Download - Br Unimix-jti(en)b 1vcp000249x
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
1/16
UniMix JTI
Secondary distribution switchgearwith rapid delivery times
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
2/16
2
UniMix JTI:thought up and built for industry customers
The JTI Just To Install acronym indicates a type of medium voltage switchgearfor primary and secondary distribution featuring very rapid delivery and puttinginto service.
DeliverDeliverDeliverDeliverDelivery of UniMix JTI switchgear usually takes place within two weeks.y of UniMix JTI switchgear usually takes place within two weeks.y of UniMix JTI switchgear usually takes place within two weeks.y of UniMix JTI switchgear usually takes place within two weeks.y of UniMix JTI switchgear usually takes place within two weeks.
By means of a product configurator which allows precise and rapid estimates tobe prepared, the customer receives complete proposals and is relieved of thetask of preparing the technical specifications and design drawings.
JTI switchgear are based on the standard switchgear design and have a range oftypes able to satisfy even special installation requirements, thanks both to theirelectrical characteristics and to their standard fitting of accessories.
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
3/16
3
UniMix JTI are always fitted with mechanical and electro-mechanical interlocksaccording to IEC 62271-200 Standards and are available with gas circuit-bre-akers. All the solutions have the incoming unit and use of the on-board circuit-breaker PR521 release or, alternatively, the REF542plus unit, as the protection unit.
The technical design documentation is immediately available and the customergives official approval of the project during the offer stage.
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
4/16
4
UniMix JTI:thought up and built for industry customers
HD4/Unimix-F gas circuit-breaker(with PR521 release and current sensors).
Current transformer.Current/voltage sensor.
SHS2 gas switch-disconnector.
REF542plus multi-function controland protection unit.
Main Components
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
5/16
5
Characteristics
VersionStandard (not arc proof)
Classification
Service continuity: LSC2A
Partitions: PM (Partition Metallic)
Degree of protection
IP2X inside the switchgear
IP3X on the external housing (except for theoperating seats)
IP2XC on the operating seats
Mechanical interlocks available
Circuit-breaker with line-side insulator
Line-side insulator with earthing switch
Door with earthing switch
Auxiliary circuit voltage
220 V a.c.
General characteristics
Units and sides made of pre-galvanised sheet
Front panel doors painted grey RAL 7035
Fixed HD4/Unimix-F circuit-breaker
On-board circuit-breaker current sensors orcombined current/voltage sensors according to DINStandards
On-board circuit-breaker PR521 protection release orREF542plus electronic protection and control unit
Conformity with Standards
IEC 62271-200
EN 62271-200
Electrical characteristicsRated voltage 24 kV
Test voltage (50 Hz/1 min) 50 kV
Impulse withstand voltage 125 kV
Rated frequency 50 Hz
Rated current 630 A
Short-time withstand current (1s) 16 kA
Peak current 40 kA
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
6/16
6
No. 1 Incoming/Outgoing Unit with CL Left Cable Riser Unit + No. 1 P1/F Unitwith fixed circuit-breaker
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release,operation counter, 2 NO + 2 NC auxiliary contacts, undervoltage release withelectronic time-delay device (selectable delay times: from 0.5 s to 3 s) and contactsignalling release de-energised
PR521 protection release with 2 on-board circuit-breaker sensors and toroid for earthfault
SHS2/IB switch-disconnector with:
- 1 removable key with line-side insulator in the closed position and 1 removable keyin the open position
- 1 removable key with earthing switch in the closed position and 1 removable key inthe open position
Configurations available
UniMix JTI:thought up and built for industry customers
JTI A1-CLsx Switchgear
Switchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear description OrOrOrOrOrdering codedering codedering codedering codedering code EquipmentEquipmentEquipmentEquipmentEquipment
JTI_A1_Z_CLSX_N_N 1VCF594000R0062 Without accessories
JTI_A1_Z_CLSX_N_R 1VCF594000R0063 Anticondensation heater
JTI_A1_Z_CLSX_I_N 1VCF594000R0064 Internal light
JTI_A1_Z_CLSX_I_R 1VCF594000R0065 Internal l ight and ant icondensat ion heater
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
7/16
7
No. 1 Incoming/Outgoing Unit with CL Right Cable Riser Unit + No. 1 P1/F Unitwith fixed circuit-breaker
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release,operation counter, 2 NO + 2 NC auxiliary contacts, undervoltage release withelectronic time-delay device (selectable delay times: from 0.5 s to 3 s) and contactsignalling release de-energised
PR521 protection release with 2 on-board circuit-breaker sensors and toroid for earthfault
SHS2/IB switch-disconnector with:
- 1 removable key with line-side insulator in the closed position and 1 removable keyin the open position
- 1 removable key with earthing switch in the closed position and 1 removable key inthe open position
JTI A1-CLdx Switchgear
Switchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear description OrOrOrOrOrdering codedering codedering codedering codedering code EquipmentEquipmentEquipmentEquipmentEquipment
JTI_A1_Z_CLDX_N_N 1VCF594000R0066 Without accessories
JTI_A1_Z_CLDX_N_R 1VCF594000R0067 Anticondensation heater
JTI_A1_Z_CLDX_I_N 1VCF594000R0068 Internal light
JTI_A1_Z_CLDX_I_R 1VCF594000R0069 In ternal l ight and ant icondensat ion heater
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
8/16
8
UniMix JTI:thought up and built for industry customers
No. 1 Incoming/Outgoing with top cable entry AC + No. 1 P1/F Unit withfixed circuit-breaker
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release,operation counter, 2 NO + 2 NC auxiliary contacts, undervoltage release withelectronic time-delay device (selectable delay times: from 0.5 s to 3 s) and contactsignalling release de-energised
PR521 protection release with 2 on-board circuit-breaker sensors and toroid for earthfault
SHS2/IB switch-disconnector with:
- 1 removable key with line-side insulator in the closed position and 1 removable keyin the open position
- 1 removable key with earthing switch in the closed position and 1 removable key inthe open position
Configurations available
JTI A1-AC Switchgear
Switchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear description OrOrOrOrOrdering codedering codedering codedering codedering code EquipmentEquipmentEquipmentEquipmentEquipment
JTI_A1_Z_AC_N_N 1VCF594000R0070 Without a ccessories
JTI_A1_Z_AC_N_R 1VCF594000R0071 Anticondensation heater
JTI_A1_Z_AC_I_N 1VCF594000R0072 Internal light
JTI_A1_Z_AC_I_R 1VCF594000R0073 Internal light and anticondensation heater
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
9/16
9
No. 1 Incoming/Outgoing with top cable entry A2 AC + No. 1 P1/F Unit withfixed circuit-breaker
Presence of voltage on busbar side and cable side
235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release, shuntclosing release, 3 NO + 4 NC auxiliary contacts, operation counter and springscharged signalling, undervoltage release with electronic time-delay device (selectabledelay times: from 0.5 s to 3 s) and contact signalling release de-energised
REF542plus protection and control unit with 3 ABB type KEVCD current/voltagesensors and toroid for earth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator closed and 1 removable key in the openposition
- with 1 removable key with the earthing switch in the closed position and 1removable key in the open position
- auxiliary contacts: 1 NO or NC for the line-side insulator and 1 NO or NC for theearthing switch
JTI A2-CLsx Switchgear
Switchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear description OrOrOrOrOrdering codedering codedering codedering codedering code EquipmentEquipmentEquipmentEquipmentEquipment
JTI_A2_Z_CLSX_N_N 1VCF594000R0074 Without accessories
JTI_A2_Z_CLSX_N_R 1VCF594000R0075 Anticondensation heater
JTI_A2_Z_CLSX_I_N 1VCF594000R0076 Internal light
JTI_A2_Z_CLSX_I_R 1VCF594000R0077 Internal l ight and anticondensat ion heater
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
10/16
10
UniMix JTI:thought up and built for industry customers
No. 1 Incoming/Outgoing Unit with CL Right Cable Riser Unit + No. 1 P1/F Unitwith fixed circuit-breaker
Presence of voltage on busbar side and cable side
235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release, shuntclosing release, 3 NO + 4 NC auxiliary contacts, operation counter and springscharged signalling, undervoltage release with electronic time-delay device (selectabledelay times: from 0.5 s to 3 s) and contact signalling release de-energised
REF542plus protection and control unit with 3 ABB type KEVCD current/voltagesensors and toroid for earth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator closed and 1 removable key in the openposition
- with 1 removable key with the earthing switch in the closed position and 1removable key in the open position
- auxiliary contacts: 1 NO or NC for the line-side insulator and 1 NO or NC for theearthing switch
Configurations available
JTI A2-CLdx Switchgear
Switchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear description OrOrOrOrOrdering codedering codedering codedering codedering code EquipmentEquipmentEquipmentEquipmentEquipment
JTI_A2_Z_CLDX_N_N 1VCF594000R0078 Without accessories
JTI_A2_Z_CLDX_N_R 1VCF594000R0079 Anticondensation heater
JTI_A2_Z_CLDX_I_N 1VCF594000R0080 Internal light
JTI_A2_Z_CLDX_I_R 1VCF594000R0081 Internal l ight and ant icondensat ion heater
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
11/16
11
No. 1 Incoming/Outgoing with top cable entry AC + No. 1 P1/F Unit withfixed circuit-breaker
Presence of voltage on busbar side and cable side
235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release, shuntclosing release, 3 NO + 4 NC auxiliary contacts, operation counter and springscharged signalling, undervoltage release with electronic time-delay device (selectabledelay times: from 0.5 s to 3 s) and contact signalling release de-energised
REF542plus protection and control unit with 3 ABB type KEVCD current/voltagesensors and toroid for earth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator closed and 1 removable key in the openposition
- with 1 removable key with the earthing switch in the closed position and 1removable key in the open position
- auxiliary contacts: 1 NO or NC for the line-side insulator and 1 NO or NC for theearthing switch
JTI A2-AC Switchgear
Switchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear description OrOrOrOrOrdering codedering codedering codedering codedering code EquipmentEquipmentEquipmentEquipmentEquipment
JTI_A2_Z_AC_N_N 1VCF594000R0082 Without accessories
JTI_A2_Z_AC_N_R 1VCF594000R0083 Anticondensation heater
JTI_A2_Z_AC_I_N 1VCF594000R0084 Internal l ight
JTI_A2_Z_AC_I_R 1VCF594000R0085 Internal light and anticondensation heater
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
12/16
12
No. 1 Incoming Line with P1/A Unit + No. 2 P1/F Transformer Protection Units
P1/A Incoming Unit235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p 230 non-motorised circuit-breaker with shunt opening release, 2 NO + 2 NCauxiliary contacts, operation counter, undervoltage release with electronic time-delay device(selectable delay times: from 0.5 s to 3 s) and contact signalling release de-energised
PR521 protection release with 2 on-board circuit-breaker sensors and toroid for earth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the openposition
- with 2 removable keys with the earthing switch in the open position
P1/F Transformer Protection Unit
Presence of voltage on cable side
HD4/Unimix-F p230 circuit-breaker with shunt opening release, 2 NO + 2 NC auxiliary contacts andoperation counter
PR521 protection release (50-51) with 2 on-board circuit-breaker 80A sensors
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the openposition
- 1 removable key with the earthing switch in the closed position and 1 removable key in the openposition
UniMix JTI:thought up and built for industry customers
Configurations available
JTI B1 Switchgear
Switchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear description OrOrOrOrOrdering codedering codedering codedering codedering code EquipmentEquipmentEquipmentEquipmentEquipment
JTI B1 1VCF594000R0056 Without accessories
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
13/16
13
No. 1 Incoming Line with P1/A Unit + No. 2 P1/F Transformer Protection Units
P1/A Incoming Unit235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p 230 non-motorised circuit-breaker with shunt opening release, shunt closing release, 3NO + 4 NC auxiliary contacts, operation counter, springs charged signalling, undervoltage release withelectronic time-delay device (selectable delay times: from 0.5 s to 3 s) and contact signalling release de-energised
REF542plus protection and control unit with 3 ABB type KEVCD current/voltage sensors and toroid forearth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the openposition
- with 2 removable keys with the earthing switch in the open position
- auxiliary contacts: 1 NO or NC for line-side insulator and 1 NO or NC for earthing switch
P1/F Transformer Protection Unit
Presence of voltage on cable side
HD4/Unimix-F p 230 circuit-breaker with shunt opening release, 2 NO + 2 NC auxiliary contacts andoperation counter
PR521 protection release (50-51) with 2 on-board circuit-breaker 80A sensors
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the openposition
- 1 removable key with the earthing switch in the closed position and 1 removable key in the open position
JTI B2 Switchgear
Switchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear description OrOrOrOrOrdering codedering codedering codedering codedering code EquipmentEquipmentEquipmentEquipmentEquipment
JTI B2 1VCF594000R0057 Without accessories
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
14/16
14
No. 1 Incoming Line with P1/A Unit + No. 2 P2 Transformer Protection Units with switch-disconnector
P1/A Incoming Unit
235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release, 2 NO + 2 NC auxiliarycontacts, operation counter, undervoltage release with electronic time-delay device (selectable delay times:from 0.5 s to 3 s) and contact signalling release de-energised
PR521 protection release with 2 on-board circuit-breaker sensors and toroid for earth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the open position
- with 2 removable keys with the earthing switch in the open position
P2 Transformer Protection Unit (unit width: 500mm)
Presence of voltage on cable side
SHS2/T2F switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the open position
- 1 removable key with the earthing switch in the closed position and 1 removable key in the open position
- shunt opening release
- fuse-holder
- mechanical trip system for blown fuse
- contact for signalling fuse blown
- auxiliary contacts: 2 NO or NC for line-side insulator and 2 NO or NC for earthing switch
Fuses not included in the supply
JTI B3 Switchgear
UniMix JTI:thought up and built for industry customers
Configurations available
Switchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear description OrOrOrOrOrdering codedering codedering codedering codedering code EquipmentEquipmentEquipmentEquipmentEquipment
JTI B3 1VCF594000R0058 Without accessories
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
15/16
15
No. 1 Incoming Line with P1/A Unit + No. 2 P2 Transformer Protection Units with switch-disconnector
P1/A Incoming Unit235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release, 2 NO + 2 NC auxiliary contacts,operation counter, undervoltage release with electronic time-delay device (selectable delay times: from 0.5 s to 3 s)and contact signalling release de-energised
PR521 protection release with 2 on-board circuit-breaker sensors and toroid for earth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the open position
- 2 removable keys with the earthing switch in the open position
P2 Transformer Protection Unit (unit width: 375mm)
Presence of voltage on cable side
SHS2/T2F switch-disconnector
- with 1 removable key with the line-side insulator in the closed position and 1 removable key in the open position
- with 1 removable key with the earthing switch in the closed position and 1 removable key in the open position
- shunt opening release
- fuse-holder
- mechanical trip system for blown fuse
- contact for signalling fuse blown
- auxiliary contacts: for line-side insulator and 2 NO or NC for earthing switch
Fuses not included in the supply
JTI B4 Switchgear
Switchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear descriptionSwitchgear description OrOrOrOrOrdering codedering codedering codedering codedering code EquipmentEquipmentEquipmentEquipmentEquipment
JTI B4 1VCF594000R0059 Without accessories
-
7/25/2019 Br Unimix-jti(en)b 1vcp000249x
16/16
16
ABB Power Technologies S.p.A.Unit Operativa SaceVia Friuli, 4I-24044 DalmineTel: +39 035 395111Fax: +39 035 395874E-mail: [email protected]
Internet://www.abb.com
ABB AGCalor Emag Medium Voltage ProductsOberhausener Strasse 33 Petzower Strasse 8D-40472 Ratingen D-14542 GlindowPhone: +49(0)2102/12-1230, Fax: +49(0)2102/12-1916E-mail: [email protected]:http://www.abb.de/calor
The
dataandillustrationsarenotbinding.
Werese
rvetherighttomakechanges
inth
ecourseoftechnicaldevelopmentoftheproduct.
1VC
P000249Rev.B,enTechnicalcatalogue
2006.1
0(UniMixJTI)