anjuli chandra

Upload: ajatshatru2612736101

Post on 07-Jul-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/19/2019 Anjuli Chandra

    1/33

    1

    Earthing configurationsfor

    LT distribution systemsby

     Anjuli Chandra 

    Director CEA

  • 8/19/2019 Anjuli Chandra

    2/33

    2

    Earthing for LT systems  – Deficient  A earthing system should be installed in a manner

    that it will limit the effect of ground potential

    gradients to such voltage and current level that willnot endanger the safety of people or equipmentunder normal and fault conditions, as well as assurecontinuity of service.

    Earthing systems adopted at Generating Stations,Substations are well designed for safety

    Substations usually have ground grid system withground mat as extra protection. Grid system has the

    form of horizontally buried grid conductor,supplemented by a number of vertical ground rodsconnected to the grid.

    It is however observed that this area is most often

    neglected especially in the LT Distribution networkand consumer premises.

  • 8/19/2019 Anjuli Chandra

    3/33

    3

    Earthing of LT networks

    The earthing system for Distributionnetworks

    Fixes the potential of live conductors withrespect to the earth in normal operation sothat it is consistent with the level of  insulation.

    Limits voltage between the frames of  electrical equipment and earth should aninsulation fault occur

    Enables having low zero phase sequenceimpedance to keep the higher fault currentand enable operation of relays for circuitbreaking under fault conditions

    Limits rises in potential due to MV faults.

  • 8/19/2019 Anjuli Chandra

    4/33

    4

    LT earthing practices

    The world has several different power Distribution

    system grounding configurations.

    In IEC standards, the various power systemconfigurations have designations based on theconnection of the Neutral wire to earth, and on theconnection of the Protective Conductor connection to

    earth.

    The IEC designation is comprised of two letters, thefirst for the Neutral conductor, and the second for theProtective Conductor.

    T=Earth N = Neutral S = Separate C = Combined I = Isolated

  • 8/19/2019 Anjuli Chandra

    5/33

    5

    Types of Earthing Configurations

    Three types of earthing

    configurations or their combinationare generally followed:

    1. TT

    2. TN2.2 TN-C

    2.3 TN-S

    2.4 TN-C-S3. IT

  • 8/19/2019 Anjuli Chandra

    6/33

    6

    Neutral of the source connected and earthed .

    Consumer or licensee must provide connection to

    earth at consumer premises, i.e. by installing a earth

    electrode local to the installation

    The protective conductor is connected to its own

    ground rod, remote from the neutral ground rod. In some

    cases, the ground rod may be the steel frame of the

    building. In any case, there is no direct copper  connection between the consumer earth and the supply

    system.

    TT System of Earthing

  • 8/19/2019 Anjuli Chandra

    7/33

    7

  • 8/19/2019 Anjuli Chandra

    8/33

    8

  • 8/19/2019 Anjuli Chandra

    9/33

    9

    TN-S System

    Neutral of the source of energy connected withearth at one point only, at or as near as isreasonably practicable to the source.

    The protective earth conductor is connected to theneutral

    The  “S”  in the designation means that theprotective earth conductor is a separate systemconductor.

    Consumer’s earthing terminal is typicallyconnected to the metallic sheath or armour of thedistributor’s service cable into the premises or to aseparate protective conductor, for instance, in anoverhead supply

  • 8/19/2019 Anjuli Chandra

    10/33

    10

    L

    L

    L L

    N

    E

    Source

    Transfor 

    mer 

    TN-S System

  • 8/19/2019 Anjuli Chandra

    11/33

    11

  • 8/19/2019 Anjuli Chandra

    12/33

    12

    TN-S System

    Unlike the TT and IT systems, in the TN-S systemthe equipment and man are grounded throughdifferent paths. If the current through the differentpaths is different, then a potential difference willoccur between the equipment and the man, andcurrent will pass through the man.

    To minimize the potential difference due to thedifference between the equipment and the man, itis imperative to keep the equipment ground circuit

    resistance as low as practicable.

  • 8/19/2019 Anjuli Chandra

    13/33

    13

    TN-S system

    For a TN-S system, grounding does not provide anequipotential environment due to the finiteresistances of the equipment grounding circuit.

    However, equipment grounding through itsprotective conductor does serve to limit the

    voltage for low fault currents.

    For higher fault currents, another scheme providesprotection against electric shock: limited durationof the current through the body by means of  

    automatic disconnection of the supply (operationof the circuit-breaker).

    Consumers having dedicated transformers for theirinstallation and installed adjacent to or within

    their premises. In such situations the usual form ofsystem earthing is TN-S.

  • 8/19/2019 Anjuli Chandra

    14/33

    14

    TN-S System

  • 8/19/2019 Anjuli Chandra

    15/33

    15

    TN-C system

    The TN-C system has a single ground rod. Source star point is earthed and the function of

    neutral and earth is combined throughout thesystem.

    The protective earth conductor is connected to the

    neutral in the equipment. There is no separate protective conductor.

    The “C” in the designation means that theprotective earth conductor is combined with the

    neutral conductor.

  • 8/19/2019 Anjuli Chandra

    16/33

    16

    TNC System

    L

    L

    L L

     N

    Source

    Transformer 

  • 8/19/2019 Anjuli Chandra

    17/33

    17

  • 8/19/2019 Anjuli Chandra

    18/33

    18

    TN-C-S system earthing

    A TN-C-S system has the supply neutral conductor of a

    distribution main connected with earth at source and atintervals along its run. This is usually referred to as

    protective Multiple earthing (PME).

    With this arrangement the distributor’s neutral conductor is

    also used to return earth fault currents arising in the

    consumer’s installation safely to the source.

    To achieve this, the distributor will provide a Consumer’s

    earthing terminal which is linked to the incoming neutral

    conductor.

    In TN-C-S system neutral must be connected to the earth

    only on supply side of the customer disconnecting switch.

    So TN-C-S system is a combination of TN-C for the power

    supply network and TN-S for the customer Network

  • 8/19/2019 Anjuli Chandra

    19/33

    19

    Protective Multiple Earthing (PME) systemWhere an PME earthing system is used, the following

    conditions should be met:

    Neutral conductor should be earthed at or near each

    LV distribution centre

    Neutral should be earthed at other points along the

    distribution system.

    Earthing should be arranged so as to ensure that

    resistance of neutral to earth at any location does not

    exceed prescribed limits.

    In PME system the high voltage and low voltage

    earthing systems should be kept separate.

  • 8/19/2019 Anjuli Chandra

    20/33

  • 8/19/2019 Anjuli Chandra

    21/33

    21

    IT system

    The distribution system has no connection toearth at all, or it has only a high impedanceconnection.

    The neutral is connected through an impedanceto its ground rod in the second case

    The protective conductor is connected to its ownground rod, remote from the neutral ground rod.In some cases, the ground rod may be the steelframe of the building.

    In any case, there is no direct copper connection

    between the enclosure and the supply system.

  • 8/19/2019 Anjuli Chandra

    22/33

    22

    One characteristic of the IT system is that the systemis tolerant of a fault to ground. That is, a fault to grounddoes not operate the circuit breaker, so the systemremains operational. (An alarm identifies the fault toground, but the system continues to operate.)

    •Advantages are all voltages with respect to earth are

    kept as low as possible and also allows an earth fault

    to develop without causing a trip.

    •Such systems must always have Earth Fault Warning

    Devices, if it is imperative for a trip to occur on anearth fault, yet the advantage of reduced voltages with

    respect to Earth are required.

    IT system

  • 8/19/2019 Anjuli Chandra

    23/33

    23

    IT system

  • 8/19/2019 Anjuli Chandra

    24/33

    24

  • 8/19/2019 Anjuli Chandra

    25/33

    25

    Governed by Rule33

    •The supplier shall provide and maintain on the

    consumer’s premises for the consumer’s use, a suitableearthed terminal in an accessible position at or near the

    point of commencement of supply as defined under rule

    58.

    Provided that in the case of medium, high or extra highvoltage installation the consumer shall, in addition to

    the aforementioned earthing arrangement, provide his

    own earthing system with an independent electrode.

    •Provided further that the supplier may not provide any

    earthed terminal in the case of installations already

    connected to his system or before the 30th June, 1966

    if he is satisfied that the consumer’s earthing

    arrangement is efficient.

    Earthing at consumer premises

    I E RULES REGARDING SAFETY AND EARTHING

  • 8/19/2019 Anjuli Chandra

    26/33

    26

    I.E.RULES REGARDING SAFETY AND EARTHING

    29: Rating sufficient for power, insulation andestimated fault current to construct in such a manner to

    ensure safety of human beings, animals and property.

    To follow relevant code of practice

    30:The supplier shall ensure that all electric supply

    lines, wires ,fittings and apparatus belonging to him or under his control, which are on a consumer premises

    are in safe conditions and in all respects fit for supplying

    energy and the supplier shall take due precautions to

    avoid danger arising on such premises from such supply

    lines, wires, fittings and apparatus.

    The consumer shall also ensure that the installation

    under his control is maintained in a safe condition.

  • 8/19/2019 Anjuli Chandra

    27/33

    27

    I.E.RULES REGARDING SAFETY AND EARTHING

    46: Periodical inspection and testing of installation

    (1) Existing installations to be checked once in five years by

    the inspector or any other appointed to assist the inspector 

    47: Testing of consumer installation

    (1)The supplier shall inspect and test the applicant’s

    installation for a new or additional supply of energy

    48: Precautions against leakage before connection

    The supplier to check for leakage before connection and

    the insulation resistanceshall be at least one Mega Ohm or

    as specified in relevant Indian standard.

  • 8/19/2019 Anjuli Chandra

    28/33

    28

    I.E.RULES REGARDING SAFETY AND EARTHING

    61 Connection with the earth

    Neutral conductor shall be earthed by not less than two

    separate and distinct connections with a minimum of 

    two different earth electrodes at sub-stations or such

    large number as may be necessary to bring the earth

    resistance to a satisfactory value both at generating

    stations and sub stations.

    The earth electrodes so provided, may also be

    interconnected to reduce earth resistance.

  • 8/19/2019 Anjuli Chandra

    29/33

    29

    I.E.RULES REGARDING SAFETY AND EARTHING

    61 Connection with the earth

    it may also be earthed at one or more points along the

    distribution system or service line in addition to any

    connection with earth which may be at the consumer’s

    premises.

    Limit earth resistance sufficiently low to permit

    adequate fault current for the operation of protective

    device in time and to reduce neutral shifting.

  • 8/19/2019 Anjuli Chandra

    30/33

    30

    I.E.RULES REGARDING SAFETY AND EARTHING

    61 A : Earth Leakage Protective device

    The supply of energy to every electrical installations

    other than low voltage installation below 5 KW and those

    low voltage installations, which do not attract

    provisions of section 30 0f the Indian Electricity act shall

    be controlled by an earth leakage protective device so

    as to disconnect the supply instantly on the occurrence

    of earth fault or leakage of current.

    Provided that the above shall not apply to overhead

    supply lines having protective devices which are

    effectively bonded to the neutral of supply transformers

    and conforming to rule 91 of I.E. Rules.

  • 8/19/2019 Anjuli Chandra

    31/33

    31

    Draft safety regulations: ELPD:

    The supply of electricity to every electrical installationother than voltage not exceeding 250 V below 5kW

    and those installations of voltage not exceeding 250V

    which do not attract provisions of Section 54 of the

    Electricity Act, 2003,shall be controlled by an earth

    leakage protective device so as to disconnect thesupply instantly on the occurrence of earth fault or 

    leakage of current:

    Conclusion

  • 8/19/2019 Anjuli Chandra

    32/33

    32

    Under present I.E.Rules It is responsibility of DISCOM to

    ensure safety

    The three earthing systems of TT, IT and TN for LTnetworks have their own advantages anddisadvantages.

    The choice depends upon the Distribution Company,type of installations, type of consumers to be served,

    operation philosophies.

    TT system are difficult to maintain in India

    TN-S or TN-C-S system are better as it provide low

    impedance path (except in situations like petrol pumps

    etc).

    TN-S system offers best properties for EMC

    Conclusion

  • 8/19/2019 Anjuli Chandra

    33/33

    33