TECHNICAL INFORMATION
S10K
SONIC CHLORINATOR
INTRODUCTIONThe S10k chlorinator is an all vacuum operat-
ed, sonically regulated unit. Direct cylinder
mounting puts the vacuum-regulating valve
right at the source, reducing gas pressure to a
vacuum immediately. It provides for econom-
ic low capacity gas feed applications for
municipal and industrial water and waste-
water treatment and disinfection, swimming
pools and industrial process water. Its ability to
handle all water treatment gases as well as its
flexible mounting configurations for cylinders,
manifolds or ton containers provides versatili-
ty for all installations. Two basic arrangements
are available in capacities of 200 and 500
pounds per day of chlorine gas. With fewer
internal parts, you can be confident that the
S10k will provide reliable, dependable service.
FEATURESPositive Indication of
Operating Status
Easy to read icons provide positive indi-
cation of cylinder status. The operator
can tell at a glance whether the container
is in the standby status (for automatic
switchover) operating, empty or off.
Positive Shutoff
An OFF position on the face of the regu-
lator allows for positive shutoff. Containers
can be changed without admitting air,
dirt or moisture into the control unit and
without shutting off the injector.
Unique Secondary Check
The 500 PPD regulator includes a
unique secondary check designed to
confine gas under pressure should the
primary valve seat not completely due to
contamination. This minimizes the
possibility of venting gas to atmosphere.
Built-in Automatic Switchover
Built-in switchover eliminates the need
for external switching devices. The non-
isolating feature allows cylinders to be
emptied thoroughly, for complete gas
consumption.
Captive Universal Yoke
Mounting
A unique self aligning captive yoke
clamp makes it easy to line up and con-
nect the chlorinator to the gasketed out-
let of a container valve. The rugged
yoke is designed to Chlorine Institute
recommenda-
tion per drawing
189. A similar
captive yoke
design is used for ammonia cylinders. A
ton container kit includes a drip leg, to
trap initial spurts of liquid, a heater for
evaporation and a replaceable filter.
Handles all Water Treatment
Gases
The unit can handle all typical water
treatment gases e.g. chlorine, sulfur
dioxide, carbon dioxide and ammonia.
Detachable Rotameters
Two sizes of rotameters, 3 and 5, are
available in 15 capacities between 1.2
500 PPD chlorine (comparable capaci-
ties for other gases). These
flowmeters can be integral to
the unit, or mounted remote,fo rinstallation flexi-
bility. Rotameters
can be ganged
together for multiple
points of
application.
standby* operating empty off
-
8/13/2019 25-200TI
2/6
TECHNICAL DATA
2
Easy to Install, Operate andMaintain
The S10k chlorinator is simple in
design, compact and easy to handle.
Injector installation only requires con-
necting to a water supply and running
plastic tubing to a main or open chan-
nel. A knob adjustment on the rotame-
ter changes gas feed rate, which is indi-
cated on a high resolution 3" or 5" scale.
Accuracy
Gas feed is 4% of the indicated flow.
Operating Range
Manual 20:1 for any flowmeter.
Automatic 10:1.
Control Modes
Manual control, start-stop or program,flow proportional, direct residual, com-
pound-loop, multiple rate control and
multiple point operation.
Distance, Supply to the
Control Unit
For flexibility, it is not necessary to install
the vacuum regulating valve close to the
control unit. It can be up to several
hundred feet from the gas control unit,
depending on maximum feed rate, the
diameter of the connecting pipe or tub-
ing and system performance requirements.
Injector Operating Water
Injector operating water must be reason-
ably clean. Injectors are fixed-throat dif-
ferential type. Maximum inlet pressure
is 300 psi to a maximum of 100 F; 150psi to a maximum of 130 F.
Pressure at Application Point
Maximum pressure with hose or poly-
ethylene tubing is 75 psi. High pressure
hose or rigid pipe will allow application
against back pressure of 75 to 160 psi.
A solution pump after the injector will
allow application against higher pressure.
Swimming Pools
For non-residential swimming pool
applications a unique package is available.
AUTOMATIC CONTROL
The S10k can accommodate automatic
feed rate control from simple to com-
plex schemes. The control system con-
sists of an actuator and either SCU(Signal Conditioning Unit) or PCU
(Process Control Unit).
SCU (see TI 40.100UA)
Operating Modes: Flow proportional,
manual
Inputs: 4-20 mA DC (from flow
transmitter)
Outputs: Control out to actuator; also
4-20 mA output for retransmission of
gas feed rate (actuator position)
Control Capability: Dosage and flow
scaling PCU (see TI 40.200UA)
Operating Modes: Direct residual feed
back, compound loop, feed forward,
flow proportional, manual
Ranges: Setpoints up to 50 mg/l and
center-zero capability for dechlorination
Control Logic: Proportional andintegral with lag
Alarms: 4 user-configurable alarms
for 16 different conditions
OPTIONS
Related options include: cylinder valves
and connections; header valves with
manifolding and connections; vent; injec-
tor water and injector outlet lines and
clamps; main connections; solenoid
valves; water line pressure gauge; high
vacuum pressure switch and alarm; gas
mask; chlorine detectors; on line
analysers; two cylinder scales; residual test
kits; injector vacuum gauges; spare parts.
Chlorine Gas Warning
All unattended chlorine gas containers
and chlorination equipment should bemonitored for leaks. Sensitive chlorine
detectors, which respond quickly to
chlorine in the atmosphere, should be
installed at each site.
See Technical Data Sheet TI 50.130UA
for further details.
Carbon Dioxide Warning
Because of the high pressure in carbon
dioxide containers, the vacuum regulat-
ing valve cannot be mounted directly on
the container. A pressure reducing valve
and pressure relief valve must be
installed between the container and the
vacuum regulating valve.
-
8/13/2019 25-200TI
3/6
3
TECHNICAL DATA
Maximum
capacity
Chlorine
lb/24 hour
Carbon Dioxide
lb/24 hour
Sulfur Dioxide
lb/24 hour
Ammonia
lb/24 hour
5 tube 500 PPD3/10/20/30/50/
75/100/150/200/250/300/400/500
2.4/8/15/24/35/58/75/116/150/
200/230/300/390
3/10/20/30/50/75/100/150/200/250/300/400/475
1.4/4.5/9/14/35/45/70/90/120/140/190/240
3 tube 200 PPD1.2/4/10/20/50/
100/150/2001/3/8/15/40/80/
120/1501.2/4/10/20/50/
100/150/2000.5/2/5/9/25/
50/70/100
*A selection of tubes in metric calibrations are also available on request
Gases and Capacities*
Vacuum Regulating Valves
Connections
Pipe and plastic tubing sizes.
Tubing to 200 lb 500 lb
3/8 x 1/2 1/2" x 5/8"control unit
gas inlet is yoke connection
to a cylinder or header valve
or, with optional adapter,
to a ton container valve
container valve
Injectors
Connection 200 lb 500 lb
3/4 male NPT or
3/4 flexible pipe1 female NPTwater inlet
same as inlet
3/4" NPT with
adaptors for 3/4, 1,
or 1-1/2 pipe or hose
water outlet
Compliance
Gas feeders, controller and actuator are
designed to conform to all applicable
NEC and NEMA specifications and
Chlorine Institute and Compressed Gas
Association recommendations.OVERALL DIMENSIONS
Chlorinator:
3 Rotameter - 7-7/8 x 7 x 11-3/4
5 Rotameter - 8-1/4 x 12 x 13
Automatic panel - 25-1/4 x 7-3/8 x
7-1/8Shipping Weight
Gas metering unit - 5 lb.
Automatic panel - 16 lb.
-
8/13/2019 25-200TI
4/6
1.0 GENERAL DESCRIPTIONThe gas feeder shall be a Wallace &
Tiernan Products S10k. It shall be a vac-
uum operated sonically regulated type
system consisting of a vacuum regulator,
flowmeter with rate valve and injector. It
shall have a maximum capacity of (200)
(500) ( ) pounds per day (chlo-
rine) (sulfur dioxide) (ammonia) (carbon
dioxide) and sized to feed ( )
PPD. It shall be (manually) (automati-
cally) controlled having a feed range of
(20:1 manual) (10:1 automatic) and the
capability to control within 4% of the
indicated feed rate.
2.0 VACUUM REGULATOR
2.1 Design
The (cylinder) (manifold) (ton container)
mounted vacuum regulator shall berated for (200PPD) (500 PPD)
( PPD) of chlorine ( ). It shall
consist of a vacuum regulator designed
to reduce full supply pressure to a vacu-
um without venting. A self aligning
yoke shall be provided as an integral
part of the vacuum regulator. The unit
shall include a selector knob and icons
to indicate the chlorine gas container
status. An off position shall be provided
to isolate the diaphragm and internal
components from atmospheric air when
the operator changes containers.
It shall contain internal pressure relief.
[It shall contain a drip leg with remov-
able filter and 110 volt heater for
mounting on a ton container]. The 500
PPD unit shall include a secondary
check to prevent gas under pressurefrom venting into the atmosphere. The
check valve shall close in the event of
leakage past the primary valve.
2.2 Automatic Switchover
An automatic switchover system shall be
furnished to change over to a new sup-
ply as the on-line supply is depleted. A
pair of vacuum regulating valves with
built-in switchover capability shall be
furnished. The regulator valve shall
include a mechanical detent to keep the
standby gas supply ready for on-line ser-
vice. When the switchover is accom-
plished gas shall continue to be drawn
from the former source until the con-
tainer(s) are empty. A separate
switchover device will not be acceptable.
Each regulator shall include easy to readindication of stand-by, operating, empty
and off position.
3.0 CONTROL UNIT
A (3 inch) (5 inch) flowmeter assembly
with a V-notch rate valve shall be fur-
nished and shall be capable of local or
remote mounting. There shall be provi-
sions for interlocking flowmeter frames
for multiple feed points. The flowmeter
tube shall be serviceable without remov-
ing the frame from its mounting.
4.0 INJECTOR
Each gas feeder shall have a PVC (3/4)
(1) inch fixed throat injector rated (200
PPD) (500 PPD) to generate the
operating vacuum for the system. The
injector shall be capable of feedingagainst a back pressure of ( ) psi
with an operating pressure of ( )
psi. It shall include built-in double
check valve protection to prevent water
from back flooding into the vacuum
regulator. The injector shall include an
integral mounting bracket. It shall be
capable of mounting in either the verti-
cal or horizontal plane.
5.0 AUTOMATIC CONTROLS
Each gas feeder shall be provided with
an integral automatic control system
consisting of a dedicated electronic con-
troller, a V-notch positioner, a 5
rotameter and a V-notch chamber. The
positioner shall move the V-notch plug
and shall contain a reversible motor
with thermal overload protection,mechanical override, feedback poten-
tiometer, selectable contacts and front
accessibility for service. The positioner,
V-notch chamber and 5 rotameter shall
be mounted remote from the gas storage
area. The positioner and controller shall
be housed in NEMA 4X enclosures.
5.1 SCU Flow Proportional
ControllerThe Flow Proportional Controller shall
be microprocessor-based with a NEMA
4X enclosure. It shall accept a 4-20 mA
process variable input signal. The user
interface shall include a membrane key-
pad and backlit LCD display.
4
Equipment specifications continued on page 5.
S10K CHLORINATOR
EQUIPMENT SPECIFICATION
-
8/13/2019 25-200TI
5/6
The display shall be scrollable to five
operating menus as follows:
(1) Main Menu shall display values
(2) Setup Menu
(3) Input and Output options
(4) Diagnostic Menu for trouble shooting
(5) Calibration Menu.
Dosage can be set from 10 to 400% of
intput. An isolated 4-20 mA output sig-
nal shall be provided for control, flow or
actuator position. The controller shall be
an SCU (Signal Conditioning Unit) as
manufactured by Wallace & Tiernan
Products.
OR
5.2 PCU Compound Loop
ControllerThe Compound Loop Controller shall
be microprocessor based and capable of
accepting 3 input signals: flow, residual
and one spare. It shall have a membrane
keypad, digital LED display of residual,
LED bar graph display of percent valve
position and 16 character alphanumeric
LED display of all operating and setup
parameters.
The user shall be able to select from six
modes of operation:
(1) direct residual control
(2) compound loop control
(3) dual signal feed forward control for
dechlorination
(4) center zero control for dechlorination
(5) flow proportional control
(6) manual control.
Four configurable alarm relays shall be
provided to select from 16 different
alarm conditions.
The controller shall have password pro-
tection to prevent tampering. The unit
shall be capable of computer interface
via RS485 serial communication. An
isolated 4-20 mA output signal shall be
provided for control, flow or actuator
position. The controller shall be a
PCU (Process Control Unit) as manu-
factured by Wallace & Tiernan
Products.
6.0 ACCESSORIES
A vacuum switch shall be supplied to
actuate on loss of gas pressure. It shall
be designed for mounting integral to the
vacuum regulator and shall be suppliedwith one normally opened, normally
closed contact rated at 10 amps.
5
1 Injector - Capacity to 500 PPD
3/4 Injector - Capacity to 200 PPD
S10K CHLORINATOR
EQUIPMENT SPECIFICATION
-
8/13/2019 25-200TI
6/6
S10K
SONIC CHLORINATOR
TECHNICAL INFORMATION
Taking care of the world's water.
Wallace & Tiernan Products
1901 West Garden Road
Vineland, NJ 08360
856.507.9000 tel
856.507.4125fax
www.wallaceandtiernan.usfilter.comLiterature # TI 25.200 UA 9/99
1999 United States Filter Corporation
6
Progressive changes in design may be madewithout prior announcements.