cabinas mt unimix-jti.pdf

Upload: pedrommm2

Post on 02-Jun-2018

264 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    1/26

    Medium voltage products

    UniMix JTISecondary distribution switchgearwith rapid delivery times

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    2/262

    The JTI Just To Install acronym indicates a type of

    medium voltage switchgear for primary and secondary

    distribution featuring very rapid delivery and putting into

    service.

    The customer usually receives the UniMix JTI switchgear

    within two weeks.

    By means of a product configuration which allows the

    preparation of precise and rapid estimates, the customer

    receives complete proposals and is relieved of the task

    of preparing the technical specifications and design

    drawings.

    UniMix JTIDesigned and built for industry customers

    The UniMix JTI switchgears are based on the standard

    switchgear design and have a range of types that can satisfy

    even partial installation requirements, thanks to both their

    electrical characteristics and the standard accessories

    supplied.

    UniMix JTI switchgears are always fitted with mechanical and

    electro-mechanical interlocks in accordance with IEC 62271-

    200 standards, and are available with gas and vacuum circuit-

    breakers; all the solutions have the incoming unit complying

    with the CEI 0-16 standard and involve the use of the

    onboard circuit-breaker relay REF601 (see warning page 3),

    or alternatively, the REF542 plus unit as the protection unit.The technical design documentation is immediately available

    and the customer gives official approval of the project during

    the offer stage.

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    3/263

    General characteristics

    Units and sides made of pre-galvanized sheet

    Front panel doors painted grey RAL 7035

    Fixed HD4/Unimix-F or fixed VD4/UniMix-F circuit-breaker

    On-board circuit-breaker current sensors or combined

    current/voltage sensors in accordance with DIN standards

    On-board circuit-breaker protection relay REF601 (see

    warning page 3) or protection and microprocessor control

    unit REF542plus

    Protection system for incoming units conforming to

    standard CEI 0-16 Edition July 2008 Provision for earthing by using mobile devices or earthing

    switch in the incoming unit on the network side

    Conformity with Standards

    IEC 62271-200

    EN 62271-200

    Version

    Standard (not arc-proof)

    Classification

    Service continuity: LSC2A

    Partitions: PM (Partition metallic)

    UniMix JTICharacteristics

    Protection degree

    IP2X inside the switchgear

    IP3X on the external housing (except for the operatingseats)

    IP2XC on the operating seats

    Mechanical interlocks available

    Circuit-breaker with line-side insulator Line-side insulator with earthing switch

    Door with earthing switch

    Auxiliary circuits voltage

    220 VAC

    Electrical characteristicsRated voltage kV 24

    Test voltage (50 Hz/1 min) kV 50

    Impulse withstand voltage kV 125

    Rated frequency Hz 50

    Rated current A 630

    Short-time withstand current kA 16

    Peak current kA 40

    WARNING!REF 601 cannot be applied for protecting systems

    characterized by the presence of high harmonic currents,

    in particular for feeders supplying:

    electronic converters, speed regulators

    active or passive PFC (Power Factor Compensation)

    systems

    induction heating and welding systems

    arc furnaces.

    Even in the case where the load is not supplied directly,

    but through a power transformer.Should the REF 601 be applied under these conditions,

    ABB decl ines any liability for possible malfunctions.

    For further information, please contact ABB.

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    4/264

    HD4/UniMix-F gas circuit-breaker

    (with REF601(*)relay and current sensors).

    Current-transformer.

    Current/voltage sensor.

    SHS2 gas switch-disconnector. REF542plus multiple-function

    control and protection unit.

    VD4/UniMix-F vacuum circuit-breaker

    (with REF601(*)relay and current sensors).

    UniMix JTIMain components

    (*) see warning page 3

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    5/265

    JTI A1-CLsx Switchgear

    No. 1 Incoming/Outgoing Unit with CL Left

    cable Riser Unit + No. 1 P1/F unit with fixed

    circuit-breaker

    Presence of voltage on busbar side and cable

    side.

    HD4/Unimix-F or VD4/UniMix-F p230 non-

    motorised circuit-breaker with shunt opening

    release, shunt closing release, operation

    counter, 2 NO + 2 NC auxiliary contacts,

    undervoltage release and contact signalling

    release de-energised. REF601 protection relay without communication

    (51, I>; 51, I>>; 50, I>>>; 51N, Io>; 50N, Io>>)

    with 3 on-board circuit-breaker sensors and

    toroid for earth fault, conforming to standard

    CEI 0-16 (see warning page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side isolator in the

    closed position and 1 removable key in the

    open position;

    1 removable key with earthing switch in the

    closed position and 1 removable key in the

    open position. Provision for earthing by means of insulating

    rod. The insulating rod is not included in the

    supply unless ordered separately.

    UniMix JTIConfigurations available

    Circuit-breaker Switchgear description Sales code FittingsHD4/UniMix-F JTI_A1_Z_CLsx_N_N_GAS 1VCF594000R0233 Without accessories

    HD4/UniMix-F JTI_A1_Z_CLsx_N_R_GAS 1VCF594000R0234 Anti-condensation heater

    HD4/UniMix-F JTI_A1_Z_CLsx_I_N_GAS 1VCF594000R0235 Internal lighting

    HD4/UniMix-F JTI_A1_Z_CLsx_I_R_GAS 1VCF594000R0236 Internal lighting and anti-condensation heater

    Circuit-breaker Switchgear description Sales code Fittings

    VD4/UniMix-F JTI_A1_Z_CLsx_N_N_VUOTO 1VCF594000R0273 Without accessories

    VD4/UniMix-F JTI_A1_Z_CLsx_N_R_VUOTO 1VCF594000R0274 Anti-condensation heater

    VD4/UniMix-F JTI_A1_Z_CLsx_I_N_VUOTO 1VCF594000R0275 Internal light ing

    VD4/UniMix-F JTI_A1_Z_CLsx_I_R_VUOTO 1VCF594000R0276 Internal light ing and anti-condensation heater

    Completion Description Sales codeInsulating rod Kit for mobile earthing 1VCF594000R0218

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0145

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    6/266

    JTI A1-CLdx Switchgear

    No. 1 Incoming/Outgoing Unit with CL Right

    cable Riser Unit + No. 1 P1/F unit with fixed

    circuit-breaker

    Presence of voltage on busbar side and cable

    side.

    HD4/Unimix-F or VD4/UniMix-F p230 non-

    motorised circuit-breaker with shunt opening

    release, shunt closing release, operation

    counter, 2 NO + 2 NC auxiliary contacts,

    undervoltage release and contact signalling

    release de-energised. REF601 protection relay without communication

    (51, I>; 51, I>>; 50, I>>>; 51N, Io>; 50N, Io>>)

    with 3 on-board circuit-breaker sensors and

    toroid for earth fault, conforming to standard

    CEI 0-16 (see warning page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side isolator in the

    closed position and 1 removable key in the

    open position;

    1 removable key with earthing switch in the

    closed position and 1 removable key in the

    open position. Provision for earthing by means of insulating

    rod. The insulating rod is not included in the

    supply unless ordered separately.

    Circuit-breaker Switchgear description Sales code FittingsHD4/UniMix-F JTI_A1_Z_CLdx_N_N_GAS 1VCF594000R0237 Without accessories

    HD4/UniMix-F JTI_A1_Z_CLdx_N_R_GAS 1VCF594000R0238 Anti-condensation heater

    HD4/UniMix-F JTI_A1_Z_CLdx_I_N_GAS 1VCF594000R0239 Internal lighting

    HD4/UniMix-F JTI_A1_Z_CLdx_I_R_GAS 1VCF594000R0240 Internal lighting and anti-condensation heater

    Circuit-breaker Switchgear description Sales code Fittings

    VD4/UniMix-F JTI_A1_Z_CLdx_N_N_VUOTO 1VCF594000R0277 Without accessories

    VD4/UniMix-F JTI_A1_Z_CLdx_N_R_VUOTO 1VCF594000R0278 Anti -condensat ion heater

    VD4/UniMix-F JTI_A1_Z_CLdx_I_N_VUOTO 1VCF594000R0279 Internal light ing

    VD4/UniMix-F JTI_A1_Z_CLdx_I_R_VUOTO 1VCF594000R0280 Internal light ing and anti-condensation heater

    Completion Description Sales codeInsulating rod Kit for mobile earthing 1VCF594000R0218

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0145

    UniMix JTIConfigurations available

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    7/267

    No. 1 Incoming/Outgoing Unit with incoming

    cables from the top AC + No. 1 P1/F unit with

    fixed circuit-breaker

    Presence of voltage on busbar side and cable

    side.

    HD4/Unimix-F or VD4/UniMix-F p230 non-

    motorised circuit-breaker with shunt opening

    release, shunt closing release, operation

    counter, 2 NO + 2 NC auxiliary contacts,

    undervoltage release and contact signalling

    release de-energised. REF601 protection relay without communication

    (51, I>; 51, I>>; 50, I>>>; 51N, Io>; 50N, Io>>)

    with 3 on-board circuit-breaker sensors and

    toroid for earth fault, conforming to standard

    CEI 0-16 (see warning page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side insulator in

    the closed position and 1 removable key in

    the open position;

    1 removable key with earthing switch in the

    closed position and 1 removable key in the

    open position. Provision for earthing by means of insulating

    rod. The insulating rod is not included in the

    supply unless ordered separately.

    JTI A1-AC Switchgear

    Circuit-breaker Switchgear description Sales code FittingsHD4/UniMix-F JTI_A1_Z_AC_N_N_GAS 1VCF594000R0241 Without accessories

    HD4/UniMix-F JTI_A1_Z_AC_N_R_GAS 1VCF594000R0242 Anti-condensation heater

    HD4/UniMix-F JTI_A1_Z_AC_I_N_GAS 1VCF594000R0243 Internal lighting

    HD4/UniMix-F JTI_A1_Z_AC_I_R_GAS 1VCF594000R0244 Internal lighting and anti-condensation heater

    Circuit-breaker Switchgear description Sales code Fittings

    VD4/UniMix-F JTI_A1_Z_AC_N_N_VUOTO 1VCF594000R0281 Without accessories

    VD4/UniMix-F JTI_A1_Z_AC_N_R_VUOTO 1VCF594000R0282 Anti-condensation heater

    VD4/UniMix-F JTI_A1_Z_AC_I_N_VUOTO 1VCF594000R0283 Internal light ing

    VD4/UniMix-F JTI_A1_Z_AC_I_R_VUOTO 1VCF594000R0284 Internal light ing and anti-condensation heater

    Completion Description Sales codeInsulating rod Kit for mobile earthing 1VCF594000R0218

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0143

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    8/268

    JTI A1-Asx Switchgear

    No. 1 Incoming Unit with Unit A with

    Left earthing switch + No. 1 P1/F Unit

    with fixed circuit-breaker

    Incoming Unit A

    Presence of voltage on cable side.

    SHS2/ES Earthing switch with:

    2 removable keys with earthing

    switch in the open position.

    P1/F Outgoing Unit

    Presence of voltage on cable side. HD4/Unimix-F or VD4/UniMix-F p230

    non-motorised circuit-breaker with

    shunt opening release, shunt closing

    release, operation counter, 2 NO +

    2 NC auxiliary contacts,

    undervoltage release and contact

    signalling release de-energised.

    REF601 protection relay without

    communication (51, I>; 51, I>>; 50,

    I>>>; 51N, Io>; 50N, Io>>) with 3

    on-board circuit-breaker sensors

    and toroid for earth fault, conformingto standard CEI 0-16 (see warning

    page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side

    insulator in the closed position

    and 1 removable key in the open

    position;

    1 removable key with earthing

    switch in the closed position

    and 1 removable key in the open

    position.

    Circuit-breaker Switchgear description Sales code Fittings

    HD4/UniMix-F JTI_A1_Z_Asx_N_N_GAS 1VCF594000R0245 Without accessories

    HD4/UniMix-F JTI_A1_Z_Asx_N_R_GAS 1VCF594000R0246 Anti-condensation heater

    HD4/UniMix-F JTI_A1_Z_Asx_I_N_GAS 1VCF594000R0247 Internal lighting

    HD4/UniMix-F JTI_A1_Z_Asx_I_R_GAS 1VCF594000R0248 Internal lighting and anti-condensation heater

    Circuit-breaker Switchgear description Sales code Fittings

    VD4/UniMix-F JTI_A1_Z_Asx_N_N_VUOTO 1VCF594000R0285 Without accessories

    VD4/UniMix-F JTI_A1_Z_Asx_N_R_VUOTO 1VCF594000R0286 Anti -condensat ion heater

    VD4/UniMix-F JTI_A1_Z_Asx_I_N_VUOTO 1VCF594000R0287 Internal light ing

    VD4/UniMix-F JTI_A1_Z_Asx_I_R_VUOTO 1VCF594000R0288 Internal light ing and anti-condensation heater

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0457

    UniMix JTIConfigurations available

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    9/269

    JTI A1-Adx Switchgear

    No. 1 Incoming Unit with Unit A with

    Right earthing switch + No. 1 P1/F

    Unit with fixed circuit-breaker

    Incoming Unit A

    Presence of voltage on cable side.

    SHS2/ES Earthing switch with:

    2 removable keys with earthing

    switch in the open position.

    P1/F Outgoing Unit

    Presence of voltage on cable side. HD4/Unimix-F or VD4/UniMix-F p230

    non-motorised circuit-breaker with

    shunt opening release, shunt closing

    release, operation counter, 2 NO +

    2 NC auxiliary contacts, undervoltage

    release and contact signalling release

    de-energised.

    REF601 protection relay without

    communication (51, I>; 51, I>>; 50,

    I>>>; 51N, Io>; 50N, Io>>) with 3

    on-board circuit-breaker sensors

    and toroid for earth fault, conformingto standard CEI 0-16 (see warning

    page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side

    insulator in the closed position

    and 1 removable key in the open

    position;

    1 removable key with earthing

    switch in the closed position

    and 1 removable key in the open

    position.

    Circuit-breaker Switchgear description Sales code Fittings

    HD4/UniMix-F JTI_A1_Z_Adx_N_N_GAS 1VCF594000R0249 Without accessories

    HD4/UniMix-F JTI_A1_Z_Adx_N_R_GAS 1VCF594000R0250 Anti-condensation heater

    HD4/UniMix-F JTI_A1_Z_Adx_I_N_GAS 1VCF594000R0251 Internal lighting

    HD4/UniMix-F JTI_A1_Z_Adx_I_R_GAS 1VCF594000R0252 Internal lighting and anti-condensation heater

    Circuit-breaker Switchgear description Sales code Fittings

    VD4/UniMix-F JTI_A1_Z_Adx_N_N_VUOTO 1VCF594000R0289 Without accessories

    VD4/UniMix-F JTI_A1_Z_Adx_N_R_VUOTO 1VCF594000R0290 Anti-condensation heater

    VD4/UniMix-F JTI_A1_Z_Adx_I_N_VUOTO 1VCF594000R0291 Internal light ing

    VD4/UniMix-F JTI_A1_Z_Adx_I_R_VUOTO 1VCF594000R0292 Internal light ing and anti-condensation heater

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0457

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    10/2610

    JTI A2-Racsx switchgear with SF6circuit-breaker

    No. 1 Incoming/Outgoing Unit with Rac Left

    cable Riser Unit + No. 1 P1/F Unit with fixed

    circuit-breaker

    235mm LV compartment.

    Presence of voltage on busbar side and cable

    side.

    HD4/Unimix-F p230 non motorised circuit-

    breaker with shunt opening release, shunt

    closing release, 3 NO + 4 NC auxiliary contacts,

    operation counter and springs charged

    signalling. REF542 plus protection and control un it (51,

    I>; 51, I>>; 50, I>>>; 50N, Io>>; 67NI; 67NC)

    with DATA LOGGER and 3 KEVCD type ABB

    voltage/current sensors and toroid for earth fault

    conforming to standard CEI 0-16.

    SHS2/IB disconnector with:

    1 removable key with line-side insulator in

    the closed position and 1 removable key in

    the open position;

    1 removable key with earthing switch in the

    closed position and 1 removable key in the

    open position; Auxiliary contacts: 2 NO or NC with line-side

    disconnector and 2 NO or NC for earthing

    switch.

    Provision for earthing by means of insulating

    rod. The insulating rod is not included in the

    supply unless ordered separately.

    Circuit-breaker Switchgear description Sales code FittingsHD4/UniMix-F JTI_A2_Z_RACsx_N_N_GAS 1VCF594000R0313 Without accessories

    HD4/UniMix-F JTI_A2_Z_RACsx_N_R_GAS 1VCF594000R0314 Anti-condensation heater

    HD4/UniMix-F JTI_A2_Z_RACsx_I_N_GAS 1VCF594000R0315 Internal lighting

    HD4/UniMix-F JTI_A2_Z_RACsx_I_R_GAS 1VCF594000R0316 Internal lighting and anti-condensation heater

    Completion Description Sales code

    Insulating rod Kit for mobile earthing 1VCF594000R0218

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0459

    UniMix JTIConfigurations available

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    11/2611

    JTI A2-Racsx switchgear with vacuum circuit-breaker

    No. 1 Incoming/Outgoing Unit with Rac Left

    cable Riser Unit + No. 1 P1/F Unit with fixed

    circuit-breaker

    235 mm LV compartment.

    Presence of voltage on busbar side and cable

    side.

    VD4/Unimix-F p230 non motorised circuit-bre-

    aker with shunt opening release, shunt closing

    release, 3 NO + 4 NC auxiliary contacts, ope-

    ration counter and springs charged signalling,

    undervoltage release and contact signallingrelease de-energised.

    REF542 plus protection and control unit (51, I>;

    51, I>>; 50, I>>>; 50N, Io>>; 67NI; 67NC) with

    3 KEVCD type ABB voltage/current sensors

    and toroid for earth fault conforming to stan-

    dard CEI 0-16.

    SHS2/IB disconnector with:

    1 removable key with line-side disconnector

    in the closed position and 1 removable key

    in the open position;

    1 removable key with earthing switch in the

    closed position and 1 removable key in theopen position;

    Auxiliary contacts: 2 NO or NC with line-side

    disconnector and 2 NO or NC for earthing

    switch.

    Provision for earthing by means of insulating

    rod. The insulating rod is not included in the

    supply unless ordered separately.

    Circuit-breaker Switchgear description Sales code FittingsVD4/UniMix-F JTI_A2_Z_RACsx_N_N_VUOTO 1VCF594000R0345 Without accessories

    VD4/UniMix-F JTI_A2_Z_RACsx_N_R_VUOTO 1VCF594000R0346 Anti -condensat ion heater

    VD4/UniMix-F JTI_A2_Z_RACsx_I_N_VUOTO 1VCF594000R0347 Internal light ing

    VD4/UniMix-F JTI_A2_Z_RACsx_I_R_VUOTO 1VCF594000R0348 Internal light ing and anti-condensation heater

    Completion Description Sales code

    Insulating rod Kit for mobile earthing 1VCF594000R0218

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0459

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    12/2612

    JTI A2-Racdx switchgear with SF6circuit-breaker

    No. 1 Incoming/Outgoing Unit with Rac Right

    Cable Riser Unit + No. 1 P1/F Unit with fixed

    circuit-breaker

    235 mm LV compartment.

    Presence of voltage on busbar side and cable

    side.

    HD4/Unimix-F p230 non motorised circuit-

    breaker with shunt opening release, shunt

    closing release, 3 NO + 4 NC auxiliary contacts,

    operation counter and springs charged

    signalling. REF542 plus protection and control unit (51,

    I>; 51, I>>; 50, I>>>; 50N, Io>>; 67NI; 67NC)

    with DATA LOGGER and 3 KEVCD type ABB

    voltage/current sensors and toroid for ear th fault

    conforming to standard CEI 0-16.

    SHS2/IB disconnector with:

    1 removable key with line-side disconnector

    in the closed position and 1 removable key

    in the open position;

    1 removable key with earthing switch in the

    closed position and 1 removable key in the

    open position; Auxiliary contacts: 2 NO or NC with line-side

    disconnector and 2 NO or NC for earthing

    switch.

    Provision for earthing by means of insulating

    rod. The insulating rod is not included in the

    supply unless ordered separately.

    Circuit-breaker Switchgear description Sales code FittingsHD4/UniMix-F JTI_A2_Z_RACdx_N_N_GAS 1VCF594000R0317 Without accessories

    HD4/UniMix-F JTI_A2_Z_RACdx_N_R_GAS 1VCF594000R0318 Anti-condensation heater

    HD4/UniMix-F JTI_A2_Z_RACdx_I_N_GAS 1VCF594000R0319 Internal lighting

    HD4/UniMix-F JTI_A2_Z_RACdx_I_R_GAS 1VCF594000R0320 Internal lighting and anti-condensation heater

    Completion Description Sales code

    Insulating rod Kit for mobile earthing 1VCF594000R0218

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0459

    UniMix JTIConfigurations available

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    13/2613

    JTI A2-Racdx switchgear with vacuum circuit-breaker

    No. 1 Incoming/Outgoing Unit with Rac Right

    Cable Riser Unit + No. 1 P1/F Unit with fixed

    circuit-breaker

    235 mm LV compartment.

    Presence of voltage on busbar side and cable

    side.

    VD4/Unimix-F p230 non motorised circuit-

    breaker with shunt opening release, shunt

    closing release, 3 NO + 4 NC auxiliary contacts,

    operation counter and springs charged

    signalling, undervoltage release and contactsignalling release de-energised.

    REF542 plus protection and control unit (51,

    I>; 51, I>>; 50, I>>>; 50N, Io>>; 67NI; 67NC)

    with 3 KEVCD type ABB voltage/current

    sensors and toroid for earth fault conforming to

    standard CEI 0-16.

    SHS2/IB disconnector with:

    1 removable key with line-side disconnector

    in the closed position and 1 removable key

    in the open position;

    1 removable key with earthing switch in the

    closed position and 1 removable key in theopen position;

    Auxiliary contacts: 2 NO or NC with line-side

    disconnector and 2 NO or NC for earthing

    switch.

    Provision for earthing by means of insulating

    rod. The insulating rod is not included in the

    supply unless ordered separately.

    Circuit-breaker Switchgear description Sales code FittingsVD4/UniMix-F JTI_A2_Z_RACdx_N_N_VUOTO 1VCF594000R0349 Without accessories

    VD4/UniMix-F JTI_A2_Z_RACdx_N_R_VUOTO 1VCF594000R0350 Anti-condensation heater

    VD4/UniMix-F JTI_A2_Z_RACdx_I_N_VUOTO 1VCF594000R0351 Internal light ing

    VD4/UniMix-F JTI_A2_Z_RACdx_I_R_VUOTO 1VCF594000R0352 Internal light ing and anti-condensation heater

    Completion Description Sales code

    Insulating rod Kit for mobile earthing 1VCF594000R0218

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0459

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    14/2614

    JTI A2-Asx switchgear with SF6circuit-breaker

    No. 1 Incoming Unit with Unit A Left

    earthing switch + No. 1 Unit P1/F with

    fixed circuit-breaker

    Incoming Unit A

    Presence of voltage on cable side.

    SHS2/ES Earthing switch with:

    2 removable keys with earthing switch

    in the open position.

    P1/F Outgoing Unit

    235 mm LV compartment. Presence of voltage on cable side.

    HD4/Unimix-F p230 non motorised

    circuit-breaker with shunt opening

    release, shunt closing release, 3 NO

    + 4 NC auxiliary contacts, operation

    counter and springs charged signalling.

    REF542 plus protection and control unit

    (51, I>; 51, I>>; 50, I>>>; 50N, Io>>;

    67NI; 67NC) with DATA LOGGER and 3

    KEVCD type ABB voltage/current sen-

    sors and toroid for earth fault confor-

    ming to standard CEI 0-16. SHS2/ES Earthing switch with:

    1 removable key with line-side

    disconnector in the closed position

    and 1 removable key in the open

    position;

    1 removable key with earthing

    switch in the closed position and 1

    removable key in the open position;

    auxiliary contacts: 2 NO or NC with

    line-side disconnector and 2 NO or

    NC for earthing switch.

    Circuit-breaker Switchgear description Sales code Fittings

    HD4/UniMix-F JTI_A2_Z_Asx_N_N_GAS 1VCF594000R0321 Without accessories

    HD4/UniMix-F JTI_A2_Z_Asx_N_R_GAS 1VCF594000R0322 Anti-condensation heater

    HD4/UniMix-F JTI_A2_Z_Asx_I_N_GAS 1VCF594000R0323 Internal lighting

    HD4/UniMix-F JTI_A2_Z_Asx_I_R_GAS 1VCF594000R0324 Internal lighting and anti-condensation heater

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0457

    UniMix JTIConfigurations available

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    15/2615

    JTI A2-Asx switchgear with vacuum circuit-breaker

    No. 1 Incoming Unit with Unit A Left

    earthing switch + No. 1 P1/F Unit with

    fixed circuit-breaker

    Incoming Unit A

    Presence of voltage on cable side.

    SHS2/ES Earthing switch with:

    2 removable keys with earthing

    switch in the open position.

    P1/F Outgoing Unit

    235 mm LV compartment. Presence of voltage on cable side.

    VD/Unimix-F p230 non motorised

    circuit-breaker with shunt opening

    release, shunt closing release, 3 NO

    + 4 NC auxiliary contacts, operation

    counter and springs charged signalling,

    undervoltage release and contact

    signalling release de-energised.

    REF542 plus protection and control unit

    (51, I>; 51, I>>; 50, I>>>; 50N, Io>>;

    67NI; 67NC) with 3 KEVCD type ABB

    voltage/current sensors and toroid forearth fault conforming to standard

    CEI 0-16.

    SHS2/ES Earthing switch with:

    1 removable key with line-side discon-

    nector in the closed position and 1

    removable key in the open position;

    1 removable key with earthing switch

    in the closed position and 1 removable

    key in the open position;

    auxiliary contacts:2 NO or NC for

    line-side insulator and 2 NO or NC

    for earthing switch.

    Circuit-breaker Switchgear description Sales code Fittings

    VD4/UniMix-F JTI_A2_Z_Asx_N_N_VUOTO 1VCF594000R0353 Without accessories

    VD4/UniMix-F JTI_A2_Z_Asx_N_R_VUOTO 1VCF594000R0354 Anti-condensation heater

    VD4/UniMix-F JTI_A2_Z_Asx_I_N_VUOTO 1VCF594000R0355 Internal l ighti ng

    VD4/UniMix-F JTI_A2_Z_Asx_I_R_VUOTO 1VCF594000R0356 Internal l ighti ng and ant i-condensat ion heater

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0457

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    16/2616

    JTI A2-Adx switchgear with SF6circuit-breaker

    No. 1 Incoming Unit with Unit A Right

    earthing switch + No. 1 P1/F Unit with

    fixed circuit-breaker

    Incoming Unit A

    Presence of voltage on cable side.

    SHS2/ES Earthing switch with:

    2 removable keys with earthing switch

    in the open position.

    P1/F Outgoing Unit

    235 mm LV compartment. Presence of voltage on cable side.

    HD4/Unimix-F p230 non motorised

    circuit-breaker with shunt opening rele-

    ase, shunt closing release, 3 NO + 4 NC

    auxiliary contacts, operation counter and

    springs charged signalling.

    REF542 plus protection and control unit

    (51, I>; 51, I>>; 50, I>>>; 50N, Io>>;

    67NI; 67NC) with DATA LOGGER and 3

    KEVCD type ABB voltage/current sensors

    and toroid for earth fault conforming to

    standard CEI 0-16 (see warning page 3).

    SHS2/ES Earthing switch with:

    1 removable key with line-side discon-

    nector in the closed position and 1

    removable key in the open position;

    1 removable key with earthing switch

    in the closed position and 1 removable

    key in the open position;

    auxiliary contacts: 2 NO or NC with

    line-side disconnector and 2 NO or

    NC for earthing switch.

    Circuit-breaker Switchgear description Sales code Fittings

    HD4/UniMix-F JTI_A2_Z_Adx_N_N_GAS 1VCF594000R0325 Without accessories

    HD4/UniMix-F JTI_A2_Z_Adx_N_R_GAS 1VCF594000R0326 Anti-condensation heater

    HD4/UniMix-F JTI_A2_Z_Adx_I_N_GAS 1VCF594000R0327 Internal lighting

    HD4/UniMix-F JTI_A2_Z_Adx_I_R_GAS 1VCF594000R0328 Internal lighting and anti-condensation heater

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0457

    UniMix JTIConfigurations available

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    17/2617

    JTI A2-Adx switchgear with vacuum circuit-breaker

    No. 1 Incoming Unit with Unit A Right

    earthing switch + No. 1 P1/F Unit with

    fixed circuit-breaker

    Incoming Unit A

    Presence of voltage on cable side.

    SHS2/ES Earthing switch with:

    2 removable keys with earthing

    switch in the open position.

    P1/F Outgoing Unit

    235 mm LV compartment.

    Presence of voltage on cable side. VD/Unimix-F p230 non motorised

    circuit-breaker with shunt opening

    release, shunt closing release, 3 NO

    + 4 NC auxiliary contacts, operation

    counter and springs charged signalling,

    undervoltage release and contact

    signalling release de-energised.

    REF542 plus protection and control unit

    (51, I>; 51, I>>; 50, I>>>; 50N, Io>>;

    67NI; 67NC) with 3 KEVCD type ABB

    voltage/current sensors and toroid for

    earth fault conforming to standardCEI 0-16.

    SHS2/ES Earthing switch with:

    1 removable key with line-side

    disconnector in the closed position

    and 1 removable key in the open

    position;

    1 removable key with earthing

    switch in the closed position and 1

    removable key in the open position;

    auxiliary contacts: 2 NO or NC with

    line-side disconnector and 2 NO or

    NC for earthing switch.

    Circuit-breaker Switchgear description Sales code Fittings

    VD4/UniMix-F JTI_A2_Z_Adx_N_N_VUOTO 1VCF594000R0357 Without accessories

    VD4/UniMix-F JTI_A2_Z_Adx_N_R_VUOTO 1VCF594000R0358 Anti-condensation heater

    VD4/UniMix-F JTI_A2_Z_Adx_I_N_VUOTO 1VCF594000R0359 Internal light ing

    VD4/UniMix-F JTI_A2_Z_Adx_I_R_VUOTO 1VCF594000R0360 Internal light ing and anti-condensation heater

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0457

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    18/2618

    JTI B1 Switchgear

    No. 1 Incoming Line with P1/A Unit + No. 2 P1/F Transformer

    Protection Units

    Incoming Unit P1/A

    235 mm LV compartment.

    Presence of voltage on busbar side and cable side.

    HD4/Unimix-F or VD4/Unimix-F p230 non-motorised circuit-

    breaker with shunt opening release, shunt closing release,

    operation counter, 2 NO + 2 NC auxiliary contacts, undervoltage

    release and contact signalling release

    de-energised.

    REF601 protection relay without communication (51, I>;

    51, I>>; 50, I>>>; 51N, Io>; 50N, Io>>) with 3 on-board

    circuit-breaker sensors and toroid for earth fault, conforming to

    standard CEI 0-16 (see warning page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side disconnector in the closed

    position and 1 removable key in the open position;

    2 removable keys with earthing switch in the open position.

    Provision for earthing by means of insulating rod. The insulating

    rod is not included in the supply unless ordered separately.

    P1/F Transformer Protection Unit

    Presence of voltage on cable side.

    HD4/Unimix-F or VD4/Unimix-F p230 non-motorised circuit-

    breaker with shunt opening release, shunt closing release, 2 NO +

    2 NC auxiliary contacts and operation counter.

    REF601 protection relay conforming to IEC standard with 3

    sensors and toroid for earth fault (see warning page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side disconnector in the closed

    position and 1 removable key in the open position;

    1 removable key with earthing switch in the closed position

    and 1 removable key in the open position.

    Circuit-breaker Switchgear description Sales code FittingsHD4/UniMix-F JTI_B1_Z_N_N_GAS 1VCF594000R0377 Without accessories

    HD4/UniMix-F JTI_B1_Z_N_R_GAS 1VCF594000R0378 Anti-condensation heater

    HD4/UniMix-F JTI_B1_Z_I_N_GAS 1VCF594000R0379 Internal lighting

    HD4/UniMix-F JTI_B1_Z_I_R_GAS 1VCF594000R0380 Internal lighting and anti-condensation heater

    Circuit-breaker Switchgear description Sales code Fittings

    VD4/UniMix-F JTI_B1_Z_N_N_VUOTO 1VCF594000R0385 Without accessories

    VD4/UniMix-F JTI_B1_Z_N_R_VUOTO 1VCF594000R0386 Anti -condensat ion heater

    VD4/UniMix-F JTI_B1_Z_I_N_VUOTO 1VCF594000R0387 Internal light ing

    VD4/UniMix-F JTI_B1_Z_I_R_VUOTO 1VCF594000R0388 Internal light ing and anti-condensation heater

    Completion Description Sales codeInsulating rod Kit for mobile earthing 1VCF594000R0218

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0147

    UniMix JTIConfigurations available

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    19/2619

    JTI B2 switchgear with SF6circuit-breaker

    No. 1 Incoming Line with P1/A Unit + No. 2 P1/F Transformer

    Protection Units

    Incoming Unit P1/A

    235 mm LV compartment.

    Presence of voltage on busbar side and cable side.

    HD4/Unimix-F or VD4/Unimix-F p230 non motorised

    circuit-breaker with shunt opening release, shunt closing release,

    3 NO + 4 NC auxiliary contacts, operation counter and springs

    charged signalling.

    REF542 plus protection and control unit (51, I>; 51, I>>;

    50, I>>>; 50N, Io>>; 67NI; 67NC) with DATA LOGGER and

    3 KEVCD type ABB voltage/current sensors and toroid for earth

    fault conforming to standard CEI 0-16 (see warning page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side disconnector in the closed

    position and 1 removable key in the open position;

    2 removable keys with earthing switch in the open position;

    auxiliary contacts: 2 NO or NC with line-side disconnector

    and 2 NO or NC for earthing switch.

    Provision for earthing by means of insulating rod. The insulating

    rod is not included in the supply unless ordered separately.

    P1/F Transformer Protection Unit

    Presence of voltage on cable side. HD4/Unimix-F or VD4/Unimix-F p230 non-motorised circuit-

    breaker with shunt opening release, shunt closing release, 2 NO +

    2 NC auxiliary contacts and operation counter.

    REF601 protection relay conforming to IEC standard with 3

    sensors and toroid for earth fault (see warning page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side disconnector in the closed

    position and 1 removable key in the open position;

    1 removable key with earthing switch in the closed position

    and 1 removable key in the open position.

    Circuit-breaker Switchgear description Sales code Fittings

    HD4/UniMix-F JTI_B2_Z_N_N_GAS 1VCF594000R0393 Without accessories

    HD4/UniMix-F JTI_B2_Z_N_R_GAS 1VCF594000R0394 Anti-condensation heater

    HD4/UniMix-F JTI_B2_Z_I_N_GAS 1VCF594000R0395 Internal lighting

    HD4/UniMix-F JTI_B2_Z_I_R_GAS 1VCF594000R0396 Internal lighting and anti-condensation heater

    Completion Description Sales code

    Insulating rod Kit for mobile earthing 1VCF594000R0218

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0147

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    20/2620

    JTI B2 switchgear with vacuum circuit-breaker

    No. 1 Incoming Line with P1/A Unit + No. 2 P1/F Transformer

    Protection Units

    Incoming Unit P1/A

    235 mm LV compartment.

    Presence of voltage on busbar side and cable side.

    VD4/Unimix-F p230 non motor ised circuit-breaker with shunt

    opening release, shunt closing release, 3 NO + 4 NC auxiliary

    contacts, operation counter and springs charged signalling,

    undervoltage release and contact signalling release

    de-energised.

    REF542 plus protection and control unit (51, I>; 51, I>>; 50,

    I>>>; 50N, Io>>; 67NI; 67NC) with 3 KEVCD type ABB voltage/

    current sensors and toroid for earth fault conforming to standard

    CEI 0-16.

    SHS2/IB disconnector with:

    1 removable key with line-side disconnector in the closed

    position and 1 removable key in the open position;

    2 removable keys with earthing switch in the open position;

    auxiliary contacts: 2 NO or NC with line-side disconnector

    and 2 NO or NC for earthing switch.

    Provision for earthing by means of insulating rod. The insulating

    rod is not included in the supply unless ordered separately.

    P1/F Transformer Protection Unit Presence of voltage on cable side.

    HD4/Unimix-F or VD4/Unimix-F p230 non-motorised circuit-

    breaker with shunt opening release, shunt closing release, 2 NO

    + 2 NC auxiliary contacts and operation counter.

    REF601 protection relay conforming to IEC standard with 3

    sensors and toroid for earth fault (see warning page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side disconnector in the closed

    position and 1 removable key in the open position;

    1 removable key with earthing switch in the closed position

    and 1 removable key in the open position.

    Circuit-breaker Switchgear description Sales code Fittings

    VD4/UniMix-F JTI_B2_Z_N_N_VUOTO 1VCF594000R0401 Without accessories

    VD4/UniMix-F JTI_B2_Z_N_R_VUOTO 1VCF594000R0402 Anti -condensat ion heater

    VD4/UniMix-F JTI_B2_Z_I_N_VUOTO 1VCF594000R0403 Internal light ing

    VD4/UniMix-F JTI_B2_Z_I_R_VUOTO 1VCF594000R0404 Internal light ing and anti-condensation heater

    Completion Description Sales code

    Insulating rod Kit for mobile earthing 1VCF594000R0218

    UniMix JTIConfigurations available

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    21/2621

    JTI B3 Switchgear

    No. 1 Incoming Line with P1/A Unit + No. 2 P2 Transformer

    Protection Units with switch-disconnector

    Incoming Unit P1/A

    235 mm LV compartment.

    Presence of voltage on busbar side and cable side.

    HD4/Unimix-F or VD4/Unimix p230 non-motorised circuit-breaker with

    shunt opening release, shunt closing release, operation counter, 2 NO

    + 2 NC auxiliary contacts, undervoltage release and contact signalling

    release de-energised.

    REF601 protection relay without communication (51, I>; 51, I>>; 50, I>>>;

    51N, Io>; 50N, Io>>) with 3 on-board circuit-breaker current sensors and

    toroid for earth fault, conforming to standard CEI 0-16 (see warning page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side disconnector in the closed position

    and 1 removable key in the open position;

    2 removable keys with earthing switch in the open position.

    Provision for earthing by means of insulating rod. The insulating rod is not

    included in the supply unless ordered separately.

    P2 Transformer Protection Unit (unit width: 500 mm)

    Presence of voltage on cable side.

    SHS2/T2F switch-disconnector with:

    1 removable key with line-side disconnector in the closed position

    and 1 removable key in the open position; 1 removable key with earthing switch in the closed position and 1

    removable key in the open position;

    shunt opening release;

    fuse-holder;

    mechanical trip system for blown fuse;

    contact for signalling fuse blown;

    auxiliary contacts: 2 NO or NC with line-side disconnector and

    2 NO or NC for earthing switch.

    Fuses not included in the supply (if not ordered separately).

    Circuit-breaker Switchgear description Sales code Fittings

    HD4/UniMix-F JTI_B3_Z_N_N_GAS 1VCF594000R0409 Without accessories

    HD4/UniMix-F JTI_B3_Z_N_R_GAS 1VCF594000R0410 Anti-condensation heaterHD4/UniMix-F JTI_B3_Z_I_N_GAS 1VCF594000R0411 Internal lighting

    HD4/UniMix-F JTI_B3_Z_I_R_GAS 1VCF594000R0412 Internal lighting and anti-condensation heater

    Circuit-breaker Switchgear description Sales code Fittings

    VD4/UniMix -F JTI_B3_Z_N_N_VUOTO 1VCF594000R0417 Withou t accessori es

    VD4/UniMix -F JTI_B3_Z_N_R_VUOTO 1VCF594000R0418 Anti- condensation heater

    VD4/UniMix -F JTI_B3_Z_I_N_VUOTO 1VCF594000R0419 Internal l ighti ng

    VD4/UniMix -F JTI_B3_Z_I_R_VUOTO 1VCF594000R0420 Internal l ighti ng and anti- condensation heater

    Completion Description Sales code

    Insulating rod Kit for mobile earthing 1VCF594000R0218

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0149

    Fuses for P2 unit Sales code Note24 kV - 16 A 1VCF594000R0194 To be ordered in sets of 3 pieces

    24 kV - 25 A 1VCF594000R0195 To be ordered in sets of 3 pieces

    24 kV - 40 A 1VCF594000R0196 To be ordered in sets of 3 pieces

    24 kV - 50 A 1VCF594000R0471 To be ordered in sets of 3 pieces

    24 kV - 63 A 1VCF594000R0197 To be ordered in sets of 3 pieces

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    22/2622

    JTI B4 Switchgear

    No. 1 Incoming Line with P1/A Unit + No. 2 P2 Transformer

    Protection Units with switch-disconnector

    Incoming Unit P1/A

    235 mm LV compartment.

    Presence of voltage on busbar side and cable side.

    HD4/Unimix-F or VD4/Unimix p230 non-motorised circuit-breaker with

    shunt opening release, shunt closing release, operation counter, 2 NO

    + 2 NC auxiliary contacts, undervoltage release and contact signalling

    release de-energised.

    REF601 protection relay without communication (51, I>; 51, I>>; 50, I>>>;

    51N, Io>; 50N, Io>>) with 3 on-board circuit-breaker current sensors and

    toroid for earth fault, conforming to standard CEI 0-16 (see warning page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side disconnector in the closed position

    and 1 removable key in the open position;

    2 removable keys with earthing switch in the open position.

    Provision for earthing by means of insulating rod. The insulating rod is not

    included in the supply unless ordered separately.

    P2 Transformer Protection Unit (unit width: 375 mm)

    Presence of voltage on cable side.

    SHS2/T2F switch-disconnector with:

    1 removable key with line-side disconnector in the closed position

    and 1 removable key in the open position; 1 removable key with earthing switch in the closed position and 1

    removable key in the open position;

    shunt opening release;

    fuse-holder;

    mechanical trip system for blown fuse;

    contact for signalling fuse blown;

    auxiliary contacts: 2 NO or NC with line-side disconnector and 2 NO

    or NC for earthing switch.

    Fuses not included in the supply (if not ordered separately).

    Circuit-breaker Switchgear description Sales code Fittings

    HD4/UniMix-F JTI_B4_Z_N_N_GAS 1VCF594000R0425 Without accessories

    HD4/UniMix-F JTI_B4_Z_N_R_GAS 1VCF594000R0426 Anti-condensation heaterHD4/UniMix-F JTI_B4_Z_I_N_GAS 1VCF594000R0427 Internal lighting

    HD4/UniMix-F JTI_B4_Z_I_R_GAS 1VCF594000R0428 Internal lighting and anti-condensation heater

    Circuit-breaker Switchgear description Sales code Fittings

    VD4/UniMix -F JTI_B4_Z_N_N_VUOTO 1VCF594000R0433 Withou t accessori es

    VD4/UniMix -F JTI_B4_Z_N_R_VUOTO 1VCF594000R0434 Anti- condensation heater

    VD4/UniMix -F JTI_B4_Z_I_N_VUOTO 1VCF594000R0435 Internal l ighti ng

    VD4/UniMix -F JTI_B4_Z_I_R_VUOTO 1VCF594000R0436 Internal l ighti ng and anti- condensation heater

    Completion Description Sales code

    Insulating rod Kit for mobile earthing 1VCF594000R0218

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0149

    Fuses for P2 unit Sales code Note24 kV - 16 A 1VCF594000R0194 To be ordered in sets of 3 pieces

    24 kV - 25 A 1VCF594000R0195 To be ordered in sets of 3 pieces

    24 kV - 40 A 1VCF594000R0196 To be ordered in sets of 3 pieces

    24 kV - 50 A 1VCF594000R0471 To be ordered in sets of 3 pieces

    24 kV - 63 A 1VCF594000R0197 To be ordered in sets of 3 pieces

    UniMix JTIConfigurations available

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    23/2623

    JTI C1 Dx JTI C1 Sx

    JTI C1 Switchgear

    No.1 Incoming Line with P1/A Unit

    Incoming Unit P1/A

    235 mm LV compartment.

    Presence of voltage on busbar side and

    cable side.

    HD4/Unimix-F or VD4/Unimix p230

    non-motorised circuit-breaker with shunt

    opening release, shunt closing release,

    operation counter, 2 NO + 2 NC auxiliary

    contacts, undervoltage release and

    contact signalling release de-energised.

    REF601 protection relay without

    communication (51, I>; 51, I>>; 50, I>>>;

    51N, Io>; 50N, Io>>) with 3 on-board

    circuit-breaker sensors and toroid for

    earth fault, conforming to standard CEI

    0-16 (see warning page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side

    disconnector in the closed position

    and 1 removable key in the open

    position;

    2 removable keys with earthing switch

    in the open position. Provision for earthing by means of

    insulating rod. The insulating rod is not

    included in the supply unless ordered

    separately.

    The busbars for coupling with adjacent

    unit are not included in the supply unless

    ordered separately.

    Circuit-breaker Switchgear description Sales code Fittings

    HD4/UniMix-F JTI_C1_Z_Sx_N_N_GAS 1VCF594000R0441 Without accessories

    HD4/UniMix-F JTI_C1_Z_Sx_N_R_GAS 1VCF594000R0442 Anti-condensation heater

    HD4/UniMix-F JTI_C1_Z_Dx_N_N_GAS 1VCF594000R0443 Without accessories

    HD4/UniMix-F JTI_C1_Z_Dx_N_R_GAS 1VCF594000R0444 Anti-condensation heater

    Circuit-breaker Switchgear description Sales code Fittings

    VD4/Un iMix-F JTI_C1_Z_Sx_N_N_VUOTO 1VCF594000R0449 Without accessori es

    VD4/Un iMix-F JTI_C1_Z_Sx_N_R_VUOTO 1VCF594000R0450 Anti-condensation heater

    VD4/Un iMix-F JTI_C1_Z_Dx_N_N_VUOTO 1VCF594000R0451 Without accessori es

    VD4/Un iMix-F JTI_C1_Z_Dx_N_R_VUOTO 1VCF594000R0452 Anti-condensation heater

    Completion Description Sales code

    Insulating rod Kit for mobile earthing 1VCF594000R0218

    Completion Height Sales code

    Raising plinth 300 mm 1VCF594000R0143

    Busbars for coupling with adjacent unit Sales code

    With 375 mm unit 1VCF594000R0208

    With 500 mm unit 1VCF594000R0207

    With 750 mm unit 1VCF594000R0206

    Note: the units concerned can only be used for coupling existing UniMix switchgears by means

    of omnibus bus bars to be ordered using the relative code.

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    24/2624

    UniMix JTIConfigurations available

    JTI C1-AC Switchgear

    No.1 Incoming Line with P1/A Unit

    with AC top exit

    Incoming Unit P1/A

    235 mm LV compartment.

    Presence of voltage on busbar side and cable

    side.

    HD4/Unimix-F or VD4/Unimix p230 non-

    motorised circuit-breaker with shunt opening

    release, shunt closing release, operation

    counter, 2 NO + 2 NC auxiliary contacts,

    undervoltage release and contact signallingrelease de-energised.

    REF601 protection relay without communication

    (51, I>; 51, I>>; 50, I>>>; 51N, Io>; 50N, Io>>)

    with 3 on-board circuit-breaker sensors and

    toroid for earth fault, conforming to standard

    CEI 0-16 (see warning page 3).

    SHS2/IB disconnector with:

    1 removable key with line-side disconnector

    in the closed position and 1 removable key in

    the open position;

    1 removable key with earthing-switch in the

    closed position and 1 removable key in theopen position.

    Provision for earthing by means of insulating

    rod. The insulating rod is not included in the

    supply unless ordered separately.

    Circuit-breaker Switchgear description Sales code Fittings

    HD4/UniMix-F JTI_C1_Z_AC_N_N_GAS 1VCF594000R0463 Without accessories

    HD4/UniMix-F JTI_C1_Z_AC_N_R_GAS 1VCF594000R0464 Anti-condensation heater

    Circuit-breaker Switchgear description Sales code Fittings

    VD4/UniMix-F JTI_C1_Z_AC_N_N_VUOTO 1VCF594000R0467 Without accessories

    VD4/UniMix-F JTI_C1_Z_AC_N_R_VUOTO 1VCF594000R0468 Anti -condensat ion heater

    Completion Description Sales code

    Insulating rod Kit for mobile earthing 1VCF594000R0218

    Completion Height Sales code

    Raising plinth 300 m 1VCF594000R0143

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    25/2625

    WD

    H

    Maximum operating temperature of

    transformer

    T [C]

    No-load losses Wo [W]

    Load losses Wcc [W]

    Load factor a

    Rated current In [A]

    Total losses Ptot. = Wo + a2 x Wcc

    Types available

    Unit W [mm] D [mm] H [mm]

    TR1 1600 1150 1950

    TR2 2000 1150 1950

    TR3 2000 1300 2250

    TR4 2200 1500 2250

    TR5 2200 1800 2250

    Type of boxTotal losses [W]

    T=100 C T=120 C T=140 C

    TR1 5.000 6.000 7.000

    TR2 6.000 7.500 8.500

    TR3 7.500 9.000 10.500

    TR4 8.500 10.000 11.500

    TR5 9.000 10.500 12.500

    No. 1 Transformer box Units

    The transformer box unit is only avai lable in the standard

    version. The transformer box is made of galvanised sheet

    with the doors painted standard RAL 7035, is supplied in an

    assembly kit and can be fitted with internal lighting. Please

    contact us for transformer boxes of different sizes.

    Selection of the transformer box units

    After having defined the type of transformer box unitaccording to the total transformer losses, it is necessary to

    check that the transformer box unit dimensions are sufficient

    to ensure adequate insulation d istances.

    Unit description Sales code

    TR1 1VCF594000R0086

    TR2 1VCF594000R0087

    TR3 1VCF594000R0088

    TR4 1VCF594000R0089

    TR5 1VCF594000R0090

    JTI (TR) Switchgears

  • 8/10/2019 Cabinas MT UNIMIX-JTI.pdf

    26/26

    Contact us

    1VCP000249Rev.L,en

    Technicalcatalogue2011.06(UniMixJTI)(mt)The data and illustrations are not binding. We reserve

    the right to make changes in the course of technical

    development of the product.

    Copyright 2011 ABB.

    All rights reserved.

    ABB S.p.A.

    Power Products Division

    Unit Operativa Sace-MV

    Via Friu li, 4

    I-24044 Dalmine

    Tel: +39 035 6952 111

    Fax: +39 035 6952 874

    E-mail: [email protected]