    LAHMEYER  Compact-transformer substation ® 

    LCS-E.6

    LCS-E.6 / 08.01

      Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-0

    08492 Neumark, Postfach 11 42 Fax: 037600/3414

    Contents

    1. Application and technical regulations-  Use-  Construction-  VDE Regulations, IEC Standards

    2. Station housing-  Construction-  Material and surface treatment-  Fastening elements-  Doors , locks-  Safety class-  Lifting, Transport-  Earthing-  Illumination

    3. MV-switchboard-  Main switch / disconnector -  Conditions for transformer 

    4. Transformer -  Transformer compartment-  Mounting or replacing the Transformer 

    5. LV-switchboard-  Main switch, fused load break switches-  LV-fuse inserts-  Output clamping-  Instrumentation-  Mains socket-  Instrument panel

    6. Earthing appliance

    7.  Transport and mounting  -  Excavation, building pit, base structure  -  Using lifting equipment, lifting points  *  Cable connection on MV and LV side

    8.  Technical documents

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    3/24

     

    LAHMEYER  Compact-transformer substation ® 

    LCS-E.6

    LCS-E.6 / 08.01

      Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-0

    08492 Neumark, Postfach 11 42 Fax: 037600/3414

    Advantages:

    •  Small volume

    •  Robust

    •  Low weight  complete station including all equipment and 630 kVA transformer   about 3400kg

    •  Transformer compartment accessible via plug-in shutter on both sidesor through the roof.

    •  Front doors, door stops left and right adjustable, swivel angle 90‘ and 135‘

    •  Construction mains supply-/emergency supply inlet

    •  The steel base (about 320kg) is hot-galvanised, 100% poreles and doublepowder coated. The base unit is off modular designed (patent).

    •  Oil spill basin, 3mm sheet stainless steel supported above ground.Leakage may be examined from the outside.

    •  Cable inlet above basepan.

    •  Leading cables through the base structure is possible.

     All in all an exceptional cheap, easy to handle and economic solution

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    4/24

     

    LAHMEYER  Compact-transformer substation ® 

    LCS-E.6

    LCS-E.6 / 08.01

      Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-0

    08492 Neumark, Postfach 11 42 Fax: 037600/3414

    1. Operation and technical regulations

    1.1 The compactstation type LCS-E is used as a mains and customer station.

    1.2 The station is tested and certetified to PEHLA at 20 kA for 1 second.  (Type of accessibility: B  closed doors)

    1.3 The station is tested and conforms to the following VDE regulations and  IEC Standards:

      VDE 0100 Erection of installations with rated voltages up to 1000V.

      VDE 0101 Erection of installations with rated voltages above 1000V.

      VDE 0105 Operation of power installations.

      VDE 0110 Insulation co-ordination for equipment with low voltage  systems.

      VDE 0111/IEC 71-1 Insulation co-ordination to equipment for three phase a.c.  systems above 1000 V

      VDE 0141 VDE regulations for Earthing a.c. equipment for rated voltages  above 1000V.

      VDE 0532/  IEC 76-1,2,3,4,5 Transformers and reactors.

      VDE 0670/IEC 466 A.c. switch gear and controlgear for voltages above 1000V.

      VDE 0670/Section 611  (EN 61330/IEC 1330) Customer ready stations HV/LV

    1.4 Mounting, set-up and operation of compact stations is executed by trained personal  only, trained in the use of MV-switchgear, transformers, LV-switchgear, the  appropriate VDE- regulations and accident preventation procedures (VBG 4).

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    5/24

     

    LAHMEYER  Compact-transformer substation ® 

    LCS-E.6

    LCS-E.6 / 08.01

      Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-0

    08492 Neumark, Postfach 11 42 Fax: 037600/3414

    2. Station housing

      Temperature class = 20‘ K  Like all LAHMEYER-Compactstations, the type LCS-E compactstation is factory tested  and supplied ready for use. The station contains one MV-compartment,  LV-compartment and a transformer compartment.

      After connecting the LV and MV cables, the station is ready for immediate operation.

    2.1 The station housing type LCS-E, is manufactured in folded sheet metal design.  It consists of the following parts:

    -  Steel base pan, hot-galvanized, 100% poreles and double powder coated.-  Alternative: Base pan with intermediate mounting frame to fit CTA10 transformers.-  Two sheet metal folded beams, connected to the base pan or intermediate

    frame, for mounting MV- and LV equipment.-  Easy removable roof, (only one screw to be removed in the LV-compartment.-  Two lockable plug-in shutters within the side walls.-  Housing including doors and shutters for the LV- and MV compartments, removable

    in one piece from the steel base pan or intermediate frame.

    2.2 Material and surface treatment

      Material (under soil): Support structure Steel sheet, 3mm, hot-galvanized,  100% poreles and double powder coated

      (zinc dust coating)

      Oil pan for mounting the transformer, stainless steel  3 mm (1.4301-2B) 

    Material (above soil level): Steel sheet, stripe galvanized (< 225 g/mq)

      Surface treatment: Computer guided powder coating and 5-zone surface  pre treatment, attain coatings

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    6/24

     

    LAHMEYER  Compact-transformer substation ® 

    LCS-E.6

    LCS-E.6 / 08.01

      Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-0

    08492 Neumark, Postfach 11 42 Fax: 037600/3414

    2.3  All housing fittings are resistend against corrosion

    2.4  Doors to the MV- and LV compartment are fitted with three hinges each.The doors are fitted with metal- swing leaver locks, prepared for fittingstandard profile cylinders with 45o ore 90o lock-in angle. The profile cylinders areprotected with weather hood’s.The same swing leaver locks are used for the plug-in shutters.

    - Profile cylinders are not supplied with the station -

    The door to the MV-compartment is fitted with 4x multiple security lock.Both doors may be hinged up either left- or right sided. This may be done onsite. Door swing: 90o and 135o.

    2.5 Safety class

    MV- and LV compartment IP 54Transformer compartment IP 43

    2.6 The compact station, type LCS-E may be transported and lifted completelyequipped.The station is lifted via the base pan or the intermediate frame.(refer to technical documentation, page 11)

    2.7  All fitted elements are electrically connected and earth’d at a central earthingstarpoint in the LV- compartment.

    2.8  All parts under voltage are shock prove covered.

    2.9. MV and LV compartment may be fitted with lights, switched by door operated  contacts.

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    7/24

     

    LAHMEYER  Compact-transformer substation ® 

    LCS-E.6

    LCS-E.6 / 08.01

      Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-0

    08492 Neumark, Postfach 11 42 Fax: 037600/3414

    3. MV- switchgear 

      Using CTA 10 transformers (12kV), the following switchgear can be fitted:  The CTA 10 transformer has direct on tank mounted fuse holders:

    •  MINEX-C, 3K,  Make  Driescher 12 kV

    •  GC, 2K + 1TS, "  Moeller (F & G) 12 kV

    •  8DJ30, 3K, "  Siemens 12 kV

    •  MD4 3 - 4 K "  Hazemeyer 12 kV

    •  MF 3 - 4 K "  Hazemeyer 12 kV

    •  DPS 12 AE, 1 K "  Driescher 12 kV

      In conjunction with DIN-Transformers 12/24 kV,  max. dimensions LxWxH = 1250x900x1650mm,

      hermetic sealed type with insulated connections or NTB-Transformers 12/24 kV,  the following switchgear may be fitted:

    •  FBA, 2 K + 1TSS, Make Alstom 12 / 24 kV

    •  MINEX-C, 3 K + 1TSS, * "  Driescher 12 / 24 kV

    •  G.I.S.E.L.A.,2 K + 1TSS, * "  12 / 24 kV

    •  GA, 2 K + 1TSS, "  Moeller (F & G) 12 / 24 kV

    •  8DJ20, 2 K + 1TSS, "  Siemens 12 / 24 kV

    •  8DJ30, 2 K + 1TSS, "  "  12 kV

    •  HH-fuses 12/24 for 2 cables "  SGB 12 / 24 kV

    •  M 3007 for 2 cables "  Driescher/SGB 12 / 24 kV

    *(24kV - HH-fuse, fitting dimension 292mm)

    Short syntax: K = Cable switch, TS = Transformer switch, TSS = Transformer   switch inc. fuses.

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    8/24

     

    LAHMEYER  Compact-transformer substation ® 

    LCS-E.6

    LCS-E.6 / 08.01

      Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-0

    08492 Neumark, Postfach 11 42 Fax: 037600/3414

    - MV-switch gear -

      Illustration : switch gear options

     Make Alstom, Typ FBA 3 sections., 2 K + 1 TSS

    Make Driescher,

    Typ MINEX-C4 sections., 3 K + 1 TSS

    Make Siemens,Typ 8DJ203 sections., 2 K + 1 TSS

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    9/24

     

    LAHMEYER  Compact-transformer substation ® 

    LCS-E.6

    LCS-E.6 / 08.01

      Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-0

    08492 Neumark, Postfach 11 42 Fax: 037600/3414

    4.  Transformer compartment

    4.1  CTA 10 transformers =

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    10/24

     

    LAHMEYER  Compact-transformer substation ® 

    LCS-E.6

    LCS-E.6 / 08.01

      Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-0

    08492 Neumark, Postfach 11 42 Fax: 037600/3414

    5. Low voltage distribution panel

    Low voltage distributionLAHMEYER- Compactstation, type LCS-E

    with low voltage distribution.Incoming feed via 910 A rail, 8 outlets.

    5.1  Option (standard)

    5.1.1 NH-fused load break switches to DIN 43623 size 3  as main switch including:

    -  reinforced copper-busbars and contacts, high  temperature resistant insulation material

    -  generously reinforced dimensioned-busbar.-  Use of Al-Oxide-ceramics for the fuse body

      at voltage: 400V

      current : 910A.

    Fuses to be used:  NH-fuse inserts to DIN 43620 and 3 pieces  VDE 0636 part 22  Operation classification gTr   Rated current 910 A  or with copper blades 1000 A

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    11/24

     

    LAHMEYER  Compact-transformer substation ® 

    LCS-E.6

    LCS-E.6 / 08.01

      Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-0

    08492 Neumark, Postfach 11 42 Fax: 037600/3414

    5.1.2 Output power 

      NH- fuses load break switches 400/630A 8 pieces

    5.1.3  Current transformer connection options 900/600/300/5A, in L2 1 piece

    5.1.4  Bimetal type current meter with peak-hold pointer (15min) 1 piece

    5.1.5  Syncron sockets for syncronizing,  fuses 3 pieces

    5.1.6  Inlet for construction site supply in the right side wall  of the LV-compartment, Ø each 100 mm 2 pieces

      optional:-  3 current meters inc. current transformers

      - 1 voltmeter incl. switch and fuses.  - 1 Schuko- mains socket, fused

      - 1 lighting and fuse

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    12/24

     

    LAHMEYER  Compact-transformer substation ® 

    LCS-E.6

    LCS-E.6 / 08.01

      Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-0

    08492 Neumark, Postfach 11 42 Fax: 037600/3414

    5.1.7 Meters, fuses and terminal strips are mounted in instrument panel  above the LV-distribution.

    5.1.8  MP and PE busbars for the entire earthing are mounted in the LV compartments  floor area.

    5.1.9  The cable fixture is placed below the removable floor panel.

    5.2 Option (with LV- counter meter)

      The illustration shows a „customer specified station“.  Four of eight outputs have been replaced by certified current transformer and  one LV-counter-meter cabinet, size 1.

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    13/24

     

    LAHMEYER  Compact-transformer substation ® 

    LCS-E.6

    LCS-E.6 / 08.01

      Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-0

    08492 Neumark, Postfach 11 42 Fax: 037600/3414

    6.  Earthing appliance

      The central earthing bar is situated in the LV-cabinet. The soil earthing lead or   deep soil earther are directly connected to the central earthing bar. In this way,  all housing parts and the base pan are directly connected to the main earthing.

    7. Transport, placing and erection  The LCS-E is manufactured ready for connection and fully tested.  For transport, placing and erection refer to technical documentation Bl.12

    7.1  Placement on the building site.  Dimensional drawing No. 283432.4 (with steel pan)

    7.2  Resulting terrain height and surface water must be considered when determving  the excavation depth.  Site excavation drawing No: 283436.4 (with steel pan)

    7.3  The excavation pit must have a strong floor bearing. Floor unevenness must be

      compensated with a levelled sand bed.  In case difficult floor conditions are encountered, a lean-concrete substructure  or concrete thresholds are recommended.

    7.4  The station is placed on site by using an adequate lifting gear.  The LCS-E can be lifted and put in place completely equipped.  Set-up for lifting, Drawing No: 283434.9 (with steel pan)

    7.5 Procedure for cable connection:

    7.5.1 To be removed on the MV- side:

    •  Face panel of the base pan

    •  Cover of the MV-switch gear- cable-connection-compartment.(see manual)

    •  Lower door threshold (screwed on sideways)

    •  Front floor panel.

    7.5.2 To be removed on the LV- side:

    •  Base pan fill skirt.

    •  Front floor panel.

    •  Lower door threshold (screwed on sideways)

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    14/24

     

    LAHMEYER  Compact-transformer substation ® 

    LCS-E.6

    LCS-E.6 / 08.01

      Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-0

    08492 Neumark, Postfach 11 42 Fax: 037600/3414

    8. Technical documentation

      - Dimensional drawing (with steel pan) 283432.4

      - lifting-set-up drawing (with steel pan) 283434.9

      - Site excavation drawing (with steel pan) 283436.4

      - loading plan (with steel pan) 283435.6

      - Typ testing Page 1+2

      - Electro magnetic field  test record

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    15/24

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    16/24

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    17/24

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    18/24

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    19/24

     

    LAHMEYER  Compact-transformer substation ® 

      LCS-E.6

    LCS-E.6  Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-008492 Neumark, Postfach 11 42 Fax: 037600/3414

    - Type testing to DIN EN 61330, VDE 0670, Part 611 -

    1. Proof testing of isolation levels on the factory -ready station

    Since all electrical parts within the ready made Station have been tested to all relevant standard’s,the test above is only to be applied on the connections between those parts, as far as the dielectricparameters are influenced by mounting and setup conditions.

    -  Connections between MV-Switch gear and transformer have been typ-testetEvery connection with cable N2XSY 12/24 kV and make-up Earthing connections have been test-loaded with 50kV for 1min to test dielectric strength.

    -  Cable used for the LV-Side are NSGAFÖU,185 mm2 Cu, 1,8/3 kV

    2. Heat testing

    -  Establishing temperature-class of the housing using a 630kVA transformer.

    The temperature class is 20 K.

    This test has been performed using transformer Fabr.-Nr. 346 268 of Fa. SBG

      The LV- distributor was integrated in the test.

      The temperature limit’s to DIN VDE 0660 part 500 are not exceeded.

    2.1 Over load testing the LV- distributor 1,15 x IN permanent load (minimum 7 hours).The temperature limit’s to DIN VDE 0660 part 500 are not exceeded.

     All build in parts remain functional.

    3. Testing to verify the safety grade, to DIN VDE 0470 ,part1

    -

      MV-Compartment and LV-Compartment: IP54-  Transformer compartment, insertion proof: IP43

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    20/24

     

    LAHMEYER  Compact-transformer substation ® 

      LCS-E.6

    LCS-E.6  Subject to technical changes!

    SGB Neumark GmbH Tel.: 037600/83-008492 Neumark, Postfach 11 42 Fax: 037600/3414

    - Type testing to DIN EN 61330, VDE 0670, Part 611 -

    4. Testing to evaluate the effects of internal error 

    - 3-phase short circuit within the cable connection compartment of the MV-Switch gear with closed  doors and short circuit current of 20 kA, 1 s

    - The criterious of valuations 1 – 6 according IEC 1330: 1995; DIN EN 61330 (VDE 0670 part 611)  1997-08 are fulfil

    5. Test for verification of mechanical resistance of the housing against mechanical stress.

    -  Roof load minimum 2500N/m (Mounting load and snow load).Verified by means of static calculation.

    -  Wind load to IEC 694 (700N/mm2).  Verified by means of static calculation.

    -  Stress by outer blow on housing, door’s, swing leaver handle and ventilation opening’s.Test using test assembly to VDE 0670 part 611 , passed.

    6. Noise level of factory ready station

    -  The sound pressure level (LPA) is reduced by 3 dB(A) when the transformer is mountedin the station.

    7. EMV-Test

    The test was performed using 910A.On all test points values < 100 µT where measured.

      See enclosure

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    21/24

      Test record electric field intensity

     Compactstation Typ: LCS-ETest equipment: Combinova FD1 measuring range: 40nT – 100yT // 4 V/m-10 kV/m(RMS)Max. permittable value : magnetic field B in Micro-Tesla : 100 yT

    Electric field E in (kV/m) : 5kV/m Attendance: green , OS

    Mains feed Uk-MV Us at short circuitFeed current MV: 34.6A

     

    The electric field strength on the sheet metal surface is max. 40V/m.

     

       M   V

      c  a   b   i  n  e   t

      Transformer 

     

       L   V

      c  a   b   i  n  e   t

    0,2 m distancerange

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    22/24

    Bearing load (bulk density) calculation to DIN 1054Lahmeyer-Compact Station LCS-E.6

    Oil pan

    Base pan

    Medium voltagecable

    Soil heap up

    Compressedgravel bed

    - Station overall weight: 3000kg

    - Floor contact section of runner0.968mq

    - Bearing load for the complete s

    - In accordance to table 1 of DINthe permissible bearing load fobuildings on non binding soilis specified at 150kN/qm!

    - above illustration shows only the stations modular base structure (patent )- Static calculations of the complete station are available.

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    23/24

    air flow section (gap between oil pan and outer wall)for gases from the cable connection compartment.

    air flow section (labyrinth pass)for draining off hot arc gases fromthe MV-compartment into thetransformer compartment.

    Oil pan

    The front support acts trough its depth,as a labyrinth passbetween MV- and transformer compartment.

    Base pan

    Medium voltagecable

    Main dimensions of the stainlesssteel pan- (DxLxH)900x1490x450Material thickness t=3mm,

    1.4301Soil heap up

    Compressed gravel bed

     NOTE:

    Modular Base unit - patent !

      New foundation concept

  • 8/20/2019 CS_LCS-E6_engl[1].pdf

    24/24

    Please don’t hesitate to contact us any time:

    Dipl.-Ing. Andreas Jahreiß

    SGB GmbHOhmstraße 1, 08496 Neumark