camhosp r
DESCRIPTION
hvacTRANSCRIPT
![Page 1: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/1.jpg)
CamHosp
1
Camfil Farr- clean air solutions
2009-07-01
CamHosp-R – MF
Camfil Farr
CamHosp-R Features in Detail
![Page 2: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/2.jpg)
CamHosp
2
Principle of a ceiling system without recirculation
CamHosp2
CLEAN AIR CLEAN AIR CLEAN AIR
Ceiling
Exhaust air
Fresh air
AHU
![Page 3: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/3.jpg)
CamHosp
3
Principle of a ceiling system incl. recirculation function
CamHosp-R
CLEAN AIR CLEAN AIR CLEAN AIR
Ceiling
Exhaust air
Fresh air
AHU
![Page 4: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/4.jpg)
CamHosp
4
General Function
• Recirculating (UCV) systems provide exactly what the name suggests:
– Generally a 3m x 3m ultra clean zone in an operating theatre
– This zone is used primarily when orthopaedic surgery is to be carried out
– Also used for open heart and ophthalmic surgery
– UCV systems assure a laminar flow clean zone by recirculating air from side areas
of the operating theatre [70%] mixed with AHU-conditioned supply air [30%]
• The air entering the clean zone is supplied through generally 12 x H14 HEPA filters
• The recirculated air is firstly filtered by 6 x F7 pre-filters
• The air is circulated by 6 x three phase fans through a control system
![Page 5: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/5.jpg)
CamHosp
5
CamHosp-R Features
![Page 6: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/6.jpg)
CamHosp
6
No sealing with silicone needed
Special gasket and clamping system
![Page 7: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/7.jpg)
CamHosp
7
Divided Screentek Laminator
![Page 8: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/8.jpg)
CamHosp
8
CamHosp-R Installation
Adaption to the wall Filter section around surgical lamp
![Page 9: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/9.jpg)
CamHosp
9
CamHosp-R Installation
Soundabsorber
Prefilter Opakfil F7
![Page 10: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/10.jpg)
CamHosp
10
Even surfaces for easy cleaning / desinfection
Pressure plenum with filter installation
![Page 11: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/11.jpg)
CamHosp
11
OP Light installation
a) Standard
blending
b) NEW !!!
Filtersection H14 around
surgical lamp
![Page 12: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/12.jpg)
CamHosp
12
Lighting system
Standard lighting system (eg. Zumtobel / Trilux) can be integrated
around the clean zone on request
![Page 13: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/13.jpg)
CamHosp
13
HEPA-Filter with Gel–gaskets
Knife Edge
![Page 14: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/14.jpg)
CamHosp
14
Filterheight 130 mm
![Page 15: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/15.jpg)
CamHosp
15
Pressure drop
in the ceiling
below
40 Pa
Pressure drop measurement with H14 filter Basis: 8.000 m³/h with MG media pack
![Page 16: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/16.jpg)
CamHosp
16
Filter performance
![Page 17: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/17.jpg)
CamHosp
17
Integrated prefilter F7 in standard depth 292mm
(Possibility to alternatively install AMC prefilters)
![Page 18: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/18.jpg)
CamHosp
18
Exclusive use of standard components
for ventilators und electronic control
![Page 19: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/19.jpg)
CamHosp
19
Media Bridges
Media bridges (eg. Dräger) can be integrated on request
Integration to the
CamHosp-R done !
![Page 20: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/20.jpg)
CamHosp
20
All validation tests performed
acc. to the new DIN 1946-4 Dec. 2008
![Page 21: CamHosp R](https://reader033.vdocuments.pub/reader033/viewer/2022042604/577c796e1a28abe05492987a/html5/thumbnails/21.jpg)
CamHosp
21
Thank you !
Any questions ??