Background, Concepts and Terms

AGENDA

• Why do we need a Safety Instrumented System (SIS)? • Defining SIS• Determining the Safety Integrity Level (SIL)• The language (and many acronyms) of Safety Instrumented Systems 

• Improving the SIS function• Issues driving the industry

www.ueonline.com/st

THE PROCESS INDUSTRY CHALLENGEBalancing Safety and Throughput

Society:Employees’ SafetyThe Community’s 

SafetyThe Environment

The Process Owner:  Make a profitMaintain assetsGood corporate 

image

www.ueonline.com/st

PAGE

5

http://youtu.be/ISNGimMXL7M(the 2:50 mark)

Because humans can make bad decisions under pressure

WHY ARE SAFETY INSTRUMENTED SYSTEMS IMPORTANT?

www.ueonline.com/st

PROCESS CONTROL VS. SAFETY 

• BPCS – continuously operates the process plant during normal startup, running and shutdown phases (engine control)

• SIS – brings the plant to a safe state from a hazardous state upon demand (antilock brakes)

When properly designed per IEC 61511, these systems are always separate, independent and autonomous.

Good process control isn’t enough!

www.ueonline.com/st

BPCS AND SIS RELATIONSHIPSeparate but equally important!

www.ueonline.com/st

THE PURPOSE OF A SAFETY SYSTEM 

…to bring a process to a safe state (ESD) or permit the process to continue in a safe manner when all specified conditions are satisfiedExamples:

‐ Emergency Shutdown System (ESD)‐ Safety Interlock- Safety Shutdown‐ Starting Permissive

www.ueonline.com/st

PROCESS SAFETY SYSTEM STANDARDS

• IEC 61508:  – Internationally‐recognized standard for safety‐related system design of hardware and software

– Applies to manufacturers of safety system components (e.g., the One Series Safety Transmitter)

– IEC 61511:– applies to the process industries that use these components to design a Safety Instrumented System (i.e., UE’s customers)

– Defines the methods a user needs to develop a safety system

IEC 61508 and IEC 61511

www.ueonline.com/st

SIF VS. SIS

SIS:  A Safety Instrumented System  …an instrumented system used to implement one or more safety instrumented functions (SIFs). An SIS is composed of any combination of sensors, logic solvers and final elements (e.g., the entire safety system of the reactor, including temperature, pressure, level, etc.)

SIF:  A Safety Instrumented Function … the method by which the risk of a specific hazard is reduced automatically, using sensors, logic solvers and final elements (e.g., high pressure interlock on a reactor)

www.ueonline.com/st

SIMPLE SIS EXAMPLE

www.ueonline.com/st

DETERMINING THE NEED FOR A SIS

• The user must conduct a Hazards and Operability study (Hazop) to determine the types of failure or malfunction that could occur in the process.  

• This hazard analysis will lead to the decision of whether a SIS is required.  

• If it is, the user must then decide what Safety Integrity Level (SIL) is required for the process.  The user can use a variety of techniques for this, including Levels of Protection Analysis (LOPA).

• Let’s look a bit closer at this.

www.ueonline.com/st

LOPA

• A LOPA uses the idea of Defense in Depth, offering many interlocking opportunities to prevent a problem from spreading

• Note:  the safer the basic process, the less you need the other layers . . .

Layers of Protection Analysis

Respond:  Plant and Community actions

Mitigate:  the SIS, passive layers like walls

Prevent: the SIS , mechanical devices, and operator actions 

Automatic Control:  The BPCS

The Design of the Process

www.ueonline.com/st

A LOPA ANALOGY 

Layers of Protection A Process A Car

Basic Design Proper specifications for the process

Proper specs for the usage (e.g., 4x4 or mini‐van)

Process Control BPCS (DCS, PLC’s, etc.) Gas pedal, transmission,engine

Prevention Alarms, interlocks, SIS functions

Steering, brakes, anti‐skidand anti‐lock brakes

Mitigation SIS functions, walls, dikes, fire suppression

Bumpers, airbags, crumple zones

Response Evacuation, fire and emergency response, communication

Onstar, cell phone, police, fire, ambulance

www.ueonline.com/st

SIL

• SIL is a measure of the performance and reliability of a SIF when it is called upon to do its job (i.e., protect).

• It can only be specified for a loop, not an individual device.  There are no “SIL 2‐Rated” devices!

• You cannot say a system is “safe” or “unsafe” – you must define the amount of risk within the process that is tolerable

Safety Integrity Level

www.ueonline.com/st

SIL

• There are four SIL categories, based on a 10X reduction of risk at each level (but there are virtually no SIL 4 applications in the process industry)

www.ueonline.com/st

SIL

• Basically, SIL is defined by:– the likelihood of a failure within the safety system:  

• Probability of Failure on Demand (PFD) and its reciprocal, the Risk Reduction Factor (RRF)

– the impact of such a failure on the system • Hardware Fault Tolerance (HFT) and • Safe Failure Fraction (SFF)

– the consequences of that failure 

• Let’s look at each of these

www.ueonline.com/st

PFD AND RRF 

• In a system that is passive under normal operating conditions, the PFDavg tells an engineer the average probability that a device won’t work when called upon.  This is expressed as a decimal (e.g., x10‐3) 

• The RRF is the reciprocal of the PFD.  For instance, if the RRF is noted as 806, then the PDFavg would be 1/806 (0.00124), putting it into the SIL2 level.

Probability of Failure on Demand,  and Risk Reduction Factor

SIL Description RRF PFDavg

1 Minor property and production Impact >10 to ≤ 100 0.1‐0.01

2 Major property & production impact; possible injury >100 to ≤ 1,000 0.01‐0.001

3 Employees and community impact >1,000 to ≤ 10,000 0.001‐0.0001

4 Catastrophic community impact >10,000 to ≤ 100,000 0.0001‐0.00001

www.ueonline.com/st

HFTHardware Fault Tolerance

• HFT is a measure of redundancy built into an instrument or system – HFT=0 The device or system loses its ability to protect if any single component fails 

– HFT=1 A device can still function properly if any one component fails (dual redundancy)

– HFT=2 A device can still function if two separate components fail (triple redundancy)

www.ueonline.com/st

SFF

• Device failures can be broken down into four blocks:

Safe Failure Fraction

Safe & DetectedA nuisance, but doesn’t affect the proper operation of the system (e.g., a normally‐visible LCD display segment is damaged)

Safe &UndetectedA nuisance, but doesn’t affect the proper operation of the system (e.g., a normally‐blank LCD display segment, visible only when a menu is triggered, is damaged)

Dangerous & DetectedSerious but allows for proactive response (e.g., an electrical surge causes the output to fail and the system recognizes this)

Dangerous and UndetectedVery serious – the safety function will not occur if required, and is unknown (e.g., a pressure spike damages the sensor, but not completely, and the output drifts erratically.  The system may not be able to detect this)

www.ueonline.com/st

SSF

• The SFF of a device is determined by:– Analyzing all of the possible failure modes in that product– Determining how each of those failures falls into the four categories 

Defining the SFF

– Adding up all but the Dangerous/Undetected faults 

– Dividing that by the total number of possible faults.

• This gives you a percentage of diagnostic coverage

www.ueonline.com/st

PUTTING SFF AND HFT TOGETHER

• The chart below shows the relationship between SFF and HFT for “complex” (electronic) devices.  The higher the SFF or the higher the HFT, the higher SIL rating that’s achievable (without redundancy of devices)

For instance, if the deviceyou want to use has a  SFF of 92% and a HFT of 0, you’ll need only one for a SIL 2 application but will need to use 2 of them to get toSIL 3

www.ueonline.com/st

THE SOURCES OF SIS FAILURES

Because they are in the environment and usually connected to the process, Sensors and Final Elements are more susceptible to failure than Logic SolversSo if we assume all devices fail (and they do), then devices with the most diagnostic coverage (highest SFF) will give us the most peace of mind 

What Could Possibly Go Wrong?

www.ueonline.com/st

IMPROVING THE SAFETY SYSTEM

• In addition to improving the reliability of the devices themselves, there are a number of ways that designers can improve the overall reliability of their systems:– Diversity– Redundancy– Voting Logic – Proof Testing Intervals

www.ueonline.com/st

DIVERSITY

• Use diverse technologies to increase overall system reliability • Use diverse technologies to avoid common mode failures

www.ueonline.com/st

REDUNDANCY

• Redundancy increases SIS availability

www.ueonline.com/st

VOTING LOGIC

1oo1 – 1 out of 1 or “Simplex” system - a single channel with zero fault tolerance

1oo2 – dual channel 1 out of 2, either channel causes an ESD, increases system integrity but causes more spurious (nuisance) trips

www.ueonline.com/st

VOTING LOGIC

• 2oo3 – Triple Modular Redundancy (TMR)– 2 out of 3, two channels must agree for ESD– If one channel fails, defaults to 1oo2

– Does not cause a spurious trip, safety is not compromised, two channels continue to operate.

– Any drawbacks or trade‐offs here?

www.ueonline.com/st

PROOF TESTING

• An SIS system must be tested periodically to prove the essential components will work when needed

• More frequent testing means greater assurance the components are in good working order

– Results in a lower Probability to Fail on Demand (PFDavg)– and higher Risk Reduction Factor (RRF)

Will your equipment work when needed?

www.ueonline.com/st

PROOF TESTING

Option IssuesDesign the SIS so that it doesn't need testing during the long periods between plant shutdowns.

Cost of components and materials that are able to achieve that?

Install bypass lines around each final control element to facilitate full proof testing while the process remains in operation

No protection during testing!Bypass lines may be inadvertently left open (so no protection ever)!

Use manual or automated partial‐stroke valve testing to reduce the PFDavg. 

May not prove that valve will close completely under demand

Want to make it easier?

www.ueonline.com/st

KEY INDUSTRY DRIVERS

The need for improved levels of safety  Lack of end user SIS & SIL understanding  Increasing adoption of SIL certified instrumentation $10b of old legacy safety systems needing replacement High cost and downtime has decreased safety by delaying 

system upgrades Both switches and transmitters are currently used, so 

retrofitting is more complicated Old systems prone to failure

What’s Keeping YOU up at night?

www.ueonline.com/st

CONCLUSIONS

• The Process Owner faces an important question:  How can I keep my process running as much as possible (to maximize profit), but prevent any accidents (to maximize safety)?

• A properly designed Safety Instrumented System plays an important role in answering that question, providing the proper balance between uptime and safety.

www.ueonline.com/st

Thank you for your interest!