aa-en-j02.351.3-gmv_pd

3
J.02 Air conditioning and heatpumps GMV-PD ATC VRF Digital scroll Outdoor unit, PD series www.airtradecentre.com VRF PD series outdoor unit type GMV-PD GMV-R type VRF heatpump digital scroll inverter outdoor unit Application Outdoor Unit Function Long refrigerant pipe, the longest connection pipe of certain units can be 150m, the largest height difference between indoor and outdoor unit can be 50m Wide outdoor units lineup, including digital compressor series, DC inverter compressor series Heat recovery and ultra-low temperature heat-pump series with digital compressor are available Precise temperature control with only ±0.5'C temperature fluctuation Powerful and advanced new controller for optional Refrigerant R410A Features High COP value Unique oil return patent design Real time intelligent defrost technology Accurate refrigerate distributing technology Wide capacity range from 5kW to 18kW Space saving outdoor unit Low noise Components optimum designed for R410a Applicable indoor units Wall mounted types: Type GMV[L]-R22G/NaA-K Type GMV[L]-R28G/NaA-K Type GMV[L]-R36G/NaA-K Type GMV[L]-R22G/NaB-K J.02 GMV-PD 1/3 - 2011/3/17 - AA-EN

Upload: dinop

Post on 23-Apr-2017

218 views

Category:

Documents


1 download

TRANSCRIPT

J.02

Air conditioningand heatpumps

GMV-PD

ATCVRFDigital scrollOutdoor unit, PD series

www.airtradecentre.com

VRF PD series outdoor unit typeGMV-PDGMV-R type VRF heatpump digital scroll inverter outdoor unit

Application¾ Outdoor Unit

Function¾ Long refrigerant pipe, the longest connection pipe of certain units can be 150m,

the largest height difference between indoor and outdoor unit can be 50m¾ Wide outdoor units lineup, including digital compressor series, DC inverter

compressor series¾ Heat recovery and ultra-low temperature heat-pump series with digital

compressor are available¾ Precise temperature control with only ±0.5'C temperature fluctuation¾ Powerful and advanced new controller for optional

Refrigerant¾ R410A

Features¾ High COP value¾ Unique oil return patent design¾ Real time intelligent defrost technology¾ Accurate refrigerate distributing technology¾ Wide capacity range from 5kW to 18kW¾ Space saving outdoor unit¾ Low noise¾ Components optimum designed for R410a

Applicable indoor unitsWall mounted types:¾ Type GMV[L]-R22G/NaA-K¾ Type GMV[L]-R28G/NaA-K¾ Type GMV[L]-R36G/NaA-K¾ Type GMV[L]-R22G/NaB-K

J.02 GMV-PD 1/3 - 2011/3/17 - AA-EN

¾ Type GMV[L]-R28G/NaB-K¾ Type GMV[L]-R36G/NaB-K¾ Type GMV[L]-R45G/NaB-K¾ Type GMV[L]-R22G/NaC-K¾ Type GMV[L]-R28G/NaC-K¾ Type GMV[L]-R36G/NaC-K¾ Type GMV[L]-R45G/NaC-K¾ Type GMV[L]-R50G/Na-K¾ Type GMV[L]-R56G/Na-K Floor/ceiling types:¾ Type GMV-R28Zd/Na-K¾ Type GMV-R36Zd/Na-K¾ Type GMV-R50Zd/Na-K¾ Type GMV-R71Zd/Na-K¾ Type GMV-R90Zd/Na-K¾ Type GMV-R112Zd/Na-K¾ Type GMV-R125Zd/Na-K

Applicable controllerCentralized controller¾ Control 64 groups (64 outdoor unit, 1024 indoor units in max)¾ Central control¾ Single control or select control¾ Weely schedule¾ Malfunction code display¾ Expanded timer function¾ Maximum wiring length of 1000m Mini centralized controller¾ Control 1 groups (16 indoor units in max)¾ Group centralized control¾ Memory restart¾ Malfunction code display¾ Key lock function

Order exampleGMV-Pd160W/Na-K ¾ GMV-Pd = Type of digital scroll outdoor unit¾ 160 = 160kW, nominal cooling capacity¾ W = number of comperessors¾ Na = Refrigerant = R410A¾ M = Power complement, M = 380V, 3ph~, 50Hz; K = 220V, 1ph, 50Hz ~

Specifications

Model

Capacity Power supply Electrical characteristics Noise Outline Dimension[mm] Net.Weight Connecting Pipe

[kW] V-ph-Hz Rated power input[kW]

Rated current input[A] dB[A] Width

[mm]Depth[mm]

Height[mm]

[kg] [mm]

Cooling Heating Cooling/Heating Cooling/Heating Gas pipe Liquid pipeGMV[L]-Pd50W/Na-K 5 6

220~240V1PH-50Hz

1.41/1.53 6.5/7.0 56 950 340 660 59  12.7 Ø6.35GMV[L]-Pd70W/Na-K 7 8 2.0/1.86 9.2/8.5 57 950 340 840 75 Ø15.9 Ø9.52GMV[L]-Pd80W/Na-K 8 9 2.3/2.25 10.6/10.3 57 950 340 840 80 Ø15.9 Ø9.52GMV[L]-Pd100W/Na-K 10 11 2.85/2.75 13.1/12.6 58 1100 340 1250 90  15.9 Ø9.52GMV[L]-Pd120W/Na-K 12 14 3.75/3.65 17.2/16.7 58 1100 340 1250 120 Ø15.9 Ø9.52GMV[L]-Pd140W/Na-K 14 16 4.25/4.05 19.47/18.54 58 1100 340 1250 135  15.9 Ø9.52GMV[L]-Pd120W/Na-M 12 14

380~415V3PH-50Hz

3.75/3.65 5.76/5.6 58 1100 340 1250 120 Ø15.9 Ø9.52GMV[L]-Pd140W/Na-M 14 16 4.35/4.06 6.74/6.29 58 1100 340 1250 135 Ø15.9 Ø9.52GMV[L]-Pd160W/Na-M 16 18 5.0/5.1 7.7/7.8 58 1100 340 1250 140 Ø19.05 Ø9.52GMV[L]-Pd200W/Na-M 20 23 6.1/6.3 9.4/9.6 60 990 905 1772 180 Ø19.05 Ø9.52GMV[L]-Pd280W/Na-M 28 30 8.75/8.25 13.4/12.7 60 990 905 1772 230 Ø22.2 Ø9.52GMV[L]-Pd300W/Na-M 30 33,50 9.6/9.28 14.7/14.2 60 990 905 1772 230 Ø22.2 Ø9.52

J.02

Air conditioningand heatpumps

www.airtradecentre.comJ.02 GMV-PD 2/3 - 2011/3/17 - AA-EN

1100340

1250

590

378

201

J.02

Air conditioningand heatpumps