VR6 Voltage Regulators
-
8/6/2019 New VR6 [Modo de ad
2/35
VR6-A
-
8/6/2019 New VR6 [Modo de ad
3/35
VR6-B
-
8/6/2019 New VR6 [Modo de ad
4/35
Product Introduction
Replacement for VR3 and VR3F VR6-B replaced the VR3F in Larne and Griffin
, VR6-A still in reliability test VR6-A and VR6-B to replace all VR3s and VR3Fs
-
8/6/2019 New VR6 [Modo de ad
5/35
Why a VR6?
VR3(F) designed in 1980s with 1980stechnology com onents becomin obsolete not designed for all the applications
Supplier contract runs out June 2002
Improvements needed for todays marketplace
-
8/6/2019 New VR6 [Modo de ad
6/35
Improvements UL508A recognized/ CSA certified
Knee Frequency Adjustment Stability Adjustment
Same model works with SE and PM generators Operates at engine speed of 500 RPM and above
Single phase sensing with SE and PMs Improved response time
-
8/6/2019 New VR6 [Modo de ad
7/35
Why 2 VR6s
Regulators functionally interchangeable Solves possible quality or supply problems
-
8/6/2019 New VR6 [Modo de ad
8/35
VR6-B Specifications AC Input Power: Self Excited, 180 to 264 VAC, single phase or three phase,
50/60 Hz. PMG, three phase, 90 to 120 VAC, 100 to 240 Hz,
3125 VA maximum.
PMG, single phase, 240 VAC, 100 to 240 Hz, 3125 VA. Output Power (with a 240 VAC Input):
12 Amps DC @ 65 VDC maximum continuous.
25 Amps DC @ 125 VDC forcing for 10 seconds. AC Sensing Voltage:
True RMS three phase or single phase,180 to 264 VAC, 60 Hz;
150 to 220 VAC, 50 Hz.
-
8/6/2019 New VR6 [Modo de ad
9/35
VR6-B Specifications Regulation Accuracy:
Less than 1% of voltage setpoint to full load. Voltage Drift:
Less than 1% voltage variation for a 40C (104F) change. Response Time:
Maximum of 4 milliseconds. Volts/Hz characteristic:
1 V/Hz with jumper between terminals 6A & 8. 2 V/Hz, with
jumper removed. Knee Frequency:
Knee frequency adjustable from 45 to 65 Hz.
-
8/6/2019 New VR6 [Modo de ad
10/35
VR6-B Specifications Voltage Adjust Range:
+10% to 25% if regulator sensing voltage. External Voltage Adjust Rheostat:
10 kohm, 2 W, potentiometer.
Reactive Droop Adjustment . 1 A or 5 A CT, less than 10 VA burden. Internal CT burden resistor. Adjustable from 0 to 10%, at rated current, 0.8 power factor.
-
8/6/2019 New VR6 [Modo de ad
11/35
VR6-B Specifications Power Dissipation:
50 W maximum. EMI Suppression: Internal filter.
o age u - p: Internal provisions for automatic voltage build-up from
generator residual voltages as low as six VAC.
Over Excitation Shutdown: Over excitation protection starts timing at 90 VDC, 5% andtakes the output to zero in greater than 30 seconds.
The output can be 125 VDC for greater than 10 seconds.
-
8/6/2019 New VR6 [Modo de ad
12/35
VR6-B Specifications UL Recognized/CSA Certified.
UL Recognized per Standard 508, UL File NO. E97035. CSA Certified per Standard CAN/CSA-C22.2 No. 14-95, CSA File No. LR
23131. CE Conformity: Conforms to:
Radiated Emissions EN50081-2.
Electric field EN61000-4-3 (10 V/m). Conducted EN61000-4-6 (10 VRMS). Conducted Emissions EN50081-2 (EN55011, Class A). ESD Immunity EN50082-2 (4 KV contact, 8 KV air). EFT Immunity EN50082-2 (2 KV coupling clamp). Magnetic Immunity EN50082-2 (30ARMS, 50 Hz). Safety: EN61010-1.
-
8/6/2019 New VR6 [Modo de ad
13/35
VR6-B Specifications Operating and Storage Temperature:
-40C (-40F) to +70C (+158F). Shock:
Withstands up to 20 g in each of three mutually
perpen cu ar axes. Vibration: Withstands the following accelerations at the stated
frequency: 0.5 g; 18 to 2000 Hz. Weight:
Approximately 1.1 kg (2.5 lbs.).
-
8/6/2019 New VR6 [Modo de ad
14/35
Wiring
-
8/6/2019 New VR6 [Modo de ad
15/35
5A Droop
Circuit5 Amp CT
5A 6
VR6-B
-
8/6/2019 New VR6 [Modo de ad
16/35
1A DroopCircuit1 Amp CT
5 6
VR6-B
-
8/6/2019 New VR6 [Modo de ad
17/35
Sensing Wires
VR3FSE &VR3FPM3-Phase
VR6-BSE & PM3-Phase
96A20
No jumper from 6A to 9
20
24
22 20 24
22
VR3FSESingle-Phase
2820
VR6-BSE & PM
Single-Phase
20
22
-
8/6/2019 New VR6 [Modo de ad
18/35
Power Wiring
VR3FSE VR6-BSE
VR3FPM
26
28
30
VR6-BPM
26
28
30
20-2822-3024-26
-
8/6/2019 New VR6 [Modo de ad
19/35
Excitation WiringVR3(F)SE and VR3(F)PM VR6-B SE & PM
F1 F2 F1 F2
-
8/6/2019 New VR6 [Modo de ad
20/35
VAR/PF Controller Basler SCP-250VAR/PF Controller
C A3
2
Without
Var/PF Controller 2 3
VR6-B VR6-B
-
8/6/2019 New VR6 [Modo de ad
21/35
Remote Adjust Pot
74
Without10K
6A 7
With
VR6-B VR6-B
-
8/6/2019 New VR6 [Modo de ad
22/35
Volts/Hz Slope2 pu volts/hz slope(no jumper 6A to 8)
1 pu volts/hz slope
86A
VR6-BVR6-B
-
8/6/2019 New VR6 [Modo de ad
23/35
VR6-B Adjustments
-
8/6/2019 New VR6 [Modo de ad
24/35
Droop Adjustment
Droop Adjustment (DRP)
Is made for parallel operation soa a genera ors w ave e
same % reactive voltage droop.
-
8/6/2019 New VR6 [Modo de ad
25/35
NOTICE---Do not operate generator at a voltagegreater than 5% above name plate rating.
Factory CalibrationFactory Voltage Adjust RangeCalibration (FAC CAL)
The factory calibration adjustment (FAC CAL)should be used by factory technicians only. Thefollowing procedure can be used if the factory
With the voltage regulator operating on agenerator, adjust the calibration potentiometer fully ccw and the voltage adjust potentiometer fully cw. Adjust the calibration potentiometer cwuntil the generator voltage is 252 1 VAC for 60Hz (226 1 VAC for 50 Hz) . Adjust the voltageadjust ccw and verify the generator voltage isbetween 156 and 180 VAC. The unit is calibrated
and the calibration potentiometer can be sealed.
-
8/6/2019 New VR6 [Modo de ad
26/35
Voltage AdjustmentVoltage Adjustment (VLT ADJ)
1. Installation of a jumper across terminals 4 and 7allows the internal (front panel) VLT ADJ
adjustment to vary the generator nominal voltageover the operating range.
2. Remove the jumper between terminals 4 and 7
potentiometer across terminals 6A and 7 to allowoperation of the external voltage adjustpotentiometer.The internal voltage adjustment should be set fullyCW for proper operation of the external adjustment.
-
8/6/2019 New VR6 [Modo de ad
27/35
Frequency Compensation
100%
Knee Frequency
Frequency
V o
l t a g
100%
50%
50%
1 Volts/Hz Slope
2 Volts/Hz Slope
-
8/6/2019 New VR6 [Modo de ad
28/35
Knee FrequencyAdjustment
Knee Frequency Adjustment (UF KNEE)The underfrequency knee can be set for 50 (60) Hz
operation as described in the following paragraphs.1. Adjust the generator frequency for 50 (60) Hz.2. Adjust the underfrequency potentiometer (UF) fullyCCW, or until voltage does not increase with further turning.3. Adjust the Voltage Adjust for 200 (240) VACsensing as seen on terminals 20, 22 or 24.4. Adjust the underfrequency potentiometer (UF) CWuntil the volta e be ins to decrease.
5. Adjust the underfrequency potentiometer (UF)CCW until the voltage just returns to the value set inStep 3.6. The underfrequency knee is now set just below thenominal operating frequency. Further rotation in theCCW direction will lower the frequency at whichunderfrequency compensation begins.7. Connecting a jumper from terminal 8 to terminal 6awill provide an underfrequency slope of 1 pu V/Hz.
No connection to terminal 8 will result in anunderfrequency slope of 2 pu V/Hz.
-
8/6/2019 New VR6 [Modo de ad
29/35
StabilityAdjustment
Stability Adjustment (STB) .
-
8/6/2019 New VR6 [Modo de ad
30/35
Voltage Regulator - Test
Illustration 15Page 33
-
8/6/2019 New VR6 [Modo de ad
31/35
Test Procedure
-
8/6/2019 New VR6 [Modo de ad
32/35
10/12 Lead PMExcited with 3-Phase Sensing
Illustration 16Page 36
-
8/6/2019 New VR6 [Modo de ad
33/35
Notes page 35
10/12 L d S lf E it d With
-
8/6/2019 New VR6 [Modo de ad
34/35
10/12 Lead Self-Excited With3-Phase Sensing
Illustration 18Page 38
-
8/6/2019 New VR6 [Modo de ad
35/35