Page 1: CamHosp R

CamHosp

1

Camfil Farr- clean air solutions

2009-07-01

CamHosp-R – MF

Camfil Farr

CamHosp-R Features in Detail

Page 2: CamHosp R

CamHosp

2

Principle of a ceiling system without recirculation

CamHosp2

CLEAN AIR CLEAN AIR CLEAN AIR

Ceiling

Exhaust air

Fresh air

AHU

Page 3: CamHosp R

CamHosp

3

Principle of a ceiling system incl. recirculation function

CamHosp-R

CLEAN AIR CLEAN AIR CLEAN AIR

Ceiling

Exhaust air

Fresh air

AHU

Page 4: CamHosp R

CamHosp

4

General Function

• Recirculating (UCV) systems provide exactly what the name suggests:

– Generally a 3m x 3m ultra clean zone in an operating theatre

– This zone is used primarily when orthopaedic surgery is to be carried out

– Also used for open heart and ophthalmic surgery

– UCV systems assure a laminar flow clean zone by recirculating air from side areas

of the operating theatre [70%] mixed with AHU-conditioned supply air [30%]

• The air entering the clean zone is supplied through generally 12 x H14 HEPA filters

• The recirculated air is firstly filtered by 6 x F7 pre-filters

• The air is circulated by 6 x three phase fans through a control system

Page 5: CamHosp R

CamHosp

5

CamHosp-R Features

Page 6: CamHosp R

CamHosp

6

No sealing with silicone needed

Special gasket and clamping system

Page 7: CamHosp R

CamHosp

7

Divided Screentek Laminator

Page 8: CamHosp R

CamHosp

8

CamHosp-R Installation

Adaption to the wall Filter section around surgical lamp

Page 9: CamHosp R

CamHosp

9

CamHosp-R Installation

Soundabsorber

Prefilter Opakfil F7

Page 10: CamHosp R

CamHosp

10

Even surfaces for easy cleaning / desinfection

Pressure plenum with filter installation

Page 11: CamHosp R

CamHosp

11

OP Light installation

a) Standard

blending

b) NEW !!!

Filtersection H14 around

surgical lamp

Page 12: CamHosp R

CamHosp

12

Lighting system

Standard lighting system (eg. Zumtobel / Trilux) can be integrated

around the clean zone on request

Page 13: CamHosp R

CamHosp

13

HEPA-Filter with Gel–gaskets

Knife Edge

Page 14: CamHosp R

CamHosp

14

Filterheight 130 mm

Page 15: CamHosp R

CamHosp

15

Pressure drop

in the ceiling

below

40 Pa

Pressure drop measurement with H14 filter Basis: 8.000 m³/h with MG media pack

Page 16: CamHosp R

CamHosp

16

Filter performance

Page 17: CamHosp R

CamHosp

17

Integrated prefilter F7 in standard depth 292mm

(Possibility to alternatively install AMC prefilters)

Page 18: CamHosp R

CamHosp

18

Exclusive use of standard components

for ventilators und electronic control

Page 19: CamHosp R

CamHosp

19

Media Bridges

Media bridges (eg. Dräger) can be integrated on request

Integration to the

CamHosp-R done !

Page 20: CamHosp R

CamHosp

20

All validation tests performed

acc. to the new DIN 1946-4 Dec. 2008

Page 21: CamHosp R

CamHosp

21

Thank you !

Any questions ??