danfossvtc datasheet

Upload: e-comfortusa

Post on 10-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/8/2019 DanfossVTC Datasheet

    1/5

    VDKIJ102 Danoss 01/10

    Data sheet ESBE VTC

    3-Way Thermic Valve

    1

    The ESBE VTC thermic valve is a thermostaticby-pass valve which regulates the temperature

    o either the supply out or the return o waterin a hydronic heating system. In a conventionalapplication, the VTC valve saeguards non-condensing boilers against corrosion romcondensation that would result i a minimumfue gas temperature is not maintained. Withthe VTC the boiler is able to recover and keepup with the drop in water temperature. TheVTC valve can also be used on a solid uelboiler or a solar application where a minimumor maximum water temperature is trying tobe maintained.

    Applications:

    Ordering Inormation:

    Code No. Series Cv Valve Size Connection

    193B1700VTC511

    10.4 1FNPT

    193B1701 16.2 1-1

    Code No. Series Typical Application

    193B1702 122F (50C)

    Return line boiler protection193B1703 131F (55C)193B1704 140F (60C)

    193B1709 149F (65C)

    Boiler outlet, storage tank eed193B1705 158F (70C)

    193B1706 176F (80C)

    Code No. Description

    193B1708 O-ring or brass plug

    VTC Valve Body, Without Thermostat*

    Internal VTC Temperature Element

    Spare Parts

    * Valve body and thermostat sold separately. Order one valve body and one thermostat to assemble a

    complete valve

    Typical Applications:

    High mass non-condensing boiler coupled

    with low return water situations, i.e. snow

    melt systems or high mass concrete radiant

    oor heating

    Gravity hot water conversion systems

    Solid uel boilers eeding storage tanks or a

    heating system

    Solar heating and stratication control orstorage tank

    Features:

    Thermostatically maintains a high and steady

    return temperature increasing the lie and

    eciency o the heat source

    Protection rom thermal shock within non-

    condensing boilers

    Sel contained thermostatic element with no

    adjustment required

    Interchangeable thermostat elements, to

    meet temperature requirements

    Low leakage rate through the ports o

    the valve

  • 8/8/2019 DanfossVTC Datasheet

    2/5

    Data sheet

    2VDKIJ102 Danoss 01/10

    ESBE VTC

    3-Way Thermic Valve

    Technical Specifcations:

    Valve Selection:

    Max. system pressure 145psi (10 bar)

    Max. medium temperature 230F (110C)

    Min. medium temperature 32F (0C)

    Fully open temperature diferential 18F (10C) higher than temperature element

    Max. diferential pressure across: B - AB & A - AB 14.5psi (1 bar)

    B - A 4.35psi (0.35 bar)

    Max. leakage rateA - AB 1% o Cv

    B - AB 3% o Cv

    Allowable medium Closed loop system, Glycol mixture up to 50%

    B ()

    AB( ) A()

  • 8/8/2019 DanfossVTC Datasheet

    3/5

    Data sheet

    3VDKIJ102 Danoss 01/10

    ESBE VTC

    3-Way Thermic Valve

    Piping Orientation:

    When the VTC is piped on the supply side

    out rom the heat source, the valve willbegin to allow water out to the system

    when the temperature o the uid meets

    the temperature o the inserted thermostat

    element.

    The VTC valve, when placed on the return

    side will open when the minimum return

    temperature o the element is reached.

    When the uid temperature reaches

    18F (10C) higher than the elements

    temperature, the return port rom the

    system will be ully open.

    Circulator

    VTC valve

    Other location or circulator

    Supply Mounted

    (149F (65C), 158F (70C), 176F (80C) elements)

    Return Mounted

    (122F (50C), 131F (55C), 140F (60C) elements)

    Circulator

    VTC

    valve

    Other location or circulator

  • 8/8/2019 DanfossVTC Datasheet

    4/5

    Data sheet

    4 VDKIJ102 Danoss 01/10

    ESBE VTC

    3-Way Thermic Valve

    Systems Applications: VTC Thermic Valve on Gravity Conversion System

    VTC Valve on Multi-zone Systems with Circulators

    VTC Valve

    Because gravity conversion systems contain

    an enormous volume o water, the water

    returning to the heat source could be

    signicantly cooler, leading to condensation

    and a shorter lie or the heat source. Adding

    a thermic valve to the system will prevent

    the boiler rom sustained operation at

    temperatures below the dew point o their

    ue gases.

    Where a high mass non condensing

    heat source is matched with a large low

    temperature system, a situation could occur

    where the heat source is unable to keep up

    with the rate o demand rom the system.

    The use o the thermic valve provides the

    opportunity or the heat source to catch-up.

    VTC Valve

    Charging o Storage Tank through Solar Heating

    With the thermic VTC valve, an ecient

    method o charging a tank can be done.

    To achieve eciency through the solar

    panel, cool water should enter allowing or

    a higher diferential temperature across the

    panel. Additionally heated uid rom the

    panel should be properly distributed within

    the tank to reduce stratication i.e. even

    temperature distribution, within the tank.

  • 8/8/2019 DanfossVTC Datasheet

    5/5

    Data sheet

    Danoss can accept no responsibility or possible errors in printed materials and reserves the right to alter its products without notice.

    All trademarks in this material are property o the respective companies. Danoss and Danoss logotype are trademarks o Danoss A/S. All rights reserved.

    DanossBaltimore, MD

    Toll Free: 866-375-HVAC (4822)

    Tel.: 443-512-0266, Fax: 443-512-0270

    www.na.heating.danoss.com

    DanossToronto, ON

    Toll Free: 866-375-HVAC (4822)

    Tel.: 905-285-2050, Fax: 905-285-2055

    www.na.heating.danoss.com

    5 VDKIJ102 Danoss 01/10

    ESBE VTC

    3-Way Thermic Valve

    Dimensions:

    Construction:

    A B C Depth Weight

    Size in (mm) in (mm) in (mm) in (mm) lbs (kg)

    1 3.66 (93) 1.34 (34) 2.72 (69) 1.85 (47) 1.85 (0.84)

    1- 4.13 (105) 1.50 (38) 2.95 (75) 2.17 (55) 3.04 (1.38)

    Valve body Nodular iron

    O-ring EPDM

    Thermostat cover Brass

    Thermostat Copper