel to a dielectric surface. bushings, ends of cables,the overhang of generator windings and where a discharge from outside touches the surface.

1.3.1 Discharges in air Figure 1.8 과 figure 1.9 에서의 V 와 에 의한 paschen curve

를 볼수있다 .(table 1.1 dotted line)

Page 7: 1 . Occurrence of Discharge

1.3.2 Surface discharge under oil Similar formula as for air Contamination , moisture greatly affect the breakdown stress. 공기중에서의 BDS 는 습도에 매우 민감하며 , 절연유내의

실혐결과보다는 대개 낮은 특성을 보인다 .

1.3.3 Surface discharge under sulphur hexafluoride gas 절연물에서의 particles 은 표면의 섬락과 부분방전의 원인이

된다 . Brokman 은 이러한 현상을 3 가지 변수로 만들어보았다 .

Page 8: 1 . Occurrence of Discharge

(1) roughness of the surface (2) semiconducting areas - contamination of the dielectric surface(Fig 1.11) (3) Particle - shape and dielectric constant of particle(Fig 1.12) -particles with sharp edges are dangerous sources of discharge The flashover voltage decreased with increasing

Page 9: 1 . Occurrence of Discharge

1.4 Inception of corona discharge Corona discharge occur in gases at sharp points in the electrical f

ield(Fig1.13) Sharp edges , HV sides, laboratory floor…

1.4.1 corona air 1.4.2 corona in sulphur hexafluoride gas. SF6 하에서는 코로나 발생시 그의 부산물은 독성이 있다 . 1.5 discharge by electrical treeing electrical trees start from defects in the insulation(Fig1.15)

Page 10: 1 . Occurrence of Discharge
Page 11: 1 . Occurrence of Discharge
Page 12: 1 . Occurrence of Discharge
Page 13: 1 . Occurrence of Discharge