-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
1/28
ADP-019-2012-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV
MEMORIA DE CLCULO FINAL
DISEO ESTRUCTURAL
TORRE AUTOSOPORTADA TIPO A+3 / 60 KV
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
2/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
TORRES AUTOSOPORTADAS 138 KV Y 60 KV
DISEO MECANICO DE TORRE AUTOSOPORTADA A+3 / 60 KV
1.0MEMORIA DESCRIPTIVA... 3
1.1GENERAL. 3
1.2CARGAS APLICADAS, ANLISIS Y RESULTADOS.. 4
1.3CONCLUSIONES.... 6
2.0MEMORIA DE CLCULO......................... 7
2.1GENERAL................... 7
2.2CRITERIOS DE CLCULO.... 8
2.3EVALUACIN DE CARGAS INTERNAS.. 11
2.4VERIFICACIN DE ELEMENTOS..... 11
2 5 DEFORMACIONES 14
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
3/28
2 5 DEFORMACIONES 14
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
DISEO MECANICO DE TORRE AUTOSOPORTADA A+3 / 60 KV
1.0 MEMORIA DESCRIPTIVA
1.1 GENERAL1.1.1. PropsitoEl presente informe tiene la finalidad de evaluar la capacidad de trabajo de laTorre Autosoportada Tipo A+3 / 60 KV bajo la aplicacin de las fuerzas de conductores,fuerzas debido a la accin del viento y hielo, as como el peso propio de la estructura, comoparte del proyecto:Adquisicin de Torres Autosoportadas 138 KV y 60 KV.
La mencionada torre est constituida por perfiles estructurales, respetando las distanciasprincipales establecidas por el cliente.
1.1.2. Cdigos y EstndaresLos Trabajos incluidos en este documento se han realizado bajo la norma:
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
4/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
Cli t El t S E t S A A
DIAGRAMA DE CARGAS
1.1.6. Caractersticas constructivasLas estructuras de uso elctrico, como es el caso, son construcciones hechas con perfilesgalvanizados y ensambladas mediante pernos. Normalmente no es permitido el uso deelementos o uniones soldadas, esto implica que todos los elementos se consideran que estnsometidos nicamente a cargas axiales.
Configuracin:
Altura de mnsula inferior: 21.00 mAltura mxima libre torre: 31.90 mAmplitud de patas: 4.20 m
1.2 CARGAS APLICADAS, ANLISIS Y RESULTADOS1.2.1 Cargas Aplicadas
La estructura ha sido modelada con todos sus perfiles, las uniones empernadas y se hanaplicado las siguientes cargas para la verificacin de su comportamiento y definicin deperfiles segn los esfuerzos resultantes:
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
5/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
1.2.2 Anlisis
La seleccin de un perfil se realiza verificando que stos aprueben los criterios de falla. Loscriterios de falla son definidos para elementos a compresin y a traccin. Los elementosanalizados corresponden al mostrado en el diagrama estructural adjunto al informe.
a) Verificacin de perfiles estructurales
Todos los elementos a compresin se verifican por su capacidad admisible que es evaluado enfuncin de su esbeltez de acuerdo al tem 3.7 de la Norma ASCE 10-97, el mismo que sedelimita segn la funcin del perfil como sigue:
L / rmin150 para montantes y crucetas200 para riostras diagonales y otros elementos
250 para elementos redundantes
Todos los elementos a tensin se verifican por su capacidad admisible, que es evaluado enfuncin de su seccin neta de acuerdo al tem 3.10 de la Norma ASCE 10-97.
La relacin de esbeltez de elementos a traccin no exceder los lmites siguientes:
L / rmin240 para miembros principales300 i b d i
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
6/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
7/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
*** Maximum Stress Summary for Each Load Case
Summary of Maximum Usages by Load Case:
Load Case Maximum Element ElementUsage % Label Type
------------------------------------
Hiptesis A 89.13 Mo1P Angle
Hiptesis B 92.71 Mo1P Angle
Hiptesis C 93.45 Mo1P Angle
2. Todas las uniones empernadas satisfacen los requerimientos de las cargas internasoriginadas por las hiptesis de cargas aplicadas.
3. La deflexin originada por las cargas de servicio se encuentra dentro del rango admisible.
4. Los grupos de perfiles asignados a la estructura son:
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
8/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
2.1.2 Alcance
El presente documento tcnico tiene como alcance los clculos estructurales de laTorre Autosoportada A+3 / 60 KV bajo las condiciones de carga presentes en lasBases ADP-019-2012-ELSE
Bases ADP-019-2012-ELSE
2.1.3 Normas y reglamentosSe han tenido en cuenta la siguiente norma de Diseo:
- ASCE STANDARD: ASCE 10-97DESIGN OF LATTICED STEEL TRANSMISSION STRUCTURES
2.2 CRITERIOS DE CLCULO
2.2.1 Modelo Analizado
) L d i l d l d l i l id l lid d d l
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
9/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
Todos los elementos estructurales debern ser galvanizados en caliente de acuerdo aASTM A123.
Pernos sern calidad ASTM A325.
Los pernos sern galvanizados en caliente segn Norma ASTM A153.
2.2.3 Hiptesis de carga
La estructura ser analizada con las hiptesis de carga siguiente:
HIPTESIS A: Carga Mxima de Trabajoviento al 100% HIPTESIS B: Rotura de Conductorviento al 60% HIPTESIS C: Rotura de Cable de Guardaviento al 60%
2.2.4. Cargas aplicadas
2.2.4.1. Carga por peso propio (p)
La carga muerta est constituida por todo el peso propio que es asignada por el software deanlisis. Adicionalmente se le considera 20% ms por el peso de placas, pernos, galvanizado y
l i d hi l di ib id b l d f i l f
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
10/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
Hiptesis A Hiptesis B
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
11/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
2.2.6. Esfuerzos Lmites Elsticos
Los valores de los lmites elsticos de los materiales considerados son los siguientes:
Acero Estructural:
ASTM A36 : 24 kg/mm2
ASTM A572G50: 36 kg/mm2
Estos valores estn dentro de las caractersticas normalizadas de los mismos.
2.3 EVALUACIN DE CARGAS INTERNAS
Para el clculo de las cargas internas sobre los elementos se ha utilizado el programaMS TOWER, en el cual se han modelado espacialmente la torre con todos sus elementos.
El modelo ha sido hecho con las dimensiones en milmetros y las cargas en kilonewtons (kN).
2.4 VERIFICACIN DE ELEMENTOS
Los perfiles estructurales se verifican segn el Manual ASCE 10-97. De acuerdo a esta seanalizarn los elementos utilizando las cargas internas resultantes tomando un factor de
d d d l d f d l l l
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
12/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
La fuerza axial admisible ser:
Para:
(Segn norma ASCE 10-97)
Para:
Si Pc es la fuerza de compresin sobre el elemento, se debe verificar que:
Fad > Pc
Donde:
E, es el mdulo de elasticidad.
y, es el esfuerzo de fluencia del material.
A f
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
13/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
2.4.2 Uniones Atornilladas (segn Especificaciones AISC-LRFD)Los pernos de unin sern de acero de calidad ASTM A325, con:
Para esfuerzos de corte : 80% del lmite elstico del acero Para esfuerzos de traccin : 100% del lmite elstico del acero
La resistencia del perno al corte se calcular mediante las Especificaciones de carga y
resistencia de diseo de estructuras metlicas (AISC-LRFD-1999 Seccin J3):
Donde:
Rc, es la resistencia total al corte de los pernos de unin.
, es el factor de disponibilidad en resistencia de corte.
As, es el rea de la seccin roscada del perno.
Fu, es esfuerzo de corte del perno.
n, es 1 si se trata de una junta simple y, 2 si la unin tiene cubrejunta.
fs, es el factor de seguridad.
Se debe hacer una verificacin por aplastamiento para los elementos en conexin; la
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
14/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
Donde:
Rn, es la resistencia al aplastamiento disponible.
, es el factor de disponibilidad en resistencia al aplastamiento.
, espesor mnimo real sometido a aplastamiento.
t, espesor del material sometido al aplastamiento.
Fu, esfuerzo de traccin ltima.
, dimetro del perno de conexin.
Realizado el clculo unitario, se verifica el conjunto en conexin haciendo la sumatoria de
Rcy Rn.
2.5 DEFORMACIONESLa mxima deflexin obtenida es: 29,68 cm en la Hiptesis A con cargas factoradas para laubicacin ms alta de la torre, la admisible es de 47,85 cm para cargas de servicio, por lo tantoes conforme.
Joint X-Displ Y-Displ Z-Displ X-Rot Y-Rot Z-Rot X-Pos Y-Pos Z-PosLabel (m) (m) (m) (deg) (deg) (deg) (m) (m) (m)
------------------------------------------------------------------------------------------- PP 0.0105 0.2646 -0.004297 -0.9638 0.0377 -0.0157 0.0105 0.2646 30
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
15/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
MODELO 3D: TAS-A+3/60-ELSE
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
16/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
PORCENTAJE DE UTILIZACIN DE ELEMENTOS
MXIMO PORCENTAJE DE UTILIZACIN PARA TODOS LOS CASOS DE CARGA
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
17/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
MXIMO PORCENTAJE DE UTILIZACIN PARA HIPTESIS A
DESPLAZAMIENTO MXIMO = 29,68 cm
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
18/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
MXIMO PORCENTAJE DE UTILIZACIN PARA HIPTESIS B
DESPLAZAMIENTO MXIMO = 25,50 cm
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
19/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
MXIMO PORCENTAJE DE UTILIZACIN PARA HIPTESIS C
DESPLAZAMIENTO MXIMO = 27,40 cm
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
20/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
NUMERACIN DE ELEMENTOS
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
21/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
22/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
23/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
*******************************************************************************
* ** TOWER - Analysis and Design - Copyright Power Line Systems, Inc. 1986-2011 *
* *
*******************************************************************************
Project Name : ELSE
Project Notes: Torre Autosoportada Tipo A+3, 60 kV - Pata Coja +3
Project File : d:\electrocom\c.cauti\proyectos en curso\else\clculos estructurales\torre a+3 - pata +3 - 60 kv.tow
Date run : 19:16:07 martes, 09 de octubre de 2012
by : Tower Version 12.10
Licensed to : Electrocom - Peru
Successfully performed nonlinear analysis
The model has 0 warnings.
Nonlinear convergence parameters: Use Standard Parameters
Member check option: ASCE 10
Connection rupture check: ASCE 10
Crossing diagonal check: ASCE 10 [Alternate Unsupported RLOUT = 1]
Included angle check: None
Climbing load check: None
Redundant members checked with: Actual Force
The model contains 24 primary and 48 secondary joints for a total of 72 joints.
Steel Material Properties:
Steel Modulus Yield Ultimate Member Member Member Member Member MemberMaterial of Stress Stress All. Stress All. Stress Rupture Rupture Bearing Bearing
Label Elasticity Fy Fu Hyp. 1 Hyp. 2 Hyp. 1 Hyp. 2 Hyp. 1 Hyp. 2(MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa)
--------------------------------------------------------------------------------------------
ASTM A36 2.06e+005 250 400 0 0 0 0 0 0
Bolt Properties:
Bolt Bolt Hole Ultimate Default Default Shear ShearLabel Diameter Diameter Shear End Bolt Capacity Capacity
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
24/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
Aggregate Angle Information:
Note: Estimate of surface area reported for painting purposes, not wind loading.
Angle Angle Material Total Total TotalType Size Type Length Surface Area Weight
(m) (m^2) (N)---------------------------------------------------------------------
SAE L 4" x 4" x 1/4" ASTM A36 96.44 39.19 9290.57
SAE L 2 1/2" x 2 1/2" x 3/16" ASTM A36 66.69 16.94 2988.98
SAE L 2" x 2" x 3/16" ASTM A36 243.53 49.49 8674.96
SAE L 3" x 3" x 1/4" ASTM A36 29.20 8.90 2088.81
SAE L 1 1/2" x 1 1/2" x 3/16" ASTM A36 107.47 16.38 2824.01
Point Loads for Load Case "Hiptesis A":
Joint Vertical Transverse Longitudinal LoadLabel Load Load Load Comment
(N) (N) (N)-----------------------------------------------
M1P 18952.9 15342.8 323.73
M3P 18952.9 15342.8 323.73
M5P 18952.9 15342.8 323.73
PP 15296.8 9466.65 235.44
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
25/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
PORCENTAJE DE UTILIZACIN DE PERFILES
*** Analysis Results:
Maximum element usage is 93.45% for Angle "Mo1P" in load case "Hiptesis C"
Maximum insulator usage is 0.38% for Clamp "Conductor 5" in load case "Hiptesis B"
Angle Forces For All Load Cases:
Positive for tension - negative for compression
Group Angle Max. Usage Max. Tens. Max. Comp. LC 1 LC 2 LC 3Label Label For All LC For All LC For All LC
% (kN) (kN) (kN) (kN) (kN)-----------------------------------------------------------------------------------
Mont1A Mo1P 93.45 0.000 -260.748 -248.681 -258.660 -260.748Mont1A Mo1X 70.05 181.982 0.000 181.982 98.002 121.109
Mont1A Mo1XY 72.76 189.040 0.000 189.040 185.672 185.491
Mont1A Mo1Y 86.65 0.000 -241.763 -241.763 -173.279 -197.568
Mont1A Mo2P 91.56 0.000 -255.448 -240.184 -252.331 -255.448
Mont1A Mo2X 68.45 177.833 0.000 177.833 95.281 117.715
Mont1A Mo2XY 71.10 184.730 0.000 184.730 181.847 182.820
Mont1A Mo2Y 83.64 0.000 -233.343 -233.343 -166.858 -190.798
Mont1A Mo3P 83.16 0.000 -232.013 -213.592 -227.630 -232.013
Mont1A Mo3X 61.40 159.522 0.000 159.522 85.130 105.127
Mont1A Mo3XY 64.35 167.189 0.000 165.688 164.119 167.189
Mont1A Mo3Y 74.29 0.000 -207.273 -207.273 -146.764 -168.548
Mont1A Mo4P 80.45 0.000 -224.464 -200.632 -217.102 -224.464
Mont1A Mo4X 56.13 145.822 0.000 145.822 74.190 92.185
Mont1A Mo4XY 60.32 156.712 0.000 151.560 150.264 156.712
Mont1A Mo4Y 69.75 0.000 -194.622 -194.622 -137.033 -157.556Mont1B Mo5P 69.84 0.000 -194.869 -170.595 -185.517 -194.869
Mont1B Mo5X 47.15 122.487 0.000 122.487 60.017 74.354
Mont1B Mo5XY 52.14 135.461 0.000 127.283 126.353 135.461
Mont1B Mo5Y 59.33 0.000 -165.549 -165.549 -114.417 -131.802
Mont1B Mo6P 62.70 0.000 -190.356 -161.556 -177.333 -190.356
Mont1B Mo6X 42.60 110.671 0.000 110.671 48.120 60.238
Mont1B Mo6XY 48.48 125.943 0.000 115.098 112.612 125.943
Mont1B Mo6Y 51.70 0.000 -156.956 -156.956 -107.944 -123.767
Mont1B Mo7P 57.73 0.000 -161.062 -133.843 -146.316 -161.062
Mont1B Mo7X 34.59 89.872 0.000 89.872 35.602 44.107
Mont1B Mo7XY 41.00 106.521 0.000 93.397 90.863 106.521
Mont1B Mo7Y 46.69 0.000 -130.278 -130.278 -86.790 -99.531
Punton PuntAP 47.19 0.000 -21.406 -21.406 -9.280 -15.745
Punton PuntAX 45.23 20.027 0.000 20.027 7.799 14.285
Punton PuntAXY 48.66 21.545 0.000 20.391 21.545 14.766
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
26/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
Diag1F DiagF2XY 20.54 6.479 -2.103 6.479 -2.103 5.263
Diag1F DiagF2Y 20.37 5.303 -6.426 -6.426 5.303 -6.261
Mont2A MoSR1P 68.62 0.000 -131.378 -106.148 -114.694 -131.378Mont2A MoSR1X 39.25 69.735 0.000 69.735 25.071 31.311
Mont2A MoSR1XY 47.92 85.142 0.000 72.337 70.168 85.142
Mont2A MoSR1Y 54.17 0.000 -103.711 -103.711 -71.835 -79.095
Mont2A MoSR2P 58.95 0.000 -112.856 -90.759 -90.757 -112.856
Mont2A MoSR2X 37.91 67.363 0.000 67.363 32.324 37.736
Mont2A MoSR2XY 49.41 87.779 0.000 69.903 73.374 87.779
Mont2A MoSR2Y 46.29 0.000 -88.619 -88.619 -63.108 -63.787
Mont2A MoSR3P 52.62 0.000 -100.751 -78.414 -78.404 -100.751
Mont2A MoSR3X 31.12 55.287 0.000 55.287 31.967 31.368
Mont2A MoSR3XY 42.36 75.267 0.000 57.266 57.605 75.267
Mont2A MoSR3Y 40.01 0.000 -76.611 -76.611 -58.602 -57.224
Mont2A MoSR4P 60.65 0.000 -76.510 -56.775 -56.102 -76.510
Mont2A MoSR4X 29.11 36.726 0.000 36.726 27.898 21.202
Mont2A MoSR4XY 42.25 53.305 0.000 37.825 33.477 53.305
Mont2A MoSR4Y 44.10 0.000 -55.636 -55.636 -48.873 -44.392Mont2A MoSR5P 37.94 0.000 -47.864 -35.216 -33.061 -47.864
Mont2A MoSR5X 14.88 18.768 0.000 18.768 17.957 5.850
Mont2A MoSR5XY 22.61 28.519 0.000 19.375 14.952 28.519
Mont2A MoSR5Y 28.23 0.000 -35.610 -34.593 -35.610 -25.176
CGuarda CGP 34.94 0.000 -22.081 -18.862 -22.081 -21.806
CGuarda CGX 12.16 10.001 -6.129 10.001 8.967 -6.129
CGuarda CGXY 18.56 15.269 0.000 10.628 8.303 15.269
CGuarda CGY 32.48 0.000 -20.527 -18.176 -20.527 -0.335
DiagSRA DiagSR1AP 55.64 0.000 -17.548 -14.923 -10.126 -17.548
DiagSRA DiagSR1AX 27.64 8.718 -4.651 8.718 -4.651 1.187
DiagSRA DiagSR1AXY 44.86 14.149 0.000 9.573 14.149 10.416
DiagSRA DiagSR1AY 46.57 0.000 -14.688 -14.688 -14.344 -9.415
DiagSRA DiagSR1BP 89.07 0.000 -28.093 -17.741 -28.093 -20.671
DiagSRA DiagSR1BX 36.48 11.505 0.000 11.505 10.744 6.465
DiagSRA DiagSR1BXY 39.84 12.565 0.000 11.685 4.887 12.565
DiagSRA DiagSR1BY 53.17 0.000 -16.769 -16.769 -2.694 -14.007
DiagSRA DiagSR2AP 35.47 2.257 -11.188 -11.188 2.257 -9.632
DiagSRA DiagSR2AX 35.64 11.241 -2.641 11.241 -2.641 8.429
DiagSRA DiagSR2AXY 64.28 20.273 0.000 11.907 20.273 11.129
DiagSRA DiagSR2AY 55.16 0.000 -17.397 -11.626 -17.397 -8.232
DiagSRA DiagSR2BP 55.50 0.000 -17.503 -4.050 -17.503 -6.908
DiagSRA DiagSR2BX 19.76 6.234 -0.700 2.409 6.234 -0.700
DiagSRA DiagSR2BXY 15.46 4.876 -2.929 2.353 -2.929 4.876
DiagSRA DiagSR2BY 34.20 10.786 -3.155 -3.155 10.786 -0.492
DiagSRA DiagSR3AP 35.36 2.843 -11.151 -11.151 2.843 -8.286
DiagSRA DiagSR3AX 33.12 10.447 -2.596 10.447 -2.596 9.317
DiagSRA DiagSR3AXY 54.44 17.171 0.000 10.891 17.171 7.985
DiagSRA DiagSR3AY 63.78 0.000 -20.114 -11.814 -20.114 -10.861
DiagSRA DiagSR3BP 34.65 3.035 -10.928 3.035 -10.928 0.343
DiagSRA DiagSR3BX 15.18 3.003 -4.789 -2.233 3.003 -4.789
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
27/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12
____________________________________________________________________________________
CuadSR-I CuadSR3AX 12.96 0.000 -8.178 -3.019 -8.178 -5.429
CuadSR-I CuadSR3AXY 13.42 1.521 -8.467 -2.873 1.521 -8.467
CuadSR-I CuadSR3AY 13.34 4.966 -8.412 -2.858 4.966 -8.412CuadSR-I CuadSR3BP 16.97 10.705 0.000 7.805 6.040 10.705
CuadSR-I CuadSR3BX 5.09 0.000 -3.209 -3.209 -0.866 -2.972
CuadSR-I CuadSR3BXY 6.97 0.000 -4.395 -3.298 -4.395 -3.074
CuadSR-I CuadSR3BY 17.15 10.816 0.000 7.892 9.501 10.816
CuadSR-I CuadSR4AP 24.56 15.489 0.000 8.000 4.404 15.489
CuadSR-I CuadSR4AX 24.77 15.627 0.000 8.153 7.153 15.627
CuadSR-I CuadSR4AXY 15.50 9.778 0.000 7.996 7.911 9.778
CuadSR-I CuadSR4AY 16.72 10.548 0.000 7.983 10.548 9.822
CuadSR-I CuadSR4BP 3.76 2.375 -1.426 2.375 2.166 -1.426
CuadSR-I CuadSR4BX 5.72 0.000 -3.608 -3.608 -1.776 -2.490
CuadSR-I CuadSR4BXY 7.10 0.000 -4.479 -3.678 -4.479 -2.570
CuadSR-I CuadSR4BY 7.69 4.849 -1.325 2.445 4.849 -1.325
CuadSR-S CuadSR2AP 45.10 28.448 0.000 15.836 27.909 28.448
CuadSR-S CuadSR2AY 35.53 22.413 0.000 15.745 22.413 22.208
CuadSR-S CuadSR2BP 15.49 9.771 0.000 9.771 5.611 7.172CuadSR-S CuadSR2BX 27.88 0.000 -15.012 -13.904 -13.565 -15.012
Rombo2 RSR1P 2.66 0.840 0.000 0.024 0.840 0.275
Rombo2 RSR1X 2.98 0.000 -0.940 -0.090 -0.940 -0.373
Rombo2 RSR1XY 2.54 0.802 -0.014 -0.014 0.802 0.232
Rombo2 RSR1Y 2.88 0.000 -0.908 -0.049 -0.908 -0.342
Rombo2 RSR3P 7.82 2.466 0.000 0.091 2.466 0.088
Rombo2 RSR3X 8.06 0.000 -2.543 -0.135 -2.543 -0.131
Rombo2 RSR3XY 7.76 2.447 -0.009 -0.009 2.447 0.014
Rombo2 RSR3Y 7.69 0.000 -2.427 -0.032 -2.427 -0.068
Rombo2 RSR4P 6.20 1.955 0.000 0.115 1.955 0.136
Rombo2 RSR4X 6.12 0.000 -1.930 -0.098 -1.930 -0.057
Rombo2 RSR4XY 6.00 1.893 0.000 0.001 1.893 0.058
Rombo2 RSR4Y 5.83 0.016 -1.839 0.016 -1.839 -0.006
*** Maximum Stress Summary for Each Load Case
Summary of Maximum Usages by Load Case:
Load Case Maximum Element ElementUsage % Label Type
------------------------------------ Hiptesis A 89.13 Mo1P Angle
Hiptesis B 92.71 Mo1P Angle
Hiptesis C 93.45 Mo1P Angle
-
5/27/2018 Memoria de C lculo Final - Torre Autosoportada A+3 - 60 kV - ELSE.pdf
28/28
ELECTRO SUR ESTE S.A.A. MC-TAS-A+3/60-ELSETORRES AUTOSOPORTADAS 138 KV Y 60 KV REVISIN: 0MEMORIA DE CLCULO FINAL TORRE AUTOSOPORTADA A+3 / 60 KV FECHA: OCT-12______________________________________________________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________________ELECTROCOM INGENIEROS S.A.C. PAG. 28
Group Summary (Compression Portion):
Group Group Angle Angle Steel Max Usage Max Comp. Comp. Comp. L/R Comp. Comp. RLX RLY RLZ L/R KL/R Length Curve No.Label Desc. Type Size Strength Usage Cont- Use Control Force Control Capacity Connect. Connect. Comp. No. Of
rol In Member Load Shear Bearing Member BoltsComp. Case Capacity Capacity Comp.
(MPa) % % (kN) (kN) (kN) (kN) (m)----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Mont1A Montantes Seccin Troncocnica - Tipo 1 SAE L 4" x 4" x 1/4" 250.0 93.45 Comp 93.45 Mo1P -260.748Hiptesi 279.009 592.956 362.903 0.200 0.200 0.200 58.82 58.82 6.028 1 6Mont1B Montantes Seccin Troncocnica - Tipo 2 SAE L 4" x 4" x 1/4" 250.0 69.84 Comp 69.84 Mo5P -194.869Hiptesi 279.009 592.956 362.903 0.400 0.400 0.400 58.82 58.82 3.014 1 6
Mont2A Montantes Seccin Recta - Tipo 1 SAE L 3" x 3" x 1/4" 250.0 68.62 Comp 68.62 MoSR1P -131.378Hiptesi 191.457 197.652 241.935 0.800 0.800 0.800 76.25 76.25 1.460 1 4
Mont2B Montantes Seccin Recta - Tipo 2 SAE L 3" x 3" x 5/16" 250.0 0.00 0.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.00 0.00 0.000 0 0
CGuarda Montante Cable de Guarda SAE L 2" x 2" x 3/16" 250.0 34.94 Comp 34.94 CGP -22.081Hiptesi 63.205 126.156 145.161 0.333 0.333 0.333 121.85 121.85 3.724 4 4
Cruceta Cruceta SAE L 2" x 2" x 3/16" 250.0 57.66 Comp 57.66 Cruc2Y -36.372Hiptesi 69.726 63.078 72.581 0.500 0.500 0.500 114.12 114.12 2.325 1 2
Riostra Riostra SAE L 1 1/2" x 1 1/2" x 3/16" 250.0 54.95 Tens 0.00 Rios3Y 0.000 21.320 63.078 72.581 0.500 0.500 0.500 180.16 180.16 2.746 4 2
Rombo1 Rombo Seccin Troncocnica SAE L 2" x 2" x 3/16" 250.0 3.29 Comp 3.29 Romb1X -1.037Hiptesi 31.987 31.539 36.290 1.000 1.000 0.500 171.94 171.94 2.682 4 1
Rombo2 Rombo Seccin Recta SAE L 1 1/2" x 1 1/2" x 3/16" 250.0 8.06 Comp 8.06 RSR3X -2.543Hiptesi 44.034 31.539 36.290 1.000 1.000 1.000 125.28 125.28 0.955 4 1
CuadSTC Cuadros Principales SAE L 2 1/2" x 2 1/2" x 3/16" 250.0 27.94 Comp 27.94 Cuad1AXY -8.811Hiptesi 54.139 31.539 36.290 1.000 1.000 1.000 148.36 148.36 1.896 4 1
CuadSR-I Cuadros Seccin Recta - Inferior SAE L 2" x 2" x 3/16" 250.0 36.36 Comp 36.36 CuadSR1AXY -22.935Hiptesi 100.578 63.078 72.581 1.000 1.000 1.000 66.26 66.26 0.675 1 2
CuadSR-S Cuadros Seccin Recta - Superior SAE L 2" x 2" x 3/16" 250.0 45.10 Tens 27.88 CuadSR2BX -15.012Hiptesi 53.850 63.078 72.581 1.000 1.000 1.000 132.51 132.51 1.350 4 2
Punton Punton SAE L 2 1/2" x 2 1/2" x 3/16" 250.0 50.24 Comp 50.24 PuntAY -22.790Hiptesi 75.072 49.413 45.363 0.250 0.250 0.250 125.95 125.95 6.440 4 1
Diag1A Diagonal STC - Primera SAE L 2" x 2" x 3/16" 250.0 57.21 Comp 57.21 DiagA1Y -13.694Hiptesi 23.935 31.539 36.290 0.544 0.544 0.250 198.76 198.76 5.701 4 1
Diag1B Diagonal STC - Segunda SAE L 2" x 2" x 3/16" 250.0 62.93 Comp 62.93 DiagB1Y -17.109Hiptesi 27.186 31.539 36.290 0.544 0.544 0.250 186.50 186.50 5.350 4 1
Diag1C Diagonal STC - Tercera SAE L 2" x 2" x 3/16" 250.0 51.59 Comp 51.59 DiagC1Y -16.271Hiptesi 33.086 31.539 36.290 0.550 0.550 0.450 169.06 169.06 3.827 4 1
Diag1D Diagonal STC - Cuarta SAE L 2" x 2" x 3/16" 250.0 84.78 Comp 84.78 DiagD1Y -21.345Hiptesi 25.178 31.539 36.290 0.550 0.550 0.550 193.80 193.80 3.590 4 1
Diag1E Diagonal STC - Quinta SAE L 2" x 2" x 3/16" 250.0 55.76 Tens 54.19 DiagE1Y -17.090Hiptesi 64.178 31.539 36.290 0.550 0.550 0.550 120.73 120.73 2.236 4 1
Diag1F Diagonal STC - Sexta SAE L 2" x 2" x 3/16" 250.0 69.20 Comp 69.20 DiagF1Y -21.824Hiptesi 70.767 31.539 36.290 0.550 0.550 0.550 112.83 112.83 2.090 1 1
Diag1G Diagonal STC - Sptima SAE L 2" x 2" x 3/16" 250.0 0.00 0.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.00 0.00 0.000 0 0
DiagSRA Diagonal Seccin Recta - Tipo 1 SAE L 1 1/2" x 1 1/2" x 3/16" 250.0 89.07 Comp 89.07 DiagSR1BP -28.093Hiptesi 40.642 31.539 36.290 0.500 0.500 0.500 130.48 130.48 1.988 4 1
DiagSRB Diagonal Seccin Recta - Tipo 2 SAE L 2" x 2" x 3/16" 250.0 0.00 0.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.00 0.00 0.000 0 0
Group Summary (Tension Portion):
Group Group Angle Angle Steel Max Usage Max Tension Tension Tension Net Tension Tension Tension Length No. No. HoleLabel Desc. Type Size Strength Usage Cont- Use Control Force Control Section Connect. Connect. Connect. Tens. Of Of Diameter
rol In Member Load Capacity Shear Bearing Rupture Member Bolts HolesTens. Case Capacity Capacity Capacity Tens.
(MPa) % % (kN) (kN) (kN) (kN) (kN) (m) (cm)-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Mont1A Montantes Seccin Troncocnica - Tipo 1 SAE L 4" x 4" x 1/4" 250.0 93.45 Comp 72.76 Mo1XY 189.040Hiptesi 259.804 592.956 362.903 444.500 6.028 6 2.000 1.746
Mont1B Montantes Seccin Troncocnica - Tipo 2 SAE L 4" x 4" x 1/4" 250.0 69.84 Comp 52.14 Mo5XY 135.461Hiptesi 259.804 592.956 362.903 444.500 3.014 6 2.000 1.746
Mont2A Montantes Seccin Recta - Tipo 1 SAE L 3" x 3" x 1/4" 250.0 68.62 Comp 49.41 MoSR2XY 87.779Hiptesi 177.671 197.652 241.935 254.000 1.460 4 2.000 1.746
Mont2B Montantes Seccin Recta - Tipo 2 SAE L 3" x 3" x 5/16" 250.0 0.00 0.00 0.000 0.000 0.000 0.000 0.000 0.000 0 0.000 0
CGuarda Montante Cable de Guarda SAE L 2" x 2" x 3/16" 250.0 34.94 Comp 18.56 CGXY 15.269Hiptesi 82.246 126.156 145.161 155.388 3.724 4 2.000 1.429
Cruceta Cruceta SAE L 2" x 2" x 3/16" 250.0 57.66 Comp 13.57 Cruc3Y 8.558Hiptesi 89.331 63.078 72.581 63.500 2.325 2 1.000 1.429
Riostra Riostra SAE L 1 1/2" x 1 1/2" x 3/16" 250.0 54.95 Tens 54.95 Rios2Y 33.663Hiptesi 61.262 63.078 72.581 65.130 2.746 2 1.000 1.429
Rombo1 Rombo Seccin Troncocnica SAE L 2" x 2" x 3/16" 250.0 3.29 Comp 1.49 Romb1P 0.470Hiptesi 89.331 31.539 36.290 31.750 2.682 1 1.000 1.429
Rombo2 Rombo Seccin Recta SAE L 1 1/2" x 1 1/2" x 3/16" 250.0 8.06 Comp 7.82 RSR3P 2.466Hiptesi 61.262 31.539 36.290 31.750 0.955 1 1.000 1.429
CuadSTC Cuadros Principales SAE L 2 1/2" x 2 1/2" x 3/16" 250.0 27.94 Comp 22.28 Cuad1AY 7.026Hiptesi 116.549 31.539 36.290 39.688 1.896 1 1.000 1.429
CuadSR-I Cuadros Seccin Recta - Inferior SAE L 2" x 2" x 3/16" 250.0 36.36 Comp 24.77 CuadSR4AX 15.627Hiptesi 89.331 63.078 72.581 79.375 0.675 2 1.000 1.429
CuadSR-S Cuadros Seccin Recta - Superior SAE L 2" x 2" x 3/16" 250.0 45.10 Tens 45.10 CuadSR2AP 28.448Hiptesi 89.331 63.078 72.581 79.375 1.350 2 1.000 1.429
Punton Punton SAE L 2 1/2" x 2 1/2" x 3/16" 250.0 50.24 Comp 48.66 PuntAXY 21.545Hiptesi 113.147 49.413 45.363 44.275 6.440 1 1.000 1.746Diag1A Diagonal STC - Primera SAE L 2" x 2" x 3/16" 250.0 57.21 Comp 37.08 DiagA1XY 11.694Hiptesi 89.331 31.539 36.290 39.688 5.701 1 1.000 1.429
Diag1B Diagonal STC - Segunda SAE L 2" x 2" x 3/16" 250.0 62.93 Comp 47.32 DiagB1XY 14.925Hiptesi 89.331 31.539 36.290 39.688 5.350 1 1.000 1.429
Diag1C Diagonal STC - Tercera SAE L 2" x 2" x 3/16" 250.0 51.59 Comp 48.02 DiagC1XY 15.146Hiptesi 89.331 31.539 36.290 39.688 3.827 1 1.000 1.429
Diag1D Diagonal STC - Cuarta SAE L 2" x 2" x 3/16" 250.0 84.78 Comp 62.06 DiagD1XY 19.572Hiptesi 89.331 31.539 36.290 39.688 3.590 1 1.000 1.429
Diag1E Diagonal STC - Quinta SAE L 2" x 2" x 3/16" 250.0 55.76 Tens 55.76 DiagE1XY 17.588Hiptesi 89.331 31.539 36.290 39.688 2.236 1 1.000 1.429
Diag1F Diagonal STC - Sexta SAE L 2" x 2" x 3/16" 250.0 69.20 Comp 60.51 DiagF1XY 19.084Hiptesi 89.331 31.539 36.290 39.688 2.090 1 1.000 1.429
Diag1G Diagonal STC - Sptima SAE L 2" x 2" x 3/16" 250.0 0.00 0.00 0.000 0.000 0.000 0.000 0.000 0.000 0 0.000 0
DiagSRA Diagonal Seccin Recta - Tipo 1 SAE L 1 1/2" x 1 1/2" x 3/16" 250.0 89.07 Comp 64.28 DiagSR2AXY 20.273Hiptesi 61.262 31.539 36.290 34.586 1.988 1 1.000 1.429
DiagSRB Diagonal Seccin Recta - Tipo 2 SAE L 2" x 2" x 3/16" 250.0 0.00 0.00 0.000 0.000 0.000 0.000 0.000 0.000 0 0.000 0