  • 8/10/2019 BruceBator Presentation C3AE

    1/20

    ProtectingElectricalEquipment

    inHazardousLocations

    Overviewoffundamentalsinregardstovariousstandards

    Presentedby: BruceBator

    EngineeringManager

    PhoenixMecano Inc.

  • 8/10/2019 BruceBator Presentation C3AE

    2/20

    KeyObjectives Providehistoricaloverviewofhazardouslocations

    ProvideExfundamentalsinregardstoignitionprevention

    Explanation

    of

    Zone

    classifications

    /relationship

    to

    Division

    DiscussprotectionmethodologiesinvariousZones

  • 8/10/2019 BruceBator Presentation C3AE

    3/20

    AHistoricalPerspective

    1815:TheDavyLampwasintroduced.

    Reasonablyrecognizedasfirsthazardous

    locationapparatus.

  • 8/10/2019 BruceBator Presentation C3AE

    4/20

  • 8/10/2019 BruceBator Presentation C3AE

    5/20

    MiningIndustryFlammablegases(methane)

    Flammabledust(coaldust)

    OilandGasIndustryFlammablegases&liquids

    ChemicalIndustyFlammablegases,liquids&solids

    EnergyProduction

    Flammablegases&oils

    Coaldust

    PaintingIndustryFlammableliquids&powders

    FoodstuffIndustryCombustabledusts(Flour,Sugar)

    AgricultureBiogases

    DisposalIndustryFlammablegases,liquids&solids

    Recycling

    IndustryFlammablegases,liquids&solids

    MetalProcessingWelding,cutoff&grinding

    processes

  • 8/10/2019 BruceBator Presentation C3AE

    6/20

    In

    order

    for

    combustion

    to

    occur,

    all

    three

    (3)

    legs

    must

    be

    present,eliminateanyleg,andtheexplosioncannothappen

  • 8/10/2019 BruceBator Presentation C3AE

    7/20

    Inhazardouslocations,thegoalistopreventignitionbyproviding

    protectionmethodsthat

    Preventexplosiveatmosphere

    Avoidignition

    Limittheeffectsofanexplosiontoanacceptablelevel

  • 8/10/2019 BruceBator Presentation C3AE

    8/20

    PrimaryMeasure

    Preventanexplosiveatmosphere

    Methods

    Ventilationsystems

    Gasdetectionsystems

    Additionofinertmaterialstodevices

    Preventintroductionofcombustiblematerials

  • 8/10/2019 BruceBator Presentation C3AE

    9/20

    SecondaryMeasure

    Avoidignition

    Methods

    Employingprotective

    measures

    against

    ignition

    Classifyingmaterials,areas,anddevices

    Definingacceptabletemperatures

  • 8/10/2019 BruceBator Presentation C3AE

    10/20

    Ignition

    Sources

    Hotsurfaces

    Electricalarcsandsparks

    Electrostaticdischarge

    Atmosphericdischarge

    Mechanicalsparks

    Chemicalreaction

    Openflame

    Electromagneticradiation

    Opticalradiation

  • 8/10/2019 BruceBator Presentation C3AE

    11/20

    ClassifyingMaterials

    GasesandVapors(ClassI)flashpoint

    ignitiontemperature

    maximumsafegap

    temperatureclass

    DustandParticles(ClassII)smolderingtemperature

    ignitiontemperature

    minimumignitiontemperature

  • 8/10/2019 BruceBator Presentation C3AE

    12/20

    ClassifyingAreas

    Group

    I

    Devicesforminingindustrywheremightbe

    minegasorcombustible

    dust

    Subdivisionin

    following

    categories

    M1 M2

    Group

    II

    Devicesforallotherareaswheremightbe

    hazardousatmosphere

    SubdivisionintoGasandDustareas

    Gas(G) Dust(D)

    Subdivisioninto categories

    1 2 3

  • 8/10/2019 BruceBator Presentation C3AE

    13/20

    Gas(G)andDust(D)aremaintainedasseparateareas

    Eachareahas3categoriesthataredesignatedzones

    Zonesdescribetheamountanddurationofmaterialpresent

    Zone0,20:(Category1)Combustibleconcentrationsare

    presentcontinuously

    or

    for

    long

    periods

    under

    normal

    operatingconditions

    Zone1,21:(Category2)Combustibleconcentrationsare

    likelytobepresentundernormaloperatingconditions

    Zone2,22:(Category3)Combustibleconcentrationsarenot

    likelyto

    exist

    under

    normal

    operating

    conditions

  • 8/10/2019 BruceBator Presentation C3AE

    14/20

    DifferencebetweenNEC500&NEC505

    Division1 Division2

    1(Zone0,20)

    2(Zone1,21)

    3(Zone2,22)

    Division1:Combustibleconcentrationscanexistsomeorallofthetimeundernormaloperatingconditions

    Division2:Combustibleconcentrationnotlikelytoexistundernormaloperatingconditions

  • 8/10/2019 BruceBator Presentation C3AE

    15/20

    ClassifyingDevicesEach

    electrical

    device

    which

    is

    to

    be

    used

    within

    an

    Ex

    area

    has

    to

    be

    Ex

    approved.

    Each

    device

    is

    approvedforuseinacategory. Thelowerthecategorynumber,themoreareasthedevicecanbe

    usedin. ThecategoryinformationdefineswhichExzonesthisspecificdeviceisallowedtobe

    used.

    category approval can be used in zone

    3G 22G 1, 2

    1G 0, 1, 2

    3D 22

    2D 21, 22

    1D 20, 21, 22

  • 8/10/2019 BruceBator Presentation C3AE

    16/20

    DefiningTemperature

    Themaximumtemperatureofanelectricdevicemustalways

    belowerthantheignitiontemperatureofthegas.

    Accordingtheirignitiontemperature,gasesaretobedivided

    intotemperature

    classes

    (T1

    to

    T6).

    Conversely,electricaldevicesareselectedaccordingtheir

    maximumworkingtemperature,andareplacedintothe

    appropriatetemperatureclass.

  • 8/10/2019 BruceBator Presentation C3AE

    17/20

    TemperatureClassifications

    TClass Max SurfaceTemp Ignitiontempofmaterial

    T1 450C >450C

    T2 300C >300C

    T3 200C >200C

    T4 135C >135C

    T5 100C >100C

    T6 85C

    >

    85C

    Tm

    Ta To

    To Surfacetemperature

    Tm Internalheatingtemperature

    Ta

    Ambienttemperature

  • 8/10/2019 BruceBator Presentation C3AE

    18/20

    ComparisonofAcceptableProtectionMethodsClassIDivision1 ClassIZone0

    IntrinsicSafety Intrinsic

    Safety

    "ia"

    Explosionproof Encapsulation"ma"

    Purge/Pressurized(TypeXorY)

    ClassIZone1

    Flameproof"d"

    Intrinsicsafety"ib"

    Encapsulated"mb"

    PowderFilling"q"

    OilImmersion

    "o"

    IncreasedSafety"e"

    Pressurization"px"or"py"

    Class1Division2 ClassIZone2

    HermeticallySealed Encapsulated"mc"

    Nonincendive Intrinsicsafety"mc"

    Nonsparking Pressurization"pz"

    Purge/Pressurized(TypeZ) EnergyLimited"nL/nC"

    Nonsparking

    "nA"

    Restrictedbreathing"nR"

  • 8/10/2019 BruceBator Presentation C3AE

    19/20

    KeyTake

    Aways

    TheuseofClassZoneinUSAbringscloseralignmentto

    internationalcommunity

    TheuseofClassZoneallowspossibleprotectionmethodsnot

    allowedunder

    Class

    Division

    Youstillmustuseanapprovedprotectionmethodforthearea

    youareplacingthedevice