    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 150.6 mm 2 297.2 kcmilNominal Diameter of Composite Core (CTC Part Number 200-003) 5.97 mm 0.235 in.Nominal Cross-sectional Area of Core 28.0 mm 2 0.043 in2

    Overall Diameter of Conductor 15.65 mm 0.616 in.Nominal Cross-sectional Area of the Conductor 178.6 mm 2 0.277 in2

    Ultimate Tensile Strength of Conductor 1,2 68.9 kN 15.5 kipsRated Strength of Core - 313 ksi (2158 MPa) 60.4 kN 13.6 kipsCore Nominal Mass per unit length 54 kg/km 36 lb/kftConductor Nominal Mass per unit length 471.2 kg/km 316.7 lb/kftAluminum Nominal Mass per unit length** 417.2 kg/km 280.4 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.74E-05 /oC 9.65E-06 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 66.5 GPa 9.6 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.1862 ohm/km 0.2997 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.1902 ohm/km 0.3062 ohm/mileAC Nominal Resistance at 75ºC 0.2277 ohm/km 0.3665 ohm/mileAC Nominal Resistance at 180ºC 0.3064 ohm/km 0.4931 ohm/mile

    519 @ 100C & 50 Hz765 @ 180C & 50 Hz

    GMR (estimated) 0.006 m 0.021 ftInductive Reactance 0.242 ohm/km 0.468 ohm/mileCapacitive Reactance 0.210 Mohm-km 0.109 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-081-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Helsinki

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 155 sq. mm (305.9 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    2/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 219.9 mm 2 434.0 kcmilNominal Diameter of Composite Core (CTC Part Number 200-003) 5.97 mm 0.235 in.Nominal Cross-sectional Area of Core 28.0 mm 2 0.043 in2

    Overall Diameter of Conductor 18.29 mm 0.720 in.Nominal Cross-sectional Area of the Conductor 247.9 mm 2 0.384 in2

    Ultimate Tensile Strength of Conductor 1,2 72.8 kN 16.4 kipsRated Strength of Core - 313 ksi (2158 MPa) 60.4 kN 13.6 kipsCore Nominal Mass per unit length 54 kg/km 36 lb/kftConductor Nominal Mass per unit length 661.0 kg/km 444.2 lb/kftAluminum Nominal Mass per unit length** 607.0 kg/km 407.9 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.88E-05 /oC 1.04E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 64.1 GPa 9.3 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.1272 ohm/km 0.2047 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.1301 ohm/km 0.2097 ohm/mileAC Nominal Resistance at 75ºC 0.1557 ohm/km 0.2508 ohm/mileAC Nominal Resistance at 180ºC 0.2094 ohm/km 0.3371 ohm/mile

    656 @ 100C & 50 Hz971 @ 180C & 50 Hz

    GMR (estimated) 0.007 m 0.024 ftInductive Reactance 0.233 ohm/km 0.451 ohm/mileCapacitive Reactance 0.201 Mohm-km 0.104 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-083-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Copenhagen

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 226.4 sq. mm (446.7 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    3/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 236.7 mm 2 467.1 kcmilNominal Diameter of Composite Core (CTC Part Number 200-005) 7.75 mm 0.305 in.Nominal Cross-sectional Area of Core 47.1 mm 2 0.073 in2

    Overall Diameter of Conductor 19.53 mm 0.769 in.Nominal Cross-sectional Area of the Conductor 283.8 mm 2 0.440 in2

    Ultimate Tensile Strength of Conductor 1,2 115.0 kN 25.9 kipsRated Strength of Core - 313 ksi (2158 MPa) 101.7 kN 22.9 kipsCore Nominal Mass per unit length 86 kg/km 58 lb/kftConductor Nominal Mass per unit length 731.3 kg/km 491.5 lb/kftAluminum Nominal Mass per unit length** 645.3 kg/km 433.7 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.71E-05 /oC 9.49E-06 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 67.0 GPa 9.7 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.1184 ohm/km 0.1905 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.1211 ohm/km 0.1951 ohm/mileAC Nominal Resistance at 75ºC 0.1449 ohm/km 0.2334 ohm/mileAC Nominal Resistance at 180ºC 0.1949 ohm/km 0.3138 ohm/mile

    692 @ 100C & 50 Hz1027 @ 180C & 50 Hz

    GMR (estimated) 0.008 m 0.026 ftInductive Reactance 0.228 ohm/km 0.441 ohm/mileCapacitive Reactance 0.197 Mohm-km 0.102 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-084-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Glasgow

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 243.7 sq. mm (480.9 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    4/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 273.6 mm 2 539.9 kcmilNominal Diameter of Composite Core (CTC Part Number 200-004) 7.11 mm 0.280 in.Nominal Cross-sectional Area of Core 39.7 mm 2 0.062 in2

    Overall Diameter of Conductor 20.50 mm 0.807 in.Nominal Cross-sectional Area of the Conductor 313.3 mm 2 0.486 in2

    Ultimate Tensile Strength of Conductor 1,2 101.1 kN 22.7 kipsRated Strength of Core - 313 ksi (2158 MPa) 85.7 kN 19.3 kipsCore Nominal Mass per unit length 76 kg/km 51 lb/kftConductor Nominal Mass per unit length 834.4 kg/km 560.8 lb/kftAluminum Nominal Mass per unit length** 758.4 kg/km 509.7 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.83E-05 /oC 1.02E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 64.9 GPa 9.4 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.1024 ohm/km 0.1648 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.1049 ohm/km 0.1691 ohm/mileAC Nominal Resistance at 75ºC 0.1255 ohm/km 0.2022 ohm/mileAC Nominal Resistance at 180ºC 0.1686 ohm/km 0.2716 ohm/mile

    754 @ 100C & 50 Hz1120 @ 180C & 50 Hz

    GMR (estimated) 0.008 m 0.027 ftInductive Reactance 0.226 ohm/km 0.436 ohm/mileCapacitive Reactance 0.194 Mohm-km 0.101 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-085-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Casablanca

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 281.6 sq. mm (555.8 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    5/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 223.1 mm 2 440.3 kcmilNominal Diameter of Composite Core (CTC Part Number 200-004) 7.11 mm 0.280 in.Nominal Cross-sectional Area of Core 39.7 mm 2 0.062 in2

    Overall Diameter of Conductor 18.82 mm 0.741 in.Nominal Cross-sectional Area of the Conductor 262.8 mm 2 0.407 in2

    Ultimate Tensile Strength of Conductor 1,2 98.3 kN 22.1 kipsRated Strength of Core - 313 ksi (2158 MPa) 85.7 kN 19.3 kipsCore Nominal Mass per unit length 76 kg/km 51 lb/kftConductor Nominal Mass per unit length 693.6 kg/km 466.2 lb/kftAluminum Nominal Mass per unit length** 617.6 kg/km 415.1 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.75E-05 /oC 9.75E-06 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 66.2 GPa 9.6 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.1256 ohm/km 0.2021 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.1285 ohm/km 0.2070 ohm/mileAC Nominal Resistance at 75ºC 0.1537 ohm/km 0.2476 ohm/mileAC Nominal Resistance at 180ºC 0.2067 ohm/km 0.3328 ohm/mile

    665 @ 100C & 50 Hz986 @ 180C & 50 Hz

    GMR (estimated) 0.008 m 0.025 ftInductive Reactance 0.231 ohm/km 0.446 ohm/mileCapacitive Reactance 0.199 Mohm-km 0.103 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-087-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Reykjavik

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 229.7 sq. mm (453.2 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    6/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 315.5 mm 2 622.6 kcmilNominal Diameter of Composite Core (CTC Part Number 200-004) 7.11 mm 0.280 in.Nominal Cross-sectional Area of Core 39.7 mm 2 0.062 in2

    Overall Diameter of Conductor 21.79 mm 0.858 in.Nominal Cross-sectional Area of the Conductor 355.2 mm 2 0.551 in2

    Ultimate Tensile Strength of Conductor 1,2 103.4 kN 23.2 kipsRated Strength of Core - 313 ksi (2158 MPa) 85.7 kN 19.3 kipsCore Nominal Mass per unit length 76 kg/km 51 lb/kftConductor Nominal Mass per unit length 947.6 kg/km 636.9 lb/kftAluminum Nominal Mass per unit length** 871.6 kg/km 585.8 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.88E-05 /oC 1.05E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 64.1 GPa 9.3 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0887 ohm/km 0.1427 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0910 ohm/km 0.1469 ohm/mileAC Nominal Resistance at 75ºC 0.1088 ohm/km 0.1754 ohm/mileAC Nominal Resistance at 180ºC 0.1461 ohm/km 0.2354 ohm/mile

    823 @ 100C & 50 Hz1227 @ 180C & 50 Hz

    GMR (estimated) 0.009 m 0.029 ftInductive Reactance 0.222 ohm/km 0.430 ohm/mileCapacitive Reactance 0.191 Mohm-km 0.099 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-089-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Lisbon

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 324.8 sq. mm (640.9 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    7/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 367.4 mm 2 725.1 kcmilNominal Diameter of Composite Core (CTC Part Number 200-005) 7.75 mm 0.305 in.Nominal Cross-sectional Area of Core 47.1 mm 2 0.073 in2

    Overall Diameter of Conductor 23.55 mm 0.927 in.Nominal Cross-sectional Area of the Conductor 414.5 mm 2 0.642 in2

    Ultimate Tensile Strength of Conductor 1,2 122.4 kN 27.5 kipsRated Strength of Core - 313 ksi (2158 MPa) 101.7 kN 22.9 kipsCore Nominal Mass per unit length 86 kg/km 58 lb/kftConductor Nominal Mass per unit length 1101.6 kg/km 740.4 lb/kftAluminum Nominal Mass per unit length** 1015.6 kg/km 682.6 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.88E-05 /oC 1.04E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 64.2 GPa 9.3 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0762 ohm/km 0.1226 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0784 ohm/km 0.1265 ohm/mileAC Nominal Resistance at 75ºC 0.0936 ohm/km 0.1510 ohm/mileAC Nominal Resistance at 180ºC 0.1256 ohm/km 0.2024 ohm/mile

    907 @ 100C & 50 Hz1355 @ 180C & 50 Hz

    GMR (estimated) 0.010 m 0.031 ftInductive Reactance 0.217 ohm/km 0.420 ohm/mileCapacitive Reactance 0.186 Mohm-km 0.097 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-091-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Amsterdam

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 378.2 sq. mm (746.4 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    8/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 421.4 mm 2 831.6 kcmilNominal Diameter of Composite Core (CTC Part Number 200-006) 8.13 mm 0.320 in.Nominal Cross-sectional Area of Core 51.9 mm 2 0.080 in2

    Overall Diameter of Conductor 25.15 mm 0.990 in.Nominal Cross-sectional Area of the Conductor 473.3 mm 2 0.734 in2

    Ultimate Tensile Strength of Conductor 1,2 135.7 kN 30.5 kipsRated Strength of Core - 313 ksi (2158 MPa) 112.0 kN 25.2 kipsCore Nominal Mass per unit length 98 kg/km 66 lb/kftConductor Nominal Mass per unit length 1264.8 kg/km 850.1 lb/kftAluminum Nominal Mass per unit length** 1166.8 kg/km 784.2 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.89E-05 /oC 1.05E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 64.0 GPa 9.3 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0666 ohm/km 0.1072 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0687 ohm/km 0.1110 ohm/mileAC Nominal Resistance at 75ºC 0.0820 ohm/km 0.1323 ohm/mileAC Nominal Resistance at 180ºC 0.1099 ohm/km 0.1771 ohm/mile

    987 @ 100C & 50 Hz1479 @ 180C & 50 Hz

    GMR (estimated) 0.010 m 0.033 ftInductive Reactance 0.213 ohm/km 0.412 ohm/mileCapacitive Reactance 0.183 Mohm-km 0.095 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-093-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Brussels

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 433.8 sq. mm (856.1 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    9/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 313.8 mm 2 619.3 kcmilNominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.Nominal Cross-sectional Area of Core 60.3 mm 2 0.093 in2

    Overall Diameter of Conductor 22.40 mm 0.882 in.Nominal Cross-sectional Area of the Conductor 374.1 mm 2 0.580 in2

    Ultimate Tensile Strength of Conductor 1,2 147.9 kN 33.2 kipsRated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kipsCore Nominal Mass per unit length 113 kg/km 76 lb/kftConductor Nominal Mass per unit length 980.2 kg/km 658.8 lb/kftAluminum Nominal Mass per unit length** 867.2 kg/km 582.8 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.70E-05 /oC 9.47E-06 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 67.4 GPa 9.8 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0893 ohm/km 0.1437 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0911 ohm/km 0.1476 ohm/mileAC Nominal Resistance at 75ºC 0.1091 ohm/km 0.1764 ohm/mileAC Nominal Resistance at 180ºC 0.1469 ohm/km 0.2369 ohm/mile

    828 @ 100C & 50 Hz1234 @ 180C & 50 Hz

    GMR (estimated) 0.009 m 0.030 ftInductive Reactance 0.220 ohm/km 0.424 ohm/mileCapacitive Reactance 0.189 Mohm-km 0.098 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-094-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Oslo

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 323 sq. mm (637.5 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    10/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 463.3 mm 2 914.3 kcmilNominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.Nominal Cross-sectional Area of Core 60.3 mm 2 0.093 in2

    Overall Diameter of Conductor 26.40 mm 1.039 in.Nominal Cross-sectional Area of the Conductor 523.6 mm 2 0.812 in2

    Ultimate Tensile Strength of Conductor 1,2 156.3 kN 35.1 kipsRated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kipsCore Nominal Mass per unit length 113 kg/km 76 lb/kftConductor Nominal Mass per unit length 1394.3 kg/km 937.1 lb/kftAluminum Nominal Mass per unit length** 1281.3 kg/km 861.2 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.86E-05 /oC 1.03E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 64.7 GPa 9.4 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0605 ohm/km 0.0974 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0625 ohm/km 0.1011 ohm/mileAC Nominal Resistance at 75ºC 0.0746 ohm/km 0.1205 ohm/mileAC Nominal Resistance at 180ºC 0.0999 ohm/km 0.1610 ohm/mile

    1049 @ 100C & 50 Hz1576 @ 180C & 50 Hz

    GMR (estimated) 0.011 m 0.035 ftInductive Reactance 0.210 ohm/km 0.406 ohm/mileCapacitive Reactance 0.180 Mohm-km 0.093 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-095-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Stockholm 2L

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 476.9 sq. mm (941.2 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    11/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 507.5 mm 2 1001.5 kcmilNominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.Nominal Cross-sectional Area of Core 60.3 mm 2 0.093 in2

    Overall Diameter of Conductor 27.72 mm 1.091 in.Nominal Cross-sectional Area of the Conductor 567.8 mm 2 0.880 in2

    Ultimate Tensile Strength of Conductor 1,2 158.7 kN 35.7 kipsRated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kipsCore Nominal Mass per unit length 113 kg/km 76 lb/kftConductor Nominal Mass per unit length 1519.8 kg/km 1021.4 lb/kftAluminum Nominal Mass per unit length** 1406.8 kg/km 945.5 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.89E-05 /oC 1.05E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 64.2 GPa 9.3 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0553 ohm/km 0.0890 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0573 ohm/km 0.0928 ohm/mileAC Nominal Resistance at 75ºC 0.0683 ohm/km 0.1104 ohm/mileAC Nominal Resistance at 180ºC 0.0914 ohm/km 0.1474 ohm/mile

    1112 @ 100C & 50 Hz1673 @ 180C & 50 Hz

    GMR (estimated) 0.011 m 0.037 ftInductive Reactance 0.207 ohm/km 0.401 ohm/mileCapacitive Reactance 0.177 Mohm-km 0.092 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-096-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Warsaw

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 522.4 sq. mm (1031 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    12/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 524.5 mm 2 1035.1 kcmilNominal Diameter of Composite Core (CTC Part Number 200-007) 9.53 mm 0.375 in.Nominal Cross-sectional Area of Core 71.3 mm 2 0.111 in2

    Overall Diameter of Conductor 28.14 mm 1.108 in.Nominal Cross-sectional Area of the Conductor 595.8 mm 2 0.923 in2

    Ultimate Tensile Strength of Conductor 1,2 183.3 kN 41.2 kipsRated Strength of Core - 313 ksi (2158 MPa) 153.8 kN 34.6 kipsCore Nominal Mass per unit length 132 kg/km 89 lb/kftConductor Nominal Mass per unit length 1583.0 kg/km 1063.9 lb/kftAluminum Nominal Mass per unit length** 1451.0 kg/km 975.2 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.86E-05 /oC 1.03E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 64.5 GPa 9.4 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0534 ohm/km 0.0859 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0553 ohm/km 0.0897 ohm/mileAC Nominal Resistance at 75ºC 0.0660 ohm/km 0.1067 ohm/mileAC Nominal Resistance at 180ºC 0.0883 ohm/km 0.1423 ohm/mile

    1136 @ 100C & 50 Hz1711 @ 180C & 50 Hz

    GMR (estimated) 0.011 m 0.038 ftInductive Reactance 0.206 ohm/km 0.398 ohm/mileCapacitive Reactance 0.176 Mohm-km 0.091 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-098-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Dublin

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 539.9 sq. mm (1065.5 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    13/31

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    14/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 567.7 mm 2 1120.3 kcmilNominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.Nominal Cross-sectional Area of Core 60.3 mm 2 0.093 in2

    Overall Diameter of Conductor 29.10 mm 1.146 in.Nominal Cross-sectional Area of the Conductor 628.0 mm 2 0.973 in2

    Ultimate Tensile Strength of Conductor 1,2 162.1 kN 36.4 kipsRated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kipsCore Nominal Mass per unit length 113 kg/km 76 lb/kftConductor Nominal Mass per unit length 1686.1 kg/km 1133.2 lb/kftAluminum Nominal Mass per unit length** 1573.1 kg/km 1057.2 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.93E-05 /oC 1.07E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 63.6 GPa 9.2 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0494 ohm/km 0.0795 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0514 ohm/km 0.0835 ohm/mileAC Nominal Resistance at 75ºC 0.0612 ohm/km 0.0991 ohm/mileAC Nominal Resistance at 180ºC 0.0818 ohm/km 0.1320 ohm/mile

    1191 @ 100C & 50 Hz1797 @ 180C & 50 Hz

    GMR (estimated) 0.012 m 0.039 ftInductive Reactance 0.205 ohm/km 0.395 ohm/mileCapacitive Reactance 0.174 Mohm-km 0.090 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-100-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Milan

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 584.4 sq. mm (1153.3 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    15/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 592.5 mm 2 1169.3 kcmilNominal Diameter of Composite Core (CTC Part Number 200-007) 9.53 mm 0.375 in.Nominal Cross-sectional Area of Core 71.3 mm 2 0.111 in2

    Overall Diameter of Conductor 29.89 mm 1.177 in.Nominal Cross-sectional Area of the Conductor 663.8 mm 2 1.029 in2

    Ultimate Tensile Strength of Conductor 1,2 187.1 kN 42.1 kipsRated Strength of Core - 313 ksi (2158 MPa) 153.8 kN 34.6 kipsCore Nominal Mass per unit length 132 kg/km 89 lb/kftConductor Nominal Mass per unit length 1773.8 kg/km 1192.1 lb/kftAluminum Nominal Mass per unit length** 1641.8 kg/km 1103.4 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.90E-05 /oC 1.06E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 63.8 GPa 9.3 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0474 ohm/km 0.0763 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0494 ohm/km 0.0802 ohm/mileAC Nominal Resistance at 75ºC 0.0588 ohm/km 0.0952 ohm/mileAC Nominal Resistance at 180ºC 0.0785 ohm/km 0.1267 ohm/mile

    1225 @ 100C & 50 Hz1850 @ 180C & 50 Hz

    GMR (estimated) 0.012 m 0.040 ftInductive Reactance 0.203 ohm/km 0.391 ohm/mileCapacitive Reactance 0.173 Mohm-km 0.089 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-101-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Rome

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 609.9 sq. mm (1203.7 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    16/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 629.2 mm 2 1241.7 kcmilNominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.Nominal Cross-sectional Area of Core 60.3 mm 2 0.093 in2

    Overall Diameter of Conductor 30.42 mm 1.198 in.Nominal Cross-sectional Area of the Conductor 689.5 mm 2 1.069 in2

    Ultimate Tensile Strength of Conductor 1,2 165.6 kN 37.2 kipsRated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kipsCore Nominal Mass per unit length 113 kg/km 76 lb/kftConductor Nominal Mass per unit length 1852.3 kg/km 1244.9 lb/kftAluminum Nominal Mass per unit length** 1739.3 kg/km 1169.0 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.96E-05 /oC 1.09E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 115.9 GPa 16.8 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 63.1 GPa 9.1 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0445 ohm/km 0.0716 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0466 ohm/km 0.0758 ohm/mileAC Nominal Resistance at 75ºC 0.0554 ohm/km 0.0898 ohm/mileAC Nominal Resistance at 180ºC 0.0738 ohm/km 0.1192 ohm/mile

    1269 @ 100C & 50 Hz1918 @ 180C & 50 Hz

    GMR (estimated) 0.012 m 0.040 ftInductive Reactance 0.202 ohm/km 0.390 ohm/mileCapacitive Reactance 0.172 Mohm-km 0.089 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-103-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Vienna

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 647.7 sq. mm (1278.2 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    17/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 668.3 mm 2 1318.9 kcmilNominal Diameter of Composite Core (CTC Part Number 200-007) 9.53 mm 0.375 in.Nominal Cross-sectional Area of Core 71.3 mm 2 0.111 in2

    Overall Diameter of Conductor 31.50 mm 1.240 in.Nominal Cross-sectional Area of the Conductor 739.6 mm 2 1.146 in2

    Ultimate Tensile Strength of Conductor 1,2 191.4 kN 43.0 kipsRated Strength of Core - 313 ksi (2158 MPa) 153.8 kN 34.6 kipsCore Nominal Mass per unit length 132 kg/km 89 lb/kftConductor Nominal Mass per unit length 1983.9 kg/km 1333.3 lb/kftAluminum Nominal Mass per unit length** 1851.9 kg/km 1244.6 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.94E-05 /oC 1.08E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 63.2 GPa 9.2 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0420 ohm/km 0.0676 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0440 ohm/km 0.0717 ohm/mileAC Nominal Resistance at 75ºC 0.0523 ohm/km 0.0849 ohm/mileAC Nominal Resistance at 180ºC 0.0697 ohm/km 0.1126 ohm/mile

    1318 @ 100C & 50 Hz1996 @ 180C & 50 Hz

    GMR (estimated) 0.013 m 0.042 ftInductive Reactance 0.200 ohm/km 0.385 ohm/mileCapacitive Reactance 0.170 Mohm-km 0.088 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-104-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Budapest

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 688 sq. mm (1357.7 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    18/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 690.7 mm 2 1363.1 kcmilNominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.Nominal Cross-sectional Area of Core 60.3 mm 2 0.093 in2

    Overall Diameter of Conductor 31.77 mm 1.251 in.Nominal Cross-sectional Area of the Conductor 751.0 mm 2 1.164 in2

    Ultimate Tensile Strength of Conductor 1,2 169.1 kN 38.0 kipsRated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kipsCore Nominal Mass per unit length 113 kg/km 76 lb/kftConductor Nominal Mass per unit length 2029.8 kg/km 1364.2 lb/kftAluminum Nominal Mass per unit length** 1916.8 kg/km 1288.3 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.98E-05 /oC 1.10E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 62.7 GPa 9.1 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0407 ohm/km 0.0655 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0428 ohm/km 0.0699 ohm/mileAC Nominal Resistance at 75ºC 0.0508 ohm/km 0.0826 ohm/mileAC Nominal Resistance at 180ºC 0.0676 ohm/km 0.1093 ohm/mile

    1340 @ 100C & 50 Hz2032 @ 180C & 50 Hz

    GMR (estimated) 0.013 m 0.042 ftInductive Reactance 0.199 ohm/km 0.385 ohm/mileCapacitive Reactance 0.169 Mohm-km 0.088 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-105-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Prague

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 711 sq. mm (1403.2 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    19/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 733.2 mm 2 1446.9 kcmilNominal Diameter of Composite Core (CTC Part Number 200-007) 9.53 mm 0.375 in.Nominal Cross-sectional Area of Core 71.3 mm 2 0.111 in2

    Overall Diameter of Conductor 32.85 mm 1.293 in.Nominal Cross-sectional Area of the Conductor 804.5 mm 2 1.247 in2

    Ultimate Tensile Strength of Conductor 1,2 195.0 kN 43.8 kipsRated Strength of Core - 313 ksi (2158 MPa) 153.8 kN 34.6 kipsCore Nominal Mass per unit length 132 kg/km 89 lb/kftConductor Nominal Mass per unit length 2169.5 kg/km 1458.1 lb/kftAluminum Nominal Mass per unit length** 2037.5 kg/km 1369.4 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.96E-05 /oC 1.09E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 62.8 GPa 9.1 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0384 ohm/km 0.0618 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0405 ohm/km 0.0661 ohm/mileAC Nominal Resistance at 75ºC 0.0480 ohm/km 0.0781 ohm/mileAC Nominal Resistance at 180ºC 0.0638 ohm/km 0.1032 ohm/mile

    1392 @ 100C & 50 Hz2113 @ 180C & 50 Hz

    GMR (estimated) 0.013 m 0.043 ftInductive Reactance 0.197 ohm/km 0.381 ohm/mileCapacitive Reactance 0.167 Mohm-km 0.087 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-106-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Munich

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 754.8 sq. mm (1489.5 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    20/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 759.0 mm 2 1497.9 kcmilNominal Diameter of Composite Core (CTC Part Number 200-009) 9.78 mm 0.385 in.Nominal Cross-sectional Area of Core 75.1 mm 2 0.116 in2

    Overall Diameter of Conductor 33.40 mm 1.315 in.Nominal Cross-sectional Area of the Conductor 834.1 mm 2 1.293 in2

    Ultimate Tensile Strength of Conductor 1,2 204.8 kN 46.0 kipsRated Strength of Core - 313 ksi (2158 MPa) 162.1 kN 36.4 kipsCore Nominal Mass per unit length 143 kg/km 96 lb/kftConductor Nominal Mass per unit length 2248.1 kg/km 1510.9 lb/kftAluminum Nominal Mass per unit length** 2105.1 kg/km 1414.8 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.96E-05 /oC 1.09E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 62.9 GPa 9.1 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0370 ohm/km 0.0595 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0391 ohm/km 0.0639 ohm/mileAC Nominal Resistance at 75ºC 0.0464 ohm/km 0.0754 ohm/mileAC Nominal Resistance at 180ºC 0.0616 ohm/km 0.0996 ohm/mile

    1424 @ 100C & 50 Hz2164 @ 180C & 50 Hz

    GMR (estimated) 0.013 m 0.044 ftInductive Reactance 0.196 ohm/km 0.379 ohm/mileCapacitive Reactance 0.166 Mohm-km 0.086 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-107-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® London

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 781.3 sq. mm (1541.9 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    21/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 813.7 mm 2 1605.8 kcmilNominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.Nominal Cross-sectional Area of Core 60.3 mm 2 0.093 in2

    Overall Diameter of Conductor 34.16 mm 1.345 in.Nominal Cross-sectional Area of the Conductor 874.0 mm 2 1.355 in2

    Ultimate Tensile Strength of Conductor 1,2 176.0 kN 39.6 kipsRated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kipsCore Nominal Mass per unit length 113 kg/km 76 lb/kftConductor Nominal Mass per unit length 2365.4 kg/km 1589.7 lb/kftAluminum Nominal Mass per unit length** 2252.4 kg/km 1513.8 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 2.03E-05 /oC 1.13E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 62.0 GPa 9.0 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0345 ohm/km 0.0555 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0368 ohm/km 0.0604 ohm/mileAC Nominal Resistance at 75ºC 0.0435 ohm/km 0.0710 ohm/mileAC Nominal Resistance at 180ºC 0.0576 ohm/km 0.0933 ohm/mile

    1480 @ 100C & 50 Hz2254 @ 180C & 50 Hz

    GMR (estimated) 0.014 m 0.045 ftInductive Reactance 0.195 ohm/km 0.377 ohm/mileCapacitive Reactance 0.165 Mohm-km 0.085 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-109-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Paris

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 837.6 sq. mm (1653 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    22/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 944.9 mm 2 1864.7 kcmilNominal Diameter of Composite Core (CTC Part Number 200-009) 9.78 mm 0.385 in.Nominal Cross-sectional Area of Core 75.1 mm 2 0.116 in2

    Overall Diameter of Conductor 36.85 mm 1.451 in.Nominal Cross-sectional Area of the Conductor 1020.0 mm 2 1.581 in2

    Ultimate Tensile Strength of Conductor 1,2 215.3 kN 48.4 kipsRated Strength of Core - 313 ksi (2158 MPa) 162.1 kN 36.4 kipsCore Nominal Mass per unit length 143 kg/km 96 lb/kftConductor Nominal Mass per unit length 2759.1 kg/km 1854.3 lb/kftAluminum Nominal Mass per unit length** 2616.1 kg/km 1758.2 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 2.02E-05 /oC 1.12E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 62.0 GPa 9.0 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0297 ohm/km 0.0478 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0321 ohm/km 0.0529 ohm/mileAC Nominal Resistance at 75ºC 0.0378 ohm/km 0.0619 ohm/mileAC Nominal Resistance at 180ºC 0.0498 ohm/km 0.0808 ohm/mile

    1623 @ 100C & 50 Hz2483 @ 180C & 50 Hz

    GMR (estimated) 0.015 m 0.048 ftInductive Reactance 0.190 ohm/km 0.367 ohm/mileCapacitive Reactance 0.161 Mohm-km 0.083 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-110-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Antwerp

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 972.7 sq. mm (1919.6 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    23/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 1006.5 mm 2 1986.3 kcmilNominal Diameter of Composite Core (CTC Part Number 200-011) 10.54 mm 0.415 in.Nominal Cross-sectional Area of Core 87.3 mm 2 0.135 in2

    Overall Diameter of Conductor 38.20 mm 1.504 in.Nominal Cross-sectional Area of the Conductor 1093.8 mm 2 1.695 in2

    Ultimate Tensile Strength of Conductor 1,2 244.9 kN 55.1 kipsRated Strength of Core - 313 ksi (2158 MPa) 188.3 kN 42.3 kipsCore Nominal Mass per unit length 164 kg/km 110 lb/kftConductor Nominal Mass per unit length 2948.8 kg/km 1981.9 lb/kftAluminum Nominal Mass per unit length** 2784.8 kg/km 1871.6 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 2.00E-05 /oC 1.11E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 62.3 GPa 9.0 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0278 ohm/km 0.0447 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0303 ohm/km 0.0499 ohm/mileAC Nominal Resistance at 75ºC 0.0356 ohm/km 0.0583 ohm/mileAC Nominal Resistance at 180ºC 0.0467 ohm/km 0.0759 ohm/mile

    1692 @ 100C & 50 Hz2594 @ 180C & 50 Hz

    GMR (estimated) 0.015 m 0.050 ftInductive Reactance 0.188 ohm/km 0.363 ohm/mileCapacitive Reactance 0.159 Mohm-km 0.082 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-112-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Berlin (Madrid Ice)

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1036.1 sq. mm (2044.7 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    24/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 1013.1 mm 2 1999.3 kcmilNominal Diameter of Composite Core (CTC Part Number 200-009) 9.78 mm 0.385 in.Nominal Cross-sectional Area of Core 75.1 mm 2 0.116 in2

    Overall Diameter of Conductor 38.20 mm 1.504 in.Nominal Cross-sectional Area of the Conductor 1088.2 mm 2 1.687 in2

    Ultimate Tensile Strength of Conductor 1,2 219.1 kN 49.3 kipsRated Strength of Core - 313 ksi (2158 MPa) 162.1 kN 36.4 kipsCore Nominal Mass per unit length 143 kg/km 96 lb/kftConductor Nominal Mass per unit length 2947.8 kg/km 1981.2 lb/kftAluminum Nominal Mass per unit length** 2804.8 kg/km 1885.1 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 2.04E-05 /oC 1.13E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 61.8 GPa 9.0 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0276 ohm/km 0.0444 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0302 ohm/km 0.0498 ohm/mileAC Nominal Resistance at 75ºC 0.0354 ohm/km 0.0581 ohm/mileAC Nominal Resistance at 180ºC 0.0464 ohm/km 0.0755 ohm/mile

    1696 @ 100C & 50 Hz2602 @ 180C & 50 Hz

    GMR (estimated) 0.015 m 0.050 ftInductive Reactance 0.188 ohm/km 0.363 ohm/mileCapacitive Reactance 0.159 Mohm-km 0.082 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-113-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Madrid

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1042.9 sq. mm (2058.1 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    25/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 228.5 mm 2 450.9 kcmilNominal Diameter of Composite Core (CTC Part Number 200-011) 10.54 mm 0.415 in.Nominal Cross-sectional Area of Core 87.3 mm 2 0.135 in2

    Overall Diameter of Conductor 20.78 mm 0.818 in.Nominal Cross-sectional Area of the Conductor 315.8 mm 2 0.489 in2

    Ultimate Tensile Strength of Conductor 1,2 201.2 kN 45.2 kipsRated Strength of Core - 313 ksi (2158 MPa) 188.3 kN 42.3 kipsCore Nominal Mass per unit length 164 kg/km 110 lb/kftConductor Nominal Mass per unit length 798.7 kg/km 536.8 lb/kftAluminum Nominal Mass per unit length** 634.7 kg/km 426.5 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.39E-05 /oC 7.74E-06 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 73.0 GPa 10.6 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.1230 ohm/km 0.1979 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.1257 ohm/km 0.2024 ohm/mileAC Nominal Resistance at 75ºC 0.1504 ohm/km 0.2422 ohm/mileAC Nominal Resistance at 180ºC 0.2024 ohm/km 0.3258 ohm/mile

    691 @ 100C & 50 Hz1027 @ 180C & 50 Hz

    GMR (estimated) 0.009 m 0.029 ftInductive Reactance 0.222 ohm/km 0.429 ohm/mileCapacitive Reactance 0.194 Mohm-km 0.100 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-133-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Monte Carlo

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 235.2 sq. mm (464.2 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    26/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 453.7 mm 2 895.4 kcmilNominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.Nominal Cross-sectional Area of Core 60.3 mm 2 0.093 in2

    Overall Diameter of Conductor 26.40 mm 1.039 in.Nominal Cross-sectional Area of the Conductor 514.0 mm 2 0.797 in2

    Ultimate Tensile Strength of Conductor 1,2 155.7 kN 35.0 kipsRated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kipsCore Nominal Mass per unit length 113 kg/km 76 lb/kftConductor Nominal Mass per unit length 1367.8 kg/km 919.3 lb/kftAluminum Nominal Mass per unit length** 1254.8 kg/km 843.3 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.85E-05 /oC 1.03E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 64.8 GPa 9.4 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0617 ohm/km 0.0993 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0637 ohm/km 0.1031 ohm/mileAC Nominal Resistance at 75ºC 0.0760 ohm/km 0.1228 ohm/mileAC Nominal Resistance at 180ºC 0.1019 ohm/km 0.1642 ohm/mile

    1039 @ 100C & 50 Hz1560 @ 180C & 50 Hz

    GMR (estimated) 0.011 m 0.035 ftInductive Reactance 0.210 ohm/km 0.406 ohm/mileCapacitive Reactance 0.180 Mohm-km 0.093 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-134-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Stockholm 3L

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 467 sq. mm (921.7 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    27/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 543.5 mm 2 1072.6 kcmilNominal Diameter of Composite Core (CTC Part Number 200-007) 9.53 mm 0.375 in.Nominal Cross-sectional Area of Core 71.3 mm 2 0.111 in2

    Overall Diameter of Conductor 28.62 mm 1.127 in.Nominal Cross-sectional Area of the Conductor 614.8 mm 2 0.953 in2

    Ultimate Tensile Strength of Conductor 1,2 184.4 kN 41.5 kipsRated Strength of Core - 313 ksi (2158 MPa) 153.8 kN 34.6 kipsCore Nominal Mass per unit length 132 kg/km 89 lb/kftConductor Nominal Mass per unit length 1643.2 kg/km 1104.4 lb/kftAluminum Nominal Mass per unit length** 1511.2 kg/km 1015.7 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.87E-05 /oC 1.04E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 64.3 GPa 9.3 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0517 ohm/km 0.0832 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0536 ohm/km 0.0870 ohm/mileAC Nominal Resistance at 75ºC 0.0639 ohm/km 0.1034 ohm/mileAC Nominal Resistance at 180ºC 0.0855 ohm/km 0.1378 ohm/mile

    1160 @ 100C & 50 Hz1748 @ 180C & 50 Hz

    GMR (estimated) 0.012 m 0.038 ftInductive Reactance 0.205 ohm/km 0.396 ohm/mileCapacitive Reactance 0.175 Mohm-km 0.091 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-135-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Kolkata

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 559.5 sq. mm (1104.1 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    28/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 685.4 mm 2 1352.6 kcmilNominal Diameter of Composite Core (CTC Part Number 200-007) 9.53 mm 0.375 in.Nominal Cross-sectional Area of Core 71.3 mm 2 0.111 in2

    Overall Diameter of Conductor 31.77 mm 1.251 in.Nominal Cross-sectional Area of the Conductor 756.7 mm 2 1.173 in2

    Ultimate Tensile Strength of Conductor 1,2 192.4 kN 43.3 kipsRated Strength of Core - 313 ksi (2158 MPa) 153.8 kN 34.6 kipsCore Nominal Mass per unit length 132 kg/km 89 lb/kftConductor Nominal Mass per unit length 2034.9 kg/km 1367.6 lb/kftAluminum Nominal Mass per unit length** 1902.9 kg/km 1278.9 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.94E-05 /oC 1.08E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 63.1 GPa 9.2 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0410 ohm/km 0.0660 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0431 ohm/km 0.0701 ohm/mileAC Nominal Resistance at 75ºC 0.0511 ohm/km 0.0830 ohm/mileAC Nominal Resistance at 180ºC 0.0681 ohm/km 0.1101 ohm/mile

    1336 @ 100C & 50 Hz2025 @ 180C & 50 Hz

    GMR (estimated) 0.013 m 0.042 ftInductive Reactance 0.199 ohm/km 0.384 ohm/mileCapacitive Reactance 0.169 Mohm-km 0.088 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-136-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Mumbai

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 705.6 sq. mm (1392.4 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    29/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 1409.7 mm 2 2782.0 kcmilNominal Diameter of Composite Core (CTC Part Number 200-011) 10.54 mm 0.415 in.Nominal Cross-sectional Area of Core 87.3 mm 2 0.135 in2

    Overall Diameter of Conductor 44.75 mm 1.762 in.Nominal Cross-sectional Area of the Conductor 1497.0 mm 2 2.320 in2

    Ultimate Tensile Strength of Conductor 1,2 267.6 kN 60.2 kipsRated Strength of Core - 313 ksi (2158 MPa) 188.3 kN 42.3 kipsCore Nominal Mass per unit length 164 kg/km 110 lb/kftConductor Nominal Mass per unit length 4065.7 kg/km 2732.5 lb/kftAluminum Nominal Mass per unit length** 3901.7 kg/km 2622.3 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 2.07E-05 /oC 1.15E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 61.2 GPa 8.9 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0199 ohm/km 0.0320 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0231 ohm/km 0.0388 ohm/mileAC Nominal Resistance at 75ºC 0.0267 ohm/km 0.0402 ohm/mileAC Nominal Resistance at 180ºC 0.0343 ohm/km 0.0432 ohm/mile

    2050 @ 100C & 50 Hz3189 @ 180C & 50 Hz

    GMR (estimated) 0.018 m 0.058 ftInductive Reactance 0.178 ohm/km 0.345 ohm/mileCapacitive Reactance 0.150 Mohm-km 0.077 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-137-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Athens

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1451.2 sq. mm (2863.8 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    30/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 880.9 mm 2 1738.4 kcmilNominal Diameter of Composite Core (CTC Part Number 200-011) 10.54 mm 0.415 in.Nominal Cross-sectional Area of Core 87.3 mm 2 0.135 in2

    Overall Diameter of Conductor 35.76 mm 1.408 in.Nominal Cross-sectional Area of the Conductor 968.2 mm 2 1.501 in2

    Ultimate Tensile Strength of Conductor 1,2 237.9 kN 53.5 kipsRated Strength of Core - 313 ksi (2158 MPa) 188.3 kN 42.3 kipsCore Nominal Mass per unit length 164 kg/km 110 lb/kftConductor Nominal Mass per unit length 2766.2 kg/km 1859.1 lb/kftAluminum Nominal Mass per unit length** 2602.2 kg/km 1748.9 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.96E-05 /oC 1.09E-05 /oFFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 MsiFinal Modulus of Elasticity Below Thermal Kneepoint 62.9 GPa 9.1 Msi

    Electrical SpecificationsNominal Resistivity of Aluminum at 20ºC, DC 63% IACS 0.0318 ohm/km 0.0512 ohm/mileTemperature Coefficient of Resistance 0.00403 0.00403Frequency 50 Hz 60 HzAC Nominal Resistance at 25ºC 0.0340 ohm/km 0.0559 ohm/mileAC Nominal Resistance at 75ºC 0.0402 ohm/km 0.0656 ohm/mileAC Nominal Resistance at 180ºC 0.0531 ohm/km 0.0861 ohm/mile

    1560 @ 100C & 50 Hz2381 @ 180C & 50 Hz

    GMR (estimated) 0.014 m 0.047 ftInductive Reactance 0.192 ohm/km 0.370 ohm/mileCapacitive Reactance 0.162 Mohm-km 0.084 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-138-D www.ctcglobal.com Date Produced: 8/28/2012

    ACCC® Bordeaux

    NOT RELEASED

    For quest ions , p lease contact CTC Appl icat ion Engineer ing Department : appl icat ionsupp ort@ctccable .com

    Metric Imperial

    Metric Imperial

    AC Current Rating at Given Temperature 3

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slightvariations in some of the indicated values.

    **ACCC ® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40°C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCC ® is 180°C and a maximum emergency temperature of 200°C (10,000 hours over the life of the conductor).

    *ACCC® conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 906.8 sq. mm (1789.6 kcmil)

  • 8/20/2019 ACCC® Helsinki Spec Sheets

    31/31

    DATA SHEET:

    Governing Units: Metric

    Mechanical SpecificationsNominal Aluminum Cross-sectional Area* 406.4 mm 2 802.0 kcmilNominal Diameter of Composite Core (CTC Part Number 210-007) 9.53 mm 0.375 in.Nominal Cross-sectional Area of Core 71.3 mm 2 0.111 in2

    Overall Diameter of Conductor 25.14 mm 0.990 in.Nominal Cross-sectional Area of the Conductor 477.7 mm 2 0.740 in2

    Ultimate Tensile Strength of Conductor 1,2 207.1 kN 46.6 kipsRated Strength of Core - 375 ksi (2586 MPa) 184.2 kN 41.4 kipsCore Nominal Mass per unit length 128 kg/km 86 lb/kftConductor Nominal Mass per unit length 1253.6 kg/km 842.5 lb/kftAluminum Nominal Mass per unit length** 1125.6 kg/km 756.5 lb/kftMaximum Allowable Operating Temperature at Surface 4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 7.51E-07 /oC 4.17E-07 /

    oF

    Coeffic