Page 1: DMC-A4A - TAKEX€¦ · ① ⑧ ③ ④ ⑤ ⑦ ⑥ ⑨ ② CAT.No.ABJ-HS-0052(2015-04月発行)3NZ No. Name POWER Functions/Operations Turns on when the power is supplied. Turns
Page 2: DMC-A4A - TAKEX€¦ · ① ⑧ ③ ④ ⑤ ⑦ ⑥ ⑨ ② CAT.No.ABJ-HS-0052(2015-04月発行)3NZ No. Name POWER Functions/Operations Turns on when the power is supplied. Turns

■ ■

①⑧

⑥⑨②

CAT.No.ABJ-HS-0052(2015-04月発行)3NZ

No. NamePOWER

Functions/OperationsTurns on when the power is supplied.Turns on when the output is ON.Selects between RUN and SET modes.Selects setting mode and menu.Changes the selected menu items.Changes the selected menu items.Sets the threshold.Indicates the setting menu or output No.Indicates the threshold (SET mode)or the input level (RUN mode).

Power indictorOUT1~OUT4 Operation indicatorRUN/SET Mode switchSELECT Select button▼ Scroll down button▲ Scroll up buttonTEACH Teaching buttonFUNC. Display (7 segments red)

MEASURE Display (7 segments green)

①②③④⑤⑥⑦⑧

PANEL DISCRIPTION

・Input/Output circuit

Internalcircuit

0V0V

0V

OUT(0~5V/0~10V)

+24V

V IN10kΩ

Voltage output (0-5V/0-10V) sensor

+24V +24V

DMC-A4A

Power supply DC24V+

-

COM

OUT1

OUT2

OUT3

Load

Load

Load

Power for loadDC30V 50mA or less for one circuitOUT4

Load

Power supply DC24V

Load

Load

Load

Power for loadDC30V 50mA or less for one circuit

Load

Current output (4-20mA) sensor

OUT(4~20mA)

0V

+24V

250Ω

0V

0V

OUT1

COM

-

+

DMC-A4A

+24V

+24V

A IN

OUT4

OUT3

OUT2Internalcircuit

CONNECTION

(75)

Guide lock

(3.5)

56.5 72

52.5

64.5

7.57.5 7.57.5 7.5

63

54.5

∅4.5

4.5×6.5 long hole

Bottom panel diagram

DIMENSIONS (Unit:㎜)

Model DMC-A4ADC24V±10%40mA or less

Sequential comparison system 10bit (1024)DC 0 to 5V/0 to 10V/0 to 20mA (selectable)DC 0 to 5V : 0.01V/0 to 10V : 0.01V/0 to 20mA : 0.1mANPN open collector output, Rating: 50mA (DC30V) or less, 4 outputs

DC24V (200mA or less) ※13 digits, 0 to 5V : 0.00 to 5.50/0 to 10V : 0.00 to 11.0/0 to 20mA : 0.00 to 22.07 segments, Red×1, Green×3, Font size: 8×4 ㎜

2000 times/sec1 to 200 counts (selectable)

On delay/Off delay (1 to 999msec, selectable)HI ON (  ) / LO ON (  ) (selectable)

Terminal block, Tightening torque: 0.3N・m or lessCase: PPE Panel: PET

DIN rail (35 ㎜ ) and screw tightening methodApprox. 130g

Instruction manual※1 Power supply directly connected

Power supplyCurrent consumptionA/D conversion methodMeasurement range (input mode)Display resolutionOutput modeSensor power supplyIndication methodIndication sizeSampling speedAvaragingOutput delayOperation modeConnectionMaterialMounting methodWeightAccessories

SPECIFICATION

ENVIRONMENTAL SPECIFICATION-10 to +55℃ (non-freezing)35 to 85%RH (non-condensing)

10 to 55Hz when tested with double amplitude of 0.75㎜in X, Y, and Z directions, 2 hours for each direction ※2

500m/s2 when tested in X, Y, and Z directions, 3 times for each direction300m/s2 when tested in X, Y, and Z directions, 3 times for each direction1000VAC for 1 minute between whole live part and case20MΩ or more when tested with 500VDC megger

※2 When mounting to the DIN rail, attach the stopper (end unit) to the product. End unit (option) model : FA7EU

Ambient temperatureAmbient humidity

When mountingdirectlyVibration When mountingto DINWhen mountingdirectlyWhen mountingto DIN

Shock

Dielectric toleranceInsulation resistance

CAUTION

●This product is designed for industrial applications to detect a various kinds of objects. It has no function to prevent disasters, accidents, death or injuries.●Takex will not held responsible for any damage or loss incurred due to accidents, faulty installation, abuse, misuse, improper maintenance or acts of God including  lightning surge.●This product can’t be used as a safety equipment to protect human body.●This product is designed and manufactured for industrial use. It can’t be use for usage or equipmennt that requires a high degree of reliabilty or considerable care or  attention to safety.●Read this instruction manual carefully and use the product properly according to it.●

Distributed byTAKENAKA ELECTRONIC INDUSTRIAL CO.,LTD.Takenaka Sensor Group

20-1 Shinomiya Narano-cho, Yamashina, Kyoto 607-8032 Japan

URL : http://www.takex-elec.co.jp email : [email protected]: +81-75-581-7111 Fax: +81-75-581-7118