University Of Piraeus Department Of Digital System
VULNERABILITIES
OF THE MODBUS PROTOCOL
Submitted by Evangeliou I. Evangelia,
University of Piraeus, Athens, Greece February 2018
Master’s Supervisor: Xenakis Christos,
Associate Professor at University of Piraeus, Department of Digital Systems
Περιεχόµενα 1. Introduction 3
2. Modbus Protocol 3
2.1 Modbus description 4
2.2 MODBUS TCP/IP 6
2.3 Function Codes 7
3. Related Work 10
4. Abbreviaton 12
5. Vulnerabilities & Attacks 12
5.1.1 Vulnerabilities 12
5.2 Attacks against industrial control systems 14
6 The detection engine 17
6.1 Finite Sate Machine 19
7 Conclusion 25
8 References 26
1. Introduction
Industrial Control Systems (ICSs), such as those in power grid including “Supervisory and Data
Acquisition (SCADA)” systems, constitute the fundamental elements in the operation of modern power
systems, providing a wide range of applications that range from applications in large control center to
substations and controls of individual components. While originally ICSs had minimal networking
capabilities, they have incorporated Ethernet modems and packet switched communications, to support
communications with large number of devices.
One of the most commonly used protocols in industrial control systems is the Modicon Communication
Bus (Modbus). It is a method used for transmitting information over serial lines between electronic
devices. Typically is used to transmit signals from instrumentation and control devices back to a main
controller or data gathering system, for example a system that measures temperature and humidity and
communicates the results to a computer. Modbus is often used to connect a supervisory computer with
a remote terminal unit (RTU) in supervisory control and data acquisition (SCADA) systems. It was not
designed to provide security. At this thesis, it is confirmed that the Modbus protocol is vulnerable to
many attacks.
This thesis is divided into eight chapters. Chapter 2 gives a brief description of the existing Modbus
protocol and the Function Codes that are used. Chapter 3 reviews related work on Modbus
vulnerabilities and attack detection systems. Chapter 4 gives a short abbreviation for Modbus and
chapter 5 refers to vulnerabilities and classified attacks that exist. Chapter 6 introduces the theory
behind the intrusion detection mechanisms and implements all function codes at Finite State Machines.
Chapter 7 concludes the thesis.
2. Modbus Protocol
The Modbus protocol was developed in 1979 by Modicon, Incorporated, for industrial automation
systems and Modicon programmable controllers. It has since become an industry standard method for
the transfer of discrete/analog I/O information and register data industrial control and monitoring
devices. Modbus is now a widely-accepted, open, public-domain protocol that requires a license, but
does not require royalty payment to its owner.
Modbus is an application layer messaging protocol, positioned at level 7 of OSI network model. It
provides client/server communication between devices connected on different types of buses or
networks. It is currently implemented using:
● TCP/IP over Ethernet
● Asynchronous serial transmission over a variety of media (wire: EIA/TIA-232-E, EIA-422,
EIA/TIA-485-A, fiber, radio, etc.)
● Modbus PLUS, a high speed token passing network
Figure 1: Modbus Communication stack
Modbus protocol allows an easy communication within all types of network architectures. Every type of
devices (PLC, HMI, Control Panel, Driver, Motion Control, I/O Device etc.) can use Modbus protocol to
initiate a remote operation and communication can be done as well either on serial line or on Ethernet
TCP/IP networks.
2.1 Modbus description The Modbus protocol defines a simple protocol data unit (PDU) independent of the underlying
communication layers. The mapping of Modbus protocol on specific buses or network can introduce
some additional fields on the application data unit (ADU). Modbus communications are two types: (i)
query/response (communications between master/slave), or (ii) broadcast (a master sends a command
to all the slaves). A Modbus transaction comprises a single query or response frame, or a single
broadcast frame. A Modbus frame message contains the address of the intended receiver, the command
the receiver must execute and the data needed to execute the command.
For the communication between Modbus devices, a master-slave (client-server) technique is used in
which only one device (the master/client) can initiate transactions, which are called queries. The other
devices (slaves/servers) respond by supplying the requested data to the master, or by taking the action
requested in the query. A slave is any peripheral device which processes information and send its output
to the master using Modbus. I/O transducer, valve, network drive or any other measuring device can
play the role of slave, as it was referred above. A typical master device is a host computer running
appropriate application software, while other devices may function as both clients (master) and servers
(slaves).
The Modbus application data unit (ADU) is built by the master/client that initiates the Modbus
transaction. Masters can address individual slaves, or can initiate a broadcast message to all slaves.
Slaves return a response to all queries addressed to them individually, while they cannot respond to
broadcast queries, and do not initiate messages on their own – they only respond to queries from the
master. A master’s query will consist of a slave address (or a broadcast address), a function code
defining the requested action, any required data, and an error checking field. A slave’s respond consists
of fields confirming the action taken, any data to be returned, and an error checking filed. If no error
occurs, the slave’s response contains the data as requested, but in case of an error in the received
query, or if the slave is unable to perform the requested action, the slave will return an exception
message as its response. The error check field of the slave’s message frame allows the master to confirm
that the contents of the message are valid. Traditional Modbus message are transmitted serially and
parity checking is also applied to each transmitted character in its data frame.
Figure 2: Modbus transaction (error free)
Figure 3: Modbus transaction (error exception)
Modbus, as an application protocol, defines rules for organizing and interpreting data, but remains
simply a messaging structure, independent of the underlying physical layer. As it is shown below at
figure 4, it defines protocol data unit (PDU) and some times, some additional fields are introduced on
Application Data Unit (ADU), which are Additional Address and Error Check. In general, it is easy
understandable, freely available and accessible to anyone and is supported by many manufacturers.
Figure 4: Modbus Structure
● The Function Code field is coded in one byte and its valid codes are between 1 … 255 decimal. In
case, that a client sends a message to a server, the Function Code has information about the
kind of action to perform. Besides, Function Code “0” is not valid. Sub-function codes are added
to some function codes to define multiple actions. Function and sub-function are referred
analytically at chapter 2.3.
● The data field in a message sent from a client to a server devices contains additional information
that server uses to take the action defined by the function code. Register addresses, quantity of
items to be handled and the count of actual data bytes in the field are some items included at
data field. In case the server does not require any additional information, the data field can be
nonexistent (of zero length).
2.2 MODBUS TCP/IP
Modbus TCP/IP (also Modbus TCP) is simply the Modbus RTU protocol with a TCP interface that runs on
Ethernet. The Modbus messaging structure is the application protocol that defines the rules for
organizing and interpreting the data independent of the data transmission medium. TCP/IP refers to the
Transmission Control Protocol and Internet Protocol, which provides the transmission medium for
Modbus TCP/IP messaging. In other words, TCP/IP allows block of binary data to be exchanged between
computers. It is a world-wide standard that serves as the foundation for the World Wide Web.
The primary function of TCP is to ensure that all packets of data are received correctly, while IP makes
sure that messages are correctly addressed and routed. The TCP/IP combination is merely a transport
protocol, and does not define what the data means or how the data is to be interpreted. The
interpretation of data is a job of the application Modbus protocol.
To sum up, Modbus TCP/IP uses TCP/IP and Ethernet to carry the data of the Modbus message structure
between compatible devices, and combines a physical network (Ethernet), with a networking standard
(TCP/IP) and a standard method of representing data (Modbus as the application protocol). Simply,
Modbus TCP/IP message is a Modbus communication encapsulated in an Ethernet TCP/IP wrapper. In
practice, Modbus TCP embeds a standard Modbus data frame into a TCP frame, without the Modbus
checksum.
The Modbus commands and user data are themselves encapsulated into the data container of a TCP/IP
telegram without being modified in any way. However, the Modbus error checking field(checksum) is
not used, as the standard Ethernet TCP/IP link layer checksum methods are used to guaranty data
integrity. Further, the Modbus frame address field is supplanted by the unit identifier in Modbus TCP/IP,
and becomes part of the Modbus Application Protocol (MBAP) header. The function code and data fields
are absorbed in their original form.
Thus, a Modbus TCP/IP Application Unit (ADU) takes the form of a 7 bytes header, which consists of
transaction identifier, protocol identifier, length field and unit identifier, and the protocol data unit,
which consists of function code and data. ADU is embedded into the data field of a standard TCP frame
and sent via TCP to system port 502. This port is specifically reserved for Modbus applications and all
servers and clients receive and listen Modbus data via it.
The Modbus Application Protocol (MBAP) header has length of 7 bytes and its fields are:
● Transaction/invocation identifier (2 bytes): It is used for transaction pairing when multiple
messages are sent along the same TCP connection by a client without waiting for a prior
response.
● Protocol identifier (2 bytes): It is always 0 for Modbus services and other values are reserved
for future extensions.
● Length(2 bytes): It is a byte count of the remaining fields and includes the unit identifier
byte, function code byte, and the data fields.
● Unit identifier (1 byte): It is used to identify a remote server located on a non TCP/IP
network (for serial bridging). In a tyical Modbus TCP/IP server application, the unit ID is set
to 00 or FF, ignored by server, and simply echoed back in the response.
2.3 Function Codes The Modbus protocol defines several function codes, each of which corresponds to a specific command.
Specially, there are three categories of MODBUS Function codes. They are:
Public Function Codes
● Are well defined function codes
● Guaranteed to be unique
● Validate by the MODBUS.org community
● Publicly documented
● Have available conformance test
● Include both defined public assigned function codes as well as unassigned function codes
reserved for future use
User-Defined Function Codes
● There are two ranges of user-defined function codes, i.e. 65 to 72 and from 100 to 110
decimal
● User can select and implement a function code that is not supported by he specification
● There is no guarantee that the use of the selected function code will be unique
● If the user wants to re-position the functionality as a public function code, he must initiate
an RFC to introduce the change into the public category and to have a new public function
code assigned
● MODBUS Organization, Inc. expressly reserves the right to develop the proposed RFC
Reserved Function Codes
● Function Codes currently used by some companies for legacy products and that are not
available for public use
PUBLIC function codes {127 – 111}
User-Defined Function Codes {110 - 101}
PUBLIC function codes {100 – 73}
User-Defined Function Codes {72 - 66}
PUBLIC function codes {65 - 1}
Table 1: MODBUS Function Code Categories
2.3.1 Public Function Codes Definition
Notification: There is an analytical description for all Public Function Codes at “MODBUS APPLICATION
PROTOCOL”, Section 6. All Public Function Codes have been designed at Finite State Machines, below, at
chapter 6 “Detection Engine”.
3. Related Work
The Modbus/TCP Fuzzer (MTF) [1] is one of the first methods for discovering MODBUS protocol faults by
providing unexpected input and monitoring for exceptions. There is an increasing need to test Modbus
protocol implementations for security vulnerabilities, as devices are accessible via internet. MTF
implementation was an important first step towards getting insights on the resilience of these systems
against new threats arising from the internet. The fuzzer operates in phases so as to minimize the
generated traffic and reduce testing time in order to reduce network noise and remain as stealth as
possible based on the knowledge it collects. It was tested against eight Modbus implementations.
Specifically, the Modbus/TCP Fuzzer (MTF) can be used to test both the master and slave sides of the
protocol. Armed with the open specification of the Modbus/TCP protocol, the research team
implemented an informed fuzzer that constructs almost-valid protocol packets with erroneous inputs.
Firstly, MTF builds a list of possible attack cases described already in the published literature in the form
of memory map boundaries and supported functions and then using this collected knowledge perform a
guided fuzzing so as to reduce the injected frames and the number of tests. The major concerns for MTF
were about DoS attack, because it was identified as inability to open new socket to the SUT, and as
socket timeout errors, which indicated that the SUT was not responsive.
Trying to limit the wide set of threats, the majority of Modbus security mechanisms use detection
techniques. Particularly, [2] proposes a set of signature based intrusion detection rules for the
Modbus/TCP, Modbus over Serial Line protocols. A total of 50 rules are described with details on
protocol requirements and construction of the IDS signature. These rules were developed to detect
malicious activity on industrial control system MODBUS communication networks and are intended for
use with SNORT Intrusion Detection System [3]. SNORT is a rule based open source network intrusion
detection and intrusion prevention tool, which collects and logs network traffic, analyzes network traffic
searching for rule violations, and alerts the administrator of suspicious activity. Quickdraw [4] is a Snort
preprocessor and another set of Snort rules developed for industrial control systems using the
MODBUS/TCP, DNP3, and Ethernet/IP communication standards. The quick draw rules include alerts for
invalid device configuration attacks, coil and register read and write attacks, high traffic volume attacks,
malformed MODBUS application data unit (ADU) content attacks, unresponsive device scenarios, and
port and function code scanning attacks.
Another approach that attempts to address the limitation at power transmission grid is through the
hybrid network IDS for protective digital relays. In [5], the authors have proposed a specification-based
intrusion detection signature based on the execution of the hybrid automata that specify the
communication rules and physical limits the system should obey. The proposal constitutes a novel use of
network intrusion detection systems (NIDSs) tailored to detect attacks against networks that support
micro-processor based on hybrid controllers and packet-switched communications that implement
power grid protection schemes. The hybrid set of IDS rules is a blending of network communication
signatures with physical constraints. The research team, firstly, created the hybrid automation that
characterizes system’s behavior, including both physical limits and communication patterns, and then,
implemented the IDS rules using Bro Network Security Monitor, which included IP packet parsers for
Modbus and DNP3 protocols. It was supposed 3 attack scenarios: injecting malicious packets, isolating
the power transformer and imitating the Master controller’s behavior. In [6], a deeper analysis at
vulnerabilities and attacks to the huge heterogeneous network of smart grid is proposed such as
solutions for these security challenges. The greater and greater number of intelligent devices, the
customer data security, IP usage and commercial off-the-shelf hardware and software, the implicit trust
between traditional power devices and the lifetime of power systems are some of the vulnerabilities
which break the confidentiality and integrity of transmitted data. As consequence, the attackers exploit
these vulnerabilities and cause different levels of damage. The authors classify into three categories the
attacks: component-wise, protocol-wise and topology-wise. Besides, it is referred the major differences
between IT and grid network security objectives which necessitate the need for new security solutions
specific for smart grid network. IDS and IPS, vulnerabilities assessment, better authentication and
authorization techniques for TLS and IPSec, VPN and PKI usage are only some of the needed measures
proposed at this paper.
In [7], another approach is described in order to analyze protocols, applications and networks. “Attack
Tree” technique, as it is known, initially described by Bruce Schneider and, although “fault trees” have
long been an accepted system analysis technique, this methodology first applied to the domain
information security Dr Dobb’s Journal article in 1999. The first published application of attack trees to a
network protocol was “An Attack Tree for the Border Gateway Protocol”, which is currently under
consideration by the IETF Routing Protocol Security working group. Building on these approaches, the
project team relied heavily on attack trees to support later vulnerability analysis and testing of
MODBUS/TCP-based devices, with the goal of identifying flaws that could result in the greatest damage
to SCADA systems. The primary benefit of using attack trees is the focus analysis on measurable attack
goals against real-world devices, networks, and protocol implementations. Another observation of
experimental observation was that the trees significantly improved other lab members’ ability to find
new exploits in SCADA systems. Last but not least, the trees were useful for selecting the most
appropriate mitigation for cutting off an avenue attack.
Modbus Protocol, as it is known, is vulnerable to flooding attacks. These commands involve injection of
commands that result in disrupting the normal operation of the control system. The research team with
head Sajal Bhatia[8], showed that an anomaly-based change detection algorithm and signature-based
Snort threshold module are capable of detecting Modbus flooding attacks. In comparison these intrusion
detection techniques, the signature-based detection requires a carefully selected threshold value and
anomaly-based change detection algorithm may have a short delay before detecting the attacks
detecting on the parameters used. Moreover, a network traffic dataset of flooding attacks on the
Modbus control system protocol was generated. Besides, Gao W. and Morris T. in [9] have described a
set of 28 cyber attacks against industrial control systems which use MODBUS application layer network
protocol. This paper also describes a set of standalone and state for signature based intrusion detection
system rules which can be used to detect cyber attacks and to store evidence of attacks for post incident
analysis. Standalone rules parse a single MODBUS packet looking for a match to a specific signature and
if the signature is present in the parsed packet, then the packet is classified as a match and an alert is
issued. State based rules require knowledge from previous MODBUS packets or from another source,
such as a process sensor. The lack of digital signature or other means to ensure the integrity of network
frames in industrial systems leads to many vulnerabilities between the HMI/MTU and the PLC. The paper
was implemented with the MODBUS application layer protocol.
4. Abbreviaton
ADU Application Data Unit HDLC High level Data Link Control HMI Human Machine Interface IETF Internet Engineering Task Force I/O Input/Output IP Internet Protocol MAC Media Access Control MB Modbus Protocol MBAP Modbus Application Protocol PDU Protocol Data Unit PLC Programmable Logic Controller TCP Transmission Control Protocol
5. Vulnerabilities & Attacks
5.1.1 Vulnerabilities MODBUS is the most widely used SCADA Protocol. Supervisory Controls and Data Acquisition (SCADA)
protocols are communications protocols designed for the exchange of control messages on industrial
networks. Over the past three decades, several hundred of these protocols have been developed for
serial LAN, and WAN-based communications in a wide variety of industries including petrochemical,
automotive, transportation and electrical generation/ distribution.
SCADA protocols have much vulnerability. MODBUS is one of the most vulnerable ones to cyber attacks.
The MODBUS/TCP protocol implementation contains too much vulnerability that could allow an attacker
to perform reconnaissance activity or issue arbitrary commands. Below are referred the basic
sections/classes of MOSBUS/TCP protocol vulnerabilities:
1. Lack of Confidentiality: All MODBUS messages are transmitted in clear text across the
transmission media.
2. Lack of Integrity: There is no integrity checks built into MODBUS application protocol. As a
result, it depends on lower layer protocols to preserve integrity.
3. Lack of Authentication: There is no authentication at any level of the MODBUS protocol. One
possible exception is some undocumented programming commands.
4. Simplistic Framing: MODBUS/TCP frames are sent over established TCP connections. While such
connections are usually reliable, they have a significant drawback. TCP connection is more
reliable than UDP but the guarantee is not complete.
5. Lack of Session Structure: Like many request/response protocols (I.e. SNMP, HTTP, etc.)
MODBUS/TCP consists of short-lived transactions where the master initiates a request to the
slave that results in a single action. When combined with the lack of authentication and poor
TCP initial sequence number (ISN) generation in many embedded devices, it becomes possible
for attackers to inject commands with no knowledge of the existing session.
These vulnerabilities allow an attacker to perform reconnaissance activity on the targeted network. The
first vulnerability exists because a MODBUS slave device may return Illegal Function Exception responses
for queries that contain an unsupported function code. An unauthenticated, remote attacker could
exploit this vulnerability by sending crafted function codes to carry out reconnaissance on the targeted
network.
An additional reconnaissance vulnerability is due to multiple illegal Address Exception responses
generated for queries that contain an illegal slave address. An unauthenticated, remote attacker could
exploit this vulnerability by sending queries that contain invalid addresses to the targeted network and
gathering information about network hosts from returned messages.
Another vulnerability is due to lack of sufficient security checks in the MODBUS/TCP protocol
implementation. The protocol specification does not include an authenticated mechanism for validating
communication between MODBUS master and slave devices. This flaw could allow an unauthenticated,
remote attacker to issue arbitrary commands to any slave device via a MODBUS master.
The MODBUS/TCP protocol contains another vulnerability that could allow an attacker to cause a denial
of service (DoS) condition on a targeted system. The vulnerability is due to an implementation error in
the affected protocol when processing Read Discrete Inputs request and response messages. . An
unauthenticated, remote attacker could exploit the vulnerability by sending request or response
parameters that contain malicious values for the data filed option to a system that contains the
vulnerable MODBUS/TCP implementation. As a consequence, the processing of the messages could
trigger a DoS condition-attack to the vulnerable system.
Moreover, another attack can be MODBUS TCP packets that exceed the maximum length. MODBUS TCP
is commonly used in SCADA and DCS networks for process control. MODBUS limits the size of the PDU to
253 bytes to allow the packet to be sent on a serial line, RS-485 interface. MODBUS TCP prepends a
7-byte MODBUS Application Protocol (MBAP) header to the PDU, and the MBAP_PDU is encapsulated in
a TCP packet. This places an upper limit on legal packet size. An attacker creates a specially crafted
longer than 260 bytes and sends it to a MODBUS client and server. If the client or server programmed
incorrectly, this could lead to a successful buffer overflow or a denial-of-service attack.
5.2 Attacks against industrial control systems There have been several documented incidents and cyber attacks affecting SCADA systems, which
clearly illustrate the above critical infrastructure vulnerabilities. These cyber attacks have produced
a variety of financial damage and harmful events to humans and their environment. In this section a
set of cyber attacks against industrial control systems (ICS) are referred and grouped into four attack
classes; reconnaissance, response and measurement injection, command injection, and denial of
service.
1. Reconnaissance attacks
Reconnaissance attacks gather control system network information, map the network architecture, and
identify the device characteristics such as manufacturer, model number, supported network
protocols, system address and system memory map. Below are referred four reconnaissance
attacks against MODBUS servers; the address scan, the function code scan, the device
identification attack, and the points scan. The address scan discovers ICS servers connected to a
network. The function code scan identifies supported network operations which can be
performed for an identified server. The device identification attack allows an attacker to learn a
discovered device’s vendor name, product code, major and minor revision etc. The points scan
allow an attacker to build a device memory map. MODBUS is an open standard and is popular
network protocol used for ICS devices. While these attacks are known to function against
MODBUS servers the vulnerabilities the attacks exploit are general enough to also likely be
found in other network protocols used for ICS.
Industrial control system users often develop standard hardware, software, control scheme parameter
configurations which are duplicated throughout a control system. For example, an electric
transmission system may use a standard panel which includes the same protective relays used
at many substations throughout a single transmission system. A second example is pump
stations for a gas pipeline. Pump stations are distributed along the gas pipeline to ensure
product flow. Programmable logic controllers (PLC) and the programmation on those controllers
will be similar throughout the system.
The combined results of the address scan, function code scan, the device identification attack, and the
points scan can be used to generate a signature for MODBUS servers common to a particular
company, use case, or vendor. Such signatures can also be used to build a database of
vulnerabilities and exploits for each aforementioned category.
2. Response and Measurement Injection Attack
Industrial Control systems commonly use polling techniques to continuously monitor the state of a
remote process. Polling takes the form of a query transmitted from the server to the client. The
state information is used to provide a human machine interface to monitor the process, to store
process measurements in historians, and as part of feedback control loops which measure
process parameters and take requisite control actions based upon process state.
Many industrial control system network protocols lack authentication features to validate the
origin of packets. This enables attackers to capture, modify and forward response packets which
contain sensor reading values. Industrial control system protocols also often take the first
response packet to a query and reject subsequent responses as erroneous. This enables to craft
response packets and use timing attacks to inject the responses into a network when they are
expected by a client.
Response injection attacks take 3 forms. First, response injection attacks can originate from control of
programmable logic controller or remote terminal unit, network endpoints which are the
servers which respond to queries from clients. Second response injection attacks can capture
network packets and alter contents during transmission from server to client. Finally, response
injections may be crafted and transmitted by a third party device in the network. In this case,
the response there may be multiple responses to a client query and the invalid response may
assume prominence due to exploiting a race condition or due to secondary attack such as a
denial of service attack which stops the true sever from responding.
3. Command Injection Attacks
Command injection attacks inject false control and configuration commands into a control system.
Human operators oversee control systems and occasionally intercede with supervisory control
actions. Hackers may attempt to inject false supervisory control actions into a control system
network. Remote terminals and intelligent electronic devices are generally programmed to
automatically monitor and control the physical process directly as a remote site. This
programming takes the form of ladder logic, C code, and registers which hold key control
parameters such as high and low limits gating process control actions. Hackers can use
command injection attacks to overwrite ladder logic, C code, and remote terminal register
settings.
The potential impacts of malicious command injections include interruption process control,
interruption of device communications, interruption of device communications, unauthorized
modification of device configurations, and unauthorized modification of process set points. As
mentioned in the response injection discussion above much industrial control system network
protocols lack authentication features t validate the origin of packets. This enables attackers to
capture and alter command packets. Additionally, attackers can craft original command packets
and directly inject them into the control system network.
4. Denial of Service Attacks
Denial of service attacks against industrial control system attempt to stop the proper functioning of
some portion of the cyber physical system to effectively disable the entire system. As such DOS
attacks may target the cyber system or the physical system. DOS attacks against the cyber
system target communication links or attempt to disable programs running on system endpoints
which control the system, log data, and govern communications. DOS attacks against the
physical system vary from the manual opening or closing of valves and switches to destruction
of portions of the physical process which prevent operation. This work concentrates on DOS
attack against the communication system. MODBUS TCP/IP is a routable protocol which allows
other devices to initiate Dos attacks targeted to a victims IP address. A device on the network
can become infected with malware and then the infected device can initiate a DOS attack
against other devices on the network.
Traffic jamming is a class of DOS attacks in which high volumes of traffic are sent to a network endpoint.
Attackers attempt to overwhelm the endpoint by either sending transmissions faster than they
can be processed or by sending packets crafted to cause software errors which generate
exceptions with crash the network stack, the running program , or the operating system of the
targeted device.
Name Classification Address Scan Reconnaissance Function Code Scan Reconnaissance Device Identification Reconnaissance Naïve Read Playload Injection NMRI Invalid Read Playload Size NMRI Naïve False Error Response NMRI Sporadic sensor Measurement Injection Attack
NMRI
Slope Sensor Measurement Injection
CMRI
High Slope Measurement Injection
CMRI
High Frequency Measurement Injection
CMRI
Altered System Control Scheme MSCI Altered Actuator State MSCI Altered Control Set Point MPCI Force Listen Only Mode MFCI Restart communication MFCI Invalid Cyclic Redundancy Code DOS MODBUS Slave Traffic Jamming DOS
6 The detection engine
When a client device sends a request to a server device it expects a normal response. One of four
possible events can occur form the client’s query for the client’s query:
● If the server device receives the request without a communication error, and can handle the
query normally, it returns a normal response.
● If the server does not receive the request due to a communication error, no response is
returned. The client program will eventually process a timeout condition for the request.
● If the server receives the request, but detects a communication error (parity, LRC, CRC etc)
no response is returned. The client program will eventually process a timeout condition for
the request
● If the server receives the request without a communication error, but cannot handle it, the
server will return an exception response informing the client of nature of the error.
With the exception function codes, the client’s application program can recognize the exception
response and can examine the data field for the exception code. The below table includes all the
exception codes that the intrusion detection system can identify to alert for an error at the Modbus
packet transmitting. The list has been produced based on the Public Function Codes which are referred
at Chapter 2.3.1. At Chapter 6.1, there is a graphical state design of all the listed Exception Codes in the
process of receiving a request packet.
A list of exception codes is below:
Code Name Meaning 01 Illegal Function The function code received in the query is not an allowable action
for the server (or slave). This may be because the function code is only applicable to newer devices, and was not implemented in the unit selected. It could also indicate that the server (or slave) is in the wrong state to process a request of this type, for example because it is unconfigured and is being asked to return register values.
01A Force Listen Only Mode Function Code == 0x08 && sub-function == 0x0004 01B Restart Communication Function Code == 0x08 && sub-function == 0x0001
01C Clear Communication Event Log
Function Code == 0x08 && sub-function == 0x0001 && data == 0xFF00
01D Change ASCII Input Length Function Code == 0x08 && sub-function == 0x0003 02 Illegal Data Address The data address received in the query is not an allowable address
for the server (or slave). More specifically, the combination of reference number and transfer length is invalid. For a controller with 100 registers, the PDU addresses the first register as 0, and the last one as 99. If a request is submitted with a starting register address of 96 and a quantity of registers of 4, then this request will successfully operate (address-wise at least) on registers 96, 97, 98, 99. If a request is submitted with a starting register address of 96 and a quantity of registers of 5, then this request will fail with Exception Code 0x02 “Illegal Data Address” since it attempts to operate on registers 96, 97, 98, 99 and 100, and there is no register with address 100.
03 Illegal Data Value A value contained in the query data field is not an allowable value for server (or slave). This indicates a fault in the structure of the remainder of a complex request, such as that the implied length is incorrect. It specifically does NOT mean that a data item submitted for storage in a register has a value outside the expectation of the application program, since the MODBUS protocol is unaware of the significance of any particular value of any particular register.
04 Server Device Failure An unrecoverable error occurred while the server (or slave) was attempting to perform the requested action.
05 Acknowledge Specialized use in conjunction with programming commands. The server (or slave) has accepted the request and is processing it, but a long duration of time will be required to do so. This response is returned to prevent a timeout error from occurring in the client (or master). The client (or master) can next issue a Poll Program Complete message to determine if processing is completed.
06 Server Device Busy Specialized use in conjunction with programming commands. The server (or slave) is engaged in processing a long–duration program command. The client (or master) should retransmit the message later when the server (or slave) is free.
08 Memory Parity Error Specialized use in conjunction with function codes 20(0x14) and 21(0x15) and reference type 6, to indicate that the extended file area failed to pass a consistency check. The server (or slave) attempted to read record file, but detected a parity error in the memory. The client (or master) can retry the request, but service may be required on the server (or slave) device.
0A Gateway Path Unavailable Specialized use in conjunction with gateways, indicates that the gateway was unable to allocate an internal communication path from the input port to the output port for processing the request. Usually means that the gateway is misconfigured or overloaded.
0B Gateway Device Target Failed to Respond
Specialized use in conjunction with gateways, indicates that no response was obtained from the target device. Usually means that the device is not present on the network.
6.1 Finite Sate Machine The set of specification utilized by the detection engine to resolve malicious behavior is expressed
through the use of a Finite State Machine (FSM). The Finite State Machine (FSM) is a framework used to
model the behavior of a system by means of limited number of states, transitions between states,
actions and events. FSM states are characterized as legitimate or malignant, and a transition from one
state to another is triggered by the node’s operation or actions. Every protocol execution is mapped to
the appropriate state (i.e. legitimate or malignant). States that have not been specified are also
considered as malignant. The developed specifications are divided into three sets, based on the
host-node’s communication condition (a) idle, (b) transmitting and (c) receiving states. In the following
sections, the FSM states are presented.
The FSM has been designed and implemented based on function codes presented at section C.1 and
exception codes presented above. At first, it is presented the generic processing of a MODBUS
transaction in server side [figure 5]. Once the request has been processed by a server, a MODBUS
response using the adequate MODBUS server transaction is built. A positive MODBUS response leads to
a request execution and a negative MODBUS response executes an exception response which gives
information concerning the error detection and its reason.
Figure 5: Server Side
The public function codes presented in the following figures [figure 6 - 11] show all positive MODBUS
function codes which lead to a request execution. The first state for all diagrams is So, since in this
condition the protocol is awaiting for a packet request from master side, and thus, it does not include
any final state designating a malicious behavior. At this state, So, the engine is initialized and begins
monitoring the protocol data unit (PDU) which include the function code byte and payload. All packets
are monitored at state S1 checking if the function code is included in the white list. The white list is
limited only to the Public Function Codes referred above. In case the function code does not belong to
the white list an alert is generating with exception code 01, state S2. All MODBUS/TCP packets include a
protocol identifier field. The protocol identifier is defined as 0 for all MODBUS/TCP packets. Other values
are illegal. Exception code 01 also alerts for TCP traffic if the identifier is not 0. In effect, this means any
TCP packet with second byte in the payload not equal to 0 is disallowed and should result in an alert.
For legal function codes the monitoring continue with states S6, S13, S15, S31, S19, S22, S26, S33, S50,
S36, S43, S47. At this states, the engine checks if the value contained in the query data field is an
allowable value for server. In case the value is illegal as described at Exception Codes and as it is shown
in the diagrams, the system responds an alert with exception code 03 state S3. If there is not an alert,
the engine continues with the data address checking. State S4 with exception code 02 will generated to
inform the system that an invalid address is detected. The start_address and end_address are written in
memory regions. The end_address may be computed by adding the length address to the start_address.
Figure 6: Function Codes 01, 02, 03, 04, 15
One of the most significant states of Finite State Machine is state S8. At this state all requests are
processing and no error detection could be occurred. The final state for all diagrams is S12 which is the
exit state. At this state the system is terminated. At this state, S12, is concluded state S10 with all
positive checked responses and state S11 with negative MODBUS exception responses. All the malicious
states are shown filled with lines. The rest no filled with lines states are not malicious. Every Finite State
Machine is easily readable because all transmitting and receiving states are reasoned in the figures.
Figure 7: Function Codes 05, 06
Figure 8: Function Codes 07, 11, 12, 17
Figure 9: Function Codes 16, 43
Figure 10: Function Codes 20, 21
Figure 11: Function Codes 22, 23, 24
7 Conclusion
The use of regular IT networks for industrial control protocols has brought new security challenges to be
addressed because of the different uses, requirements and restrictions of that kind of systems. MODBUS
TCP/IP is a wide spread protocol that came from legacy serial communication systems. With no build in
capabilities protection, monitoring and analysis, it is necessary to achieve a reasonable security level.
This thesis presents much vulnerability which could be exploited by hackers with dangerous results for
MODBUS systems, such as network classified attacks. MODBUS TCP/IP is no other than an application
protocol. So many intrusion detection engines could be used to analyze and monitor it. At this thesis,
many Exception Codes are presented based on the Public Function Codes of the protocol. All these
Exception Function Codes are implemented at Finite State Machines in combination with the MODBUS
sequence response and the Public Function Codes. The exception codes could be enriched in case this
analysis was implemented in a real time industrial system. In industrial systems, such as water, coil and
solar power grid, MODBUS protocol is widely used. So an implementation at a system like the above
examples could produce more exception codes because the parameters and setting points for the
normal function are in variety.
8 References
1. Artemios G. Voyiatzis, Konstantinos Katsigiannis , Stavros Koubias, “A Modbus/TCP Fuzzer for
Testing Internetworked Industria Systems”
2. Thomas H. Morris , Bryan A. Jones, Rayford B. Vaughn, Yoginder S. Dandass, “Deterministic
Intrusion Detection Rules for MODBUS Protocols”, Hawaii 2013
3. Caswell, B. Bealeand, J. Foster, J. and Faircloth, “Snort2.0 Intrusion Detection”, Syngress,
Feb.2003
4. Morris T., Vaughn R., Dandass Y. “A Retrofit Network Intrusion Detection System for MODBUS
RTU and ASCII Industrial Control Systems”, Proceedings of the 45th IEEE Hawaii International
Conference on System Sciences, January 4-7 2012
5. Georgia Koutsandria, Vishak Muthukumar, Masood Parvania, “A Hybrid Network IDS for Protective Digital Relays in the Power Transmission Grid”,
Venice-Italy 2014
6. Fadi Aloula , A. R. Al-Alia , Rami Al-Dalkya , Mamoun Al-Mardinia , Wassim El-Hajjb, “Smart Grid
Security: Threats, Vulnerabilities and Solutions”, International Journal of Smart Grid and Clean
Energy, 2012
7. E.J. Byres, M. Franz and D. Mille, “The Use of Attack Trees in Assessing Vulnerabilities in SCADA
Systems”, Lisbon – Portugal 2004
8. Sajal Bhatia, Nishchal Kush, Chris Djamaludin, James Akande, Ernest Foo, “Practical Modbus
Flooding Attack and Detection”, New Zealand 2014
9. Wei Gao, Thomas H. Morris, “On cyber attacks and signature based intrusion detection for
modbus based industrial control systems”, Journal of Digital Forensics, Security and Law, 2014
10. MODBUS APPLICATION PROTOCOL SPECIFICATION
11. MODBUS MESSAGING TCP/IP IMPLEMENTATION GUIDE
12. https://www.schneider-electric.com/en/faqs/FA168406/
13. https://www.lammertbies.nl/comm/info/modbus.html