cordexcxci 10_e03

Upload: goutam-saha

Post on 06-Apr-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/3/2019 CordexCXCI 10_E03

    1/2

    >Control and monitor via Internet Explorer browser

    >Internet Ready, Integrated SNMP

    >User defnable alarms and data logging

    >Flexible battery management eatures

    >Integrated Option On 2RU Cordex Rectifers

    >Upgradeable I/O via CXC Smart peripherals

    Cordex CXCIIntegrated System Controlle

    Cordex CXC controllers bring advanced monitoring technology to the Cordex series o rectifers. The compact CXCIsystem controller is an integrated option or 2RU Cordex rectifer shelves and includes the standard complete range o

    Cordex sotware eatures.

    The integrated CXCI controller includes a web server, providing easy set up via local or remote IP access using a standardWindows Internet Explorer browser. The CXCI also includes LED indicators and an LCD screen or voltage and current display.

    The integrated logging eature, typically only available with an advanced standalone data logging system, allows the

    capture o data rom multiple inputs or AC/DC voltages, load / battery current, and cell voltage/temperature. Common

    applications o the CXCI logging include power system details, thermal perormance o outdoor enclosures, battery cell

    specifcs, or mains variations captured by an AC voltage watchdog.

    The CXCI I/O eature set can be easily expanded with the addition o CXC Smart Peripherals such as battery cell

    monitoring, shunt multiplexing, and alarm relay expansion.

    Cordex CXC system controllers ensure eortless operation o the Cordex rectifer amily. Time consuming, complicated set

    up and monitoring o DC power systems are now a thing o the past.

    CXCI

  • 8/3/2019 CordexCXCI 10_E03

    2/2

    Canada: Burnaby, British Columbia Tel: 604 436 5900 Fax: 604 436 1233 #048-660-10 (10/2007)

    United States: Bellingham, Washington Tel: 360 647 2360 Fax: 360 671 4936

    Argus Technologies reserves the right to make changes to the products and inormation contained in this document without notice.Copyright 2007 Argus Technologies. All Rights Reserved. Argus is a registered trademark o Argus Technologies. member o The Alpha Group is a trademark o Alpha Technologies.Cordex is a trademark o Argus Technologies.

    Argus Technologies For more inormation visit www.argusdcpower.com

    Cordex CXCI System ControllerPart Number: List option on 2RU rectifer shelves

    Features continued

    Log Files:

    Daily Statistics: ...............Min., max. and average on analogue input

    channels with date and time stamp

    Battery current, rectifer current and AC mainsvoltage or last 90 days

    Event Log: ................ .......All events such as alarms, power on, change o

    state on digital inputs or other events

    Battery Log: ....................Battery health history on last 20 discharges with

    time o discharge and battery capacity.

    Data Logging: .................Up to 16 user confgurable logs o all system

    signals including Smart Peripherals

    Electrical

    Input Voltage: .................... 9 to 65VDC

    Current: .............................