Download - Relay Alarm Connection(VMS)
1
Vietnam VMS Project
Power Relay Alarm Connection
1Relay Alarm Connection in ZXDU68 B201Relay Alarm Connection in ZXDU68 T301BTS Connection and ConfigurationRNC/BSC Connection and Configuration
Agenda 23Relay Alarm Connection in ZXDU68 B201Hardware Location
ZXDU68 B201 DC power supply.We will install this equipment on the rack.4
Relay Alarm Connection in ZXDU68 B201Hardware LocationThe output relay of ZXDU68 B201 is on SIB board of the Monitoring Unit.On SIB board, X16, X17, X18 and X19 are the output relay ports which we can use to connect BTS.5Relay Alarm Connection in ZXDU68 B201SIB Board Interfaces Description
6Relay Alarm Connection in ZXDU68 B201Cable Connection
X16, X17, X18 and X19 are the output relay ports which we can use to connect BTS.7Relay Alarm Connection in ZXDU68 B201Parameter Configuration on Monitoring Unit of ZXDU68 B201
Output relay can be modified as the figure below.8Relay Alarm Connection in ZXDU68 B201Parameter Configuration on Monitoring Unit of ZXDU68 B201
Enter the Alarm Para. We can set the output relay. We can check the meaning of the Parameter as figure below.
9Relay Alarm Connection in ZXDU68 B201Relay Alarm Connection in ZXDU68 T301BTS Connection and ConfigurationRNC/BSC Connection and Configuration
Agenda Relay Alarm Connection in ZXDU68 T30110
The output relay of ZXDU68 T301 is on SIB board of the Monitoring Unit.On SIB board, X15, X16, X17 and X18 are the output relay ports which we can use to connect BTS, RNC and BSC.Hardware Location11Relay Alarm Connection in ZXDU68 T301SIB Board Interfaces Description
Relay Alarm Connection in ZXDU68 T301Use the cable to connect SIB board to BSC and BTS equipment as figure.
12Cable Connection
Relay Alarm Connection in ZXDU68 T30113Parameter Configuration on Monitoring Unit of ZXDU68 T301
14Relay Alarm Connection in ZXDU68 T301Parameter Configuration on Monitoring Unit of ZXDU68 T301
Enter the Alarm Para. We can set the output relay as figure.
15Relay Alarm Connection in ZXDU68 T301Parameter Configuration on Monitoring Unit of ZXDU68 T301Alarm typeAlarm levelrelayAC Aux SW offAC main SW offAC power offMajorA1SMR AlarmMajorA2DC Under-Vol.MajorA3Bat loop breakMajorA4othersdefault0Configure the parameter of output relay as below
16Relay Alarm Connection in ZXDU68 B201Relay Alarm Connection in ZXDU68 T301BTS Connection and ConfigurationRNC/BSC Connection and Configuration
Agenda Relay Cable for BTS and BSC
Relay Cable for BTS and BSC
NoInterface DesignationSignal DescriptionCable Color1DB25_1NODEB_IN1PWhiteDB25_14NODEB_IN1NBlue2DB25_2NODEB_IN2PWhiteDB25_15NODEB_IN2NOrange3DB25_3NODEB_IN3PWhiteDB25_16NODEB_IN3NGreen4DB25_4NODEB_IN4PWhiteDB25_17NODEB_IN4NBrownBTS Connection and Configuration18Relay Connection between ZXG10 B8700 and ZXDU68 B201
19BTS Connection and ConfigurationRelay Connection between ZXG10 B8800 and ZXDU68 B201
20BTS Connection and ConfigurationRelay Connection between ZXG10 B8900 and ZXDU68 B201
21Relay Alarm Connection in ZXDU68 B201Relay Alarm Connection in ZXDU68 T301BTS Connection and ConfigurationRNC/BSC Connection and Configuration
Agenda 22iTC Connection and ConfigurationRelay Connection between iTC and ZXDU68 T301
23BSC Connection and ConfigurationRelay Connection between BSC and ZXDU68 T301
24RNC Connection and ConfigurationRelay Connection between RNC and ZXDU68 T301
Agenda 25