Prefabricated busbar trunkingfrom 800 -4000 A
Canalis
Catalogue
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
2/205
-
7/21/2019 Canalis KTA 800_4000A
3/2053Schneider Electric
Contents
Presentation and description
Panorama of Canalis range K9AE11000/2General K9AE12000/2Run sections K9AE12000/3Disconnectors and run protective devices K9AE12000/4
Change of direction sections K9AE12000/5Connection sections K9AE12000/6Connection accessories K9AE12000/12Supports and fixings K9AE12000/14Tap-off units K9AE13000/2
Catalogue numbers and dimensions
Run components K9AE21010/2Elbow components for changing direction K9AE22010/2Zed components for changing direction K9AE22020/2Canalis interfaces K9AE23000/2Feed units for switchboards and oil immersed transformers K9AE24010/2Feed units for dry-type transformers K9AE24020/2Supports and fixings K9AE25000/2Tap-off units K9AE26010/2
Coupling isolators and protection of the run K9AE26030/2Special products K9AE27000/2
Design guide
Characteristics K9AE39000/2Design guide K9AE31000/2Selection guide K9AE31000/14Degree of protection K9AE32000/2Harmonic currents K9AE33000/2Direct current K9AE34010/2Frequencies K9AE34020/2Measurements and metering K9AE34030/2Fire resistance K9AE35000/2Testing and commissioning procedure K9AE36010/2
Installation guide
Layout advice K9AE41000/2Horizontal distribution K9AE41000/12Rising mains K9AE45000/2Panorama of connection solutions K9AE42000/2Connection to LV switchboards K9AE42000/4Connection to cast resin transformers K9AE43000/2Connection to oil immersed transformers K9AE44000/2
Recommendations
Reception, handling and storage 2Maintenance 2Recycling 3
Introduction
In decentralised distribution, Canalis hits the high note! K9AE01010/3With Canalis, you play all the right notes! K9AE01020/2Canalis, in total harmony with the environment! K9AE01030/2Canalis, fortissimo throughout the range! K9AE01040/2Canalis KT, a display of advantages! K9AE02010/2Canalis KT, everyone to their music! K9AE02020/2Play all the worlds musicwith Canalis! K9AE02030/2With the Canalis tools and services, let us compose your project! K9AE02040/2
-
7/21/2019 Canalis KTA 800_4000A
4/205
-
7/21/2019 Canalis KTA 800_4000A
5/205
PD2023
82
PD202380
PD202088-104
3Schneider Electric
Introduction
In decentralised distribution,Canalis hits the high note!
Canalis on its second world tourTo better meet your needs, Canalis extends its system solutions.New low and medium power busbar trunking products.Pre-equipped luminaires.Strip lighting.Specially designed cable trays.
A total coordination with theSchneider Electric systemCanalis is now part of a comprehensive offering of Schneider Electric productsdesigned to operate together. This concept covers all low and mediumvoltage electrical distribution components. The result is an optimised electrical
installation with even higher performance through full electrical, mechanical andcommunication compatibility.With the new Canalis range, you get a complete, tested distribution solutionthat complies with standards. It is perfectly suited to traditional applications(factories, warehouses, etc.) and to the distribution of electrical power from theincoming transformer on through to all types of loads in offices, commercialpremises, laboratories, etc.
Canalis KT is changing to provide youwith
more flexibility. The adjustable section adapts to the worksite thus makingsure you meet deadlines.
bbbbb
b
ease of connection with the plug and play transformer and switchboardconnections.
more assistance. Our teams will assist you throughout your project.
b
b
Canalis moves forward without changingthe way you workThe new Canalis range is fully compatible with the existing range.An existing installation can be upgraded without any problem.
More than 50,000 km of Canalis busbar trunking has been
sold around the world.
K9AF01010
-
7/21/2019 Canalis KTA 800_4000A
6/205K9AE01020
PD202043
PD202044
PD202155
2 Schneider Electric
Introduction
With Canalis, you play all the rightnotes!
Distribution systems Schneider Electric offers different distribution systems tofi
t your operating needs.
Centralised distribution
For all continuous processes:cement plantsoil and gaspetrochemicalssteelpaper, etc.Centralised distribution offers:continuity of servicecombined distribution of power, control and monitoring circuitssupervision, etc.
Our solutions:
Prisma Plus and Okken switchboards.
bvvvvvbvvv
b
Decentralised distribution
For manufacturing industries:mechanicaltextileslumberinjection mouldingelectronicspharmaceuticals
livestock, etc.Decentralised distribution lets you:design installations without layout detailsupgrade without shutting down productionget systems up and running sooner thanks to faster installationgenerate savings depending on the number of loads.
Our solutions:Prisma Plus switchboardsCanalis busbar trunking.
bvvvvvvvbvvvv
bb
Combined distribution
Where the advantages of both centralised and decentralised distribution arerequired.
Commercial and service buildings:
officesstoreshospitalsexhibition halls, etc.Infrastructures:airportstelecommunicationsinternet data centrestunnels, etc.Industrial facilities:pharmaceuticalsfood processing, etc.
Our solutions:Prisma Plus and Okken switchboardsCanalis busbar trunking.
b
vvvvbvvvvbvv
bb
-
7/21/2019 Canalis KTA 800_4000A
7/205K9AE01020
PD202383
PD202427
3Schneider Electric
Introduction
With Canalis, you play all the rightnotes!
The Canalisdecentraliseddistribution concept
Electrical power available at all points,throughout theinstallation.
Exclusive features of the Schneider Electric systemTotal coordination of the Schneider Electric system provides maximum safety of lifeand property, continuity of service, upgradeability and ease of installation.Total coordination is made easy by the tables in the Selection Guide. They helpyou chose the right combination of circuit breakers and busbar trunking.Product characteristics are checked by calculations and tests carried out in ourlaboratories.
A competitive installation.Simplicity, upgradeability, safety and continuity of service and operation.
Savings start with installationWith tap-off points every 3 metres, Canalis busbar trunking reduces installationcosts.Given the low cost of adding new circuits, savings increase as the number of loadsincreases, a natural consequence of the growth of your business.
Upgradeable during operationIn decentralised distribution, evolving operating requirements and costs areintegrated right from the start.
The addition, relocation or replacement of load equipment can be carried outquickly, without de-energising the supply trunking or shutting down operation.
The cost of making such changes is greatly reduced:loads are located close to supply pointstap-off points are always available
tap-units can be reused or new ones added quickly for load relocation orreplacement needs.
b
bvv
v
Reusable in the event of major changesWhen making major modifications to your installation, the existing trunking can beeasily dismantled and reused.
DD205658
-
7/21/2019 Canalis KTA 800_4000A
8/205K9AF01030
DD205675
D
D205674
2 Schneider Electric
Introduction
Canalis, in total harmony with theenvironment!
Safety of life and property With Canalis, no risk in case of fireThe busbar trunking has a low combustible load. Its construction uses very littleconsumable material and is halogen free.In the event of a fire, the busbar trunking does not emit any gas or toxic smoke.
An inherent fire barrier, the busbar trunking helps prevent the propagation of afire through partition walls and floors for a duration of 2 hours.
Halogen-sensitive applicationsPublic buildings (infrastructures, hospitals, schools, etc.).Buildings with evacuation difficulties (high-rises, ships, etc.) and service-activity
buildings.Sensitive processes (production of electronic components, etc.).
Canalis contains no PVCs
When PVCs burn, they produce large amounts of smoke that can be a serioussafety hazard.Reduced visibility:risk of paniccomplicates rescue workSmoke toxicity:hydrogen chloride gas (highly toxic)carbon monoxide (danger of asphyxiation).
bb
b
bvvbvv
Canalis reduces the risk of exposure to electromagnetic fieldsAccording to the WHO (World Health Organisation), exposure to electromagneticfields can be a health hazard starting at levels as low as 0.2 micro-Teslas andcould represent a long-term risk of cancer. Some countries have created standards
that stipulate limits (e.g. 0.2 T at 1 metre in Sweden).
All electrical conductors generate magnetic fields proportional to the distancebetween them. The design of Canalis busbar trunking with tightly spacedconductors in a metal enclosure helps to considerably reduce radiatedelectromagnetic fields.
The electromagnetic field characteristics of Canalis busbar trunking are well-defined and measurements show that they are far below potentially dangerouslevels.You will find the magnetic induction values of our products on the Characteristicspages.
Example:Consequences of a fire in a 100 m2 office withelectrical distribution by cables.200 kg of cables (i.e. 20 kg of PVC) produces:
4400 m3 of smoke7.5 m3 of hydrochloric acid3.7 kg of corroded steel.
bbb
Health
-
7/21/2019 Canalis KTA 800_4000A
9/205K9AF01030
DD205673
3Schneider Electric
Introduction
Canalis, in total harmony with theenvironment!
Environment Canalis is fully recyclableCanalis busbar trunking can be reused.Canalis busbar trunking is designed for a long service life and can easily bedismantled, cleaned and reused.
All packaging materials can be recycled (cardboard or recyclable polyethylenefilm).
All Canalis products are designed for safe end-of-life recycling. PVC, on theother hand, requires neutralisation of the hydrochloric acid produced using limeand generates dioxins that are extremely toxic.
Canalis helps conserve natural resourcesThe depletion of raw materials (copper, plastics, etc.) is one of our ongoingconcerns.For this reason, we have optimised the used of all materials used to make ourbusbar trunking.
Reduction of dangerous or polluting materials. We design our products to meet
future European directives.Reduction in the weight of insulating materials.Reduction in the use of plastics for improved fire performance: less energy
released during combustion, thereby limiting propagation and facilitating extinction(lower calorific value).
b
b
b
b
bb
Example:1 kg of PVC generates 1 kg of waste.
Energy savings Canalis reduces your line losses by 40 %Canalis divides your consumption of copper and insulation
by a factor of threeThe cost of an electrical installation includes the initial investment for theequipment and its installation, the cost of maintenance and the cost of energylosses during operation.The cross-sections of our products are dimensioned to minimise the total cost ofyour installation over a 3-year period for medium intensity use (30 % load level,5 days a week and 10 hours a day).
Example:30 m of Canalis KS 250 A trunking equipped with ten 4-pole 25 A feeders.
DD205656
-
7/21/2019 Canalis KTA 800_4000A
10/205K9AE01040
PD202384
2 Schneider Electric
Introduction
Canalis, fortissimo throughoutthe range!
-
7/21/2019 Canalis KTA 800_4000A
11/205K9AE01040 3Schneider Electric
Introduction
Canalis, fortissimo throughoutthe range!
-
7/21/2019 Canalis KTA 800_4000A
12/205
-
7/21/2019 Canalis KTA 800_4000A
13/205K9AE02010
PD202229-68
PD202386
3Schneider Electric
IntroductionComplete safety Busbar trunking temperature rise and short-circuit withstand are known andindependent of the installation. Coordination of the Schneider Electric system
results in complete control of the electrical network.
Installation standards UTE C 15-105 chapter B.6.2 and IEC 60 364 chapter5.523.6 stipulate that above 4 parallel cables, it is preferable to use busbartrunking. Paralleling many cables leads to uneven distribution of currents and therisk of abnormal temperature rise.
The busbar trunking and tap-off units are designed to guarantee the safety ofpersonnel and equipment:
plug-on connections to silver-plated copper bars,bolted connections with tightening torque guaranteed by torque nuts,foolproof system to avoid the risk of assembly errors,IP55 certified splash and dust protection,sprinklerresistance test in compliance with Volkswagen specifications,access to live parts have IPxxD protection (1 mm wire diameter).
Its metal enclosure and high protection degree protect the busbar trunking from allexternal aggressions (corrosion, rodents, etc).
b
b
b
vvvvvv
Operating continuity When working on the electrical installation, the busbar trunking provides immediatereadability of the electrical circuit thus allowing the appropriate zone to be quicklyidentified.Tap-off units can be plugged-on and off without the need for a shutdown; service
continuity is thus irreproachable.The quality of the electrical contacts guarantees maintenance free operatingcontinuity.
A large range of tap-off units Canalis KS tap-off units are fully compatible with Canalis KT:they cover all your requirements:Canalis KS tap-off units: 63 to 400 A,Canalis KT tap-off units: 400 to 1000 A,they offer circuit breaker or fuse protection.
This offer includes tap-off units that can be fitted with the Transparent Readysystem:
they monitor your installation to avoid overloads, thus ensuring service continuity,they provide metering to allow accurate management of your electrical
distribution network (allocation of costs to each consumer).
bvvb
vv
Canalis KT, a display ofadvantages!
-
7/21/2019 Canalis KTA 800_4000A
14/205K9AE02020
PD202391
PD202388
PD202387
PD202389
PD202390
2 Schneider Electric
Introduction
Canalis KT, everyone totheir music!
Key pointsFire barrier.
Halogen free.
Small size.
Operating continuity.
b
b
b
b
Office and hospital buildings
Key points
Halogen free.
Distribution and metering.
Able to be evolved.
Sprinklers.
b
b
b
b
Shopping centres, airportsand exhibition centres
-
7/21/2019 Canalis KTA 800_4000A
15/205K9AE02020
PD395077-68
PD202392
PD202393
109405
PD202394
PD202395
3Schneider Electric
Introduction
Canalis KT, everyone totheir music!
Key pointsOperating continuity.
Able to be evolved.
Low voltage drops.
Network readability.
b
b
b
b
Car industry andindustrial buildings
Key points
Operating continuity.
High tap-off density.
Able to be evolved.
Network compactness and readability.
b
b
b
b
Internet Data Centers
-
7/21/2019 Canalis KTA 800_4000A
16/205K9AE020302 Schneider Electric
Introduction
Play all the worlds musicwith Canalis!
Tertiary
Name Lighting and low current Medium current Highcurrent
Country
KDP KBA KBB KN KS KT
Offices
PD202244 Air France (headquarters) b b France
Allianz b b Germany
Axa b b France
Chamber of Commerce b b Luxembourg
Commerz Bank b b Germany
Lexel b b b Sweden
Telefnica b b Spain
Trade Center b b Spain
Tour du RDC b b Tunisia
Turning Torso b Sweden
Vodafone b b New Zealand
Internet Data Center
PD202245 Banco Commercial Portugus b b Portugal
Colt b b France
Digiplex b b Sweden
IBM b b b b Spain, Italy
MCI-Worldcom b b b b Italy, United Kingdom
Hotels and restaurants
PD202246 Hyatt b Tunisia
Mc Donalds b France
Soldeo Andorra Hotel b b Spain
Hospitals
PD202247 Children Clinic b b Sweden
Brussels University Hospital b Belgium
Derby Hospital b United KingdomOran Hospital b b Algeria
St Joseph Hospital b France
Stockholm Hospital b Sweden
Val de Grce Hospital b France
Michalon Hospital b b France
Manussia Hospital b Egypt
Supermarkets and hypermarkets
PD202248 Alcampo b b b Spain
Auchan b b b b b b World
B&Q b b b United Kingdom
Carrefour b b b b b b World
Coop b b b
Italy
Fnac b b Spain, France
Ikea b b b b b China, Spain, France,Sweden
Mark & Spencer b Belgium, Spain,United Kingdom
ToysR Us b Spain
-
7/21/2019 Canalis KTA 800_4000A
17/205K9AE02030 3Schneider Electric
Introduction
Play all the worlds musicwith Canalis!
Industry
Name Lighting and low current Medium current Highcurrent
Country
KDP KBA KBB KN KS KT
Car industry
PD202249 BMW b b b b Italy
Citron b b b b b b China, Spain, France
Daewo b South Korea
Dacia b b b b b Romania
Iveco b b b b Spain, Italy
Peugeot b b b b China, Spain, France
Nissan b b b b b Spain
Renault b b b b b Spain, France, CzechRepublic
Seat SpainValo b b b China, France, Italy,
Poland
Volkswagen b b b Spain, Germany
Other industriesAerospace industry
Airbus b b b Italy
Food-processing industry
Coca-Cola b b Spain, Italy, Belgium
Danone b b b World
Pasquier b b France
Livestock production farms and greenhouses
Favier henhouse b b France
Greenhouse b Netherlands
Ceramic industry
Esmalglas ceramic b b b b b Spain
Electricity
Legrand b France, Turkey
Watch-making
Rolex b b b Switzerland
Microelectronics
Intel b b b b Irelande
ST Micro-lectronique b b b b France
Lead industry and water treatment
Grundfos b China
Industrial technology
Bosch b b China
Telephony
Phillips b Netherlands
Nokia b b Sweden
Textile industry
Louis Vuitton b b b Spain
Delta b b Israel
-
7/21/2019 Canalis KTA 800_4000A
18/205K9AE020304 Schneider Electric
Introduction
Infrastructure
Name Lighting and low current Medium current Highcurrent
Country
KDP KBA KBB KN KS KT
Airports
PD202250 Paris Airport b b b b b France
Cairo Airport b Egypt
Heathrow Airport b b b United Kingdom
Hong-Kong Airport b China
Landvetter Airport b Sweden
Arlanda b b b Sweden
Satelite Barajas b Spain
Marine
PD202251 Chantier de lAtlantique b b France
Meyerwerft b b Germany
Undergrounds
PD202252 Guanghzou Underground b China
London Underground b United Kingdom
Madrid Underground b b Spain
Singapore Underground b Singapore
Other infrastructuresAlexandria Library b b Egypt
Centre international dexpositionde Suzhou
b b China
CERN b b Switzerland
Stade de France b b France
Play all the worlds musicwith Canalis!
-
7/21/2019 Canalis KTA 800_4000A
19/205K9AE02030 5Schneider Electric
Introduction
-
7/21/2019 Canalis KTA 800_4000A
20/205K9AE020402 Schneider Electric
Introductio
n
With the Canalis tools andservices, let us compose yourproject!
Technical files The technicalfi
les have been compiled from completed contracts and provideanswers to questions concerning the installation of Canalis busbar trunking inspecific business sectors.
In data centersReference:ART 3722DESBS001FR
In exhibition centresReference:ART 65946KD0C00CTAFEEN / 65946
In shopping centresReference:Available in your sales office.
In electronics factoriesReference:ART 65944KD0C00CTAFEEN / 65944
In tiles factoriesReference:DEBU005EN
In car plantsReference:
Available in your sales office.
In livestock buildingsReference:DESWED105010EN
In greenhousesReference:ART 808260DESWED105013EN
In logistic centresReference:ART 807993DESWED105011EN
In cruise shipsReference:DESWED105014EN
In garagesReference:DESWED103004EN
Find a large range of Cahier Technique publications on the Schneider Electricweb site: www.schneider-electric.com.
-
7/21/2019 Canalis KTA 800_4000A
21/205K9AE02040
PD202396
DD210861
3Schneider Electric
Introductio
n
With the Canalis tools andservices, let us compose yourproject!
Work-out yoursolution together
Our teams are available to provide customers with technical assistance throughoutthe installation of their projects.
Design of electrical distribution architectures:design of decentralised transport and distribution systems,technical and financial optimisation of busbar trunking design projects,transformer / switchboard link,installation coordination and discrimination.
Full installation drawings:3D Autocad drawings with corresponding parts lists,2D drawing with dimensions,detailed connection drawings.
Site supervision and commissioning assistance.
Training for designers and contractors.
bvvvv
bvvv
b
b
Project
launch
Technical
support
CanBrass
drawing
Autocad
drawing
Production
Project
management
On-site
instruction
and
installation
After-sales
service
-
7/21/2019 Canalis KTA 800_4000A
22/205K9AE020404 Schneider Electric
Introductio
n
Enter Canalis run characteristics.
With the Canalis tools andservices, let us compose yourproject!
Switchboard access estimation of material and labour costs.
Schneider Electric offers a comprehensive design and costing software.The CanBrasssoftware, edited by Schneider Electric, was developed to help youdesign and cost Canalis busbar trunking runs.
CanBrass, a comprehensive toolThe CanBrass software allows you to quickly design the best layout for yourproject.It allows:
the material needed to be easily chosen,a list of catalogue numbers and their exact quantities to be defined,a comprehensive quote that includes material and labour.
There are 2 options:linear metre costing,graphical costing.
bbb
bbb
CanBrass gives you all thehelp you need
Design guide
Linear metre costingThe user enters the following parameters:
for the power run: rating, polarity, protection degree,for each feeder: number of machines, rating and protection,overall run length, number of change-of-direction sections and the connection
type.
bbb
PD202374
PD202375
PD202376
-
7/21/2019 Canalis KTA 800_4000A
23/205K9AE02040 5Schneider Electric
Introductio
n
With the Canalis tools andservices, let us compose yourproject!
Definition of catalogue numbersThe software gives an optimum breakdown of the project and provides a bill ofmaterials: catalogue number, quantity, price.The software can also generate 2D or 3D drawings with dimensions.
Breakdown of the run by product function.
QuoteThe CanBrass software can generate a comprehensive customised quote (quantity,catalogue number, unit price, total net price and installation time).
Graphical costingSimply create a 3D drawing of the busbar trunking using appropriate dialogueboxes.Enter the following:
rating,polarity,connection types.
bbb
PD202377
PD202378
PD202379
-
7/21/2019 Canalis KTA 800_4000A
24/205K9AE110002 Schneider Electric
Presentation
Presentation
Range Canalis KDP Canalis KBA
PD202216
PD202217
Run componentsDegree of protection IP55 IP55
Number of circuits 1 1
Rating 20 A 25 and 40 A
Tap-off intervals 1200 - 1350 - 1500 - 2400 - 2700 and 3000 mm 500 - 1000 and 1500 mm
Standard lengths 24 and 192 meters 2 and 3 meters
Finish - Galvanised steel
Maximum distance between fixing points 0,33 meter 3 meters
KDP-KBA-KBB tap-off units
PD202225
PD202225
Rating 10 and 16 A 10 and 16 A
Option- White RAL 9010
- Bus conductor
- -
Panorama of Canalis rangeLighting distribution
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
25/205K9AE11000 3Schneider Electric
Presentation
Canalis KBB Canalis KBX
PD202219
PD202220
IP55 IP20
1 or 2 1
25 and 40 A 25 A
500 and 1000 mm -
2 and 3 meters 1,53 and 3,06 meters
Galvanised steel White
5 meters 3 meters
PD202225
10 and 16 A
White RAL 9010 -
Bus conductor -
Clean earth -
Presentation
Canalis KTA
Panorama of Canalis rangeLighting distribution
-
7/21/2019 Canalis KTA 800_4000A
26/205K9AE110004 Schneider Electric
Presentation
Range Canalis KN Canalis KS
PD202221
PD202222
Run componentsDegree of protection IP55 IP55
Polarity 3L + N + PE 3L + N + PE
Rating 40, 63, 100 and 160 A 100, 160, 250, 400, 500, 630,
Tap-off intervals 500 - 1000 or 3000 mm 1000 mm on each face
Standard lengths 3 meters 3 and 5 meters
Finish White RAL 9001 White RAL 9001
Maximum distance between fixing points 3 meters 3 meters
Tap-off units
PD
202227
PD
202228
Rating Plug-in 16 to 63 A 25 to 400 A
Bolt-on
OptionRemote control conductor -
Presentation
Canalis KTA
Panorama of Canalis rangePower distribution
-
7/21/2019 Canalis KTA 800_4000A
27/205K9AE11000 5Schneider Electric
Presentation
Canalis KS colonne montante Canalis KT
PD202223
PD202088-74
IP55 IP55
3L + N + PE 3L + PE ; 3L + N +PE ; 3L + N + oversized PE
and 1000 A 100, 160, 250, 400, 500, 630, 800 and 1000 A 800, 1000, 1250, 1600, 2000, 2500, 3200 and 4000
500 mm 500 - 1000 mm
Defined by the floor pitch 2 and 4 meters
White RAL 9001 White RAL 9001
Li au pas dtage 3 meters
PD
202228
PD
202229
25 to 400 A 25 to 400 A
400 to 1000 A
- -
Presentation
Canalis KTA
Panorama of Canalis rangePower distribution
-
7/21/2019 Canalis KTA 800_4000A
28/205K9AE11500
PD202312
PD202328
2 Schneider Electric
Presentation
Canalis KTA from 800 to 4000 AFor horizontal transport anddistribution
Presentation
Run sections Tap-off units Change-of-direction sections
Rating: 800 to 4000 A.Transport sections:fixed lengths: 2 and 4 metres,non-standard lengths: 0.5 and 3 metres,Distribution sections:fixed lengths: 2 and 4 metres,Adjustable lengths 1.10 to 1.50 metres.
bbvvbvb
Canalis KS plug-on tap-off units arecompatible with the Canalis KT busbartrunking:
protection by 25 to 400 A fuses,protection by 100 to 400 A Compact NS
circuit breakers.Canalis KT fixed tap-off units:protection by 400 to 1000 A Compact NS
circuit breakers
b
vv
bv
Change-of-direction sections adapt to allbusbar trunking requirements.There are both fixed and made-to-
measure lengths.
b
b
PD202313
PD202314
PD202315
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
29/205K9AE11500
PD202300
3Schneider Electric
Presentation
Presentation Canalis KTA from 800 to 4000 AFor horizontal transport anddistribution
Interface connections Universal supply connections Horizontal fixing supports
Pre-fabricated interfaces connections canbe incorporated into:Prisma Plus and Okken switchboards,France Transfo dry-type transformers.
b
vv
Supply connections allow thebusbar trunking to be connected to theswitchboards busbar or to the transformer.
b There are two types of support forinstalling the busbar trunking horizontally.One type of fixing: to fix the busbar
trunking to its support.
b
b
PD202431
PD202317
PD202318
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
30/205K9AE115004 Schneider Electric
Presentation
Run sectionsRating: 800 to 4000 A.
Distribution sections,fi
xed 2 metre lengths.Transport sections for going through floor slabs,fixed 0.5 to 3 metre lengths.
b
bb
PD202320
PD202319
Vertical fixing supportFor installing the busbar trunking vertically, they
ensure:height and depth adjustment,load sharing,absorption of expansions, vibrations, etc.They can be fixed either to the floor, the wall or to
a bracket.
b
vvvb
PD202321
Tap-off unitsCanalis KS tap-off units are compatible with the
Canalis KT busbar trunking:protection by 25 to 400 A fuses,protection by 100 to 400 A Compact NS circuit
breakers.Canalis KT fixed tap-off units:protection by 400 to 1000 A Compact NS circuit
breakers.
b
vv
bv
PD202322
Presentation Canalis KTA from 800 to 4000 AFor distribution to different levelsRising mains
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
31/205K9AE11500 5Schneider Electric
Presentation
Rating (A) Type of protectionModular switchgear Compact NS Fuses Compact NS with
measurement and metering
Plug-on tap-off units
25 to 125
PD202149
PD202150
PD202138
25 / 50 A for NF / DIN fuses32 A for BS fuses63 A, 8 x 18 mm modules
PD202148
PD202147
For Compact NS100 circuit breaker
100 A, 12 x 18 mm modules
63 A for DIN fuses100 A for NF / DIN fuses80 A for BS fuses
160
PD202150
PD202150
PD202323
For NG125 / 160 circuit breaker For Compact NS160 circuit breaker 160 A for NF / DIN / BS fuses
250 to 400
PD202324
PD202184 Fitted with DIN rail for Powerlogic
PM810
PD
202324
For Compact NS250 circuit breaker
PD202325
For Compact NS250 circuit breaker
PD202325
250 / 400 A for NF / DIN fuses
For Compact NS400 circuit breaker
For Compact NS400 circuit breaker
Fixed tap-off units
400 and 630
PD202326
For Compact NS400 and NS630circuit breaker
800 and 1000
PD202327
For Compact NS800 and NS1000circuit breaker
Tap-off units from 25 to 1000 APresentation
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
32/205
DD202387
DD202388
DD202389
DD202434-m
DD202435-m
DD202436-m
DD202445
DD202498
2 Schneider Electric
Description
8 ratings are available, from 800 to 4000 A.4 aluminium live conductors with identical cross-sections (3L + N + PE version).Conductors insulated using polyester film, class B 130 C, halogen free.Standard busbar trunking is IP55.Insulation voltage: 1000 Volts.Available polarities: 3L + PE, 3L + N +PE, 3L + N + PER (reinforced PE)
The KT busbar trunking is of compact design and can be installed edgewise, flat orvertically.This design, without the addition of a fire barrier joint, allows the busbar trunking tobe installed through a floor slab or fire barrier wall.As standard, the Canalis KT busbar trunking acts as a 2-hour fire barrier inaccordance with
ISO 834.The RAL 9001 pre-lacquered galvanized steel casing provides protection andmechanical fixing of the conductors.Further, it is used as the PE protective conductor (in accordance with NFC 15100and IEC 60367).In its reinforced version 3L + N + PER, the busbar trunking is fitted with anadditional internal conductor with a cross-section equal to half that of the phaseconductor.This version also has lateral reinforcements to allow high short-circuit currents (Isc)to be supported.
The Canalis KT busbar trunking is suitable for applications containing harmonics bytaking into account the appropriate derating factor. See Harmonic currents in theDesign guide.
bbbbbb
The conductors are sandwiched together inside the metal
casing.
The electrical contact pads of the sections are made from
bonded bimetallic aluminium / copper.
The junction between sections is made using a joint block.The joint block provides the following:
electrical junction between live conductors and between PE protective
conductors, mechanical link between the two sections.
It provides simultaneous continuity between all conductors.It is tightened using torque bolt(s) (1 to 4 depending on the rating) with snap-offheads.The nut head snaps-off, freeing a red washer, when the correct tightening torque isreached.
This operation is checked visually:if the red washer is absent: it has been tightened,if the red washer is visible: it has not been tightened.
This device guarantees the necessary contact pressure between live conductorsand is operator independent.
For dismantling or maintenance operations, the nut has a second head.The tightening torque is 6 daN.m.
All sections (apart from ER and EL feed units) are supplied with their jointblock, delivered in a separate parcel.If the run has a feed unit (ER or EL) at each end, an additional joint blockmust be ordered.
b
bb
The KS plug-on tap-off units are connected to the busbar trunking whilst live (off-load) via spring jaw connections.Contact zone coating:
silver-plated copper at jaw contact points,aluminium / silver-plated copper bimetallic saddle welded to the live conductors.
bb
3L + N + PER
Description
The Canalis KT busbar trunking is intended for high power distribution andtransport in industrial, commercial and tertiary buildings.Assembly of prefabricated sections that adapt to all run configurations.
General
3L + PE
3L + N + PE
Run sections
Tap-off contact
Joint block
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
33/205
DD202390
DD202438
DD202437
DD202483
3Schneider Electric
Description
Run sections
Transport sections - Type ETTransport the current without tap-off points.Available in 2 and 4 metre fixed lengths or made to measure from 0.50 to 3 metres.
Adjustable section -Type AJCompensates for dimensional differences in the installation.
Adjustable length from 1.10 to 1.50 metres.
Sections with tap-off points for plug-on tap-off units
Type EDED run sections are for current distribution.They use 25 to 400 A KS tap-off units.These tap-off units can be plugged-on whilst live, but off-load.
Available in fixed 2 or 4 metre lengths with 3 tap-off points on one side.
Sections with tap-off points for fixed tap-off units - Type EBEB run sections are for current distribution.They use specific KT 400 to 1000 A tap-off units.These tap-off units can only be fitted / removed when the run is not energised.
Available in a 2 metre fixed length with one tap-off point or a 4 metre fixed lengthwith 2 tap-off points.
Description
Canalis KTA
Straight sections
-
7/21/2019 Canalis KTA 800_4000A
34/205
DD202391
DD202392
DD202439
DD202
441
DD202440
DD2024
46
DD210811A
DD210813
4 Schneider Electric
Description
The TP type transposes the phases.b
Expansion section - Type DBIt controls and absorbs the expansion of Canalis runs and must be used on runsover 30 metres and each time the busbar trunking passes through a buildingexpansion joint.Refer to the installation guide.
Available in a 1 metre length, it can be fitted vertically or horizontally.At its centre it has flexible conductor joints and a sliding case able to absorb therelative movements of each part of the section.
Transposition sections - Types TN, TPUsed when the phase order of the switchboard is different to that of thetransformer.Available in a 1 metre length and is the same physical size as a transport section.
The TN version transposes the neutral.b
Additional joint block - Type YAIf the run has a feed unit (supplied without a joint block) at each end, an additionaljoint block must be ordered.Each joint block is supplied with the necessary covers, nuts and bolts.
Run end cover - Type FAThe end cover protects and insulates the conductor ends and is fitted to the lastsection.
Other run sectionsDisconnectors and run protectivedevices
Fitted between 2 flat or edgewise sections, they isolate or protect a busbartrunking part run.Each assembly is supplied fitted with a 3 or 4-pole device complete with rotaryhandle.Supplied with:
an auxiliary connection terminal,lifting rings,upstream and downstream terminal shields.
Colour: white RAL 9001, 100 % polyester paint on galvanized sheet steel.Refer to manufacturers data for switchgear characteristics.Fitted with a rotary handle, the tap-off unit can only be opened once the device
has been switched off.
Run disconnector tap-off units - Type SLType SL for:
Compact NS 1000 to 1600 A type NA fixed isolators:unhingeable door,3-point closing (possibility of locking with key lock, not supplied),Interpact INV isolator, 2000 to 2500 A:unhingeable door,3-point closing (possibility of locking with key lock, not supplied),Masterpact NW 3200 A type HF fixed isolator supplied with:transparent protection cover,adaptation kit for Ronis lock + 1 Ronis lock,complete Harting plug, not cabled.
Run protection tap-off units - Type PL
Type PL for:Compact NS 1000 to 1600 A type N fixed circuit-breakers:unhingeable door,3-point closing (possibility of locking with key lock, not supplied).
For circuit-breakers greater than 1600 A, consult the sales office.
bbb
bvvbvvbvvv
bvv
Description
Canalis KTA
Other run sections
Disconnectors and run protective devices
-
7/21/2019 Canalis KTA 800_4000A
35/205
DD202393
DD
202394
DD202395
DD2023
96
DD202397
DD202398
DD202433
DD202432
5Schneider Electric
Description
Elbows - Types LP and LCTo go up or down, to turn right or left:
type LP, flat elbow available in fixed or made-to-measure lengths,b
Zeds - Types ZP, ZC, CP3-branch made-to-measure:
flat or edgewise, to move the run axis upwards, downwards, to the right or to theleft without having to bend the busbar trunking:
type ZP, flat Zed,
b
v
Edgewise T junctions - Type TCTo feed runs perpendicular to the main run.
Change of direction sectionsDescription
type LPpC, flat made-to-measure angled elbow,b
type LC, edgewise elbow available in fixed or made-to-measure lengths,b
type LCpC, edgewise made-to-measure angled elbow.b
type ZC, edgewise Zed,v
edgewise / flat, to provide the busbar trunking with a bend.Type CP, edgewise and/or flat Zed.
bv
Canalis KTA
Simple changes of direction
Changes of direction
-
7/21/2019 Canalis KTA 800_4000A
36/205
DD202306
DD202310
DD202314
6 Schneider Electric
Description
To connect the KTA busbar trunking to different terminals or to transformer,switchboard, generator set, etc. busbars. Canalis offers high performanceconnection sections which meet all requirements.
These sections provide installation flexibility combined with quick and simpleassembly.
Further, the connections are made using torque bolts which provide both easeof installation (use of a standard spanner for tightening to 6 daN.m) and a visualcheck before energising.
Direct connection to Trihal transformers and Prisma Plus & Okken switchboards.Supplied factory or panelbuilder assembled and tested to IEC 60439-1 and 2.Quick and simple connection of the busbar trunking to the interface.Reduced size.Joint block integrated into the interface.A sealing kit (rating dependent) must be ordered.
Connection sectionsDescription
Sealing kit
Prisma Plus and Okken switchboardsFor fixed or draw-out incoming device, front or rear connection:
Masterpact NW08 to NW40 or NT06 to NT16 circuit-breaker,Compact NS630b to NS1600 circuit-breaker.
Possibility of switching the phases around.
bb
Prisma Plus switchboard
Okken switchboard
Canalis KTA
Connections via interface to Prisma Plus, Okken and Trihal
-
7/21/2019 Canalis KTA 800_4000A
37/205
DD202503
7Schneider Electric
Description
Connection sectionsDescription
France Transfo Trihal dry type transformersFor naturally ventilated or force ventilated transformers.Protection degree:
IP00,IP31.
Secondary voltage: 410 V
15 mm adjustment in the 3 axes.
bb
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
38/205
DD202399
DD21
0777
DD202502
8 Schneider Electric
Description
Feed units - Type ERThey allow the busbar trunking to be connected to a switchboards busbar, or to theterminals of an oil immersed transformer, generator set, etc.
They come complete with a mounting plate fitted:either directly to the roof of the switchboard,or via the intermediary of a protective cover.
Vertical or horizontal incoming busbar trunking.
bb
Connection:either directly to the busbar,or by flexible bars and connection plates,or by braids,or by cables.
ER feed units are supplied without a joint block.If the run has a feed unit at each end, an additional joint block must be ordered.
bbbb
bb
Types ER N1/N2
Connection sectionsDescription
Canalis KTA
Universal connections to switchboards and oil immersed transformers
Types ER N3/N4 Types ER N5/N6 Type ER N7
-
7/21/2019 Canalis KTA 800_4000A
39/205
DD20232
1
DD202325
10276-03-d1
10276-303-d4
DD205623
DD205624
9Schneider Electric
Description
Protective covers - Types CS, CR, BCProtects the external part of the connection.
Type CSHeight adaptable flexible protective cover adaptable for ER N1 to N6 feed unitswith a between centres distance of 115 mm.
b
Connection sectionsDescription
For a vertical incomer - Types CR1 to CR3Made-to-measure rigid protective cover for ER N1 to N7 feed units.They are height adjustable by 50 mm.
Type CR 1 for a horizontal incomer.b
Types CR7 and CR8Protective covers for oil immersed transformers.Only for ER N1 to N6 feed units with a between centres distance of 150 or 170 mmdepending on the rating.
Fit directly onto the BT series transformer tanks.
Type CR7 for a vertical incomer.
b
v
Type BCProtective cover for direct cable connection to ER N1 to N6 feed units with abetween centres distance of 115 mm.
v
Type CR8 for a horizontal incomer.v
Canalis KTA
Types CR2 and CR3 for a vertical incomer.b
-
7/21/2019 Canalis KTA 800_4000A
40/205
DD202444
DD202443
DD202442
DD202448
DD20
2447
10 Schneider Electric
Description
Feed units - Type ELFor dry type transformers with the neutral between the phases.They allow optimum connection to the busbar trunking.
The junction with the busbar trunking is achieved:either from the side,b
Connection sectionsDescription
They are of similar design to straight transport sections and can be installededgewise or flat.If installed flat, a set of angle brackets can be ordered.
The following must be specified at the time of order:phase order,distance between phases (a 20 mm lateral adjustment can be made use of onsite).
The link between the transformer terminals and the connection section is either byflexible bar connection plates or by braids.
Type EL N1/N2
or from the centre.b
Type EL N3/N4 Type EL N5
Canalis KTA
Universal connections to dry type transformers
-
7/21/2019 Canalis KTA 800_4000A
41/205
DD202343
DD202346
DD202342
11Schneider Electric
Description
Protective covers - Type CR4 to CR6These protect the connections with an IP31 casing when connecting to atransformer.
They are height adjustable by 50 mm.
Type CR4Protective cover for EL N1 to N4 feed units.Edgewise assembly.
b
Connection sectionsDescription
Type CR5Protective cover for EL N1 to N4 feed units.Flat assembly.
b
Type CR6Protective cover for EL N5 feed unit.Edgewise assembly.
b
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
42/205
DD202400
DD202411
DD202410
DD202403
DD202402
DD202401
DD202363
DD202478
DD210784
12 Schneider Electric
Description
The conductors of ER N1 to N6 feed units are connected directly to the
switchboard busbars.YB2 copper spacers are available to compensate differences in thickness betweenthe switchboard bars (10 mm) and the connection part(6 mm).
Make-up of kit:8 x 2 mm thick copper spacers,16 off M12 x 60 mm bolts, class 8.8,16 contact washers,16 torque nuts,8 steel spacer plates.
Order a set per feed unit whatever the rating.
bbbbb
The conductors of ER N1 to N6 feed units are connected via connection plates tothe switchboard busbars.
The YC types are flexible bars made up of 5 copper sheets of 1 x 100 mm (500mm cross-section).The number of connection plates needed is proportional to the busbar trunkingrating.There are 3 types:
YC1, uninsulated 600 mm long bar with 4 oblong holes at one end.The length of the holes at the switchboard side are to be adapted on-site.b
Connection accessoriesDescription
YC2, uninsulated bar, made-to-measure length of 250 to 600 mm with 4 oblongholes at each end, ready to use.b
YC5, insulated 1000 mm long flexible bar, stripped at one end and with 4 oblongholes.The length of the holes at the switchboard side are to be adapted on-site.
b
Nuts and bolts
The connection plates are fixed to the feed unit using the YB3 nut and bolt kit,made up of:
16 off M12 x 60 mm bolts, class 8.8,16 contact washers16 torque nuts,8 steel spacer plates.
ClampsYS1 clamps enable high short-circuit current levels to be withstood; only for barswith a 115 mm spacing.
bbbb
Canalis KTA
Switchboard connection accessories using connection plates
Accessories for direct connection to the switchboard
InsulationA YF sheath is available to insulate the phases from one another.It can be fitted to the YC1 and YC2 connection plates once they have beenconnected.
-
7/21/2019 Canalis KTA 800_4000A
43/205
DD
202412
DD202414
DD202413
DD202415
DD20
2450
13Schneider Electric
Description
The feed unit conductors are connected to the transformer bars via connection
plates or braids:connection plates, YC types, are flexible bars made up of 5 copper sheets of 1 x
100 mm (500 mm cross-section).braids, YT type, are copper braids with a 600 mm cross-section.
The number of connection plates needed is proportional to the busbar trunkingrating.
Connection platesThe YC3 is an uninsulated bar with an expansion kink; it is 400 mm long and has 4holes at one end.They can be fitted to the transformer side:
either using bar clamps (no drilling),or drilled and bolted (to be carried out on site).
b
b
bb
Connection accessoriesDescription
YS2 and YS3 bar clamps enable connection without the need to drill the connectionplates.They allow height adjustment.
Type YS2, bar clamps for 100 mm transformer connection terminals.Type YS3, bar clamps for 120 mm transformer connection terminals.
Make-up of kit: 1 set of 8 parts.
bb
The YC4 is an uninsulated bar with an expansion kink; it is 400 mm long and has4 oblong holes at each end (ready to use).b
BraidsType YT, 400 mm long insulated braid with 4 holes at each end.
The connection plates and braids are fixed to the feed unit using the YB4 nut andbolt kit, made up of:
16 off M12 x 80 mm bolts, class 8.8,16 contact washers,16 torque nuts,8 steel spacer plates.
bbbb
Canalis KTA
Transformer connections - Types YC, YT
-
7/21/2019 Canalis KTA 800_4000A
44/205
DD202372
DD202
484
DD202486
DD202485
DD202369
DD202368
DD202496
DD202374
14 Schneider Electric
Description
Supports and fixings
The ZA types allow the busbar trunking to be fixed and adjusted along its length, as
well as absorbing its movements.
Supports for horizontal sectionsType ZA1, to support edgewise busbar trunking only, consists of a steel angle
bracket and 2 x 1.2 metre threaded M10 rods.The maximum distance between supports is:
3 metres for edgewise busbar trunking,2 metres for flat busbar trunking.
See installation precautions.
b
vv
Fixing bracketThe ZA3 keeps the busbar trunking in place on its support, without blocking it, inorder to allow expansion movements.
The ZA5 is for supporting vertical sections.They fix sections of a vertical run to the buildings structure.This type of fixing support has the following advantages:
assembly:to a wall,to a wall bracket,to the floor,height and depth adjustment,spring adjustment to ensure distribution of the load at each floor,avoids the transmission of building forces to the busbar trunking (expansion and
vibration).
bvvvbbb
Description
Type ZA4, to support the busbar trunking from the top.These supports are needed to fix edgewise EL N1 to N4 feed units for dry type
transformers.
bb
For KTA08 to KTA16. For KTA20 to KTA40.
To a wall. To a wall bracket. To the floor.
Canalis KTA
Horizontal supports
Vertical supports
-
7/21/2019 Canalis KTA 800_4000A
45/205K9AE13000
DD210466
DD202012
DD210275
DD210276
2 Schneider Electric
Description
Tap-off units
The tap-off units are used to instantly connect loads or secondary runs, and complywith installation standards and regulations, whatever the earthing system (TT, TNS,TNC or IT).
When off-load, they can be plugged-on and off and be operated whilst live.Plugging-on and plugging-off automatically opens and closes the tap-off point.
Description
No live part is accessible with the door open. The protection degree is IPXXB(finger protection).
They are IP55 by construction (no accessory is required).
Safety and operationFuse and modular switchgear tap-off units (AC22 to AC20) are isolated as soon asthe tap-off unit door is opened.This isolating operation must only be carried out off-load.For circuit breaker tap-off units, there are safety mechanisms to prevent:
the tap-off unit being plugged-on and plugged-off with the tap-off unit doorclosed,
the door being closed if the tap-off unit has not been locked onto the busbartrunking,
access to the electrical equipment and connection terminals when live,the door being opened in the ON position for tap-off units fitted with a Compact
NS or NG circuit breaker.
These tap-off units can be fitted with accessories such as:door early break contacts,adapter for lead sealing,etc.
The sheet steel tap-off units are fitted with a carrying handle.
Characteristics of tap-off units up to 125 A
Colour:white (RAL 9001) body and carrying handles,transparent green door (similar design to the Kaedra enclosures).Material: self-extinguishing, halogen-free insulating plastic (fire resistant and very
high temperature withstand).Other characteristics: cable gland drilling zone, stainless steel screws and the doorcan be lead sealed.
Characteristics of tap-off units from 160 to 400 AColour:white (RAL 9001) body,black carrying handles (RAL 9005),100 % polyester paint.Material: galvanized sheet steel.
Other characteristics:unhingeable door (120 opening hinges),vertically bevelled polyurethane seals with a double fold for increased rigidity
(similar design to the Sarel Spatial 3D enclosures),25 mm grill type gland plates for a maximum access area.
b
b
bb
bbb
bvvb
bvvvb
bb
b
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
46/205K9AE13000
DD210465
DD210461
DD202154
DD210454
3Schneider Electric
Description
Plug-on tap-off units for circuitbreakers
Isolator tap-off units for modular switchgearMost 18 mm Multi 9 modular devices can be fitted into these tap-off units.They have a window on the front face for switchgear control and visualisation.
A transparent shutter ensures the window can be sealed.Two tap-off ratings are available:
63 A nominal current for 8 modules,125 A nominal current for 12 modules (accepts C120 and NG125 circuit
breakers).
bb
Tap-off units for NG type modular switchgearThese tap-off units are fitted with a DIN rail and upstream connections for 18 mmwide modular devices.The switchgear is operated via a rotary handle which prevents door opening when
the circuit breaker is in the ON position.Nominal current: 160 A for a 13-module capacity (accepts NG125 or NG160 fittedwith a Vigi unit).
Isolator tap-off units for Compact NS circuit breakersThese tap-off units are fitted with mounting plates and upstream connections forfixed, front-connected 160 to 400 A Compact NS circuit breakers (N, H or L version)with a rotary handle.
The 400 A tap-off units can only be fitted onto straight lengths with a rating greaterthan 400 A.
For plug-on circuit breakers, Vigi units, etc, please consult your Schneider Electriccontact.
Measurement and metering isolator tap-off unitsThese tap-off units allow sub-metering to re-allocate power consumption costs byconsumer and to monitor installations by, for example, following run load levels.The values measured using the Compact NS TI unit are sent to the measurementunit which then sends the information to a central unit via a bus.(See Measurement and metering).
They are fitted with:
a mounting plate for a Compact NS 250 or 400 A circuit breaker with anextended rotary handle and a Compact NS current transformer module (TI unit),a DIN rail for installing a Powerlogic PM810 measurement unit, a set of
terminals, etc.
In severe operating conditions (> 40C ambient temperature), we recommend theuse of a PM810 without display.
b
b
Description
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
47/205K9AE13000
DD210472
DD202012
DD210466
4 Schneider Electric
Description
These tap-off units provide the tap-offs with fuse protection (fuses not supplied).They can only be fitted to a horizontally mounted busbar trunking.
Plastic tap-off unitsFitted with carriers for:
50 to 100 A cylindrical NF fuses,25 to 63 A DIN screwed fuses,100 A DIN blade fuses,32 to 80 A BS screwed fuses.
bbbb
Plug-on tap-off units for fusesDescription
Steel tap-off unitsFitted with carriers for:
160 to 400 A NF / DIN blade fuses,160 A BS screwed fuses.
bb
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
48/205K9AE13000
DD202451
DD202497
5Schneider Electric
Description
Fixed tap-off units for circuitbreakers
Steel tap-off unitsThese tap-off units are used to supply loads or secondary runs (e.g. medium powerdistribution using Canalis KS).They are fitted to specific EB type straight lengths.They comply with installation standards and regulations, whatever the earthingsystem (TT, IT, TNS or TNC):
tap-off units fitted with a mounting plate for Compact NS400/1000 A, 3 or 4 P:fixed device,front connections,
extended rotary handle.2 models:
Compact NS400/630 A, connection capacity:3 x 300 mm2cables for the phases and neutral (hole diameter = 15 mm),150 mm for the PE,Compact NS800/1000 A, connection capacity:4 x 300 mm2cables for the phases and neutral (hole diameter = 15 mm),200 mm2for the PE (cable clamp).
The standard tap-off unit is IP54.
bvv
v
bvvbvv
Characteristics of tap-off units from 400 to 1000 AColour:white (RAL 9001) body,Material: galvanized sheet steel.Other characteristics:the cables exit laterally through 2 aluminium plates (to be drilled by the
installation contractor),cabling space can be increased by using the cable box supplied with the tap-offunit,
the door is fixed using 6 captive M6 screws and can be completely removed tofacilitate cabling.
bvbbv
v
v
Description
Safety and operationThe electrical connection is made by plugging-on the tap-off unit into dedicated tap-off point whilst the busbar trunking is de-energised (plugging-off the unit must also
be done with the busbar trunking de-energised).The connection is mechanically tightened using a one-use torque bolt (10 daN.m).A mechanical foolproof system avoids the risk of incorrect assembly.The door can only be opened once the load has been isolated (rotary handle).The bolt can only be tightened or untightened with the door open.No live part is accessible with the door open, protection degree IP2X.
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
49/205
-
7/21/2019 Canalis KTA 800_4000A
50/205K9AE20000 Schneider Electric 3
C
ataloguenumbers
D
imensions
Catalogue-number coding
K T pp p p p p p p ppFour digits indicationg
the rating of the trunking.Important : for an 800 A rating,indicate KTA0800.
b
Two letters identifying the type of component.
Type Code
Adjustable straight length AJCable box BCBolt-on tap-off unit CBEdgewise and flat zed CPRigid protective cover CRFlexible protective cover CSExpansion unit DB
Distribution length for bolt-on tap-off units EBDistribution length for plug-in tap-off unts EDFeed unit for dry-type transformers ELFeed unit ERFeeder length ETEnd cover FAEdgewise elbow LCFlat elbow LPTap-off unit with protective device PLTap-off unit with isolator SLEdgewise tee TCNeutral crossover TNPhase crossover TPSealing kit TTConnection device YAConnection torque nut kit YB
Flexible bar YCBracket YEInsulating sheath YFBar supports YSBraids YTSupports and fixing devices ZAEdgewise zed ZCFlat zed ZP
b
One digit indicating the trunkingpolarity
Polarity Code
3L + PE 3
3L + N + PE 43L + N + PER(1) 7(1) PER = oversized PE.
b
Variable number of alphanumericcharacters indicating characteristicsspecific to the component.See the section dealing with the givencomponent.
b
Trunking cross section
Rating (A) 800 1000 1250 1600 2000 2500 3200 4000
Number of bar jointing bolts 1 1 1 2 2 2 4 4
Bar cross-section (mm) 70 x 6 100 x 6 120 x 6 160 x 6 200 x 6 2 x (120 x 6) 2 x (160 x 6) 2 x (200 x 6)
Trunking height H (mm)
D
D202180
DD202181
Holes for connections (mm)
DD202182
Y 230 230 230 350 350 350 510 510
Catalogue-number composition
One letter designating the material.
Type Code
Aluminium A
Non conducting B
b
Catalogue numbers anddimensions
Canalis KTA
-
7/21/2019 Canalis KTA 800_4000A
51/205K9AE21010
DD210794
DD210795
DD210796
DD210797
2 Schneider Electric
D
imensions
Catalogue numbers anddimensions
Straight feeder lengths
Run componentsIP55
Type Length L(mm)
Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Fixed 4000 KTAppppE T34 0 KTAppppE T44 0 KTAppppET740
2000 KTAppppE T32 0 KTAppppE T42 0 KTAppppET720Made tomeasure
500 to 1500 KTAppppET31A KTAppppET41A KTAppppET71A
1501 to 1999 KTAppppET32B KTAppppET42B KTAppppET72B
2001 to 2500 KTAppppET32C KTAppppET42C KTAppppET72C
2501 to 3000 KTAppppET33D KTAppppET43D KTAppppET73D
KTAppppETppp
Ordering
Complete the catalogue number by replacing pppp by the rating.
Important: for the 800 A rating, add a 0 in the catalogue number : KTA0800,add the dimensions of the selected component as a technical comment
Example:the catalogue number of an 800 A feeder length, 3L + N + PE,2450 mm long, is:KTA0800ET42C, L = 2450
bb
Rating
(1) See the Trunking cross-sectiontable opposite.
Canalis KTA
Adjustable straight lenghts
Type Length L(mm)
Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Adjustable 1300 (basic)Adjustable: 200
KTAppppAJ31 0 KTAppppAJ41 0 KTAppppAJ710
KTAppppAJp10
(1) See the Trunking cross-sectiontable opposite.
Table of dimensions
Rating (A) Dimension A (mm) Weight (kg)
800(2) 180 52.001000 200 68.001250 240 78.001600 285 102.002000 325 121.002500 405 141.003200 495 179.004000 695 218.00(2) for the 800 A rating, indicate KTA0800 .
KTAppppETppp
KTAppppAJp10
-
7/21/2019 Canalis KTA 800_4000A
52/205K9AE21010
DD2
10798
DD210799
DD210800
3Schneider Electric
C
ataloguenumbers
D
imensions
Catalogue numbers anddimensions
Run componentsIP55
Straight lengths with plug-in tap-off units
Type Length
L (mm)
Number of
tap-offs
Cat. no.
Fixed 4000 3 KTAppppED340 KTAppppED440 KTAppppED740
2000 3 KTAppppED320 KTAppppED420 KTAppppED720
KTAppppEDp40
Trunking cross-section
Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000
Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38
3L + N + PE 13 16 18 22 26 30 37 45
3L + N + PER 15 19 21 26 31 36 46 56
Height H (mm)Width W (mm)
DD
202180
DD210867
(1) Important: for the 800 A rating, indicate KTA0800 .
(1) See the Trunking cross-sectiontable below.
Canalis KTA
KTAppppEDp20
KTAppppEDp20
KTAppppEDp40
-
7/21/2019 Canalis KTA 800_4000A
53/205K9AE21010
DD2
10801
DD210802
DD210803
DD210766
4 Schneider Electric
D
imensions
Straight lengths with bolt-on tap-off units
Type Length
L (mm)
Number of
tap-offs
Cat. no.
Fixed 4000 2 KTAppppE B3 40 KTAppppE B4 40 KTAppppEB740
2000 1 KTAppppE B3 20 KTAppppE B4 20 KTAppppEB720
KTAppppEBp40
(1) See the Trunking cross-sectiontable below.
KTAppppEBp20
KTAppppEBp20
KTAppppEBp40
Trunking cross-section
Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000
Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38
3L + N + PE 13 16 18 22 26 30 37 45
3L + N + PER 15 19 21 26 31 36 46 56
Height H (mm)Width W (mm)
DD
202180
DD210867
(1) Important: for the 800 A rating, indicate KTA0800 .
Catalogue numbers anddimensions
Canalis KTA
Run componentsIP55
-
7/21/2019 Canalis KTA 800_4000A
54/205K9AE21010
5Schneider Electric
C
ataloguenumbers
D
imensions
-
7/21/2019 Canalis KTA 800_4000A
55/205K9AE21020
DD210805
DD210806
DD210807
DD210808
DD210809
DD210810
2 Schneider Electric
D
imensions
Catalogue numbers anddimensions
Straight expansion unit
Additional run componentsIP55
Type Length L(mm)
Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Fixed 1000 KTAppppDB310 KTAppppDB410 KTAppppDB710
KTAppppDBp10
Ordering
Complete the catalogue number by replacing pppp by the rating.
Important: for the 800 A rating, add a 0 in the catalogue number : KTA0800,add the dimensions of the selected component as a technical comment
Example:the catalogue number of a 1250 A neutral crossover length,3L + N + PE, 1000 mm long, is:KTA1250TN410
bb
Rating
(1) See the Trunking cross-sectiontable opposite.
Canalis KTA
Neutral crossover length
Type Length L(mm)
Cat. no.
3L + N + PE
Fixed 1000 KTAppppTN410
KTAppppTNp10
(1) See the Trunking cross-sectiontable opposite.
Phase crossover length
Type Length L(mm)
Cat. no.
3L + N + PE
Fixed 1000 KTAppppTP410
KTAppppTPp10
(1) See the Trunking cross-sectiontable opposite.
KTAppppDBp10
KTAppppTNp10
KTAppppTPp10
-
7/21/2019 Canalis KTA 800_4000A
56/205K9AE21020
DD2
10811
DD210812
DD210
813
DD210814
DD210868
3Schneider Electric
C
ataloguenumbers
D
imensions
Catalogue numbers anddimensions
Additional run componentsIP55
Additional jointing units
Type Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Jointing unit KTAppppYA3 KTAppppYA4 KTAppppYA4
KTAppppYAp
(1) See the Trunking cross-sectiontable below.
Canalis KTA
End covers
Type Rating of thetrunking (A)
Height H of thetrunking (mm)
Cat. no.
End cover 800(1) 74 KTB0074FA1000 104 KTB0104FA1250 124 KTB0124FA1600 164 KTB0164FA2000 204 KTB0204FA2500 244 KTB0244FA3200 324 KTB0324FA4000 404 KTB0404FA
KTB0pppFA
KTAppppYAp
KTB0pppFA
Trunking cross-section
Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000
Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38
3L + N + PE 13 16 18 22 26 30 37 45
3L + N + PER 15 19 21 26 31 36 46 56
Height H (mm)Width W (mm)
DD
202180
DD210867
(1) Important: for the 800 A rating, indicate KTA0800 .
(1) For the 800 A rating, indicate KTA0800 .
(2) See the Trunking cross-sectiontable below.
-
7/21/2019 Canalis KTA 800_4000A
57/205K9AE22010
DD210822
DD210824
DD210815
DD210816
DD210821
DD210823
2 Schneider Electric
D
imensions
Catalogue numbers anddimensions
Elbow components for changingdirectionIP55
Flat elbows
Type Position ofneutral
Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Fixed N1 KTAppppLP3A1 KTAppppLP4A1 KTAppppLP7A1
N2 KTAppppLP3A2 KTAppppLP4A2 KTAppppLP7A2Made tomeasure
N1 KTAppppLP3B1 KTAppppLP4B1 KTAppppLP7B1
N2 KTAppppLP3B2 KTAppppLP4B2 KTAppppLP7B2
KTAppppLPppp
Ordering
Complete the catalogue number by replacing pppp by the rating.
Important: for the 800 A rating, add a 0 in the catalogue number : KTA0800,add the dimensions of the selected component as a technical comment
Example:the catalogue number of a 2000 A flat elbow, N1, 3L + N + PE withdimensions A = 300 mm and B = 650 mm is:KTA2000LP4B1, A = 300, B = 650.
bb
Rating
(1) See the Trunking cross-sectiontable opposite.
Dimensions
Type Rating (A) Dimensions (mm)
A B
Fixed All 300 300Made tomeasure(2)
All 300 301 to 799301 to 799 300
(2) Only one llmb may be made to measure.
Canalis KTA
Flat elbows with made to measure angles
Type Position ofneutral
Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Made tomeasure angle
N1 KTAppppLP3C1 KTAppppLP4C1 KTAppppLP7C1
N2 KTAppppLP3C2 KTAppppLP4C2 KTAppppLP7C2
KTAppppLPpCp
(1) See the Trunking cross-sectiontable opposite.
Dimensions
Type Rating (A) Dimensions (mm)
A B W
Made to measure All 300 300 91 to 179
KTAppppLPpp1
KTAppppLPpp2
KTAppppLPpC1
KTAppppLPpC2
-
7/21/2019 Canalis KTA 800_4000A
58/205K9AE22010
DD2
10825
DD210826
3Schneider Electric
C
ataloguenumbers
D
imensions
Catalogue numbers anddimensions
Elbow components for changingdirectionIP55
Edgewise elbows
Type Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Fixed KTAppppLC3A KTAppppLC4A KTAppppLC7A
Made to measure KTAppppLC3B KTAppppLC4B KTAppppLC7B
KTAppppLCpp
(1) See the Trunking cross-sectiontable below.
Dimensions
Type Rating (A) Dimensions (mm)
A BFixed 800(2) 275 275
1000 290 2901250 300 3001600 320 3202000 340 3402500 360 360
3200 400 4004000 440 440Made tomeasure(3)
800(2) 276 to 774 275275 276 to 774
1000 291 to 789 290290 291 to 789
1250 301 to 799 300300 301 to 799
1600 321 to 819 320320 321 to 819
2000 341 to 839 340340 341 to 839
2500 361 to 859 360360 361 to 859
3200 401 to 899 400400 401 to 899
4000 441 to 939 440440 441 to 939
(2) For the 800 A rating, indicate KTA0800 .
(3) Only one llmb may be made to measure.
Canalis KTA
KTAppppLCpp
Trunking cross-section
Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000
Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38
3L + N + PE 13 16 18 22 26 30 37 45
3L + N + PER 15 19 21 26 31 36 46 56
Height H (mm)Width W (mm)
DD
202180
DD210867
(1) Important: for the 800 A rating, indicate KTA0800 .
-
7/21/2019 Canalis KTA 800_4000A
59/205K9AE22010
DD2
10819
DD210820
4 Schneider Electric
D
imensions
Catalogue numbers anddimensions
Canalis KTA
Elbow components for changingdirectionIP55
Edgewise tee
Type Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Fixed KTAppppTC3 KTAppppTC4 KTAppppTC7
KTAppppTCp
KTAppppTCp
(1) See the Trunking cross-sectiontable below.
Dimensions
Type Rating (A) Dimensions (mm)
A B CFixed 800(2) 275 275 275
1000 290 290 2901250 300 300 3001600 320 320 3202000 340 340 3402500 360 360 3603200 400 400 4004000 440 440 440
(2) For the 800 A rating, indicate KTA0800.
Trunking cross-section
Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000
Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38
3L + N + PE 13 16 18 22 26 30 37 45
3L + N + PER 15 19 21 26 31 36 46 56
Height H (mm)Width W (mm)
DD
202180
DD210867
(1) Important: for the 800 A rating, indicate KTA0800.
-
7/21/2019 Canalis KTA 800_4000A
60/205K9AE22010 5Schneider Electric
C
ataloguenumbers
D
imensions
-
7/21/2019 Canalis KTA 800_4000A
61/205K9AE22020
DD202183
DD202184
DD202186
DD202185
DD210827
2 Schneider Electric
D
imensions
Catalogue numbers anddimensions
Zed components for changingdirectionIP55
Edgewise zed units
Type Position ofneutral
Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Made tomeasure
N1 KTAppppZC31 KTAppppZC41 KTAppppZC71
N2 KTAppppZC32 KTAppppZC42 KTAppppZC72
KTAppppZCpp
Flat zed units
Type Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Made to measure KTAppppZP3 KTAppppZP4 KTAppppZP7
KTAppppZPp
Ordering
Complete the catalogue number by replacing pppp by the rating.
Important: for the 800 A rating, add a 0 in the catalogue number : KTA0800,add the dimensions of the selected component as a technical comment
Example:the catalogue number of a 1600 A edgewise zed unit, N2, 3L + N + PEwith dimensions A = 300 mm, B = 450 mm, C = 300 mm is:KTA1600ZC42, A = 300, B = 450, C = 300.
bb
Rating
(1) See the Trunking cross-sectiontable opposite.
Dimensions
Rating (A) Dimensions (mm)
A B C
All 300 130 to 599 300
(1) See the Trunking cross-sectiontable opposite.
Dimensions
Rating (A) Dimensions (mm)
A B C
800(2) 275 90 to 549 2751000 290 90 to 579 2901250 300 90 to 599 3001600 320 90 to 639 3202000 340 90 to 679 3402500 360 90 to 719 3603200 400 90 to 799 4004000 440 90 to 879 440
KTAppppZPp
KTAppppZCp1
KTAppppZCp2
Canalis KTA
(2) For the 800 A rating,
indicate KTA0800 .
-
7/21/2019 Canalis KTA 800_4000A
62/205K9AE22020
DD2
02187
DD202188
DD210828
DD210829
DD210830
DD202367
3Schneider Electric
C
ataloguenumbers
D
imensions
Catalogue numbers anddimensions
Zed components for changingdirectionIP55
Edgewise and flat zed units
Type Position of
neutral
Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Made tomeasure
N1 KTAppppCP31 KTAppppCP41 KTAppppCP71
N2 KTAppppCP32 KTAppppCP42 KTAppppCP72
N3 KTAppppCP33 KTAppppCP43 KTAppppCP73
N4 KTAppppCP34 KTAppppCP44 KTAppppCP74
(1) See the Trunking cross-sectiontable below.(2) For the 800 A rating,
indicate KTA0800 .
Canalis KTA
KTAppppCPp1
KTAppppCPp2
KTAppppCPp3
KTAppppCPp4
Trunking cross-section
Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000
Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38
3L + N + PE 13 16 18 22 26 30 37 45
3L + N + PER 15 19 21 26 31 36 46 56
Height H (mm)Width W (mm)
DD
202180
DD210867
(1) Important: for the 800 A rating, indicate KTA0800 .
KTAppppCPp3and KTAppppCPp4
KTAppppCPp1and KTAppppCPp2
Dimensions
Rating (A) Dimensions (mm)
A B C
800(2)
300 195 to 574 2751000 300 210 to 589 2901250 300 220 to 599 3001600 300 240 to 619 3202000 300 260 to 639 3402500 300 280 to 659 3603200 300 320 to 699 4004000 300 360 to 739 440
-
7/21/2019 Canalis KTA 800_4000A
63/205K9AE23000
DD2
02304
DD20230
6
DD202305
DD202307
2 Schneider Electric
Ca
taloguenumbers
Catalogue numbers Canalis interfaces for Prisma PlusLV switchboard
Interfaces for Masterpact NW circuit breakers
Circuit
breaker
Type of circuit
breaker
Number of
poles
Connection Cat. no.
Top direct Rear
NW08 / 16 Fixed or drawout 3 b b 04715
4 b b 04716
NW20 / 25 Fixed or drawout 3 b b 04725
4 b b 04726
NW32 Fixed or drawout 3 b b 04735
4 b b 04736
NW40 Fixed or drawout 3 b 04737
4 b 04738
For the position in the switchboard, see the Installation guide.
For connection to the PER, consult your sales agency.
Number of modules required in the switchboard
Circuit breaker Connection Type of circuit
breaker
Number of vertical
modules
(1)
NW08 / 16 Top direct Fixed or drawout 27
Rear Fixed 16
Drawout 17
NW20 / 25 Top direct Fixed or drawout 28
Rear Fixed 16
Drawout 17
NW32 Top direct or rear Fixed or drawout 28
NW40 Rear Fixed or drawout 36
(1) 1 module = 50 mm.
Canalis KTA
Interfaces for Masterpact NT and Compact NS circuit breakers
Masterpact NT
Circuitbreaker
Type of circuitbreaker
Number ofpoles
Connection Cat. no.
Top direct Rear
NT06 / 12 Fixed or drawout 3 b b 04703
4 b b 04704
NT16 Fixed or drawout 3 b 04703
4 b 04704
For the position in the switchboard, see the Installation guide.
For connection to the PER, consult your sales agency.
Compact NS
Circuitbreaker
Type of circuitbreaker
Number ofpoles
Connection Cat. no.
Top direct Rear
NS630b / 1250 Fixed or drawout 3 b b 04703
4 b b 04704
NS1600 Fixed or drawout 3 b 04703
4 b 04704
For the position in the switchboard, see the Installation guide.
For connection to the PER, consult your sales agency.
Number of modules required in the switchboard
Circuit breaker Connection Type of circuitbreaker
Number of verticalmodules(1)
NT06 / 12NS630b / 1250
Top direct Fixed 17
Drawout 18
Rear Fixed or drawout 16
NT16NS1600
Rear Fixed or drawout 16
(1) 1 module = 50 mm.
Top direct connection
Rear connection
Top direct connection
Rear connection
-
7/21/2019 Canalis KTA 800_4000A
64/205K9AE23000
DD2
02308
DD202309
3Schneider Electric
Ca
taloguenumbers
Catalogue numbers
Canalis KTA
Canalis interfaces for Prisma PlusLV switchboard
Interface supports and protection covers
Masterpact NW
Circuitbreaker
Type of circuitbreaker
Connection Supports Terminalextensionbar supports
Cover
NW08 / 32 Fixed ordrawout
Top direct 03561 3 x 04694 04871 + 04861
Rear 03561 2 x 04694 04871 + 04863
NW40 Fixed ordrawout
Top direct 03561 - 04871 + 04861
Rear 03561 - 04871 + 04863
Masterpact NT
Circuitbreaker
Type ofcircuitbreaker
Numberof poles
Connection Supports Canalis /circuitbreakerconnection
Cover
NT06 / 12 Fixed ordrawout
3P Top direct 03561 04712 04871 + 04852
Rear 03561 04713 04871 + 04853
4P Top direct 03561 04712 04871 + 04852Rear 03561 04714 04871 + 04853
NT16 Fixed ordrawout
3P Rear 03561 04713 04871 + 04854
4P Rear 03561 04714 04871 + 04854
Compact NS
Circuitbreaker
Type ofcircuitbreaker
Numberof poles
Connection Supports Canalis /circuitbreakerconnection
Cover
NS630b /1250
Fixed 3P Top direct 03561 04712 04871 + 04851
4P Top direct 03561 04712 04871 + 04851
Rear 03561 04714 04871 + 04853
Drawout 3P Top direct 03561 04711 04871 + 04852
Rear 03561 04713 04871 + 04854
4P Top direct 03561 04712 04871 + 04852
Rear 03561 04714 04871 + 04854
NS1600 Fixed 3P Rear 03561 04713 04871 + 04853
4P Rear 03561 04714 04871 + 04853
Drawout 3P Rear 03561 04713 04871 + 04854
4P Rear 03561 04714 04871 + 0485403561
04711
047120471304714
Arc-chute covers
Circuit breaker Type of circuit breaker Number of poles Cat. no.
Masterpact NT Fixed 3P 47335
4P 47336
Compact NS Fixed 3P 33596
4P 33597
-
7/21/2019 Canalis KTA 800_4000A
65/205K9AE23000
DD2
02310
DD20231
2
DD202311
DD2
02313
4 Schneider Electric
Ca
taloguenumbers
Catalogue numbers Canalis interfaces for OkkenLV switchboard
Interfaces for Masterpact NW circuit breakers
Fitting the interface does not change switchboard modularity as fixed by the devices.
Circuitbreaker
Type of circuitbreaker
Number ofpoles
Connection Cat. no.
Top direct Rear
NW08 / 16 Drawout 3 b 87811
b 87821
4 b 87812
b 87822
NW20 / 25 Drawout 3 b 87813
b 87823
4 b 87814
b 87824
NW32 Drawout 3 b 87815
b 87825
4 b 87816
b 87826NW40 Drawout 3 b 87817
b 87827
4 b 87818
b 87828
For the position in the switchboard, see the Installation guide.
For connection to the PER, consult your sales agency.
Canalis KTA
Interfaces forMasterpact NT circuit breakers
Fitting the interface does not change switchboard modularity as fixed by the devices.
Circuitbreaker
Type of circuitbreaker
Number ofpoles
Connection Cat. no.
Top direct Rear
NT08 / 16 Drawout 3 b 87811
b 87821
4 b 87812
b 87822
For the position in the switchboard, see the Installation guide.
For connection to the PER, consult your sales agency.
Interface supports
Circuit breaker Type of circuit breaker Connection Cat. no.
NW08 / 40NT08 / 16
Drawout Top direct 87800
NW08 / 32(1)
NT08 / 16Drawout Rear 87801
(1) For rear connection of the interface to a Masterpact NW40 circuit breaker, the supports are
supplied with the interface.
Top direct connection (RDH)
Rear connection (RAR)
Top direct connection (RDH)
Rear connection (RAR)
-
7/21/2019 Canalis KTA 800_4000A
66/205K9AE23000
DD2
02314
5Schneider Electric
Ca
taloguenumbers
Catalogue numbers
Canalis KTA
Sealing kitsIP55
Sealing kits for switchboard and Trihal transformer roofs with interface
Type Rating of the
trunking (A)
Height H of the
trunking (mm)
Cat. no.
Sealing kit 800 74 KTB0074TT01
1000 104 KTB0104TT01
1250 124 KTB0124TT01
1600 164 KTB0164TT01
2000 204 KTB0204TT01
2500 244 KTB0244TT01
3200 324 KTB0324TT01
4000 404 KTB0404TT01
KTB0pppTT01
-
7/21/2019 Canalis KTA 800_4000A
67/205K9AE24010
DD210831
DD210832
2 Schneider Electric
Dimensions
Catalogue numbers anddimensions
Feed units for switchboards andoil immersed transformersIP55
Straight feed units
Type Position ofneutral
Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Fixed N1 KTAppppER31 KTAppppER41 KTAppppER71
Made to measure N2 KTAppppER32 KTAppppER42 KTAppppER72
KTAppppERp1, KTAppppERp2
To order
Complete the catalogue number by replacing pppp by the rating.
Important: in the catalogue number for the 800 A rating, add a 0: KTA0800,add the dimensions of the selected unit as a technical comment.
Example:the catalogue number of a 1250 A made to measure end feed unit, N2,3L + N + PE, 235 mm long and with between centres J, K and M = 170 mm, is:KTA1250ER42, A = 235, J = 170, K = 170 and M = 170.
bb
Rating
(1) See the Trunking cross-sectiontable opposite.(2) PE drilled diameter = 14 mm pour cables with crimped lugs.
Table of dimensions
Rating (A) Neutral Dimensions (mm)
A J, K, M Y800(3)to 1250 N1 235 115 230
N2 235 to 534 80 to 250 2301600 to 2500 N1 235 115 350
N2 235 to 534 80 to 250 3503200 to 4000 N1 235 115 510
N2 235 to 534 80 to 250 510(3) For the 800 A rating, indicate KTA0800 .
KTAppppERp1KTAppppERp2
Canalis KTA
Dimensions of connection pads
Rating (A) 800 1000 1250 1600 2000 2500 3200 4000
Drilling for connection (mm)
DD202182
-
7/21/2019 Canalis KTA 800_4000A
68/205K9AE24010
DD2
10833
DD210835
DD210834
DD210836
3Schneider Electric
C
ataloguenumbers
D
imensions
Flat elbow feed units
Type Position of
neutral
Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Made to measure N3 KTAppppER33 KTAppppER43 KTAppppER73
N4 KTAppppER34 KTAppppER44 KTAppppER74
KTAppppERp3
(1) See the Trunking cross-sectiontable below.(2) PE drilled diameter = 14 mm pour cables with crimped lugs.
Tableau of dimensions
Rating (A) Neutral Dimensions (mm)
A B J, K, M Y800(3)to 1250 N3, N4 200 to 534 300 80 to 250 2301600 to 2500 N3, N4 200 to 534 300 80 to 250 3503200 to 4000 N3, N4 200 to 534 300 80 to 250 510(3) For the 800 A rating, indicate KTA0800 .
KTAppppERp3
KTAppppERp4
Catalogue numbers anddimensions
Canalis KTA
Feed units for switchboards andoil immersed transformersIP55
Cut-out drawing for feed units placed directly on the device roof
Table of dimensions
Rating (A) Dimensions (mm)
Y U V800(1)to 1250 230 K / 2 + J + 80 K / 2 + M + 801600 to 2500 350 K / 2 + J + 80 K / 2 + M + 803200 to 4000 510 K / 2 + J + 80 K / 2 + M + 80(1) For the 800 A rating, indicate KTA0800 .
KTAppppERp4
Trunking cross-section
Rating (A) 800(1) 1000 1250 1600 2000 2500 3200 4000
Weight (kg / m) 3L + PE 12 14 16 19 22 25 31 38
3L + N + PE 13 16 18 22 26 30 37 45
3L + N + PER 15 19 21 26 31 36 46 56
Height H (mm)Width W (mm)
DD
202180
DD210867
(1) Important: for the 800 A rating, indicate KTA0800 .
-
7/21/2019 Canalis KTA 800_4000A
69/205K9AE24010
DD210839
DD2
10837
DD210838
DD210836
4 Schneider Electric
Dimensions
Edgewise elbow feed units
Type Position of
neutral
Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Made to measure N5 KTAppppER35 KTAppppER45 KTAppppER75
N6 KTAppppER36 KTAppppER46 KTAppppER76
KTAppppERp5
KTAppppERp5
KTAppppERp6
(1) See the Trunking cross-sectiontable opposite.(2) PE drilled diameter = 14 mm pour cables with crimped lugs.
Table of dimensions
Rating (A) Neutral Dimensions (mm)
A B J, K, M Y800(3) N5, N6 175 to 509 275 80 to 250 2301000 N5, N6 190 to 524 290 80 to 250 2301250 N5, N6 200 to 534 300 80 to 250 2301600 N5, N6 220 to 554 320 80 to 250 3502000 N5, N6 240 to 574 340 80 to 250 3502500 N5, N6 260 to 594 360 80 to 250 3503200 N5, N6 300 to 634 400 80 to 250 5104000 N5, N6 340 to 674 440 80 to 250 510(3) For the 800 A rating, indicate KTA0800 .
Cut-out drawing for feed units placed directly on the device
Table of dimensions
Rating (A) Dimensions (mm)
Y U V
800(1)to 1250 230 K / 2 + J + 80 K / 2 + M + 801600 to 2500 350 K / 2 + J + 80 K / 2 + M + 803200 to 4000 510 K / 2 + J + 80 K / 2 + M + 80(1) For the 800 A rating, indicate KTA0800 .
Catalogue numbers anddimensions
Canalis KTA
Feed units for switchboards andoil immersed transformersIP55
KTAppppERp6
Dimensions of connection pads
Rating (A) 800 1000 1250 1600 2000 2500 3200 4000
Drilling for connection (mm)
DD202182
-
7/21/2019 Canalis KTA 800_4000A
70/205K9AE24010
DD202316
DD2
02315
DD202317
5Schneider Electric
C
ataloguenumbers
D
imensions
Catalogue numbers anddimensions
Canalis KTA
Feed units for switchboards andoil immersed transformersIP55
Bar feed units, flat outlets
Type Cat. no.
3L + PE 3L + N + PE 3L + N + PER
Made to measure KTAppppER37 KTAppppER47 KTAppppER77
Connection pad dimensions are identical to those of the feed units.
KTAppppERp7
KTAppppERp7
(1) See the Trunking cross-sectiontable below.
Table of dimensions
Rating (A) Dimensions (mm)
A P - Q S - R ou R - S Q, R, S minimum Y800(2)to 1250 235 to 734 160 to 600 160 to 600 80 2301600 to 2500 235 to 734 160 to 600 160 to 600 80 3503200 to 4000 235 to 734 160 to 600 160 to 600 80 510(2) For the 800 A rating, indicate KTA0800 .
Cut-out drawing for straight feed units connected directly to the device
Table of dimensions
Rating (A) Dimensions (mm)
Y U V800(1)to 1250 230
U = P + 80if S > R, V = S + 80if R > S, V = R + 80
1600 to 2500 35