ee&cs (2)
TRANSCRIPT
-
8/3/2019 EE&CS (2)
1/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 1
EX.NO. 1A
LOAD TEST ON DC SHUNT MOTOR
OBJECTIVETo conduct the Load test on DC shunt motor and draw the characteristic curves.
APPARATUS REQUIRED
S.No Equipments Type Range Quantity
1. Voltmeter MC (0-300)V 1
2. Ammeter MC (0-15)A 1
3. Tachometer Digital - 1
4. Rheostat Wire wound 360 /1.1A 1
5. Connecting Lead - - -
PROCEDURE
1. Note down the name plate details of the motors.
2. Connections are made as per the circuit diagram shown in figure.
3. Supply is given by closing the DPST switch.
4. Using the DC three point starter, start the motors.
5. The field rheostat is adjusted to run the motor at rated speed.
6. At no load condition, the input voltage, current and speed are noted and enter the value in
the table.
7. Increase the load current in the steps of1/4th, 1/2th, 3/4th, full load and one 1/4th of the
load.
8. Note down the corresponding ammeter, voltmeter, spring balance reading and speed and
enter the values in the table.
9. Then the load is gradually decreased and field rheostat is brought to the minimum
resistance position and the supply is switched off.
10. The torque, input power, output power and percentage efficiency are calculated by using
the using the above formula and enter the values in the table.
-
8/3/2019 EE&CS (2)
2/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 2
-
8/3/2019 EE&CS (2)
3/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 3
FORMULA USED
1. Torque (T) = (S1-S2)*R*9.81 in Nm
S1, S2 spring balance reading in Kg
R Radius of the brake drum in M
2. Input power (Pi) = VL IL in watts
VL Line voltage in volts.
IL Line current in amps.
3. Output power(Po) = 2NT/60 in watts
N - Speed in rpm
T - Torque in rpm
4. Efficiency () = (output power/input power)*100 in %
TABULATION
S.No
Load
Current
IL
inAmps
Load
Voltage
VL
in volts
Input
power
Pi in
watts
ILVL
Speed
N in
rpm
Spring balance
reading in Kg Torque
T
in Nm
Output
Power
Po
in watts
Efficiency
in %S1 S2 S1~S2
-
8/3/2019 EE&CS (2)
4/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 4
GRAPH
The performance characteristics curves are drawn as shown in figure
Electrical characteristics
1.Output Power Vs Line Current
2.Output power Vs Speed
3.Output power Vs Torque
4.Output power Vs Efficiency
Mechanical characteristics
1. Torque Vs Speed
-
8/3/2019 EE&CS (2)
5/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 5
MODEL CALCULATION
RESULT
Thus the load test on DC shunt motor was conducted and the characteristic curves were
drawn.
-
8/3/2019 EE&CS (2)
6/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 6
EX.NO.1 B
LOAD TEST ON DC SERIES MOTOR AIM
To conduct the Load test on DC series motor and draw the characteristic curves.
APPARATUS REQUIRED
S.No Equipments Type Range Quantity
1. Voltmeter MC (0-15)A 1
2. Ammeter MC (0-300)V 1
3. Tachometer Digital - 1
4. Connecting Lead - - -
Theory
As the name implies the field coils, consisting of few turns of thick wire, are connected in series
the armature, as illustrated in figure. The cross sectional area of the wire used for field coils has to be
fairly large to carry the armature current, but owing to the higher current, the number of turns of wire in
them need not be large. In D.C series motor,
Armature Current, Ia = Series field current, Ise
= Line current, IL = I
Back emf developed, Eb = V I(Ra+Rse)
Power drawn from supply mains = VI
Mechanical Power Developed
Pm = Power input Losses in armature and field
= VI - I2
(Ra + Re) = I [V- I (Ra+Rse)] = EbI
= VIa I2
aRa= Ia (V - IaRa) = EbI
-
8/3/2019 EE&CS (2)
7/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 7
PRECAUTION
The DC series motor should always be started with some load. Otherwise the speed will be
enormous and fuse will blown out.
PROCEDURE
1. Note down the name plate details of the motors.
2. Connections are made as per the circuit diagram.
3. Ensure that 1/4th of the load are applied to the brake drum.
4. Supply is given by closing the DPST switch and the motor is started.
5. At 1/4th load condition, Note down the ammeter, voltmeter, spring balance reading and
speed and enter the values in the table.
6. Then increase the load current in the steps of1/2th
, 3/4th
rated value and one 125% of the
rated value.
7. Note down the corresponding ammeter, voltmeter, spring balance reading and speed and
enter the values in the table.
8. The torque, input power, output power and percentage efficiency are calculated by using
the using the above formula and tabulated in observation table.
FORMULA USED
1. Torque (T) = (S1- S2)*R*9.81 in Nm
Where, S1, S2 Spring Balance Reading in Kg
R Radius of the brake drum in m
2. Input power (Pi) = VLIL in watts
VL Line voltage in volts.
IL Line current in amps.
3. Output power(Po) = 2NT/60 in watts
N Speed in rpm
T Torque in Nm
4. Efficiency () = (Output Power/ Input Power)*100 in %
-
8/3/2019 EE&CS (2)
8/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 8
-
8/3/2019 EE&CS (2)
9/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 9
TABULATION
S.No
Load
Current
IL
inAmps
Load
Voltage
VL
in volts
Input
power
Pi in
watts
ILVL
Speed
N in
rpm
Spring balance
reading in Kg Torque
T
in Nm
Output
Power
Po
in watts
Efficiency
in %
S1 S2 S1~S2
-
8/3/2019 EE&CS (2)
10/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 10
GRAPH
The performance characteristics curves are drawn as shown in figure
a) Electrical characteristics
1. Output power Vs Line current
2. Output power Vs Speed
3. Output power Vs Torque
4. Output power Vs Efficiency
b) Mechanical characteristics
1. Torque Vs Speed
-
8/3/2019 EE&CS (2)
11/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 11
MODEL CALCULATION
RESULT
Thus the load test on DC series motor was conducted and the characteristic curves were drawn.
-
8/3/2019 EE&CS (2)
12/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 12
EX.NO.2A
OPEN CIRCUIT CHARACTERISTICS AND LOAD CHARACTERISTICS OF DC SHUNT GENERATOR
AIM
To obtain open circuit characteristics and load characteristics of DC shunt generator.
APPARATUS REQUIRED
S. No Description Range Quantity
1. Voltmeter (0-300V)MC 1
2. Ammeter (0-2A)MC 1
3. Ammeter (0-10A)MC 1
4. Rheostat 400/1.4A 2
5. Tachometer - 1
6. Connecting wires - As per requirement
FORMULAE
Eg = V + Ia Ra (Volts)
Ia = IL + If(Amps)
Eg : Generated emf in Volts
V : Terminal Voltage in Volts
Ia : Armature Current in Amps
IL : Line Current in Amps
If : Field Current in Amps
Ra : Armature Resistance in Ohms
-
8/3/2019 EE&CS (2)
13/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 13
-
8/3/2019 EE&CS (2)
14/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 14
PROCEDURE
I Open Circuit Characteristics
1. Connections are made as shown in the circuit diagram
2. The motor field rheostat should be in minimum resistance position and the generator field
rheostat should be in maximum resistance position while switching ON and switching OFF
the supply side DPST switch.
3. Ensure that the DPST switch on the load side is open.
4. Switch ON the supply DPST switch.
5. Using the 3- point starter the DC motor is started and it is brought to rated speed by
adjusting the motor field rheostat.
6. Keeping the DPST switch on the load side open, the generated voltage Eg and field current
Ifof generator is noted down by varying the generator field rheostat.
7. The above step is repeated till 125 % of rated voltage is reached.
8. Plot the graph for reading taken as shown in model graph.
II Load Characteristics
Connections are made as shown in the circuit diagram
1. The motor field rheostat should be in minimum resistance position and the generator field
rheostat should be in maximum resistance position while switching ON and switching OFF
the supply side DPST switch.
2.
Ensure that the DPST switch on the load side is open.3. Switch ON the supply DPST switch
4. The generator is brought to its rated voltage by varying the generator field rheostat.
5. The DPST switch on the load side is closed, and the load is varied for convenient steps of
load current up to 120 % of its rated capacity and the voltmeter V L and ammeter Ia
readings are observed. On each loading the speed should be maintained at rated speed.
6. Plot the graph for reading taken as shown in model graph.
-
8/3/2019 EE&CS (2)
15/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 15
TABULAR COLUMN: Open Circuit Characteristics
S.No.
Field Current
If (Amps)
Armature Voltage
Eo (Volts)
TABULAR COLUMN: Load Circuit Characteristics
S.No.
Field
Current
If (Amps)
Load
Current
IL (Amps)
Terminal
Voltage
(V) Volts
Ia = IL + If
(Amps) Eg =V + Ia Ra
(Volts)
-
8/3/2019 EE&CS (2)
16/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 16
PROCEDURE: Determination of Armature Resistance
1. Connections are made as per the circuit diagram.
2. Supply is given by closing the DPST switch.
3. Readings of Ammeter and Voltmeter are noted.
4. Armature resistance in Ohms is calculated as Ra = (Vx1.5) /I
CIRCUIT DIAGRAM: DETERMINATION OF ARMATURE RESISTANCE
TABULATION TO DETERMINATION OF ARMATURE RESISTANCE
S.No. Voltage
V (Volts)
Current
I (Amps)
Armature Resistance
Ra (Ohms)
-
8/3/2019 EE&CS (2)
17/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 17
MODEL GRAPH: Open Circuit Characteristics
MODEL GRAPH: Load Characteristics
RESULT:
Thus the open circuit characteristics and load characteristics of DC shunt generator are
obtained.
VL,
E
(Volts)
If, IL (Amps)
V Vs IL
E Vs IL
Eo
If
Critical Resistance = Eo / IfOhmsEo
(V
olts)
If (Amps)
-
8/3/2019 EE&CS (2)
18/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 18
EX.NO. 2 B
OPEN CIRCUIT CHARACTERISTICS AND LOAD CHARACTERISTICS OF DC SERIES GENERATOR
AIM
To conduct OCC and load characteristics of DC series Generator & obtain the
characteristics
APPARATUS REQUIRED
S.No Equipment Type Range Quantity
1 Ammeter MC (0-1)A 1
2 Ammeter MC (0-10)A 1
3 Voltmeter MC (0-300) V 1
4 Rheostat Wire wound 175 / 1.1 A 1
5 Rheostat Wire wound 50 /5 A 1
6 Loading Rheostat Resistive 5 KW 1
7 Tacho Meter Digital - 1
PRECAUTION
At the time of starting
1. Motor field rheostat should be kept at minimum position
2. Generator field rheostat should be kept at max position
-
8/3/2019 EE&CS (2)
19/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 19
-
8/3/2019 EE&CS (2)
20/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 20
-
8/3/2019 EE&CS (2)
21/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 21
TABULATION
(i)OCC Circuit
S.No Field CurrentOpen Circuit Voltage
(to) Volts
(ii) Load Characteristics
S.No
Load Current
IL=IF=Ia Amps
Terminal Voltage (VL)
Volts
IL(Ra +Rse) VoltsGenerated emf
Eg=VL+IL (Ra +Rse)
-
8/3/2019 EE&CS (2)
22/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 22
PROCEDURE
(i)OCC
1. Close the DPST switch and start the DC shunt motor
2. Increase field regulating resistance and bring the speed of the M/R & Generator (1500
rpm)
3. Switch On the load to increase the current through the series field winding look for any
change in speed has taken place
4. If so bring back the speed for rated speed
5. Note down the Ammeter, Voltmeter reading and enter in the tabulation
6. Repeat the steps above previous step till the generator reach the rated current
(ii) Load Characteristics
1. Close the DPST switch & start the DC shunt motor
2. Increase the regulative resistance & bring the speed of the M/R & genset equal for the
rated speed
3. Switch on some load to increase the load current and tabulate the reading
4. Switch on some load to increase the load current greater than the previous and tabulation
the readings.
5. Likewise take readings up to 125% of the rated current.
6. Switch off the supply and return the apparatus safely.
MODEL CALCULATION
-
8/3/2019 EE&CS (2)
23/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 23
MODEL GRAPH: Open Circuit Characteristics
MODEL GRAPH: Load Characteristics
RESULT
Thus the open circuit characteristics and load characteristics of DC series
generator are obtained.
Eo
If
Critical Resistance = Eo / IfOhmsEo
(V
olts)
If (Amps)
-
8/3/2019 EE&CS (2)
24/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 24
EX.NO.3
SPEED CONTROL OF DC SHUNT MOTOROBJECTIVE
To control the speed of the given DC shunt motor by field and armature control methods
and also to draw their characteristic curves.
APPARATUS REQUIRED
S.No Apparatus Type Range Quantity
1. Ammeter MC (0-25)A 1
2. Ammeter MC (0-2)A 1
3. Voltmeter MC (0-300)A 1
4. Voltmeter MC (0-50)A 1
5. Rheostat Wire wound 50/5A 1
6. Rheostat Wire wound 360/1.1A 1
7. Tachometer Digital - -
8. Connecting leads - - -
THEORY
The different ranges of speeds are required for different applications. A single motor can be used
for various work in different speeds. Smooth speed control is possible in DC shunt motor. The
speed of a DC motor can be expressed by the equation,
N = K(V-IaRas) /
Neglecting the small voltage drops IaRa, the speed is directly proportional to the voltage across
armature and inversely proportional to the flux or field current. Hence, the speed of the DC motor
is controlled by either voltage or field current.
Filed current (or) flux control method
In field current method, the speed of the DC motor is inversely proportional to the flux per
pole. When armature voltage is kept constant, the change of field current can change the flux per
pole of a DC motor. The field current can be changed with the help of shunt field rheostat. As the
-
8/3/2019 EE&CS (2)
25/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 25
field resistance is increased, the current flowing through the field is decreased. So, the speed is
increased. In this method, the speed can be varied above the rated speed.
Armature (or) voltage control method
This method is used when the speed required is below the rated the rated speed. The
voltage across the armature is varied by inserting a variable resistance in series with the armature
circuit. As the armature resistance is increased, the voltage across the armature is decreased. So
the armature speed is decreased.
PRECAUTIONS
1. The motor field rheostat should be kept at minimum resistance position at the time of
starting.
2. The motor armature rheostat be kept at minimum resistance position at the time of
starting.
3. The motor should be in no load condition throughout the experiment
4. The motor should run in anticlockwise direction.
PROCEDURE
Field control method :
1. Note down the name plate details of the motors.
2. Connections are made as per the circuit diagram.
3.
Using the three point DC starter, start the motor.4. The armature rheostat is adjusted to run the motor at rated speed.
5. Keep the armature voltage constant at rated value.
6. Increase the speed in steps of 50rpm above the rated speed and note down the
corresponding field current value in table.
Armature control method:
1. Connections are made as per figure.
2.
Using the three-point starter the motor is stared to run.3. The armature rheostat is adjusted to run the motor at rated speed by means of applying
the rated voltage.
4. Keep the field current constant at rated speed.
5. Decrease the speed in steps of 50 rpm below the rated speed and note down the
corresponding field current value in table.
-
8/3/2019 EE&CS (2)
26/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 26
-
8/3/2019 EE&CS (2)
27/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 27
TABULATION:
FIELD CONTROL METHOD
ARMATURE CONTROL METHOD
S.No
Armature voltage, Va=
Speed (N) rpm Field current (If) Amps
S.No
Field current, If=
Speed (N) rpm Armature voltage, Va (Volts)
-
8/3/2019 EE&CS (2)
28/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 28
MODEL GRAPH:
The graphs are drawn for the following
1. Armature voltage (Va) Vs Speed (N)
2. Field current (If) Vs Speed (N)
RESULT
Thus an experiment to control the speed of a DC shunt motor was conducted and its
Characteristics curves were drawn.
-
8/3/2019 EE&CS (2)
29/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 29
EX.NO.4
LOAD TEST ON SINGLE PHASE TRANSFORMER
AIM
To conduct the load test on the given single phase transformer and determine its
performance.
APPARATUS REQUIRED
S.No Apparatus Type Range Quantity
1 Voltmeter MI
(0-300) V
(0-150) V
1
2 Ammeter MI
(0-10) A
(0-5)A
1
3 Wattmeter LPF 300 V / 10 A,UPF 1
4 Autotransformer 1 Phase (0-270) V / 10 A 1
5 Transformer 1 Phase Step Down 230 V / 110 V 1 KVA 1
PRECAUTIONS
1. At the time of stating, the DPST switch on secondary side should be kept in open
condition.
2. At the time of starting, there should be no lode on the loading rheostat.
FORMULA
1.Output power = Vs Is cos in watts
Where
Vs Secondary voltage in volts
Is secondary current in Amps
cos - power factor
2.Input power = wattmeter reading in watts
3.Efficiency = (output power/ input power)* 100%
-
8/3/2019 EE&CS (2)
30/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 30
4.Voltage regulation=( Vno load - Vload ) / Vno load
THEORY
Transformer is a static device, which is used to convert AC electricity from one
voltage to another without any change in frequency. Transformer works only with AC
and this is one of the reasons why mains electricity is AC. Step-up transformers
increase voltage, Step-down transformers decrease voltage. Most power supplies use a
step-down transformer to reduce the dangerously high mains voltage (230V) to a safer
low voltage.
PROCEDURE
1. Note down the name plate detail of the machine
2. Connection are made as per the circuit diagram
3. Supply is given by closing the DPST switch on the primary side and the secondary is
kept open
4. Adjust the auto transformer to energise the transformer with rated primary voltage
5. At no load condition, the input voltage, current and power are noted and enter the
values in the table
6. Close the secondary winding and increase the load in steps of1 amps and note down
the corresponding ammeter, voltmeter and wattmeter readings in both the primary
and secondary sides and enter the values in the table7. Then the load is gradually decreased and the auto transformer is brought to the
minimum voltage position and the supply is switched off
8. The output power, efficiency and regulation are calculated by using the formulae and
enter the values in the table.
-
8/3/2019 EE&CS (2)
31/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 31
-
8/3/2019 EE&CS (2)
32/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 32
TABULATION
Primary
voltage
VP
(Volts)
Primary
current
IP
(Amps)
Secondary
voltage
VS(Volts)
Secondary
current
IS(Amps)
Wattmeter
reading
Wi(watts)
Input
power Pi
(watts)
Output
power
Po(watts)
Efficiency
(%)
Regulation
R (%)
-
8/3/2019 EE&CS (2)
33/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 33
MODEL GRAPH
The graph is drawn between Output power Vs efficiency
MODEL CALCULATION
RESULT
Thus the load test on the given single phase transformer was conducted and performance
characteristics were drawn.
-
8/3/2019 EE&CS (2)
34/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 34
EX.NO.5
OPEN CIRCUIT AND SHORT CIRCUIT TEST ON SINGLE PHASE TRANSFORMER
AIM
(I) To conduct O.C. and S.C. test on single phase transformer
(II) To find the equivalent circuit parameters
(III)To predetermine the performance of single phase transformer
APPARATUS REQUIRED
S.No Apparatus Type Range Quantity
1 Voltmeter MI (0-300) V 1
2 Voltmeter MI (0-150) V 1
3 Ammeter MI (0-10) A 1
4 Ammeter MI (0-10) A 1
5 Wattmeter LPF 300 V / 10 A 1
6 Wattmeter UPF 150V / 10 A 1
7 Autotransformer 1 Phase (0-270) V / 10 A 1
8 Transformer 1 Phase Step Down 230 V / 110 V 1 KVA 1
9 Connecting leads - - -
PRECAUTIONS
1. At the time of stating, the transformer should be in the minimum voltage position.
2. For O.C test, the HV side of the transformer is in open circuit condition.
3. For S.C test, the LV side of the transformer is short circuited
-
8/3/2019 EE&CS (2)
35/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 35
-
8/3/2019 EE&CS (2)
36/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 36
-
8/3/2019 EE&CS (2)
37/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 37
PROCEDURE FOR O.C TEST
1. Note down the name plate details of the machine.
2. Connections are made as per circuit diagram shown in the Figure
3. Supply is given by closing the DPST Switch
4. Vary the Autotransformer such that the voltmeter reads the rated LV side of the
transformer.
5. Note down the corresponding reading of the ammeter, voltmeter and wattmeter and
enter the value in Table
PROCEDURE FOR S.C TEST
1. Connections are given as per circuit diagram shown in the Figure
2. Supply is given by closing the DPST Switch
3. Vary the Autotransformer such that the ammeter reads the rated HV side of the
transformer.
4. Note down the corresponding reading of the ammeter, voltmeter and wattmeter and
enter the value in Table.
FORMULAE USED
O.C TEST
1. No load power factor, COS 0 =[Woc / (Vocx1oc)]
WhereW oc No Load Losses
V oc No Load Voltage
I oc No Load Current
2. Magnetizing component, Im = Ioc x sin 0
3. Working component, Iw = Ioc x cos 0
4. No load resistance, R0 = Voc / Iw in ohms
5. No load reactance, X0 = Voc / Im in ohms
6. Primary winding resistance, R1 = Wsc / Isc2
in ohms
Where
Wsc Short circuit power in watts
Isc short circuit current in amps
-
8/3/2019 EE&CS (2)
38/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 38
7. Primary winding impedance, Z1 = Wsc / Isc2
in ohms
Where
Vsc Short circuit voltage in volts
8. Primary winding reactance, X1 =
9. Secondary Winding Resistance R2= Wsc / Isc2
in ohms
10.Secondary Winding Impedance, Z2=
11.Secondary Reactance, X2 =
12.Transformer Ratio (K) V2/V1
13.Equivalent Secondary Resistance referred to primary side, R2 = R2/K2 in ohms
14.Equivalent Secondary Reactance referred to primary side, X2 = X2/K2 in ohms
EFFICIENCY
15. Iron loss, =
Where,
16.Copper loss
Where,
17.Total loss,
18.Output power,
Where
19. Input power,
20.Efficiency
REGULATION
21.Percentage regulation,=
22.Total resistance as referred to primary side, Ro1 = in ohms
23.
Total reactance referred to primary side, X01 = in ohms
-
8/3/2019 EE&CS (2)
39/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 39
OPEN CIRCUIT TEST:
Voltage Voc
(volts)
Current Ioc
(Amps)
No load lossesWoc
(Watts)
SHORT CIRCUIT TEST:
Current Isc
(Amps)
Voltage Vsc
(volts)
No load lossesWsc
(Watts)
TO CALCULATE THE EFFICIENCY:
S.NoLoad
Fraction X
Iron Loss
Wi
(Watts)
Copper
Loss
X2Wsc
(Watts)
Total Loss
W (Watts)
Output Power
P0
(Watts)
Input
Power Pi
(Watts)
Efficiency
%
UPFPF=
0.8UPF
PF=
0.8UPF
PF=
0.8
1 0.25
2 0.5
3 0.75
4 1.00
5 1.25
6 1.5
-
8/3/2019 EE&CS (2)
40/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 40
TO CALCULATE THE REGULATION:
Power factor cos 125% Load
X=1.25
100% Load
X=1
75% Load
X=0.75
Lagging Leading Lagging Leading Lagging Leading
0.2
0.4
0.6
0.8
1
MODEL GRAPH
The graph is drawn
1. Output power Vs efficiency
-
8/3/2019 EE&CS (2)
41/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 41
2. Power factor Vs regulation
MODEL CALCULATION:
-
8/3/2019 EE&CS (2)
42/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 42
EQUIVALENT CIRCUIT OF SINGLE PHASE TRANSFORMER
RESULT
(I) Open circuit and short circuit tests were conducted on single phase transformer.
(II) The equivalent circuit parameters are calculated.
(III)Efficiency & voltage regulation performance are estimated.
-
8/3/2019 EE&CS (2)
43/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 43
EX.NO.6
REGULATION OF A THREE PHASE ALTERNATOR BY EMF AND MMF METHODS
AIM
To predetermine the voltage regulation of the given three phase alternator by (1) EMF and
(2) MMF methods and draw its characteristics curves.
APPARATUS REQUIRED
S.No Equipments Name Type Range Qty
1. Ammeter MI (0-10)A 1
2. Ammeter MC (0-2) A 1
3. Voltmeter MI (0-600) V 1
4. Rheostat Wire wound 400 / 1.1A 2
5. Rheostat Wire wound 50 / 5A 2
6. Tacho Meter Digital - 1
7. Connecting wires - - Few
PRECAUTION
y Motor field rheostat in minimum position
y Output voltage setting in the potential divider in minimum position.
PROCEDURE: OPEN CIRCUIT CHARACTERISTICS
1. Connections are made as per the circuit diagram.
2. Close the DPST switch
3. Start the DC motor using 3 point starter.
4. Increase the field regulating rheostat of the motor and drive the alternator at its rated
speed
5. Note down the Ammeter and Voltmeter Readings
6. Close the SPST switch
7. Increase the output voltage of the potential divider and hence the current through the
alternator field winding little greater than the previous.
8. Look for any change in speed has taken place. If so bring back the speed to earlier value
9. Note down the Ammeter and Voltmeter Readings
10.Repeat the step 7,8 and 9 till rated voltage is applied to the alternator field winding.
-
8/3/2019 EE&CS (2)
44/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 44
CIRCUIT DIAGRAM
-
8/3/2019 EE&CS (2)
45/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 45
PROCEDURE: SHORT CIRCUIT CHARACTERISTICS
1. Close the DPST switch
2. Start the DC motor using 3 point starter.
3. Increase the field regulating rheostat of the motor and drive the alternator at its rated
speed
4. Close the TPST switch
5. Note down the Ammeter and Voltmeter Readings
6. Close the SPST switch
7. Increase the current through the alternator field winding to increase the short circuit
current greater than the previous value
8. Look for any change in speed has taken place. If so bring back the speed to earlier value
9. Note down the Ammeter and Voltmeter Readings
10.Repeat the step 7,8 and 9 till rated current
FORMULA
-
8/3/2019 EE&CS (2)
46/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 46
TABULATION: Open circuit test
S.NO OPEN CIRCUIT LINE
VOLTAGE VL (VOLTS)
FIELD CURRENT IF
(AMPS)
OPEN CIRCUIT PHASE
VOLTAGE VPH =VL/
(VOLTS)
Short circuit test
S.NO SHORT CIRCUIT CURRENT
(AMPS)
FIELD CURRENT IF (AMPS)
-
8/3/2019 EE&CS (2)
47/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 47
TO FIND PERCENTAGE REGULATION (EMF METHOD)
S.NO POWER FACTOR LAGGNG LEADING
TO FIND PERCENTAGE REGULATION (MMF METHOD)
s.no Power factor Laggng leading
-
8/3/2019 EE&CS (2)
48/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 48
CIRCUIT DIAGRAM: DETERMINATION OF STATORWINDING RESISTANCE
PROCEDURE: DETERMINATION OF STATORWINDING RESISTANCE
1. Connections are made as per the circuit diagram.
2. Supply is given by closing the DPST switch.
3. Readings of Ammeter and Voltmeter are noted.
4. Stator winding resistance in Ohms is calculated as Ra = (Vx1.5) /I
TABULAR COLUMN: DETERMINATION OF STATORWINDING RESISTANCE
S.NO. VOLTAGE
V (VOLTS)
CURRENT
I (AMPS)
STATOR WINDING
RESISTANCE
RA (OHMS)
-
8/3/2019 EE&CS (2)
49/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 49
MODEL CALCULATION
-
8/3/2019 EE&CS (2)
50/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 50
MODEL GRAPH
RESULT
The regulation of 3 phase alternator by EMF and MMF methods were determined and its
characteristics curve was drawn.
-
8/3/2019 EE&CS (2)
51/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 51
EX.NO.7
V CURVE & INVERTED V CURVE OF SYNCHRONOUS MOTOR
AIM
To plot V Curve & Inverted V curve of given Synchronous Motor
APPARATUS REQUIRED
S.No Equipments Name Type Range Qty
1. Ammeter MI (0-10)A 1
2. Ammeter MC (0-5) A 1
3. Voltmeter MI (0-500) V 1
4. Voltmeter MI (0-300) V 1
5. Wattmeter UPF 6 A, 250 V 2
6. Rheostat Wire wound 50 / 5A 2
7. Tacho Meter Digital - 1
8. Connecting wires - - -
PROCEDURE
1. Connection are given as per the circuit diagram
2. Supply is given to stator of Motor by adjusting 3 phase autotransformer and it is made to
run as induction motor
3. Now close DPST switch & DC supply is given to rotor circuit and made to run as
Synchronous Motor
4. DC supply is increased step by step by varying potential divider in the rotor circuit and
corresponding readings are tabulated
5. Graph is drawn for IF and Ia, IF & PF.
6. Switch off the supply and return the apparatus safely.
-
8/3/2019 EE&CS (2)
52/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 52
CIRCUIT DIAGRAM
-
8/3/2019 EE&CS (2)
53/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 53
TABULATION
MODEL CALCULATION
S.NO. TERMINAL
VOLTAGE VL
IN VOLTS
LOAD
CURRENT IL
IN AMPS
FIELD
CURRENT IF
IN AMPS
WATTMETER READING IN
WATTS
POWER
FACTOR PF=
Pi/(3 VLIL)W1 W2 Pi=W1+W2
-
8/3/2019 EE&CS (2)
54/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 54
MODEL GRAPH
Load
Current
In amps
Field current in amps
Power
Factor
Field current in amps
RESULT
Thus the V Curve & Inverted V curve characteristics of Synchronous Motor are obtained.
-
8/3/2019 EE&CS (2)
55/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 55
EX.NO.8
LOAD TEST ON THREE PHASE SQUIRREL CAGE INDUCTION MOTOR
AIM
To conduct load test on three phase squirrel cage induction motor and draw its characteristics
curves
APPARATUS REQUIRED
S.No Apparatus Type Range Quantity
1 Voltmeter MI (0-500) V 1
2 Ammeter MI (0-5) A 1
3 Wattmeter UPF 250 V / 6 A 2
4 Tachometer Digital - 1
5 Connecting leads - - -
FORMULAE USED
1. Torque T = (S1=S2)9.81R in N-m
S1 S2 Spring Balance Reading in KG
R - Radius of Brake Drum in m
2. Output power = 2NT/60 Watts
3. Input power = Wattmeter Reading in Watts.
4. % Efficiency = Out Power x 100
Input Power
5. % of Slip = NS Nr x 100
NS
6. Power Factor (Cos ) = Input Power / VI
-
8/3/2019 EE&CS (2)
56/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 56
-
8/3/2019 EE&CS (2)
57/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 57
THEORY
The Induction motor is a single phase and three phase AC motor and is the most
widely used machine. These motors are probably the simplest and most rugged of all
electric motors. The supply is connected to the stator and the rotor power is received
by induction caused by the stator rotating flux, hence the motor obtains its name
induction motor. Its characteristic features are:
1. Simple and rugged construction.
2. Low cost and minimum maintenance.
3. High reliability and sufficiently high efficiency.
4. Needs no extra starting motor and need not be synchronized
PROCEDURE
1. Note down the name plate detail of the machine
2. Connection are made as per the circuit diagram
3. Supply is given by closing the TPST switch
4. Using star- delta starter, start the motor
5. At no load condition, the input voltage, current and power are noted and enter the
values in the table
6. Then increase the load gradually in steps and tabulate the different readings
7. Then the load is gradually decreased and the supply is switched off
8.
The torque, output power, efficiency, slip and power factor are calculated by usingthe formulae and enter the values in the table.
-
8/3/2019 EE&CS (2)
58/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 58
-
8/3/2019 EE&CS (2)
59/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 59
MODEL GRAPHS
a) Electrical characteristics
1. Efficiency Vs Po 2. Line current Vs Po 3. Speed N Vs Po
4. Power factor Vs Po 5. Torque Vs Po
b) Mechanical characteristics
Speed Vs Torque
-
8/3/2019 EE&CS (2)
60/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 60
MODEL CALCULATIONS
RESULT
Thus the load test on three phase squirrel cage induction motor was conducted and
characteristic curves were drawn.
-
8/3/2019 EE&CS (2)
61/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 61
EX.NO.9
SPEED CONTROL OF THREE PHASE SLIP RING INDUCTION MOTOR BY STATOR VOLTAGE CONTROL
AIM
To obtain speed control characteristic of three phase slip ring induction motor by stator
voltage control.
APPARATUS REQUIRED
S.No Equipments Type Range Quantity
1. Voltmeter MI (0-600)V 1
2. Ammeter MI (0-10)A 1
3. Tachometer Digital - 1
4. Auto transformer 3 (0-470)V 1
5. Connecting Lead - - -
THEORY
Stator voltage control is cheapest and easiest method but rarely used, because a large
voltage is required for a relatively small change in speed. This large change in voltage will result in
a large change in the flux density thereby seriously disturbing the magnetic conditions of the
applied voltage.
PROCEDURE
1. Close the TPST Switch
2. Increase the output voltage of variac / Auto Transformer to rated voltage of motor
3. Note down the readings of Speed, Voltage, Current and enter then in tabulation
4. Decrease the voltage less than the previous value and measure the speed, Voltage,
Current and enter then in tabulation as a 2nd
reading
5. Repeat the step 4 for 4 to 5 readings and enter in tabulation.
-
8/3/2019 EE&CS (2)
62/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 62
CIRCUIT DIAGRAM
-
8/3/2019 EE&CS (2)
63/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 63
TABULATION
No load condition
S.NO. STATOR VOLTAGE IN VOLTS SPEED IN RPM
Load condition
S.NO. STATOR VOLTAGE IN VOLTS SPEED IN RPM
-
8/3/2019 EE&CS (2)
64/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 64
MODEL GRAPH
SPEED
IN
RPM
STATOR VOLTAGE IN VOLTS
RESULT
Thus the speed control characteristic of three phase slip ring induction motor by
stator voltage control was obtained.
-
8/3/2019 EE&CS (2)
65/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 65
EX.NO.10
LOAD TEST ON SINGLE PHASE INDUCTION MOTOR
AIM
To conduct the load test on the given single phase induction motor and draw its characteristic
curves.
APPARATUS REQUIRED
S.No Apparatus Type Range Quantity
1 Voltmeter MI (0-300) V 1
2 Ammeter MI (0-10) A 1
3 Wattmeter UPF 250 V / 6 A 1
4 Autotransformer 1 Phase (0-270) V / 10 A 1
5 Tachometer Digital - 1
6 Connecting leads - - -
FORMULAE USED
1. Torque T = (S1=S2)9.81R in N-m
S1 S2 Spring Balance Reading in KG
R - Radius of Brake Drum in m
2. Output power = 2NT/60 Watts
3. Input power = Wattmeter Reading in Watts.
4. % Efficiency = Out Power x 100
Input Power
5. % of Slip = NS Nr x 100
NS
6. Power Factor (Cos )= Input Power / VI
-
8/3/2019 EE&CS (2)
66/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 66
-
8/3/2019 EE&CS (2)
67/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 67
-
8/3/2019 EE&CS (2)
68/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 68
THEORY
A single phase induction motor is similar to a three phase squirrel cage induction motor
in physical appearance. The rotor of single phase squirrel cage induction motor is essentially the
same as that employed in three phase induction motors and needs no further description. There is
uniform air-gap between stator and rotor but no electrical Connection between them. Except for
shaded pole types, the stator core is also very similar. A single phase motor can be wound for any
even number of poles two, four and six being most common. A single phase induction motor is
similar to a three phase squirrel cage induction motor.
PROCEDURE
1. Note down the name plate of the motor
2. Connection are made as per the circuit diagram
3. Keep the various I zero position before the II PST switch is Switched ON
4. The II PST is closed and the Autotransformer is adjusted for rated voltage
5. At no load the speed current voltage and power are noted
6. Switch off the supply after reducing the load and draw the graph
MODEL CALCULATION
-
8/3/2019 EE&CS (2)
69/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 69
MODEL GRAPHS
a) Electrical characteristics
1. Efficiency Vs Po 2. Line current Vs Po 3. Speed N Vs Po
4. Power factor Vs Po 5. Torque Vs Po
b) Mechanical characteristics
Speed Vs Torque
RESULT
Thus the load test on single phase induction motor was conducted and characteristic
curves were drawn.
-
8/3/2019 EE&CS (2)
70/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 70
EX.NO.11
STUDY OF AC STARTERS AND DC STARTERS
AIM
To study about the ac starters and dc starters.
Necessity of Starter
The necessity of starter is not only to start the motor but also for the following functions
y Reduction of the heavy starting current
y Over load and no voltage protection
THREE POINT STARTERS
The component used and the internal wiring for a three point starter are shown. Three
terminals L, Z, and A are available in the starter circuit for connecting to the motor. The starting
resistance Rs provided with tapping and each tapping is connected to a brass stud. The handle of
the starter, H is fixed in such a way to move over the brass studs. Two protective devices namely
over load release and no voltage coil provided to protect the motor during over and during failure
of supply.
To start the motor, the starter handle, full resistance is connected in series with the armature
and the armature circuit of the motor is closed through the starting resistance and over load
release coil. Field circuit of motor is also closed through the no voltage coil. Then the handle is
moved over the studs against the spring force offered by a spring Sp mounted on the handle. As
handle movers, the staring resistance is gradually cut out from the motor circuit.
A soft iron pieces is attached to the handle. The no voltage coil, NVC consists of an electro
magnet energized by the field current. When the handle reaches the ON position, the NVC attracts
the soft iron piece and holds the handle firmly.
Whenever there is a failure of supply, the NVC de-energies and releases the handle. The
handle position returns to off position due to the spring tension. If this arrangement is provided,
then when the power supply is restored, the armature alone will be connected to the supply and
the current through the armature will be high and it will damage the armature winding. Thus the
armature is protected against failure of supply by NVC.
-
8/3/2019 EE&CS (2)
71/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 71
The over load release also has an electromagnet and the line current energizes it. When the
motor is overloaded, the iron strip P is attracted to the contacts (c and c) due to the
electromagnetic force produced by the overload release coil and the contacts c and c are bridged.
Thus in this case NVC is de-energized and the handle comes to off position thus the motor is
protected against overloading.
We can see that under normal running of the motor the starting resistance when the handle
touches the first stud it also touches the brass arc through which full voltage is supplied to the
field coil.
Three point starter
-
8/3/2019 EE&CS (2)
72/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 72
Disadvantage
This three point starter is not suitable when we have to control the speed of the motor by
connecting a variable resistance in series with the field winding. When the speed, the no voltage
coil will be de-energized and handle will return the off position. Due to this disadvantage, four
point starters is widely used for starting shunt and compound motors.
FOUR POINT STARTER
The basic difference between three point and four starters is the connection ofNVC. In three
point, NVC is in series with the field winding while in four point starter NVC is connected
independently across the supply through the fourth terminal called N in addition to the L, F
and A.
Hence any change in the field current does not affect the performance of the NVC. Thus it is
ensured that NVC always produce a force which is enough to hold the handle in Run position,
against forces of the spring, under all the operating conditions. Such a current is adjusted through
NVC with the help of fixed resistance R connected in series with the NVc using fourth point N as
-
8/3/2019 EE&CS (2)
73/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 73
shown
FOUR POINT STARTER
Disadvantages:
The only limitation of the four point starter is , it does not provide high speed protection to
the motor. If under running condition, field gets opened, the field current reduces to zero. But
there is some residual flux present and NJ
E1
the motor tries to run with dangerously high speed.
This is called high speeding action of the motion. in three point starter as NVC is in series with the
field, under such field failure, NVC releases handle to the OFF position. But in four point starter
NVC is connected directly across the supply and its current is maintained irrespective of the
-
8/3/2019 EE&CS (2)
74/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 74
current through the field winding, hence it always maintains handle in the RUN position, as long as
supply is there. And thus it does not protect the motor from field failure condition which result
into the high speeding of the motor.
TWO POINT STARTER:-
Three point and four point starters are used for d.c. shunt motors. In case of series motors,
field and armature are inserted and hence starting resistance is inserted in series with the field and
armature. Such a starter used to limit the star4ting current in case of dc series motor is called two
point starters. The basic construction of two point starter is similar to that of three point starter
the fact that is has only two terminal namely line (L) and field F. The terminal is one end of the
series combination of field and the armature winding.
The action of the starter is similar to that of three point starter. The handle of the starter is
in OFF position. When it is moved to on, motor gets the supply and the entire starting resistance is
in series with the armature and field. It limits the starting current. The current through no volt coil
energizes it and when handle reaches to RUN position, the no volt coil holds the handle by
attracting the soft iron piece on the handle. Hence the no volt coil is also called hold on coil.
The main problem in case of dc series motor is it over speeding action when the load is
less. This can be prevented using two point starters. The no volt coil is designed in such a way that
it holds the handle in RUN positions only when it carries sufficient current, for which motor can
run safely. If there is loss of load then current drawn by the motor decreases, due to which no volt
coil losses its required magnetism and releases the handle. Under spring force, handle comes back
to OFF position, protecting the motor from over speeding. Similarly if there is any supply problem
such that voltage decreases suddenly conditions.
-
8/3/2019 EE&CS (2)
75/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 75
Two point starter
The overload condition can be prevented using overload magnet increases. This energizes the
magnet up to such an extent that it attracts the lever below it. When lever is lifted upwards, the
triangular piece attached to it touches the two pints, which are the two ends of no volt coil. Thus
no volt coil gets shorted, losing its magnetism and releasing the handle back to OFF position. This
protects the motor from overloading conditions.
-
8/3/2019 EE&CS (2)
76/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 76
NECESSITY FOR STARTER
At starting when full voltage is connected across the stator terminals of an induction
motor, large current is drawn by the windings. This is because, at starting (i.e before the rotor
starts rotating) the induction motor behaves as a short circuited transformer. This induced emf of
the rotor will circulate a very large current through its windings, due to short. The primary will
draw very large current nearly 7 times of the rated current from the supply main to balance the
rotor ampere turns. This current will however be gradually decreasing as the motor will pick up
speed.
Hence if induction motors are started direct-online heavy current is drawn by the motor,
such as heavy starting current of short duration may not cause harm to the motor since the
construction of induction motors are rugged. Moreover, it takes time for intolerable temperature
rise to endanger the insulation of the motor windings. But this heavy in high of current will cause
a large voltage drop in the lines leading to the motor. Other motors and equipment connected to
the supply lines will receive reduced voltage.
In industrial installation, however, it a number of large motors are started direct on-line,
the voltage drop will be very high and may be really objectionable for the other types of loads
connected to the system. The amount of voltage dro0p will no only dependent on the size of the
motor but also on factors like the capacity of the power supply system, the size and length of the
line leading to the motors, etc.
Types of starters available for induction motors are:
1. Full voltage direct online starting
a. DOL starter
2. Reduced voltage starting Stator control
a. Star-Delta starter
b. Auto transformer starter
3. Rotor resistance starter Rotor control
-
8/3/2019 EE&CS (2)
77/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 77
FULL VOLTAGE DIRECT ONLINE STARTING:
D.O.L STARTER:
It is recommended that large three phase squirrel-case induction motors be started with
reduced voltage applied across the stator terminals at starting. But small motors up to 5HP ratings
may however be started Direct ON-Line (DOL)
Direct-on-line method of starting of induction motors applicable up to a rating of5 HP is shown in
fig1. In the circuit in addition to fuses, thermal motor windings against overload.
Derivation for starting current and torque in case of DOL starters
Rotor input kTTNS !T2 (1)
Rotor copper loss vS rotor input
@ kTSRI v!22
23
-
8/3/2019 EE&CS (2)
78/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 78
@ SIT /2
2w 9if R20is the same
Now 12 II w
@ SIT /2
1w (or) SIKT /
2
1!
At starting moment, S = 1
@2
ststIKT ! where Ist = Starting current
If,
If = normal full load current and
Sf = Full load slip
THE STARTERS FOR SQUIRREL CAGE INDUCTION MOTOR
REDUCED VOLTAGE STARTING:
STATOR RESISTANCE (OR) PRIMARY RESISTANCE STARTER:
Their purpose is to drop some voltage and hence reduce the voltage applied across the
motor terminals. In this way, the initial current drawn by the motor is reduced. However, it
should be noted that whereas current varies directly as the voltage, the torque varies as square of
applied voltage.
[Note: When applied voltage is reduced, the rotating flux J is reduced which in turn
decreases rotor e.m.f and hence rotor current I2. Starting torque which depends both on J and I2
suffers on two counts when impressed voltage is reduced]
-
8/3/2019 EE&CS (2)
79/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 79
For example if voltage applied across motor terminals is reduced by 50%, starting current
is reduced by 50%, but torque is reduced to 25% of the full-voltage value.
Then,
fff SKIT /2
!
@ ff
st
f
stS
T
I
T
T.
2
!
When motor is direct-switched on to normal voltage, then starting current is the short
circuit current Isc.
@ fff
sc
f
stSaS
T
I
T
T..
2
2
!
!
Where fsc IIa /!
Suppose in a case, ,7 fsc II !
Sf = 4% = 0.04,
Then,
96.104.072
!v!f
st
T
T
@ Starting torque = 1.96 x Full load torque.
-
8/3/2019 EE&CS (2)
80/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 80
Hence, even if current is greater than full load current the starting torque is only 1.96
times full-load torque.
If applied voltages/phase can be reduced by fraction x, then
scstxII ! and scst TxT
2!
f
f
sc
f
f
st
f
stS
I
xIS
I
I
T
T..
22
!
!
f
f
scS
I
xIx .
2
2
!
f
f
stSax
T
T..
22!
f
f
stSax
T
T..
22!
-
8/3/2019 EE&CS (2)
81/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 81
It is obvious that the ratio of starting torque of full-load torque is x2
of that obtained with
direct switching (or) across the line starting. This method is useful for the smooth starting of small
machines only.
(ii). PRIMARY REACTANCE STARTER:
The working principle of the primary reactance starter is same as that of primary
resistance starter except that voltage drop occurs across the reactor, so that i/p voltage applied to
the stator of induction motor reduces.
AUTO TRANSFORMER STARTERS
An auto transformer consists of a n auto transformer and a switch as shown in fig.
When the switch S is put on start position, a reduced voltage is applied across the motor
terminals. When the motor picks up speed, say to 80 percent of its normal speed, the
switch is put to RUN position. Then the quato-transformer is cut out of the circuit and full
rated voltage gets applied across the motor terminals.
-
8/3/2019 EE&CS (2)
82/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 82
The switch making these changes from start to run may be air break (for small motors)
or may be oil-increased (for large motors) to reduce sparking.
Derivation for autotransformer starter:
When full voltage is applied without suing autotransformers say starter, then current
taken by the motor is 5 times the full load current. If V is pre line voltage then
voltage/phase across the motor is 3/V .
@Z
VISI fsc
3!! Where Z is starter impedance /phase
In the case of autotransformer, if a tapping of transformation ratio k is used, then phase
voltage across motor is 3/kV
@ Motor starting currentZ
kV
Z
kVI33
2 !!
The current taken from supply (or) by auto transformer is2
21 kkII !!
scif TkS
2.! if magnetizing current of the transformer is ignored phase is
reduced only k times, the direct switching current ,1k3 the current taken by the line is
reduced to k2
times.
The torque is proportional to square of the voltage, we get, (i) with direct =switching,
;3/ 21
VT w with auto transformer,
22
3/kVT w
2
2
1
2
3/
3/
V
kV
T
T!@
(or)
scTkT
2
2 !
@ Torque with quto transformer starter is, = k2 x Torque with direct switching.
-
8/3/2019 EE&CS (2)
83/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 83
AmpereIIPLD
3!
Relation between starting and full-load torque:
It is seen that voltage across the motor phase on direct switching is 3/V and starting
current isscst
II ! . With autotransformer starter, voltage across the motor phase is 3/kV
andscst
kII !
Now,
12 !w SITstst and
..
2
f
f
st
f
stS
I
I
T
T
!@
(Or)
..
2
2
f
f
sc
f
stS
I
Ik
T
T
!
..922
f
f
stSk
T
T!@
scst kII !@
From Fig. it is seen than for star connection of windings, phase current.
P
LYpZ
VII
1
3v!! Ampere
when ILY is the line current when windings are connected and Zp is the windings impedance per
phase.
For delta connection of windings
p
pZ
VI !
and
-
8/3/2019 EE&CS (2)
84/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 84
The ratio of line currents drawn in star and delta connection is therefore,
p
p
L
LY
ZV
ZV
I
I
/3
3/ v!
(
3
1!
LD
LY
I
I
STAR DELTA STARTER:
In this method, the stator phase windings are first corrected in star and full voltage is
connected across its free terminals. As the motor pickup speed, the windings are disconnected
through a switch and they are reconnected in delta across the supply terminals. The current drawn
by the motor from the lines is reduced to 1/3 as compared to the current it would have drawn if
connected in delta.
PROOF:
Thus, by connecting the motor windings, first in star and then in delta, the line current
drawn by the motor at starting is reduced to one third as compared to starting with the
windings delta connected.
(! ILI
I
LD
LY
3
1
-
8/3/2019 EE&CS (2)
85/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 85
Reduced Torque due to star connection:
In induction motor, torque developed is proportional to the square of applied voltage. As
the phase voltage is reduced to 3/1 times that in star-connection, the starting torquewill be reduced to one third. To get full torque in the motor, it must be switched over to
delta connection.
In making connections for star-delta starting, care should be taken such that sequency of
supply connections to the winding terminals does not change wile changing form star-
connection to delta-connection. Otherwise the motor will start rotating in opposite
direction, when connections are changed from star to delta.
Star-delta starters are available for manual operation using push-button control. An
automatic star-delta starters uses time-delay relays (TDR) through which star to delta
-
8/3/2019 EE&CS (2)
86/87
ELECTRICAL ENGINEERING LABORATORY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Page 86
connections take place automatically with some pre-fixed time fixed keeping in view the
starting time of the motor.
Derivation:
Relation between starting and full load torque:
Ist per phase ScI
3
1!
per phase.
Where ISc is the current /phase which ( -connected motor would have taken if switched on
to supply directly (however line current at start 3/1!of Line ISC).
Now,
2
ststIT w 1!s
@f
f
st
st
stS
I
I
T
T.
2
!
f
f
scS
II .1.3
2
!
fSa .3
1 2!
f
f
stSa
T
T.
3
1 2!@
Here, Ist and ISC represent phase values.
It is clear that star-Delta switch is equivalent to a n auto-transformer of ratio 3/1 (or)
58% approximately.
-
8/3/2019 EE&CS (2)
87/87
ELECTRICAL ENGINEERING LABORATORY
THE STARTERS FOR SLIP RING INDUCTION MOTORS:
ROTOR RESISTANCE STARTERS:
The easiest method of starting wound rotor (slip-ring) induction motors is to
connect some extra resistance in the rotor circuit as shown in fig. Connection of extra resistance
in the rotor circuit decreases the starting current and at the same time increases the starting
torque. As the motor starts rotating the extra resistance is gradually cut out. When the motor
attains rated speed the resistance is fully cut out.
When the motor attains rated speed the resistance is fully cut out and the slip ring
terminals are short circuited. The motor now operates on its own characteristics which give rise to
maximum torque at a low slip.