    ACTIVE HARMONIC FILTER

  • 8/13/2019 ActiveHarmonicFilterBrochure Siemens

    2/8

    A proven technology is now available to isolate

    harmonic current and protect the equipmenton your power distribution system fromdamage due to harmonic voltage distortion.

    By actively monitoring the non-linear current

    demanded by the load, the ASIRobicon ActiveHarmonic Filter (AHF) electronically generatesan adaptive current waveform which matchesthe shape of the non-linear portion of the

    load current.

    By injecting this matching current in the bus,

    the AHF stops the destructive current at thepoint of connection.

    By this mode of cancellation, the AHF

    provides the industrys best attenuation ofharmonic currents.

    The AHFs IGBT Converter Bridge reacts at

    micro-second speed to changes in thenon-linear load current, allowing cancella-tion even as the high frequency harmoniccomponents change.

    The AHF is not affected by changes in theimpedance in the system, nor will it reactwith other devices. The AHF will not adverselyaffect the resonant points in the system.

    The AHF has no series components, allow-ing an easy-to-install connection. If greater

    capacity is required, the AHF has built-incircuitry to allow for simple paralleling.Paralleled systems are available for singlepoint eld connection.

    Eliminate Harmonic Distortion Damagewith ASIRobicons Active Harmonic Filter

    True Harmonic Current Cancellation from t

  • 8/13/2019 ActiveHarmonicFilterBrochure Siemens

    3/8

    Adaptive Injection Mode

    Continuously monitors the load harmoniccurrent and cancels it.

    Industrys Best HarmonicCancellation Device

    Superior non-linear current cancellation from the2nd to 51st harmonic. Greatly reduces notchingcaused by SCR switching, diode rectication

    and other load generated transients.

    Parallel Connection

    With no series components, the AHF can

    be easily installed without major re-work.Current measurement is made with currenttransformers. Energy consumption is low.

    Electronic VAR Current

    In addition to harmonic cancellation current,the AHF electronically produces leading VARcurrent, aiding in the improvement of system

    power factor without the negative effects of

    traditional power factor correction capacitors.

    Current Limited

    The AHF unit is limited and can work in anysystem without damage, regardless of themagnitude of harmonic current demanded bythe load.

    Safety and Access

    The AHFs power selections are coveredwithin the enclosure. Removable panels allow

    easy front access and clear view of majorcomponents.

    IEEE 519-1992

    The AHF units are easily paralleled andcan be sized to guarantee compliance withIEEE 519-1992 harmonic standards undermost load conditions.

    Certications

    UL, cUL, CE Mark

    Available Options

    EMC FilterMolded-Case Disconnect SwitchSplit Core CTsNEMA 1 EnclosureDigital Display

    Features

    PICTURED, 100 AMP MODEL CONTAINS:

    High Frequency/EMI FilterIGBT Switching-Mode Power Stage

    DC Bus CapacitorsSoft Start Contactor Circuit

    Fast Acting/High Interrupting FusesMolded-Case Disconnect Switch

    World Leader in Electronic Current Control

  • 8/13/2019 ActiveHarmonicFilterBrochure Siemens

    4/8

    Adaptive Injection ModeHarmonic Filter

    The AHFs electronic bridge drawsleading reactive current from the

    power line, stores it in a DC capacitorbus, and delivers it back to the lineas harmonic current, meeting the

    loads demand for non-linear currentat the point of connection. The sourcedelivers fundamental current.

    Industrys Best HarmonicCancellation Device

    Unlike a tuned lter, the AHFcontinuously measures the loads

    changing non-linear current and injects

    the required waveform to supply theloads harmonic current demand fromthe 2nd to the 51st harmonic.

    Easy to Apply

    The AHF is a non-resonating, non-tuned device. It can be installedanywhere in the distribution system. A

    simple measurement to determine themagnitude of harmonic current is allthat is needed. For new installationsthe equipment manufacturer or your

    AHF supplier can provide the requireddata.

    IGBT Bridge

    AHFs Class-D Switching Mode CurrentSource Amplier uses Insulated GateBipolar Transistors. These are high

    frequency switched power electronicdevices that allow high resolution andmicro-second response to match theloads non-linear current waveform.

    The AHF is connected parallel to thebus through a soft start circuit. Whenenergized, the AHF draws leading

    reactive current and the converter usesthis to charge a DC Bus.

    The current transformers on two ofthe phases measure the load currentAn electronic notch lter rejects thefundamental frequency component

    and passes the distortion currentcomponents (harmonic as well asnon-harmonic, transient and sub-harmonic components). Electronically

    controlled linear attenuators reducethe harmonic current signals to limit

    the AHFs harmonic current output tothe units rated RMS value.

    The amplier control logic uses thissignal to modulate current waveform

    which matches the non-fundamentacurrent demanded by the non-lineaload.

    Unique Features

  • 8/13/2019 ActiveHarmonicFilterBrochure Siemens

    5/8

    3 Wire Models: Chassis Only Enclosure-NEMA 1 Approx. Approx Approx ApproxAmps Volts Freq Hz Size (in) Weight (lbs) Size (in) Weight (lbs)

    25 208-600 50-60 31X16X14 115 31X16X14 13050 208-600 50-60 49X16X14 175 49X16X14 190

    100 208-600 50-60 75X20X15 375 86X24X20 600150 208-600 50-60 75X28X15 420 86X32X20 700200 208-600 50-60 75X44X15 450 86X48X20 875300 208-600 50-60 75X44X15 550 86X48X20 700400 208-600 50-60 75X44X15 650 86X48X20 850

    4 Wire Models: Chassis Only Enclosure-NEMA 1 Approx. Approx Approx ApproxAmps Volts Freq Hz Size (in) Weight (lbs) Size (in) Weight (lbs)

    25 208-600 50-60 31X16X14 115 31X16X14 13050 208-600 50-60 49X16X14 175 49X16X14 190100 208-600 50-60 75X20X15 375 86X24X20 600150 208-600 50-60 75X28X15 420 86X32X20 700200 208-600 50-60 75X44X15 450 86X48X20 875300 208-600 50-60 75X44X15 550 86X48X20 700400 208-600 50-60 75X44X15 650 86X48X20 850

    Chassis models include a control/display panel, 6 feet of ribbon cable, current transformers and 200k AIC fuses.

    Product Offering Summary3-wire and 4-wire models range between 25-400 amps withinputs of 208 through 600 VAC. 60 Hz is standard. 50Hz isavailable upon request. Current Transformer (CT) requirements

    must maintain a ratio of 2000:1 to achieve proper operation.CT dimensions are specied per application. Split core CTs areavailable upon request. AHFs can be paralleled with one set of

    CTs. These units are available in chassis or NEMA 1 enclosures.

    Consult factory for special enclosure requirements.

    All models include a control/display panel with the following

    switch and LED indicators.

    Supplied loose with chassis modelsOn-Off/Reset . . . . . . . . . Selector Switch

    Power Applied . . . . . . . . LED IndicatorOperate . . . . . . . . . . . . LED IndicatorAt Max. Capacity . . . . . . LED Indicator

    Fault . . . . . . . . . . . . . . LED Indicator

    Temperature Warning . . . LED Indicator

    Dimensions

  • 8/13/2019 ActiveHarmonicFilterBrochure Siemens

    6/8

    ASIRobicon AHF FieldResults- 100 Amp

    Attenuation From the 2ndto 51st Harmonic

    Typical results of the AHF duringoperation in parallel with SCR Bridge

    Rectier non-linear load, seen fromDelta side of a Delta-Wye transformer.

    Typical ConnectionDiagram

    CURRENT (AHF OFF) CURRENT (AHF ON)

    VOLTAGE (AHF OFF) VOLTAGE (AHF ON)

    Source Without AHF Conditioner Source With AHF Conditioner

  • 8/13/2019 ActiveHarmonicFilterBrochure Siemens

    7/8

    3A025B6-xx 60 208 25 10 27 3.5 0.5

    3A050B6-xx 60 208 50 19 54 6.9 0.9

    3A100B6-xx 60 208 100 38 107 14.0 1.93A150B6-xx 60 208 150 57 160 20.5 2.8

    3A200B6-xx 60 208 200 76 213 27.3 3.8

    3A300B6-xx 60 208 300 114 321 42.0 5.7

    3A400B6-xx 60 208 400 144 428 56.0 7.6

    3A025C6-xx 60 240 25 11 27 4.4 0.5

    3A050C6-xx 60 240 50 21 54 8.8 0.9

    3A100C6-xx 60 240 100 42 108 18.0 1.9

    3A150C6-xx 60 240 150 63 163 26.0 2.8

    3A200C6-xx 60 240 200 82 216 34.0 3.8

    3A300C6-xx 60 240 300 126 324 54.0 5.7

    3A400C6-xx 60 240 400 168 432 72.0 7.6

    3A025G6-xx 60 480 25 17 30 14.0 0.6

    3A050G6-xx 60 480 50 33 60 27.0 1.13A100G6-xx 60 480 100 65 119 54.0 2.2

    3A150G6-xx 60 480 150 98 179 81.4 3.3

    3A200G6-xx 60 480 200 130 238 108.0 4.4

    3A300G6-xx 60 480 300 195 357 162.0 6.6

    3A400G6-xx 60 480 400 260 476 216.0 8.8

    3A022H6-xx 60 600 22.5 19 29 20.0 0.6

    3A045H6-xx 60 600 45 38 59 39.0 1.1

    3A090H6-xx 60 600 90 75 117 78.0 2.2

    3A135H6-xx 60 600 135 113 176 117.0 3.3

    3A180H6-xx 60 600 180 150 234 156.0 6.6

    3A300H6-xx 60 600 270 225 351 234.0 6.6

    3A400H6-xx 60 600 360 300 468 312.0 8.8

    3A025F5-xx 50 400 25 14 29 9.3 0.6

    3A050F5-xx 50 400 50 27 57 19.0 1.0

    3A100F5-xx 50 400 100 54 114 37.0 2.1

    3A150F5-xx 50 400 150 81 170 56.0 3.1

    3A200F5-xx 50 400 200 104 225 72.0 4.2

    3A300F5-xx 50 400 300 162 342 111.0 6.3

    3A400F5-xx 50 400 400 216 456 148.0 8.4

    Line Voltage Nominal +6%, -14% steady state (+/- 10% at 208 VAC)

    Nominal +11%, -19% 20 minutes (+/- 15% at 208 VAC)

    Transient IEEE 587, class B

    Line Frequency Nominal +/- -5%

    Interrupting Capacity 200kA, fused

    Peak Harmonic Current 3x nominal RMS maximum rating

    Reactive Current Injected 85% electronically generated

    Response Time 300 microseconds

    Temperature 0 to 40 C operating, -30 to 50 C storage

    Humidity up to 95%, non-condensing

    Altitude to 1500 meters

    Technical Data

    (consult factory for 4-wire models)

    Cancellation Corrective Total Corrective Losses @ 3-Wire Freq Nominal Harmonic Reactive Current VARs RatedModel Number Hz Voltage Current Arms Current Arms Injected Arms kVARs Output kW

  • 8/13/2019 ActiveHarmonicFilterBrochure Siemens

    8/8

    SALES AND SYSTEM INTEGRATION

    BRAZILASIRobicon do Brasil Ltda.Rua Karl Richter, 5805709-030 So Paulo SP BrazilPhone +55.11.3507.1922Fax +55.11.3507.1707

    CANADA

    ASIRobicon Canada Ltd.380 Armour Road, #215Peterborough, ONCanada, K9H 7L7Phone +1.705.755.1166Fax +1.705.755.1174

    CHINA

    ASIRobicon ChinaMetal SystemsRm 816, Tower BCNT, Manhattan Building6 Chaoyangmen Beidajie Er Huan LuDong Cheng DistrictBeijing 100027Phone +86.10.6554.4490Fax +86.10.6554.4493

    ASIRobicon (Shanghai) Electric Co. Ltd.460 Gao Xiang Huan RoadPudong New AreaShanghai 200137P.R. ChinaPhone +86.21.5306.5218

    Fax +86.21.5306.5190

    FRANCE

    ASIRobicon s.a.Loire AutomationZ.I. du Buisson, Rue de la PoudrireF-42230 Roche-La-MolirePhone +33.4.7790.7600Fax +33.4.7790.7629

    www.asirobicon.com

    CUSTOMER SERVICE AND SUPPORT CALL CENTERS

    AMERICAS

    ASIRobicon, Corp.500 Hunt Valley RoadNew Kensington, PA 15068, USAPhone +1.724.339.9501Fax [email protected]

    ASIA-PACIFIC

    ASIRobicon China460 Gao Xiang Huan RoadPudong New AreaShanghai 200137P.R. ChinaPhone +86.21.5306.5218Fax [email protected]

    EUROPE, MIDDLE EAST, AFRICA

    ASIRobicon S.p.A.

    Viale Sarca, 336I-20126 Milano, ItalyPhone +39.02.6445.4254Fax [email protected]

    GERMANYASIRobicon GmbH

    Industrial SystemsWahlerstrasse 12D-40472 DsseldorfPhone +49.211.96507.0Fax +49.211.96507.111

    ROMANIA

    ASIRobicon Romania, S.R.L.Boulevard Laminorului 113Bucarest Sector 1Phone +40.21.210.9458Fax +40.21.211.8252

    UNITED KINGDOM

    ASIRobicon Ltd.Hill GrahamLincoln Road, CressexHigh Wycombe, BucksHP12 3RBPhone +44.1494.833.600Fax +44.1494.438.810

    USA

    ASIRobicon, Corp.Metal Systems100 Sagamore Hill RoadPittsburgh, PA 15239Phone +1.724.334.6210Fax +1.724.334.6251

    BUSINESS UNITS

    ITALYASIRobicon S.p.A.Metal SystemsCorso Perrone, 11I-16152 GenovaPhone +39.010.6063.409Fax +39.010.6063.773

    ASIRobicon S.p.A.BMB-ISE Automation SystemsS.S.11 Ca Sordis 4I-36054 Montebello Vicentino (VI)Phone +39.0444.449.100Fax +39.0444.440.001

    ASIRobicon S.p.A.

    Drives and Power ControlsViale Sarca, 336I-20126 MilanoPhone +39.02.6445.4523Fax +39.02.6445.4401

    ASIRobicon S.p.A.AC and DC DrivesS.S.11 Ca Sordis 4I-36054 Montebello Vicentino (VI)Phone +39.0444.449.100Fax +39.0444.449.270

    ASIRobicon S.p.A.CRELP - Centro di Ricerca diElettronica di PotenzaTorre WTC - Via De Marini, 1I-16149 GenovaPhone +39.010.64025.1Fax +39.010.64025.40

    ASIRobicon S.p.A.Electric Motors and GeneratorsVia Marconi, 1I-34074 Monfalcone (GO)Phone +39.0481.717.230Fax +39.0481.717.330

    ASIRobicon S.p.A.IEG MotorsVia Flavia 130I-34147 TriestePhone +39.040.280.744Fax +39.040.829.708

    USAASIRobicon, Corp.Drives and Power Controls500 Hunt Valley Road

    New Kensington, PA 15068

    Phone +1.724.339.9500

    Fax +1.724.339.9504

    Copyright 2003 by ASIRobicon. All rights reserv

    V2