intertr ippin g DIP 5000
Commercial presentat ion
-
7/28/2019 Presentation DIP5000 En
3/31
> Titre de la prsentation - Date - Rfrences3 3
In t roduct ion
In t roduct ion
-
7/28/2019 Presentation DIP5000 En
4/31
> Titre de la prsentation - Date - Rfrences4 4
in ter t r ipp ing Funct ion
Intertripping is designed to transfer protection commands originating, in
most cases, from distance protection relay contacts to ONE remote
location through a communication medium. Communication between the
intertripping equipment is a bidirectional point-to-point communication
Poste lectrique A
Protection relay
Digital Telecom
network
Intertripping
DIP 5000
Poste lectrique B Ligne HT
And / or direct fiber optic link
Intertripping
DIP 5000
Monitoring system
TMS 5000
Protection relay
-
7/28/2019 Presentation DIP5000 En
5/31
> Titre de la prsentation - Date - Rfrences5 5
in ter t r ipp ing Funct ion
Functioning in voice frequency mode on Power line carrier
Line Trap
H.V.
TRANSPORT
NETWORK
Services
Control
command
or
SCADA
Services
Power line
Carrier
PLC5000
Line matching unit
LMU5000
Intertripping
DIP 5000
Management
software for
PLC 5000 and
DIP 5000
http://images.google.fr/imgres?imgurl=www.tsr.ch/emission/abe/photo/ondes/pylones.jpg&imgrefurl=http://www.tsr.ch/emission/abe/archive/98/980929.html&h=140&w=175&prev=/images%3Fq%3Dhaute%2Btension%26svnum%3D10%26hl%3Dfr%26lr%3D%26ie%3DUTF-8%26oe%3DUTF-8http://images.google.fr/imgres?imgurl=www.cfmo.ch/menus/exploitation/Distribution/Notre%2520distribution_fichiers/image006.jpg&imgrefurl=http://www.cfmo.ch/menus/exploitation/Distribution/Notre%2520distribution.htm&h=242&w=321&prev=/images%3Fq%3Dhaute%2Btensio -
7/28/2019 Presentation DIP5000 En
6/31
> Titre de la prsentation - Date - Rfrences6 6
intertr ipp ing Cri ter ia
The 3 main characteristics of intertripping are :
Transfer time : During a fault, damage incurred to HV equipment will
depend on the fault clearance time.
The transfer time of the intertripping equipment, (the time between
the acquisition of a protection signal to its restitution at the otherend), must therefore be as short as possible to minimize the fault
clearance time.
Reliability/Dependability : Since the communication can be altered by noise
due to the high voltage environment, the intertripping signal shall be
transmitted in a way to minimize the risk of losing a command that would
lead to the non functioning of the fault clearance process. This value is
expressed as the Probability of Missing commandPmc.
-
7/28/2019 Presentation DIP5000 En
7/31> Titre de la prsentation - Date - Rfrences7 7
intertr ipp ing Cri ter ia
The 3 main characteristics of a intertripping are (continued ):
Security : Since intertripping is often used to protect strategic lines on which a shut-down would have heavy consequences, the intertripping has to ensure that a
command that can disconnect an HV line is a TRUE command and not due to
noise coming from the HV environment. This value is expressed as theprobability of unwanted command Puc for the worst-case being with the highest
noise .
All intertripping equipment shall meet as a minimum, the security,
dependability and transfer time criteria defined by an IEC
standard IEC 60834-1
-
7/28/2019 Presentation DIP5000 En
8/31> Titre de la prsentation - Date - Rfrences8 8
DIP5000 Requ irements
Dig ital TPWhat we are expec t ing From
-
7/28/2019 Presentation DIP5000 En
9/31> Titre de la prsentation - Date - Rfrences9 9
What we are waiting for from Digi tal intertripp ing
To Increase the safety of the electrical network
Faster transfer time
Increase reliability and security
Increase monitoring capabilities
Increase the number of commands
To reduce cost ownership
Easier and faster commissioning
Preserve the investment
- A faster return on Invest -
-
7/28/2019 Presentation DIP5000 En
10/31> Titre de la prsentation - Date - Rfrences10 10
DIP5000
Character ist ics and Advantages
How DIP5000 fit these
requirements
-
7/28/2019 Presentation DIP5000 En
11/31> Titre de la prsentation - Date - Rfrences11 11
DIP 5000
DIGITAL in tertr ipp ing
Built to operate for at least 25
years without maintenance
DIP 5000 isImproving transfer time and is Increasing
reliability and securityAdded security with
possibility of duplicated
power supply
-Inc rease the safety o f your electr ic al network -
Protection
Mode
Transfer Time
With E1
Interface4 or 8
commands
Reliability
(Pmc)
Security (Puc)
Worst case
Blocking 1 ms 1E-30 < 2E-7
Permissive 1 ms 1E-35 6E-14
Direct Tripping 1.5 ms 1E-19 1E-20
Faster transfer time : The fault clearance process isreduced saving expensive HV equipment.
-
7/28/2019 Presentation DIP5000 En
12/31> Titre de la prsentation - Date - Rfrences12 12
DIP 5000
DIGITAL in tertr ipp ing
Characteristics with digital communication interface
- Inc rease thesafety of you r electr ical newtork -
-
7/28/2019 Presentation DIP5000 En
13/31> Titre de la prsentation - Date - Rfrences13 13
Characteristics with voice frequency interface
DIP 5000 DIGITAL in tert rip p ing
-
7/28/2019 Presentation DIP5000 En
14/31> Titre de la prsentation - Date - Rfrences14 14
Possibility to select alarms in
case of too high transmission
time or high BER or
Programmable alarms
contacts on lengthy command
DIP 5000
DIGITAL in tertr ipp ing
Continuous self testing of theequipment and continuousmonitoring of the communicationchannel with REAL TIME BER andTransfer Time monitoring
Event and alarm recording
DIP 5000 is increasing monitoring capabilities
512 events 1 ms stamping
allowing fault analysis and
tracking
-Inc rease the safety o f your electr ic al network -
-
7/28/2019 Presentation DIP5000 En
15/31> Titre de la prsentation - Date - Rfrences15 15
DIP 5000
DIGITAL in tertr ipp ing
DIP 5000 isEasy to Install and to do commissioning
- To reduce cost ow nership -
Configuration on line, off line, downloaded on site to the local
and remote DIP5000 with PC ( digital interface only )
User friendly Man Machine
Interface Under Windows NT or
Later
-
7/28/2019 Presentation DIP5000 En
16/31> Titre de la prsentation - Date - Rfrences16 16
DIP 5000
DIGITAL in tertr ipp ing
DIP 5000 isadapated to all kind of communication
- To reduce cost ow nership -
All interfaces available to suit your needs:
Two Types of BUILT IN Single mode Optical Fiber
Medium Range
Laser 1310 nm
e.g 60 km with fiber 9/25m - 0.25 dB/km
Long rangeLaser 1550 nm
e.g 110 km with fiber 9/25m - 0.25 dB/km
Electrical interfacesj
V11/RS422
G703.1 (64 Kbit/s)G703.6 (E1 2 Mbit/s)
Analogue interface for pilot wires or communication
with Power line carrier
-
7/28/2019 Presentation DIP5000 En
17/31> Titre de la prsentation - Date - Rfrences17 17
DIP 5000
DIGITAL in tertr ipp ing
DIP 5000 is also available for voice frequency
communication
Voice frequency interface for communication on pilot wires or
leased line or communication with Power line carrier (PLC ) ( 4
wires interface ) .
Up to 4 independant commands
No requirement for extra bandwitdh when used with PLC ( silent
mode )
-
7/28/2019 Presentation DIP5000 En
18/31> Titre de la prsentation - Date - Rfrences18 18
DIP 5000
DIGITAL INTERTRIPPING
- To reduce cost ow nership -
You can use electrical converterOCM 5000 optical to electrical converter to
fit with your substation constraints
50km 50km 50km
Optic al / electr ical converter OCM 5000 developed by AREVA fo r
use in harsh su bstat ion envi ronm ent in compl iance wi th IECstandard
-
7/28/2019 Presentation DIP5000 En
19/31> Titre de la prsentation - Date - Rfrences19 19
DIP 5000
DIGITAL in tertr ipp ing
DIP 5000 isEasy to install and to commission
- To reduce cost ow nership -
Protection room Telecom room
V11
G703 64 kbit/s
G703 Mbit/s
Up to 8
Commands
Direct optical fibre
connection
DIP5000
V11Or V24
OCM5000
Analogue 4
wires
Up to 4
Commands
V11
G703 64 kbit/s
G703 2Mbit/s
Or optical I
Up to 8
CommandsDIP5000
You can use
OCM5000
converter to fit
your installation
constraints
-
7/28/2019 Presentation DIP5000 En
20/31> Titre de la prsentation - Date - Rfrences20 20
DIP 5000
DIGITAL in tertr ipp ing
DIP 5000 isEasy to Install and to commission
- To reduce cost ow nership -
Programmable alarms contacts on
lengthy command
Customer is able to qualify its link with
1. Test mode with trip transfer
2. loop back function
-
7/28/2019 Presentation DIP5000 En
21/31> Titre de la prsentation - Date - Rfrences21 21
DIP 5000
DIGITAL in tertr ipp ing
DIP 5000 ispreserving your investment
- To reduce cost ow nership -
Plug-in easy access boards
inside the DIP 5000
reducing repair time
You can easily modify your
interfaces or upgrade from
copper to optical interface
-
7/28/2019 Presentation DIP5000 En
22/31> Titre de la prsentation - Date - Rfrences22 22
DIP5000 Architecture
Techn ical data
DIP5000 T h i l d t
-
7/28/2019 Presentation DIP5000 En
23/31
> Titre de la prsentation - Date - Rfrences23 23
- in tertr ipp ing DIP 5000 -
Input / Output logic combination capacity
Firmware Up gradable on site by simple download
24 to 250 VDC power supply with power supply duplication
as an option
Up to 8 independent fast solid state relay output + 1 copycontact for each output :
Rating Max 2A, cut off power 120 W
DIP5000 Techn ical data
-
7/28/2019 Presentation DIP5000 En
24/31
> Titre de la prsentation - Date - Rfrences24 24
DIP5000 Techn ical data
- DIP 5000 Type tes ted -
Type tested as per IEC 60834-1 by Bureau
Veritas / LCIE Laboratory
Compliance with latest IEC standart :
IEC 68-2
EMC compliance as per
IEC 61000
Conforms to European Directives
EN 50204 Class A
EN 55011 Class A
EN 55022 Class A
Equipment is CE compliant.
-
7/28/2019 Presentation DIP5000 En
25/31
> Titre de la prsentation - Date - Rfrences25 25
DIP5000 Architecture
New featu res
000
-
7/28/2019 Presentation DIP5000 En
26/31
> Titre de la prsentation - Date - Rfrences26 26
DIP5000 Remote superv isio n
Access IP / LAN et network management
Possibility to connect the AREVA
TMS 5000 monitoring software to
monitor a DIP 5000 network alarm
status on a real time basis
DIP 5000 Real tim e mon ito ring
Intranet network
DIP5000 B k O ti l / di i t l i t f
-
7/28/2019 Presentation DIP5000 En
27/31
> Titre de la prsentation - Date - Rfrences27 27
DIP5000 Back up Optic al / dig ital interface
Capacity to switch communication from
the optical interface to an other digital
interface according to user definedcriteria
Main path
Alternatepath V11 or
G703
DIP5000 R f
-
7/28/2019 Presentation DIP5000 En
28/31
> Titre de la prsentation - Date - Rfrences28 28
DIP5000 References
References
DIP 5000 REFERENCES
-
7/28/2019 Presentation DIP5000 En
29/31
> Titre de la prsentation - Date - Rfrences29 29
DIP 5000 REFERENCES
MORE THAN 1500 UNITS IN OPERATION SINCE Year 2000
IN OPERATION IN MORE THAN 15 COUNTRIES FOR UP TO500 KV
NO RECORD OF FALSE OR UNWANTED COMMAND DUE TO
THE EQUIPMENT
- A REL IABLE PRODUCT IN USE IN MORE THAN
15 COUNTRIES -
DIP5000 C l i
-
7/28/2019 Presentation DIP5000 En
30/31
> Titre de la prsentation - Date - Rfrences30 30
DIP5000 Conclu sio n
Conclus ion
C l i
-
7/28/2019 Presentation DIP5000 En
31/31
Conclus ion
The Reference in terms o f intertr ippin g equipment
Increase the safety of the electrical network
Fastest transfer time
Highest level of reliability and security
Enhanced monitoring capabilities
Built in optical interface
Up to 8 independent commands
TESTED as per latest IEC and ANSI EMC requirement
Reduce your entry cost and your cost ownership Intuitive commissioning
Powerful HMI
Plug in board for easy hardware upgrade
DIP 5000 is the best way to