dasd-rh 시리즈 매뉴얼(eng)

Upload: pham-long

Post on 07-Aug-2018

234 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/20/2019 DASD-RH (ENG)

    1/49

    =================================================

    DOOSAN AC SERVO MOTOR/DRIVER

    DASD - RH Series

    Model : 1.0/2.0/3.5 KW

    Maintenance manual

  • 8/20/2019 DASD-RH (ENG)

    2/49

    1. For the prevention of electric shock

    2. For the fire prevention

    3. For the injury prevention

    Please make a wire work and inspection more than 5 minute later after power is

    off, and do the next work after checking the voltage by a tester because it may

    cause the electric shock.

    Please make sure to ground the servo driver and servo motor.

    Please make the wire work and inspection by an authorized expert.

    Please make the wire work after setting up the servo driver and servo motor.

    Please do not touch the switch by wet hand to prevent the electric shock.

    Please do not damage and stress the cable.

    Please do not put the heavy goods on the cable because it may cause the electric

    shock.

    Please install the servo driver and servo motor to the noninflammble materials. If

    you install it to the inflammble materials directly or near the inflammble materials,

    it may cause the fire.

    In case the servo driver is broken, please turn off the power from the part of

    electric shock on the servo driver. If the high electric current is flowed

    continuously, it may cause the fire.

    Please permit the correct voltage in the maintenance manual to each terminal only to

    prevent the breakage, damage and rupture.

    Please do not make a mistake when terminal connection. it may cause the breakage and

    damage.

    Please make sure the right pole( + , - ) to prevent the breakage and damage.

    Please do not touch the heat sink of servo driver and servo motor when power is on

    or a few moment after power is off because it is heated. Do not touch the parts

    (cable, etc), it may cause the damage and burn.

  • 8/20/2019 DASD-RH (ENG)

    3/49

    Caution for safety operation ≫

    Caution before installation

    Please keep the installation direction.

    Please do not throw down it and make an impact.

    Please do not install it at the place of water, corrosive gas, inflammble gas

    and materials.

    Caution for the wire work

    Please use only AC 200 ~220V for the input power supply of servo driver.

    Please connect the ground to the ground terminal.

    Please do not connect the main power supply to servo motor directly.

    Please do not connect the main power supply to output terminal U, V, W of servo

    driver directly.

    Please use only the compression terminal with insulated tube when wiring the

    power terminal of servo driver.

    Please wire the cable for power(U, V, W) and encoder cables of servo motor

    separately.

    Caution for operation

    Please check and adjust each manu before operation.

    Please do not touch the shaft of motor rotation when operating motor.

    Please do not touch the heat sink when operating motor.

    Please connect or disconnect the connecter of CN1,CN2 when power is off,

    General caution

    The contents of this manual may be changed according to the product modification

    and the standard change.

  • 8/20/2019 DASD-RH (ENG)

    4/49

    Caution when the first installation

    Please make sure the power voltage (AC200~220V) and the wire before power is on.

    Please apply the first power when the servo is turned off.

    First of all, please check the name of motor and the number of encoder pulse

    before power is on.

    And then, set up the operation mode of servo driver by connecting with the upper

    numerical controller like the menu.

    Please wire CN1 connector of servo driver according to each operation mode as

    referring to the system structure.

    Caution when the maintenance and inspection

    Please turn off l1,l2 of the control power and L1,L2,L3 of the main power, and

    check the state of power off after enough time passes. After that, please do the

    maintenance and inspection.

    It is dangerous because the charged voltage in inner electrolytic condenser is

    remained.

    Please do not touch the terminal when power is on because high voltage flows.

    It may cause the electric shock.

    Please do not repair, inspect, replace the components except for authorized

    expert and engineer.

    Please do not alter the products.

  • 8/20/2019 DASD-RH (ENG)

    5/49

    < CONTENTS >

    IMPORTANT

    1. Specifications of TURRET Servo Motor and Driver

    1.1 Specifications of TURRET Servo Motor

    1.2 Specifications of TURRET Servo Driver

    1.3 Torque-Speed Characteristics of Servo Motor

    2. Explanation of Driver Structure and connection diagram

    2.1 Explanation of CN1 Connector

    2.2 Flow chart of CN1 connector terminal

    2.3 Flow chart of CN2 connector terminal

    2.4 Structure of driver Input/Output circuit

    2.5 Connection diagram

    3. Operation

    3.1 Automatic operation

    3.2 Method of machine reset

    4. Explanation of each mode display

    4.1 Status mode

    4.2 Diagnosis mode

    4.3 Parameter setting mode

    4.4 Parameter list

    4.5 Detailed explanation of parameter setting mode for user

    4.6 Alarm record mode

    5. Maintenance and inspection

    5.1 Maintenance and inspection

    5.2 Trouble diagnosis and countermeasure

  • 8/20/2019 DASD-RH (ENG)

    6/49

    IMPORTANT

    . Definition of Symbols for Warning

    . Warning

    1) Do not use in areas near corrosive, inflammable or explosive gas.

    2) Take appropriate measures of protection while the servo motor is in operation.

    3) While installing and wiring, turn the power switch off, in order to prevent electric

    shock.

    4) Ground the PE terminal block of the front panel terminal block L1(R), L2(S), L3(T) to

    one-point with the class 3 (below 100 ) ground circuit, in order to prevent electric

    shock or other malfunctions. For PE terminal block, use wire 30mm

     

    2thicker than the

    electric wire of the terminal L1, L2, L3.

    5) Connect the PE terminal block of the servo motor to the PE terminal block U, V, W of

    the servo driver in order to prevent electric shock. To connect the wire, use wire

    30mm

     

    2thicker than the power line of U, V, W.

    6) Take precautions while mounting, dismantling, uninstalling and transferring the servo

    motor.

    7) Cover the terminal block while using the servo driver in order to prevent electric

    shock.

    8) Use SELV for maintenance brake power switch, input and output power switch and input

    and output signal in order to prevent electric shock.

    9) Do not dismantle the servo driver for another 5 minutes after the main power is turned

    off-charged voltage may still remain inside the driver.

    10) This product uses batteries. Take the following precautions while using the battery.

    If used inappropriately, explosion or fire may occur. The contents of the battery are

    harmful to the eye.

    Do not heat above 100 and do not open when there is fire.℃

    Do not take it apart. (The contents are harmful to the eye)

    Do not recharge it.

    11) During emergency shut down, stop the servo motor before shutting down the servo driver

    (terminal L1, L2, L3).

    1)

    Warning : This symbol means of not handled properly, there is

    possible danger such as electric shock.

    2)

    Caution : This symbol means if not handled properly, there is possible

    danger of acquiring mild to severe injuries or machine damages.

  • 8/20/2019 DASD-RH (ENG)

    7/49

    . Caution

    1) To avoid burns, do not touch the heat protecting board or the regenerative resistor

    of the servo motor and driver while the servo motor is in operation or right after

    the power switch is turned off. Take appropriate measures of protection.

    2) Avoid the following to prevent damages to the servo motor and servo driver.

    Do not connect the power directly to the U, V, W terminal block of the servo motor.

    The servo motor will be damaged.

    Avoid external impact such as hammering to the servo motor. The encoder inside the

    servo motor will be damaged.

    Do not connect the power to the U, V, W terminal block of the servo driver.

    While doing the resisting pressure test or insulation voltage test, disconnect the

    terminal of the servo driver terminal block or all the connectors and avoid the test

    voltage from affecting the servo driver. Also avoid the test voltage from affecting the

    encoder connector terminal of the servo motor.

    Do not install the servo motor and the servo driver differently than it should.

    Prevent water or oil from directly touching the servo motor. Use in areas free of

    water or oil to prevent it from touching the main wire of the servo motor.

    Do not use the servo motor and driver differently other than stated in this manual.

  • 8/20/2019 DASD-RH (ENG)

    8/49

    1. Specifications

    1.1 Specifications of Turret Servo Motor

    Items Model

    DS-RH10ZA-1 DS-RH20ZA-1 DS-RH35ZA-1

    Rated output(KWatt) 1.0 2.0 3.5

    Rated Torque

    kgf cm 48.7 97.4 170.5

    N m 4.7 9.5 16.6

    Instant

    maximum Torque

    kgf cm 146.1 365.4 511.4

    N m 14.2 37.3 49.8

    Rated speed(RPM) 2000 2000 2000

    Maximum speed(RPM) 3000 3000 3000

    Rotor inertia

    gf cm sㆍ

     

    27.33 14.05 35.50

    GD²4

    (kg m²×10 

    −4)

    7.48 14.31 34.79

    Insulation grade F Class F Class F Class

    Detector Multi-turn Absolute Encoder

    (17bits/1rotation)

    Protection, cooling method Totally closed, self cooled

    Ambient temperature 0 ~ 40°

    Ambient humidity 20 ~ 80

    Mounting structure Flange type

    Insulation resistance DC 500V 50 MΩ

    Insulation voltage AC 1500V one minute

    Vibration grade V15

  • 8/20/2019 DASD-RH (ENG)

    9/49

    1.2 Specifications of TURRET Servo Driver

    1.3 Torque-Speed Characteristics of Servo Motor

    Items Model DASD-RH10SPZA DASD-RH20SPZA DASD-RH35SPZB

    Rated current[Arms] 6.5 12.3 19.8

    Main input voltage Triple phase AC 200 ~ 220V, +10/-15 , 50/60Hz

    Control method IPM full wave rectified, sine wave PWM control

    Control mode Position, Speed, Torque control

    Control signal input Servo ON, Start, Stop, Jog, Sensor

    Position input 7bit pulse reference input

    Control signal output Alarm, Ready, Inposition, Unclamp

    Position output 7bit present position output

    Protection

    over voltage, under voltage, over current,

    over speed, over load, encoder error

    Mounting Rack Mount Type

    Dimension[mm] (W x H x D) 115 x 230 x 203 140 x 250 x 250

    DS-RH10ZA-1

    DS-RH20ZA-1

    DS-RH35ZA-1

  • 8/20/2019 DASD-RH (ENG)

    10/49

    2. Explanation of Driver Structure and connection diagram

    2.1 Explanation of CN1 Connector

    2.1.1 CN1 Connector Explanation of DASD-RH10SPZA, DASD-RH20SPZA

    Signal PIN No. Description I/O

    /SENSOR 21 This signal judges an Unclamp or Clamp. Input

    /SVON 22

    This signal makes the motor ready to start operation. When this

    signal is off, the motor remains free .

    Input

    /JOG+(CCW)

    /JOG-(CW)

    20

    23

    According to the fixed value of parameter 3, there are 2 types

    of modes.

    - fixed direction signal (fix value of parameter 3 to 0 )

    When the position is moving, the direction of the rotation

    can be fixed to one direction.

    CCW signal is OFF : Direction of the rotation is automatically

    set by short distance.

    CCW signal is ON : Direction of the rotation is fixed counter-

    clock wise.

    CW signal is ON : Direction of the rotation is fixed clock

    wise.

    CCW, CW is ON : Can not be defined.

    - JOG Operation signal (fix value of parameter 3 to 1 )

    Used for manual jog operation signal.

    JOG+ signal is ON : When the signal is on, the motor rotates

    counter-clock wise and when it is off, the motor stops at the

    nearest POST.

    JOG- signal is ON : When the signal is on, the motor rotates

    clock wise, and when it is off, the motor stops at the nearest

    POST.

    Rotation speed and Accel/Decel time is the same as when it is

    operated automatically, but ignore it during running by

    automatic operation.

    Input

    /STOP 4

    When the signal is ON, the motor stops. When the motor starts

    according to input, and runs the rest of the distance.

    Input

    /SPARE 3 This is spare signal. Input

    COM1 5

    COMMON terminal of sequence input signals (When DC 24V is input,

    the signal turns ON)

    Input

    /START 8

    When this signal is ON while SVON signal is ON, it moves toward

    the POST of position data input (POSI0~POSI6) of the motor.

    Maintain the time it is ON at minimum 50msec.

    Input

    /POSI0, /POSI1,

    /POSI2, /POSI3,

    /POSI4, /POSI5,

    /POSI6

    24, 25,

    26, 27,

    28, 6,

    7

    Input POST to 7bit binary code to set the position data input

    signal.

    Input data more than 10msec before the START signal is ON.

    (minimum input data is '1'.)

    Input

    COM2 9 COMMON terminal(+24V) of START, POSI0~POSI6 signals. Input

  • 8/20/2019 DASD-RH (ENG)

    11/49

    Signal PIN No. Description I/O

    ALM 30

    Alarm signal is on, output is 'OFF' and when it is normal, the

    output is 'ON'.

    Output

    SVRDY 10

    The servo is ready. When the SVON is ON, the driver turns on

    after the normal condition. When the SVON is OFF, the driver

    turns off.

    Output

    UN-SOL 29

    This signal is running the contact point of Unclamp solenoid.

    (This signal is Unclamp after it is ON)

    Output

    COM3 11 COMMON terminal of sequence output signals(ALM, SVRDY, SPARE). Output

    BRAKE+

    BRAKE-

    12

    13

    In case there is an inner brake in the motor, this signal

    controls the power ON/OFF for the brake.

    (The current flow capacity is within 30mA due to the output of

    photo coupler contact point, thus a different relay contact point

    must be used from the actual brake ON/OFF. the circuit so that

    when output contact point is ON, the brake is free, when output

    contact point is OFF, design the circuit diagram to control the

    brake).

    when SVON is ON and this turns on after fixed time of parameter

    14 and then SVRDY is ON after fixed time of parameter 13.

    When SVON is OFF and this turns off after fixed time of parameter

    14.

    Output

    VPF 16

    Position completion signal output.

    After the motor moved, if the pulse error is within the fixed

    value of parameter 18, the signal turns ON.

    Output

    POSO0, POSO1,

    POSO2, POSO3,

    POSO4, POSO5

    POSO6

    31, 32,

    33, 34,

    35, 36,

    14

    As position data output signal, the POST number is sent out in

    7bit binary code.

    While the motor is rotating, the signal will not be on. It will

    be on before the VPF turns on.

    When SVON is OFF, it will output data of the nearest POST number.

    Output

  • 8/20/2019 DASD-RH (ENG)

    12/49

    2.1.2 CN1 Connector explanation of DASD-RH35SPZB

    Signal PIN No. Description I/O

    /SENSOR 6 This signal judges an Unclamp or Clamp. Input

    /SVON 7

    This signal makes the motor ready to start operation. When this

    signal is off, the motor remains free.

    Input

    /JOG+(CCW)

    /JOG-(CW)

    8

    22

    According to the fixed value of parameter 3, there are 2 types

    of modes.

    - fixed direction signal (fix value of parameter 3 to 0 )

    When the position is moving, the direction of the rotation

    can be fixed to one direction.

    CCW signal is OFF : Direction of the rotation is automatically

    set by short distance.

    CCW signal is ON : Direction of the rotation is fixed counter-

    clock wise.

    CW signal is ON : Direction of the rotation is fixed clock

    wise.

    CCW, CW is ON : Can not be defined.

    - JOG Operation signal (fix value of parameter 3 to 1 )

    Used for manual jog operation signal.

    JOG+ signal is ON : When the signal is on, the motor rotates

    counter-clock wise and when it is off, the motor stops at the

    nearest POST.

    JOG- signal is ON : When the signal is on, the motor rotates

    clock wise, and when it is off, the motor stops at the nearest

    POST.

    Rotation speed and Accel/Decel time is the same as when it is

    operated automatically, but ignore it during running by

    automatic operation.

    Input

    /STOP 23

    When the signal is ON, the motor stops. When the motor starts

    according to input, and runs the rest of the distance.

    Input

    /SPARE 24 This is spare signal. Input

    COM1 40

    COMMON terminal of sequence input signals (When DC 24V is input,

    the signal turns ON)

    Input

    /START 43

    When this signal is ON while SVON signal is ON, it moves toward

    the POST of position data input (POSI0~POSI6) of the motor.

    Maintain the time it is ON at minimum 50msec.

    Input

    /POSI0,

    /POSI1,

    /POSI2,

    /POSI3,

    /POSI4,

    /POSI5,

    /POSI6

    10, 11,

    12, 26,

    27, 28,

    42

    Input POST to 7bit binary code to set the position data input

    signal.

    Input data 10msec before the START signal is ON.

    (minimum input data is '1'.)

    Input

    COM2 44 COMMON terminal(+24V) of START, POSI0~POSI6 signals. Input

  • 8/20/2019 DASD-RH (ENG)

    13/49

    Signal PIN No. Description I/O

    ALM 4

    Alarm signal is on, output is 'OFF' and when it is normal, the

    output is 'ON'.

    Output

    SVRDY 35

    The servo is ready. When the SVON is ON, the driver turns on

    after the normal condition. When the SVON is OFF, the driver

    turns off.

    Output

    UN-SOL 3

    This signal is running the contact point of Unclamp solenoid.

    (This signal is Unclamp after it is ON)

    Output

    COM3 36 COMMON terminal of sequence output signals(ALM,SVRDY,SPARE). Output

    BRAKE+

    BRAKE-

    19

    20

    In case there is an inner brake in the motor, this signal

    controls the power ON/OFF for the brake.

    (The current flow capacity is within 30mA due to the output of

    photo coupler contact point, thus a different relay contact point

    must be used from the actual brake ON/OFF. the circuit so that

    when output contact point is ON, the brake is free, when output

    contact point is OFF, design the circuit diagram to control the

    brake).

    when SVON is ON and this turns on after fixed time of parameter

    14 and then SVRDY is ON after fixed time of parameter 13.

    When SVON is OFF and this turns off after fixed time of parameter

    14.

    Output

    VPF 47

    Position completion signal output.

    After the motor moved, if the pulse error is within the fixed

    value of parameter 18, the signal turns ON.

    Output

    POSO0, POSO1,

    POSO2, POSO3,

    POSO4, POSO5

    POSO6

    14, 15,

    16, 30,

    31, 32,

    46

    As position data output signal, the POST number is sent out in

    7bit binary code.

    While the motor is rotating, the signal will not be on. It will

    be on before the VPF turns on.

    When SVON is OFF, it will output data of the nearest POST number.

    Output

    BAT+

    BAT-

    49

    50

    Battery(3.6V) voltage power (+),

    Battery(3.6V) voltage power (-).

    GND 1 GROUND

    SHIELD 18 Frame ground (it is connected with Shield of cable.)

  • 8/20/2019 DASD-RH (ENG)

    14/49

    2.2 Flow chart of CN1 connector terminal

    2.2.1 Flow chart of CN1 connector terminal of DASD-RH10SPZA, DASD-RH20SPZA

    Spec. : 10236-52A2JL (Housing), 10136-3000VE (Plug) , Manufacturer : 3M

    19 21 23 25 27 29 31 33 35

    2 4 6 8 10 12 14 16 18

    2.2.2 Flow chart of CN1 connector terminal of DASD-RH35SPZB

    Spec. : MR-50RMA (Housing), MR-50LF (Plug) , Manufacturer : HONDA

    18 SHIELD

    17

    16 POSO2

    15 POSO1

    14 POSO0

    13

    12 POSI2/

    11 POSI1/

    10 POSI0/

    9

    8 JOG+/

    7 SVON/

    6 SENSOR/

    5

    4 ALM

    3 UN-SOL

    2

    1 GND

    32 POSO5

    31 POSO4

    30 POSO3

    29

    28 POSI5/

    27 POSI4/

    26 POSI3/

    25

    24 SPARE/

    23 STOP/

    22 JOG-/

    21

    20 BRAKE-

    19 BRAKE+

    50 BAT-

    49 BAT+

    48 COM4

    47 VPF

    46 POSO6

    45

    44 COM2

    43 START/

    42 POSI6/

    41

    40 COM1

    39

    38

    37

    36 COM3

    35 SVRDY

    34

    33

  • 8/20/2019 DASD-RH (ENG)

    15/49

    2.3 Flow chart of CN2 connector terminal

    2.3.1 Flow chart of CN2 connector terminal of DASD-RH10SPZA, DASD-RH20SPZA

    규격 : 10220-52A2JL (Housing), 10120-3000VE (Plug), Manufacturer : 3M

    2.3.2 Flow chart of CN2 connector terminal of DASD-RH35SPZB

    Spec. : MR-20RMA (Housing), MR-20LF (Plug) , Manufacturer : HONDA

    7

    6

    5

    4

    3 +5V

    2 +5V

    1 +5V

    13 GND

    12 GND

    11 GND

    10

    9

    8

    20 SHIELD

    19 BAT-

    18 BAT+

    17

    16

    15 PRX/

    14 PRX

  • 8/20/2019 DASD-RH (ENG)

    16/49

    2.4 Structure of driver Input/Ouput circuit

    Input

    The signals of SENSOR, SVON, JOG+, JOG-, STOP, SPARE, START, POSI0~POSI6 can be used the

    following method.

    (The current is limited to 5mA due to inner resistance.)

    4.4K

    TLP620 or EQ.

    SW

    TR

    5mA

     AC SERVO DRIVE

     

    +24V

    COM1

    COM2

    Output

    The signals of SVRDY, ALM, VPF, POSO0~POS06 are photo coupler output, thus the current is

    limited to 50mA.

    R

    COM3 or COM4

    L

    O

     A

    D

    +24V

    50mA max

     AC SERVO DRIVE

     

  • 8/20/2019 DASD-RH (ENG)

    17/49

    2.5 Connection diagram

    2.5.1 Connection diagram of DASD-RH10SPZA and DASD-RH20SPZA

    M

    B

    PG

    COM1

    SPARE

    5

    STOP

    JOG -

    JOG +

    SVON

    sensor

    COM3

    SVRDY

    ALM

    BRAKE +

    BRAKE -

    COM2

    START

    POSI6

    POSI5

    POSI4

    POSI3

    POSI2

    POSI1

    POSI0

    COM4

    VPF

    POSO5

    POSO4

    POSO3

    POSO2

    POSO1

    POSO0

    GND

    FG

    L1 (R)

    L2 (S)

    L3 (T)

    U

    V

    W

    PE

    A

    B

    C

    D

    E

    F

    K

    L

    M

    N

    P

    R

    H

    G

    J

    F

    I

    B

    D

    E

    G

    HDC24V   RY2

    SHIELD

    3

    4

    23

    20

    22

    21

    11

    10

    30

    29

    5

    13

    9

    8

    7

    6

    28

    27

    26

    25

    24

    15

    16

    14

    36

    35

    34

    33

    32

    31

    17

    1

    2

    19

    6

    7

    8

    9

    10

    16

    15

    14

    17

    18

    19

    1

    11

    2

    12

    3

    13

    20

    RX

    RX

    +5V

    GND

    VBAT-

    VBAT+

    RY1

    RY2

    RY1MC1

    MC1

     M C  1  

     M C  1  

     M C  1  

    NOISE

    FILTER

     M C  C  B 

    AC SERVO MOTOR

    TURRETSERVO DRIVE

    NC

    SEQUENCE OUTPUT

    POSITION INPUT

    POSITION OUTPUT

    SHIELD

    CN1

    CN2

    TB1

    CN3OPERATOR

    12

    POWEROFF

    POWERON

    3 Phase AC 220V

    SEQUENCE INPUT

    DC24V

    DC24V

    DC24V

    DC24V

    DC24V

    NOTE

    1.

      ; Twisted Pair Shielded Cable

    2. Use for Built-In Brake Type Motor

    *1

    *1

    *2

    *2

    Battery

    3 Phase AC 220V

    RY3

    POSO6

    UNSOL

  • 8/20/2019 DASD-RH (ENG)

    18/49

    2.5.2 Connection diagram of DASD-RH35SPZB

  • 8/20/2019 DASD-RH (ENG)

    19/49

    3. Operation

    3.1 Automatic operation

    If the drive operates normally after 500msec) after the POWER is ON , the absolute

    encoder will detect the initial position and output the position data according to the

    initial position. After that output the inposition signal VPF).

    When SVON signal is ON and, SVRDY will turn ON after inner GATE is ON.

    When START signal is ON, the servo will move according to the position data.

     Maintain ON status of START signal to about 50msec~100msec)

    When the operation is started and UNCLAMP SENSOR will turn on after UNCLAMP SOLENOID is ON.

    After UNCLAMP SENSOR is ON, this signal waits for the fixed time of parameter 31.

    When movement is started, VPF inposition signal) will turn OFF .

    After position movement is completed, UNCLAMP SOLENOID signal is OFF and UNCLAMP SENSOR

    input will turn off. After UNCLAMP SENSOR is OFF, this signal waits for the fixed time of

    parameter 32. The current position data will be output and then the inposition signal VPF)

    will be ON .

    From the upper controller, if VPF signal is ON , please turn OFF the SVON signal.

     Move to the next position after SVRDY signal is OFF)

  • 8/20/2019 DASD-RH (ENG)

    20/49

    3.2 Method of machine reset

    When assembling the first motor, please set the zero-point of absolute encoder to the

    status of original machine.

    The Setting method is as follows.

    (The below steps should be done when the external servo signal is OFF.)

    Turn 'ON' the power to the machine power supply.

    Clamp the Turret.

    Fix the POST number of the current position to parameter 8 .

    Press the MODE key and change the operating display to parameter setting mode.

    MODE

    parameter setting mode

    Press UP key and change the number of the first two segments to 08.

    Press SET key and the dot under the first two segments will be blinking.

    SET

    Press UP or DOWN key to adjust the data of last 4 segments on the POST number of the

    current position.

    (example :If the current position number is 10, 10 is set as the initial POST)

  • 8/20/2019 DASD-RH (ENG)

    21/49

    Press SET key and the dot under first two segments will disappear.

    The data will be stored and the dot will appear after a while.

    The display will turn back to the former status. (After turn off the power and then turn on

    it again, the stored data will be displayed)

    ⇨ ⇨

    Set the zero-point at zero-point setting mode in diagnosis mode.

    Press the MODE key and change the operating mode to the diagnosis mode of servo ON/OFF.

    MODE

    Diagnosis display

    Press the DOWN key and change the display to zero-point setting mode.

    Press SET key for 5 seconds and the display will set the parameter related to the

    zero-point automatically and turn back to the zero-point setting mode.

    SET

  • 8/20/2019 DASD-RH (ENG)

    22/49

    SET

    press for 5 secs.

    Turn OFF the power and then ON again. The zero-point setting is completed.

  • 8/20/2019 DASD-RH (ENG)

    23/49

    4. Explanation of each mode display

  • 8/20/2019 DASD-RH (ENG)

    24/49

    4.1

    Status mode

    The function of status mode can check the status of the driver during the operation.

    Command pulse accumulation

    The command pulse accumulation will accumulate the pulse capacity counted by the inner

    position control device to move the target position after the START signal is on and

    it will be displayed and divided into lower and upper word(16bit).

    When SVON signal is off, it will resume to '0'.

    : Lower word display range of command pulse accumulation value

    [00000 ~ 65535]

    : Upper word display range of command pulse accumulation value

    [00000 ~ 65535]

    Current position

    The absolute current position within one turret rotation will be displayed by pulse counts.

    It will be displayed and divided into lower and upper word(16bit).

    Display range [00000 ~ pulse per turret rotation]

    : Lower word of current position

    : Upper word of current position

    Remaining pulse

    It will display the Error capacity between position command and position feedback as

    accumulating the pulse unit. If the pulse exceeds over the set value of the parameter 19,

    the overload alarm of position deviation will appear.

    If the value is minus pulse, the dot under the segment will light up and when SVON signal

    turns OFF, it will resume to '0'.

    : Display range of remaining pulse accumulation value

    [6.0.0.0.0.0. ~ 600000]

    : minus display (-100)

  • 8/20/2019 DASD-RH (ENG)

    25/49

    Current POST number

    This displays the post number of current position. The value will be renewed only when

    the motor stops or when SVON signal is OFF.

    : Display range of current POST number [1 ~ max POST no.]

    Motor rotation speed

    The rotation speed of the motor is displayed by RPM unit. The changes of fast speed cannot

    be seen due to inner filtering process. (To view the speed changes, use the monitor output)

    In case of counterclockwise rotation (clock wise in side of motor), '-' will be displayed.

    : Display range of motor rotation speed [-3000 ~ 3000]

    : minus display (-1000rpm)

    Absolute value of encoder rotation count

    Displays the rotation count of the absolute value of encoder built in the motor.

    (a count per motor rotation) When the count exceeds 8191, it will resume to '0'.

    : Display range of absolute value of encoder rotation speed count

    [0 ~ 8191]

    Absolute value of encoder one rotation

    Displays the pulse count per rotation of the absolute value of encoder built in the motor.

    (2048 count per rotation) When the count exceeds 2047, it will resume to '0'.

    : Display range of absolute value of encoder pulse count per rotation

    [0 ~ 2047]

    Effective load factor

    It is displayed the percent( ) unit counted the effective value of current load.

    (100 is standardization). If the value is the minus, a '-' will be displayed and

    it will resume to '0' when the SVON signal is OFF.

    : Display range of effective load factor [-300.0 ~ 300.0]

    : minus display (-100 )

  • 8/20/2019 DASD-RH (ENG)

    26/49

    Maximum load factor

    It is displayed the percent( ) unit counted the maximum value of current load.

    While the SVON signal is ON, it is always renewed the maximum value and can be resumed to

    '0' as pressing the operator SET key. If the value is the minus, a '-' will be displayed

    and it will resume to '0' when the SVON signal is OFF.

    : Display range of maximum load factor [-300.0 ~ 300.0]

    : minus display (-250 )

    4.2 Diagnosis mode

    This is very convenient mode to verify the external sequence status and the system

    condition.

    It will display on the OP panel LED display of driver. The contents and it's use is as

    follows.

    Servo ready status

    : SVON signal is OFF and then displays the free status of motor.

    : SVON signal is ON and displays the available running status.

    Sequence I/O signal

    Display ON/OFF status of external input signal in 7 segments.

    < external input signal >

    SEQUENCEINPUT

    SENSOR

    SVON

    JOG +

    JOG -STOP

  • 8/20/2019 DASD-RH (ENG)

    27/49

    Display ON/OFF status of external output signal in 7 segments.

    < external output signal >

    The I/O display of 7 segment LED display panel will be displayed when the LED is on and

    this will verify ON and OFF. (If it is ON, the LED will be on, if it is OFF, the LED

    will be off.)

    Position data I/O signal

    Display the ON/OFF status of position data input signal in 7 segments.

    < PLC input signal >

    POSITION

    INPUT

    START

    POSI6

    POSI5

    POSI4

    POSI0

    POSI1

    POSI2

    POSI3

    SEQUENCEOUTPUT

    BAT_L

    ALM

    BRAKE

    SVRDY

  • 8/20/2019 DASD-RH (ENG)

    28/49

    Display the ON/OFF status of the position data output signal in 7 segments.

    < PLC output signal >

    The I/O display of 7 segment LED display panel will be displayed when the LED is on and

    this will verify ON and OFF. (If it is ON, the LED will be on, if it is OFF, the LED

    will be off.)

    Passive Unclamp output

    It outputs Unclamp signal by the hand.

    ; set the output data by the SET key.

    UCON signal OFF UCON signal ON

    ; Resume to initial display mode

    VPF

    SOL-OUT

    POSO5

    POSO0

    POSO1

    POSO2

    POSO3POSO4

    POSITIONOUPUT

    SET

    SET

    SET

    SET

  • 8/20/2019 DASD-RH (ENG)

    29/49

    Jog operation

    The driver operates jog operation by itself regardless of external signals.

    When setting the zero-point, use this to move the right position of fixed POST.

    The driver will rotate according to the fixed speed of parameter 27 while pressing the UP

    or DOWN key.

    If press the SET key and the SVON signal will turn ON automatically, and it will change to

    Jog operation mode.

    ; Jog operation mode

    CCW rotation CW rotation

    ; Resumes to initial display mode

    Parameter initialization

    Saves in Memory as resetting the parameters by fixing value when outgoing.

    The stored value when sending out will be reset if pressing the SET key, but The parameters

    related to the zero-point setting will remain the value as it is.

    Press SET key and it will carry out the Parameter initialization.

    SET

    SET

    SET

  • 8/20/2019 DASD-RH (ENG)

    30/49

    Initialization of position compensation value

    Saves in Memory as initializing the position compensation value per POST to '0'.

    Press the SET key and it will start the initialization.

    Press the SET key and it will initialize the position compensation value.

    4.3 Parameter setting mode

    The parameter must be set according to the system composition and operation contents

    before the motor operation. the setting method is as follows.

    Set the operator display to parameter setting mode by pressing the MODE key.

    Parameter setting mode

    Set the first two segments for intended setting number by pressing the UP key.

    (example : set 08)

    The dot will appear under the first two segments when Press the SET key.

    Set the latter 4 segments for intended setting number by pressing the UP or DOWN key.

    (example : in case of fixing the data to 10)

    SET

    SET

  • 8/20/2019 DASD-RH (ENG)

    31/49

    When Press the SET key in current status, the dots under first two segments from

    parameter 00 to 09 will appear, and the data will be saved. After a while, the dot

    will appear and it will resume to the initial value before the set up.

    When press the SET key, the dot under the first two segments from parameter 10 to 33

    will appear, and it will display the set value.

    When the zero-point setting, parameters from 34 to 45 is set automatically.

    The parameter is for maker management. Please do not change it.

    (If you change this parameter, Driver will not operate properly)

    SET

    SET

  • 8/20/2019 DASD-RH (ENG)

    32/49

    4.4 Parameter list

    Note. Adjusted parameter operated as follows.

    N0. Abbr. Name Range Default Unit Division

    00 MPC

    motor power capacity

    0 0 A, B

    01 MRD

    motor running direction

    0 ~ 1 1 A, B

    02 -

    reserve parameter

    0 0 A, B

    03 JFS

    fixed direction, jog function selection

    0 ~ 1 0 A, B

    04 -

    reserve parameter

    0 0 A, B

    05 MPN

    maximum POST number

    2 ~ 127 12 POST A, B

    06 GR1

    gear ratio - motor side

    1 ~ 9999 33

    Rev

    A, B

    07 GR2

    gear ratio - machine side

    1 ~ 9999 12 POST A, B

    08 HSP

    POST number of home

    1 ~ 127 1 A, B

    09

    reserve parameter

    0 0 A, B

    10 PKP

    position loop proportional gain

    0 ~ 2048 256 B, C

    11 VKP

    speed loop proportional gain

    0 ~ 2048 250 B, C

    12 VKI

    speed loop integral gain

    0 ~ 2048 1 B, C

    13 SROT

    servo ready on delay time

    0 ~ 40 0 50 msec B, C

    14 BFT

    brake off control delay time

    0 ~ 40 0 50 msec B, C

    15 BOT

    brake on delay time

    0 ~ 40 0 50 msec B, C

    16 VTO

    monitor offset voltage

    -12 ~ 12 0 10/128 V B, C

    17 VTM

    monitor selection

    0 ~ 3 0 B, C

    18 INP

    positioning complete range

    1 ~ 9999 100 PULSE B

    19 RPA

    remaining pulse allowance

    1 ~ 6000 6000 100 PULSE B

    20 FFG

    position loop feed-forward gain

    0 ~ 100 0 B

    21 FTC

    feed-forward filter time constant

    0 ~ 100 0 4 msec B

    22 TLP1

    positive torque limit 1

    0 ~ 300 250 B

    23 TLN1

    negative torque limit 1

    0 ~ 300 250 B

    24 TLP2

    positive torque limit 2

    0 ~ 300 50 B

    25 TLN2

    negative torque limit 2

    0 ~ 300 50 B

    26 VLS

    speed limit

    0 ~ 3000 1850 rpm B

    27 JSP

    jog speed at set home

    1 ~ 1000 100 rpm B

    28 VEL

    operation speed

    10 ~ 3000 1800 rpm B

    29 ATC

    acceleration time

    0 ~ 500 50 msec B

    30 DTC

    deceleration time

    0 ~ 500 80 msec B

    31 UDT

    speed monitor output voltage

    0 ~ 1000 100 msec B

    32 CDT

    torque monitor output voltage

    0 ~ 1000 100 msec B

    33 ISD

    initial status display

    0 ~ 10 6 B

    34 AOL

    encoder coordinates compensation lower)

    D

    35 AOM

    encoder coordinates compensation upper)

    D

    36 HOL

    set value of machine zero-point lower)

    D

    37 HOM

    set value of machine zero-point upper)

    D

    38 IKP

    current loop proportional gain

    D

    39 IKI

    current loop integral gain

    D

    40 EPN

    encoder pulse per one rotation

    D

    41 FPL

    feedback pulse lower)

    D

    42 FPM

    feedback pulse upper)

    D

    43 ACR

    acceleration rate of remaining value

    D

    44 REM

    accel rate compensation of remaining value

    D

    45 -

    reserve parameter

    D

    Section Contents

    A

    Power is OFF after parameter setting, and the setting value will be valid if it is put into again.

    B

    Available to set on SVON is OFF. After the setting, it will be vaild right away.

    C

    Valid to set on SVON status, but temporary save. It has to be reset on SVON is OFF.

    D

    When machine zero-point setting, User can not set it as automatic setting or for a maker management.

  • 8/20/2019 DASD-RH (ENG)

    33/49

    4.5 Detailed explanation of parameter setting mode for user

    [1] No.0 : Motor power capacity

    This is the parameter that enables to select the applied motor capacity.

    The capacity is selected according to each ROM now.

    0 : 1.0KW / 2.0KW / 3.5 KW

    [2] No.1 : Motor rotation direction

    This sets the motor rotation direction. Please set it according to the structure of

    the equipment.

    0 : In case that The motor rotation direction accords with the rotation direction of

    equipment.

    1 : In case that The motor rotation direction discords with the rotation direction of

    equipment.

    [3] No.2 : Spare parameter

    [4] No.3 : Direction fixing and selection of JOG function

    Defines the function of JOG+(no.20) and JOG-(no.23) signal of CN1 connector.

    0 : Defines the signal of direction fixing.

    This is applicable if the parameter 1 is set to '0'.

    If the parameter is set to '1', it rotates to the opposite.

    1 : Defines JOG operation signal

    JOG+ JOG- Rotation direction

    OFF OFF Rotates to distinguish the shortest distance.

    OFF ON The motor always rotates to clock wise.

    ON OFF The motor always rotates to counter-clock wise.

    ON ON The motor always rotates to counter-clock wise.

    JOG+ JOG- Contents

    OFF OFF Only operates by position data input.

    OFF ON Do Step JOG operation toward decreasing of POST number

    ON OFF Do Step JOG operation toward increasing of POST number

    ON ON Can not be defined.

  • 8/20/2019 DASD-RH (ENG)

    34/49

    This is applicable if the parameter 1 is set to '0'.

    If the parameter is set to '1', it rotates to the opposite.

    Position data input is ignored if JOG+ and JOG- signal is ON.

    For more detailed explanation, refer to 'JOG operation' section.

    [5] No.4 : Spare parameter

    [6] No.5 : Maximum POST number

    This sets the maximum POST number. The position data input exceeding the set data

    is ignored.

    Setting range : 2 ~ 127, Outgoing value : 12

    [7] No.6 : Gear ratio of motor side

    This sets the rotation count when it moves as the POST number set at parameter 7.

    Setting range : 1 ~ 9999, Outgoing value : 33

    [8] No.7 : Gear ratio of machine side

    This sets the POST number when the motor rotates as the set value at parameter 6.

    Setting range : 1 ~ 9999, Outgoing value : 12

    [9] No.8 : Origin POST number

    Inputs the POST number that sets as the origin when setting the machine origin(zero-point).

    Setting range : 1 ~ 127, Outgoing value : 1

    [10] No.9 : Spare parameter

    [11] No.10 : Position loop proportionality gain

    The position loop proportionality gain is the parameter that determines the response of

    position control loop. If the value increases, the mechanical response gets better.

    Example)

    1. The machine is 10 POST turret. When the motor makes 30.75 rotations and in case the

    deceleration ratio is fixed so that the turret is made 1 rotation, Turret 1 rotation

    fits the 10 POST movement, thus the value will be set as follows.

    [5] Maximum POST data : 10

    [6] Gear ratio of motor side : 3075

    [7] Gear ratio of machine side : 1000

  • 8/20/2019 DASD-RH (ENG)

    35/49

    However, the added impact for machine increases when the motor starts or stops.

    If the value decreases, the mechanical response will be late, and the position

    error may increase due to the remaining pulse. This is also related to the speed

    loop proportionality gain.

    Setting range : 0 ~ 2048, Outgoing value : 256

    [12] No.11 : Speed loop proportionality gain

    The speed loop proportionality gain is the parameter that determines the response of

    speed control loop. On the external characteristics, it determines the degree of rigidity.

    If the value of the proportionality gain increases, the rigidity becomes strong.

    Thus, it is good as large as possible, but if it is larger than any degree, it may cause

    the oscillation and hunting. Accordingly, the value will be set as large as possible under

    stable condition.

    Setting range : 0 ~ 2048, Outgoing value : 250

    [13] No.12 : Speed loop integral gain

    The speed loop integral gain is the compensatory factor that reduces the normal state

    error, and increases the rigidity. If the value of integral gain is increased, the rigidity

    will get larger, but if it is increased too much, it may cause the oscillation, and the

    system may become unstable.

    Setting range : 0 ~ 2048, Outgoing value : 1

    [14] No.13 : Brake off delay time

    In case of the brake motor, this is the delay time until SVRDY signal is ON after the brake

    signal is ON. Please set the value higher than the time releasing the actual brake.

    The unit is 50msec.

    Setting range : 0 ~ 40 [x 50msec], Outgoing value : 0

    [15] No.14 : Brake off control delay time

    In case the brake motor, this is the delay time until BRAKE signal is ON after SVON signal

    is input. After this delay, the brake signal turns OFF.

    Setting range : 0 ~ 40 [x 50msec], Outgoing value : 0

    [16] No.15 : Brake ON delay time

    In case the brake motor, this is the delay time until the gate of the power device is OFF

    after the brake signal turns OFF and the SVON signal turns OFF.

    (Of course SVRDY signal is off as the same time)

  • 8/20/2019 DASD-RH (ENG)

    36/49

    Please set the value higher than the time operating the actual brake.

    Setting range : 0 ~ 40 [x 50msec], Outcome value : 0

    [17] No.16 : Spare parameter

    [18] No.17 : Spare parameter

    [19] No.18 : Positioning decision completion range

    When position control, it is set the positioning decision completion range.

    If the error between the target position and the current position is within the set range,

    the VPF terminal (Number 16 of CN1 connector) will turn ON.

    Setting range : 1 ~ 9999 [pulse], Outgoing value : 100

    [20] No.19 : Remaining pulse allowance

    When position control, The difference of position command and position feedback per each

    position control loop is accumulated. lf this difference value exceeds the set value, the

    overload alarm of position deviation will appear.

    Setting range : 1 ~ 6000 [x 100 pulse], Outgoing value : 6000

    [21] No.20 : Position loop feed-forward gain

    This can be enable to have a response characteristic that shortens the position determine

    time by using the feed-forward control. However, if the value is set too high, it may cause

    the oscillation in the machine.

    Setting range : 1 ~ 100 [ ], Outgoing value : 0

    [22] No.21 : Feed-forward filter time constant

    This sets the time constant when the first delay filter is put in the feed-forward position

    command.

    Setting range : 0 ~ 500 [x 4msec], Outgoing value : 0

    [23] No.22 : Positive torque limit 1

    This limits the torque output of positive (+) polarity in the areas except the positioning

    decision completion range. If the value is set at 0 , the positive torque will not occur.

    If the value is set too low, the hunting may occur when the motor starts or stops.

    Setting range : 0 ~ 300 [ ], Outgoing value : 250

  • 8/20/2019 DASD-RH (ENG)

    37/49

    [24] No.23 : Negative torque limit 1

    This limits the torque output of negative (-) polarity in the areas except the positioning

    decision completion range. If the value is set at 0 , the negative torque will not occur.

    If the value is set too low, the hunting may occur when the motor starts or stops.

    Setting range : 0 ~ 300 [ ], Outgoing value : 250

    [25] No.24 : Positive torque limit 2

    This limits the torque output of the positive (+) polarity in the areas within the

    positioning decision completion range. After the position decision completes, if the low

    value is set on the use to provide the invariable load constantly under SVON signal of

    driver is ON, it can be avoided from the overstrain of the equipment or motor.

    Setting range : 0 ~ 300 [ ], Outgoing value : 50

    [26] No.25 : Negative torque limit 2

    This limits the torque output of the negative (-) polarity in the areas within the

    positioning decision completion range. After the position decision completes, if the low

    value is set on the use to provide the invariable load constantly under SVON signal of

    driver is ON, it can be avoided from the overstrain of the equipment or motor.

    Setting range : 0 ~ 300 [ ], Outgoing value : 50

    [27] No.26 : Speed limit

    This limits the maximum operation speed.

    Even when overshooting and such cases occur during the accelerating, the speed is limited

    within the set value. Please set the value more than at least 50rpm as compared with

    parameter 28 (operating speed).

    Setting range : 0 ~ 3000 [rpm] Outgoing value : 1850

    [28] No.27 : Origin (Home) set jog speed

    This sets the speed of internal jog operation in order to move equipments of turret,

    magazine and so on to the right position of when the origin (zero-point) set.

    This is discussed separately from the step jog speed.

    Setting range : 1 ~ 1000 [rpm], Outgoing value : 100

    [29] No.28 : Operation speed

    This is the motor speed when automatic operation or when step jog operation.

    Setting range : 10 ~ 3000 [rpm], Outgoing value : 1800

  • 8/20/2019 DASD-RH (ENG)

    38/49

    [30] No.29 : Acceleration time

    This sets the time that takes from zero movement (motor stops) to the fixed speed at

    parameter 28. If the value is set too low, the speed overshooting may occur when

    accelerating.

    Setting range : 0 ~ 500 [msec], Outgoing value : 50

    [31] No.30 : Deceleration time

    This sets the time that takes from the fixed speed at parameter 28 to zero movement

    (motor stops). If the value is set too low, the position decision time may be delayed

    due to the hunting when the motor stops.

    Setting range : 0 ~ 500 [msec], Outgoing value : 80

    [32] No.31 : UNCLAMP delay time

    Operate UNCLAMP for the transfer when inputs the start signal after SVON is ON and after

    NCLAMP SENSOR signal is ON, this is the delay time before the actual transfer.

    Setting range : 0 ~ 1000 [msec], Outgoing value : 0

    [33] No.32 : CLAMP delay time

    Operate CLAMP after the transfer and after turning off UNCLAMP SENSOR, this is the delay

    time before the completion signal is output.

    Setting range : 0 ~ 1000 [4msec], Outgoing value : 0

    [34] No.33 : Initial status display selection

    Please select the initial status display after the main power switch ON.

    Outgoing value : 06 (Motor rotation speed)

    [35] No.34 ~ No.45 : Automatic setting and parameter managed for the maker management

    (manufacturer)

    When setting the machine origin(zero-point), the parameter will be set automatically or

    Set

    value

    Initial display content

    Set

    value

    Initial display content

    00 Accumulated value of command pulse (lower word) 06 Motor rotation speed

    01 Accumulated value of command pulse (upper word) 07 Absolute encoder rotation

    02 Current position (lower word) 08 Absolute encoder-one rotation

    03 Current position (upper word) 09 Effective load ratio

    04 Accumulated value of remaining pulse 10 Maximum load ratio

    05 Current POST number

  • 8/20/2019 DASD-RH (ENG)

    39/49

    it is for manufacturer's management use. Please do not set it according to then user's

    purpose. It may not be operated normally if setting for user's purpose only.

    4.6 Alarm record mode

    It stores the recent alarm records till 9 rotations.

    Press UP or DOWN key for checking the previous alarm records.

    All records of alarm will be cleared by pressing SET key at this mode.

    : alarm record mode

    : 1 time alarm display

    (ex. in case of overload of 1 time alarm)

    : 2 times alarm display

    : 9 times alarm display

    5. Maintenance and inspection

    5.1 Maintenance & Inspection

    This chapter explains the servo motor, the maintenance and inspect method of driver,

    the trouble shooting and countermeasure.

    5.1.1 Notice

    When checking motor voltage : The wave of pulse shape is displayed as the voltage

    applied from the servo driver to the motor controls PWM. Please use the exact voltmeter

    for correct measurement because measured value may occur big differences according to

    the types of meter.

    When checking motor current : Please use to connect the ammeter to the motor directly

    because the pulse wave is smoothed as sine wave by the motor reactance.

  • 8/20/2019 DASD-RH (ENG)

    40/49

    The other devices : please use not to contact the ground when using oscilloscope,

    digital volt meter. Please use the input current less than 1 mA as well.

    5.1.2 Checkpoint

    Inspection of servo motor

    (note1) check between one of the servo motor power line U,V,W and FG

    Inspection of servo driver

    Please refer to the below inspection of servo driver. Daily inspection is not necessary,

    but check it over 1/year.

    Inspection item Inspection period Inspection and handling Remark

    Vibration, noise Every month Sense of touch, hearing

    Not bigger than normal

    condition

    External

    appearance

    According to

    demage or

    contamination

    Cleanup with cloth or air -

    Insulating

    resistance

    measurement

    Minimum 1/year

    Disconnect with driver,

    measure it by 500V mega.

    if over 10M , this is a

    normal.(note1)

    If under 10M , call to our

    service depart.

    Change oil seal Minimu 1/5000hr

    Detach from the machine, and

    replace it.

    In case the motor with oil

    seal

    General

    inspection

    Minium 1/20000hr or

    1/5year

    Call to service dept in

    company

    Do not dismantle and clean

    servo motor.

    Check part Check time Inspection method Handling when trouble

    Clean main board and

    circuit board

    Minimum 1/year Remove dust, oil and etc Clean it with air or cloth

    Loose screw Minimum 1/year

    Tighten connection terminal,

    connector screw

    Tighten

    Trouble of part

    defects on main

    board and circuit

    board

    Minimum 1/year

    Check changed color, damage and

    disconnection by overheat

    call to company

    When you check, it is remained the charged voltage in inner smoothing

    condense, so do the inspection after power off and wait about 5 minute

    because it may be dangerous.

  • 8/20/2019 DASD-RH (ENG)

    41/49

    5.1.3 Period of part replace

    The parts age because of mechanical friction or as time passes, therefore it is necessary

    to check the regular inspection and replacement not only preventing the falling-off in

    quality and trouble but also keeping the prevention conservation.

    Smoothing condenser : the characteristics age due to the affects of ripple current.

    Sometimes the life time of condenser is affected by the surrounding temperature and use

    condition, but in case of continual operation under the condition of normal environment,

    10 years are standard. The inspection period is minimum 1 per year (less than 1 per year

    when left short life time) because the condenser aging is fast in a limited period

    sometimes.

    Check point as external appearance

    1. Case condition : the side and bottom of case are expanded

    2. Top plate condition : prominent expansion, extreme crack, break

    3. Condition of explosion sides : sides expansion, already operation.

    4. Life time is the time that periodically the standard capacity of condenser is under 85

    about the appearance, external crack, break, changed color, leak.

    Relay kind : Contact faultiness may occur due to the contact abrasion by the switching

    current, so the standard life time is 100,000 times( accumulated switching number) because

    the relay is affected by the power capacity .

    Motor bearing : replaces it on the basis of the standard replace time is 2~30,000 hrs

    under rated speed, and load. The motor bearing is affected by the operating conditions,

    so replace the motor bearing when abnormal noise or vibration is occurred.

    Battery : replaces it 1 per 5 years under rated speed and load.

    [standard replacement period of parts]

    Part name Standard replacement period Replacement method

    Smoothing condenser 10 year Replacement decide after check)

    Relay kind

    Switching ON/OFF) No is

    100,000

    Decide after check

    Fuse 10 year Replacement

    Electrolytic condenser 10 year Decide after check

    Cooling fan 5 year Replacement over 3 KW )

    Motor bearing - Decide after change

    Motor oil seal 5,000 hrs Replacement

    Battery 5 year Replacement

  • 8/20/2019 DASD-RH (ENG)

    42/49

    5.2 Trouble diagnosis and countermeasure

    Alarm signal example) ALP-UU is displayed on the window of loader display when trouble

    occurs during the operation. In this case, please take the following steps.

    If the trouble is not remedied by these steps, please call to service dept.

    5.2.1 Servo motor

    [Trouble reason , check method, handling]

    Phenomenon Reason Check method Handling

    Not

    operated

    Parameter setting

    error

    Check parameter like motor, capacity,

    encoder pulse value, control mode

    Parameter reset

    (refer to chapter 4)

    Over load Check rotation condition Re-adjust machine

    Motor defective Check motor red terminal by tester

    Replace motor in case of

    normal voltage

    Screw loosened Check connect part by drive Re-tighten loosed screw

    External wrong wirng,

    disconnected cable

    Check motor & encoder wiring Re-wire, and change cable.

    Encoder defective Check output wave Change encoder.

    unstable

    motor

    rotation

    defective connection

    Check connection of motor

    lead terminal

    Repair defective part.

    Low input voltage Check driver input voltage Change power supply.

    Over load Check machine condition.

    Remove residue from rotator,

    and lubricating oil supply.

    Motor

    overheat

    Ambient temp is high

    Check motor ambient temp of setting

    point (should be lower than40 )

    Change heat sink structure.

    Motor surface

    contamination

    Check adhesion of residue on

    motor surface.

    Clean motor surface.

    Over load

    Check load rate of driver.

    Check ac/deceleration cycle.

    Decrease load, increase

    ac/deceration time.

    Magnet magnetism

    decrease

    Check electromotive voltage and

    wave type of voltage.

    Replace motor.

    Abnormal

    noise

    Coupling defective

    Check screw tightness of the coupling

    & concentricity of joints.

    Re-adjust coupling.

    Bearing defective Check vibration and abnormal noise Call to company.

    Parameter setting

    error (motor/encoder

    pulse value, gain)

    Check parameter related to gain.

    Refer to parameter setting

    method of chapter4.

  • 8/20/2019 DASD-RH (ENG)

    43/49

    5.2.2 Servo drive

    When the alarm occurs, error signal out contact(ALARM) is turned off, and motor is stopped

    automatically.

    [Alarm cord and inspection]

    Main

    LED

    OP panel

    LED display

    Alarm type Corrective method

    Lack voltage : occurs when voltage of inner

    DC link is under standard value.

    - check the input power is low.

    - check the short of motor power cable .

    Over voltage : occurs when voltage of inner

    DC link is over standard value.

    - check the input power is high.

    - check the operation frequency is over

    the standard value.

    - check regenerative resistor is damaged

    Main circuit error : occurs in case of error

    of inner IPM device.

    - check the temp of heat sink is over 100

    degrees.

    - check the operation frequency is over

    the standard value.

    Encoder I/F module error : occurs when

    assembly of inner encoder I/F module is not

    correct.

    - check the assembly of encoder I/F module

    is correct.

    Encoder signal error : A,B,Z signal error

    among signal of encoder

    - check the encoder cable is pulled out or

    signal line is disconnected.

    Over speed : occurs when the motor speed

    exceeds the maximum rotation count.

    - check the encoder cable is pulled out or

    wrong assembly.

    Over load : occurs when the over load

    status continues over the standard time.

    - check the motor power cable is

    disconnected.

    - check if the parameter is set correctly.

    CPU error : occurs when the CPU malfunctions

    or inner board is defective

    - check the parameter set is correct.

    Parameter error : occurs when the save value

    of parameter is not within the setting

    range.

    - check the parameter set is correct.

    Excessive position deviation : occurs a case

    that the remaining pulse exceeds the fixed

    value of parameter 19 when positioning

    control.

    - check the value of parameter 18 is set

    too low.

    Unclamp solenoid error: occurs when no

    operation of clamp solenoid.

    - check Unclamp and clamp.

    Encoder battery error : occurs when the

    backup battery of inner encoder

    is discharged or pulled out.

    - change the battery.

  • 8/20/2019 DASD-RH (ENG)

    44/49

    NO. Inspection item Inspection result Handling

    1 Check the power voltage

    Under AC 150V Re-check the power

    Normal AC 220V

    Do investigation and handling of

    investigation article 2

    2

    Occurs alarm intermittently

    when accelerating

    Occurs alarm

    when accelerating

    Re-check power capacity.

    Occurs alarm

    unconditionally

    Change the driver unit or PAB

    NO. Inspection item Inspection result Handling

    1

    Secure regular power

    capacity

    Power capacity lack Power capacity increase.

    No problem.

    Do investigation and handling of

    investigation article 2.

    2

    Check the voltage is over

    170V by tester

    when decelerating motor.

    Under 170V . Power capacity increase.

    Over 170V .

    Do investigation and handling of

    investigation article 3.

    3

    Check the voltage of line

    R-S, S-T, T-R by tester

    Voltage difference between

    lines is over 10V.

    Balance improvement on the power

    No problem.

    Do investigation and handling of

    investigation article 4.

    4

    Check the wiring, setting

    circumstance

    1) Is the ground right?

    2) Is a machine that makes

    a noise beside the unit?

    1) Ground instability Right set of ground.

    2) Easy to occur the alarm

    when some special machine is

    operate.

    Counter-plan execution for the

    machine that makes a noise

    No problem. Change the driver unit or PAB

    5.2.3 detailed explaination of alarm code

    (1) ALP - UU : low voltage alarm

    (2) ALP - OU : over voltage

    ; DC bus voltage exceeds over 400V.

  • 8/20/2019 DASD-RH (ENG)

    45/49

    NO. Inspection item Inspection result Handling

    1 Inspect the occur area.

    Occurs Servo is OFF. Replace the driver unit or PAB.

    Occurs after servo ON .

    Do investigation and handling of

    investigation article 2.

    2

    Check the setting value of

    oparameter NO.23, NO.24.

    No set of normal value Decrease load capacity.

    Set of normal value.

    Do investigation and handling of

    investigation article 3.

    3

    Check the amount of load

    when transferring

    Load capacity is over 100 . Decrease load capacity.

    Load capacity is under 100 .

    Do investigation and handling of

    investigation article 4.

    4

    Check wiring between drive

    unit and motor U, V, M.

    1)Check the looseness of

    screw in terminal

    2)Check the shorted wire

    3)Check the grounded phase,

    and open 2 side of cable

    when checking 2),3).

    1) loosened. Tighten it correctly.

    2) cut Change the cable.

    3) grounded. Change the cable.

    No problem. Do investigation and handling of

    investigation article 5.

    5

    Check the motor insulation.

    Measure the line and

    earth of motor by Mega

    Resistance value is under 1MΩ Replace the motor.

    Resistance value is over 1M .

    Do investigation and handling of

    investigation article 6.

    6 Check the power voltage.

    Sometimes voltage is under 170V

    when ac/decelerating.

    Re-check the power voltage.

    Always over 171V .

    Do investigation and handling of

    investigation article 7.

    7

    Check the wiring, setting

    circumstance

    1)Is the ground right?

    2) Is a machine that

    makes a noise beside the

    unit?

    1) Ground instability correct ground set.

    2) Easy to occur the alarm

    when some special machine

    is operate.

    Counter-plan execution for the

    machine that makes a noise

    No problem. Change the driver unit or PAB.

    (3) ALP - OH : power module trouble

    ; In case the trouble occurs in power module used for driver unit .

    1) operated the over current protect.

    2) downed the base power voltage.

    3) overheated.

  • 8/20/2019 DASD-RH (ENG)

    46/49

    NO. Inspection item Result Handling

    1

    Shake it by hand and check the

    detector connector(CN2) is

    connected or disconnected.

    Loosened. Set it correctly.

    Normal.

    Do investigation and handling of

    investigation article 2.

    2

    Power off, and check the detector

    cable connection.

    Connection faultiness Change the detector cable.

    Normal connection. Change the motor.

    NO. Inspection item Result Handling

    1

    Shake it by hand and check

    the cnnector(CN2) of speed

    detector is connected or

    disconnected.

    Loosened.

    Set it correctly.

    Change the detector cable.

    Normal.

    Do investigation and handling

    of investigation article 2.

    2

    Check the wiring, setting

    circumstance

    1) Is the ground right?

    2) Is a machine that makes a

    noise beside the unit?

    3) Is the shield of speed/

    positioning detector

    cable correctly?

    1) Ground instability Correct ground set.

    2) Easy to occur the alarm

    when some special machine is

    operate.

    Counter-plan execution for the

    machine that makes a noise

    3) Shield is not set correctly Correct Shield set.

    No problem. Change the driver unit or PAB.

    (4) ALP - CA : encoder signal trouble

    (5) ALP - OS : over speed

  • 8/20/2019 DASD-RH (ENG)

    47/49

    NO. Inspection item Result Handling

    1

    Check the setting value of

    parameter NO.23, NO.24.

    No set of normal value Decrease load capacity.

    Set of normal value.

    Do investigation and handling

    of investigation article 2.

    2

    Check wiring between drive unit

    and motor U, V, M.

    1)Check the looseness of screw

    in terminal

    2)Check the shorted wire

    3)Check the grounded phase, and

    open 2 side of cable when

    checking 2),3).

    1) Loosened. Tighten it correctly.

    2) cut Change the cable.

    3) grounded. Change the cable.

    No problem.

    Do investigation and handling

    of investigation article 3.

    3

    Shake it by hand and check the

    cnnector(CN2) of speed detector

    is connected or disconnected.

    Loosened.

    Set it correctly.

    Normal.

    Do investigation and handling

    of investigation article 4.

    4

    Power off, and check the detector

    cable connection by tester.

    Connection faultiness or

    disconnection

    Change the detector cable.

    Connect it correctly

    Normal.

    Do investigation and handling

    of investigation article 5.

    5 Check the motor load capacity.

    Load capacity exceeds motor's

    rating.

    Make load capacity within

    motor's rating.

    No problem

    Do investigation and handling

    of investigation article 6.

    6 check the rotation of motor.

    Motor is closed. Re-chech the machine.

    No problem.

    Change the driver unit or

    PAB.

    (6) ALP - OL : over load

    ; due to the current flowed to the motor is the value exceeded the overload detection

    level, a case that time continues over the overload detection time

    [Overload characteristic curve of servo motor]

  • 8/20/2019 DASD-RH (ENG)

    48/49

    NO. Inspection item Result Handling

    1 Inspect the re-occur.

    Always occurs when power on. Change the driver unit or PAB.

    Occurs sometimes.

    Do investigation and handling

    of investigation article 2.

    2

    Check the wiring, setting

    circumstance

    1) Is the ground right?

    2) Is a machine that makes

    a noise beside the unit?

    1) Ground instability Correct ground set.

    2) Easy to occur the alarm

    when some special machine

    is operate.

    Counter-plan execution for the

    machine that makes a noise

    No problem. Change the driver unit or PAB

    NO. Inspection item Result Handling

    1 Inspect the re-occur.

    Always occurs when power on. Change the driver unit or PAB.

    Occurs sometimes.

    Do investigation and handling

    of investigation article 2.

    2

    check the wiring, setting

    circumstance

    1) Is the ground right?

    2) Is a machine that makes

    a noise beside the unit?

    1) Ground instability Correct ground set.

    2) Easy to occur the alarm

    when some special machine is

    operate.

    Counter-plan execution for the

    machine that makes a noise

    No problem. Change the driver unit or PAB

    (7) ALP - SE : CPU trouble

    (8) ALP - PE : parameter trouble

  • 8/20/2019 DASD-RH (ENG)

    49/49

    NO. Inspection item Result Handling

    1

    Check wiring between driver

    unit and motor U, V, M.

    Abnormal connection. Correct line wiring.

    Normal connection.

    Do investigation and handling of

    investigation article 2.

    2

    Check the setting value of

    parameter(NO.18)

    Normal value is not set. Correct set

    Abnormal value is set.

    Do investigation and handling of

    investigation article 3.

    3

    Check load capacity when

    transferring.

    Load capacity is over 100 . Decrease the load capacity.

    Load capacity is under 99 .

    Do investigation and handling of

    investigation article 4.

    4

    Shake it by hand and check

    the cnnector(CN2) of speed

    detector is connected or

    disconnected.

    Disconnected. Correct set

    Connected.

    Do investigation and handling of

    investigation article 5.

    5

    Power off, and check the speed

    detector cable connection by

    tester.

    Connection faultiness or

    disconnection

    Change the detector cable.

    Make the correct connection.

    Normal connection. Change the driver unit.

    NO. Inspection item Result Handling

    1

    Inspect the occurrence

    area.

    Always occurs

    when transferring.

    Check the clamp sensor.

    check the solenoid.

    Occurs sometimes.

    Do investigation and handling of

    investigation article 2.

    2

    Check the setting value of

    parameter(NO.31,NO.32)

    Normal value is set

    Do investigation and handling of

    investigation article 3.

    Normal value is not set.

    Adjust the value of parameter

    (NO.31, NO.32).

    3

    Check the wiring

    of solenoid and sensor.

    Shorted or grounded. Change the cable.

    No problem.

    Change the driver unit or PAB.

    change the sensor.

    NO. Inspection item Result Handling

    (9) ALP - rP : speed gap exaggeration

    ; in case the speed order and current speed gab exceeds the setting value at parameter

    (NO.18)

    (10) ALP - UC : solenoid trouble

    (11) ALP - En : battery trouble