automaticsetdistrelayonsriescompensatedlines

Upload: 1453h

Post on 03-Apr-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 AutomaticSetDistRelayOnSriesCompensatedLines

    1/6

    *Rua Delmiro Gouveia, 333, anexo II, sl. B-216, Bongi, 50761-901, Recife-PE, tel:81-3229.4434

    VII Seminrio Tcnico de Proteo e Controle22 a 27 de Junho de 2003Rio de Janeiro - RJ

    Artigo: 37558002

    AUTOMATICALLY SETTING DISTANCE RELAYS FOR USE ON

    SERIES COMPENSATED LINES

    Gustavo Arruda1*

    ([email protected])

    Patrcia Ramos Morais1

    ([email protected])

    Ashok Gopalakrishnan 2

    ([email protected])

    (1) CHESF, Brasil.

    (2) Electrocon International Inc., USA.

    1 ABSTRACT

    This paper presents a novel procedure for modeling the

    Metal Oxide Varistor (MOV) for use in steady-statephasor based short-circuit programs. The MOV ismodeled iteratively in phase coordinates, rather than in

    the sequence domain. A method for automaticallycomputing the protection settings of distance relays, inthe context of series compensated lines, is also

    described.

    Keywords: series compensation, MOV, distance

    relays, relay setting.

    2 INTRODUCTION

    Power system engineers are familiar with the use ofseries capacitors for voltage compensation on long

    transmission lines. To protect the capacitor fromovervoltages that develop in the presence of short-circuit faults, metal oxide varistors (MOVs) are used in

    parallel with the capacitor. The MOV is basically anon-linear resistor that limits the voltage across thecapacitor during a fault condition. When the fault

    condition is cleared, the MOV allows almost

    instantaneous re-insertion of the capacitor into thetransmission line.

    Protective relaying of series compensated lines iscomplicated by a number of factors voltage

    inversion, current inversion and sub-synchronousoscillations for faults near the capacitor. Thesephenomena cause the zone 1 element of the distance

    relays to overreach, and the relay will have to performsome special functions to avoid overreaching. It isimportant to note that even relays not directly on the

    compensated line can also be affected by the seriescapacitor.

    Further complications are introduced by the action ofthe MOV that protects the series capacitor from over-

    voltages. The MOV is typically studied using transient(time-domain) programs like the ATP. Modeling theMOV for use in steady-state phasor domain programs

    is a challenging task because of the non-zero inter-sequence coupling terms that appear in the systemimpedance matrices for unbalanced faults. The separate

    phase MOVs operate independently and may conductdifferently.

    When setting a relay, the relay engineer typically usesa phasor based short-circuit program to perform anumber of fault studies. The results of these studies are

    used to determine the relay settings. If a seriescapacitor/MOV is present near the relay, it must beaccurately modeled to get realistic short-circuit results.

    Several methods of modeling the MOV for use inshort-circuit programs have been proposed:

    Goldsworthy [1], Coursol et al [2] and Mahseredjian etal [3]. In [1], a linearized model for MOV-protectedseries capacitors was first introduced. For balanced

    faults, the capacitor and MOV are replaced by anequivalent linear impedance in the system impedancematrix. This equivalent impedance is a function of the

    total capacitor/MOV current and is denoted by ZEQ.

    The parameters of the function are determined bycomputer simulations. An iterative procedure is used toarrive at the final value of ZEQ.

    When the fault is unbalanced, the unequal conduction

    in the phases of the MOV will produce a sequence-domain matrix that is no longer diagonal. In [2] and[3], the authors compensate for the non-zero inter-

    sequence coupling terms by different methods. Thesolution however takes place in the sequence domainand the sequence networks have to be correctly put

    together. This means that the algorithmic equationsdepend on the type of fault.

    The technique presented in this paper uses phasecoordinates rather than sequence coordinates. This

  • 7/29/2019 AutomaticSetDistRelayOnSriesCompensatedLines

    2/6

    2

    method also uses the ZEQ of [1]. However, since eachphase is iterated independently of the other phases, theinter-sequence coupling does not affect the

    computations. That is, both balanced and unbalancedfaults can be easily handled. Further, the MOVcomputation does not need any knowledge of the fault

    dependent sequence circuits. This means that any typeof system unbalance can be treated correctly.

    The MOV conduction is represented by a series faultacross the capacitor. Since the capacitors are retainedin the computation, recalculation of the system

    impedance matrices is not required.

    The computation algorithm is described in the next

    section of this paper. The method was tested byincorporating it into an existing short-circuit program[4].

    The paper also describes a protection simulation

    environment that helps the relay engineer determinethe settings of protective relays. Many different short-circuit computations are automatically performed,based on rules that are specified by the engineer and

    the appropriate relay settings are determined, [5].Finally, the relay settings are validated by a stepped-event simulation of the tripping sequence [6], using

    detailed relay comparator equations. Miscoordinationsbetween primary and backup protection can be foundin this way.

    3 MOV COMPUTATION ALGORITHM

    3.1 Representing the MOV Device

    Figure 1 shows a single MOV device in parallel with a

    capacitor. The total current through the capacitor/MOVcomponent is IC. If the triggered gap and the bypassswitch are open, IC will flow through the capacitor

    (ICAP) and the MOV (IMOV). The capacitor and MOVcurrents by themselves are not sinusoidal, but IC, thesum of these two currents, is approximately sinusoidal

    [1].

    CONTROL

    SERIES CAPACITOR

    ZMOV

    TRIGGERED GAP

    BYPASS SWITCH

    ZCAPIC ICAP

    IMOVBUS1 BUS2

    Figure 1: Series Capacitor and MOV Arrangement.

    First, the current IPU is defined as

    II

    IPU

    C

    PR

    = (1)

    where IPR is the capacitor protective level current and

    is usually 2 to 2.5 times the rated current of thecapacitor bank.

    The equivalent phase impedance ZEQ of the capacitorand MOV, as a function of IPU can be written as (1):

    Z (I ) R (I ) jX (I )EQ PU C'

    PU C'

    PU= (2)

    By means of extensive computer simulations,Goldsworthy [1] showed that the MOV begins to

    conduct for values of IPU 0.98, and equation 2 can beused to compute the equivalent MOV/Capacitorimpedance. Please see (1) for the actual equations that

    are used to compute RC'and XC

    '. For values of IPU