Users Guide 1
Introducing the
ElectriCalc
ProNow NEC -Updateable! The ElectriCalc Pro is an invaluablecalculator for todays busy electricalprofessional. Unlike a regular calcula-tor, it has intuitively labeled electricalkeys and conforms to the 2002 and
future National Electrical Codes , allow-ing you to solve Code-related problemsquickly and accurately. The most com-mon NEC tables are now at your finger-tips!
An important new feature of the Elec- triCalc Pro is that it is now programmedto accept future NEC changes, allowingyou to conveniently install future Codeeditions in a few simple steps.
-
8/12/2019 Electric Calc Pro
4/68
2 ElectriCalc Pro
The ElectriCalc Pro instantly solves forthe following:
Volts, Amps, Volt-Amps, Watts,kVA, kW, PF%, EFF%, and DCResistance
Copper or Aluminum Wire SizesParallel & Derated Wire Sizes
Voltage Drop Wire Sizes, % andActual Voltage Drops, VoltageDrop Distances and Wire Resis-tances
Grounding Conductors Sizes
Motor Full-Load Amps
Overload Protection Sizes
NEMA Starter Sizes
Conduit Sizes
And much more!
-
8/12/2019 Electric Calc Pro
5/68
Users Guide 3
Table of Contents
Installing NEC Updates . . . . . . . . . . . . . .4Key Definitions . . . . . . . . . . . . . . . . . . .5Preference Settings . . . . . . . . . . . . . . .26Default Settings . . . . . . . . . . . . . . . . .27Basic Math Operations . . . . . . . . . . . . .28Percent Calculations . . . . . . . . . . . . . .28Memory Functions . . . . . . . . . . . . . . . .29Kerchoffs Law . . . . . . . . . . . . . . . . . .30Motor Horsepower . . . . . . . . . . . . . . . .34
Ampacity Wire Sizing . . . . . . . . . . . . . .36Voltage Drop . . . . . . . . . . . . . . . . . . .42Ground Conductor Wire Size . . . . . . . . .48Equip. Grounding Conductor Wire Size . .49Fuse and Circuit Breaker Size . . . . . . . .50
Starter Size . . . . . . . . . . . . . . . . . . . .51Overload Protection Size . . . . . . . . . . . .51Conduit Size . . . . . . . . . . . . . . . . . . . .52Error Codes . . . . . . . . . . . . . . . . . . . .57Battery Information . . . . . . . . . . . . . . .572002 NEC References . . . . . . . . . . . . . .58Updating Future Code Revisions . . . . . . .58Settings . . . . . . . . . . . . . . . . . . . . . . .59Warranty . . . . . . . . . . . . . . . . . . . . . .60
Legal Notices . . . . . . . . . . . . . . . . . . .64
-
8/12/2019 Electric Calc Pro
6/68
4 ElectriCalc Pro
Installing NEC UpdatesYour ElectriCalc Pro is now updateablefor future National Electrical Code editions that are updated every three(3) years (next Code update is 2005).To upgrade your unit, follow the instruc-
tions below:1) Purchase the NEC Update from CI(see pricing & details from CIs Website: www.calculated.com or call 1-800-854-8075). This Update is in theform of a chip that contains the newCode.
2) Once you receive the NEC Updatechip, you need to install it in yourElectriCalc Pro:a)Turn calculator off.b)As a precaution, remove the bat-
tery (located back of calculator, topof unit) by sliding battery door out
with your thumbnail. Set aside.c) Using a screwdriver, pop out thesquare tab located in the middlesection on the back of your calcu-lator.
d)Replace it with the new Update tabby inserting it into the slot.
e) Replace the battery door.f) Turn calculator on. Your calculator
is now updated and ready to use.
-
8/12/2019 Electric Calc Pro
7/68
Users Guide 5
Key Definitions
Standard Calculator Functions
[On/C] On/ClearTurns on power. Pressing once clearsthe last entry and the display. Pressing
twice clears all non-permanent values.
[Off] OffTurns all power off. Clears the memoryand most internal registers.
[+] [] [x] [] [=]Arithmetic operation keys.
[0] [9] & []Used for keying in numbers.
[%] PercentFour function percent key.
[ ] Back Space FunctionUsed to delete entries one keystroke ata time (unlike the On/C function, whichdeletes the entire entry).
-
8/12/2019 Electric Calc Pro
8/68
6 ElectriCalc Pro
[Set] Second FunctionAccesses the secondary functions
shown above the keys when pressedprior to selection.
[Stor] StoreUsed to store values when pressed just
before a storage register (i.e., M+,AMPS, VOLTAGE, etc.).Displays: STOR.
[Rcl] RecallRecalls a value stored in a register(e.g., to recall voltage drop % press[Rcl] [VD%]). Displays: RCL.
[Set] [ + ] Pi (
)Constant = 3.141593
[Set] [] Change Sign (+/)Toggles the sign of the displayed value(from positive to negative or from nega-tive to positive).
[Set] [%] x 2
Squares the displayed value.
[Set] [ ] Square Root ( x )Square root function.
-
8/12/2019 Electric Calc Pro
9/68
Users Guide 7
[Stor] [0] Cumulative MemoryAdds displayed value to Memory (e.g.,
10 [M+], 20 [M+], [Rcl] [M+] = 30).Clears when the calculator is shut off.
[Rcl] [0] Memory RecallDisplays the value saved in (M+).
[Rcl] [Rcl] Display/Clear MemoryDisplays and clears the value saved in(M+).
[Set] [Rcl] Clear MemoryClears the value saved in (M+) withoutchanging displayed value.
Mode Set-up Functions
[Set] [x] All-Clear (AC)Resets all settings and values to theirdefault settings.
[Set] [] PreferencesUse to set default settings or modes(see Preference Settings page 26)
[Set] [1] Single-Phase (1)Sets calculator to single-phase mode.Displays: 1.
-
8/12/2019 Electric Calc Pro
10/68
8 ElectriCalc Pro
[Set] [3] Three-Phase (3)Sets calculator to three-phase mode.
Displays: 3.
[Set] [2] Ambient Temperature (Amb)Permanently enters ambient tempera-
ture for determining ampacity derivedwire sizes. Ambient temperature willonly change when entering a new valueor by resetting the calculator ( [Set] [x] ).Defaults to 30C (86F). Amb willdisplay when the ambient temperatureis other than 30C (86F). Displays:Amb.
NOTE: The temperature units can be displayed in Celsius (C) or Fahrenheit (F) by using the preference function ( [Set][] ).
[Set] [4] Copper/AluminumUsed to toggle between copper (de-fault) and aluminum wire types. Whenthe wire type is revised, any calculatedwire size will be re-calculated automati-cally. If a wire size is entered with thewrong wire type, pressing [Set] [4] willchange the material type withoutchanging the size.
Displays: Al or Cu.
-
8/12/2019 Electric Calc Pro
11/68
Users Guide 9
[Set] [5] Free Air (FrAir)Sets calculator into Free Air mode,
which refers to NEC Table 310-17 forwire size calculations. Displays: FrAir.
[Set] [6] 60C Wire InsulationSets calculator to 60C wire insulation
type for wire size calculations. This isthe default setting. Displays: 60.
[Set] [7] 75C Wire InsulationSets calculator to 75C insulation typefor wire size calculations.Displays: 75.
[Set] [9] 90C Wire Insulation
Sets calculator to 90C insulation typefor wire size calculations.Displays: 90.
Electrical Functions
[kilo-] Kilo-This key is used with watts, amps,volts, and volt-amps to identify kilo-values.
[Set] [kilo-] Milli-This key sequence is used with other
keys watts, amps, volts, and volt-ampsto identify milli- values.
-
8/12/2019 Electric Calc Pro
12/68
10 ElectriCalc Pro
[Amps] AmpsEnters or calculates amps (using volts
and VA or watts). Displays: AMPS,KAMP or mAMP.
[Volts] VoltsEnters or calculates volts (using amps,
HPth, and VA or watts). Default value is240 volts. Displays: VOLT, KV, or mV.
[Set] [Volts] DC ResistanceCalculates and displays DC resistance.Displays: OHMS.
[VA] Volt-AmpsEnters or calculates volt-amps (using
amps, volts and horsepower or watts).Displays: VA, KVA, or mVA.
[Watts] WattsEnters or calculates watts (using amps,volts, and VA or horsepower).Displays: WATT, KW, or mW.
[Set] [Watts] Power FactorEnters or calculates power factor per-centage (based on watts and VA). De-faults to 100%. Entered or calculatedpower factors greater than 100% willresult in an error. Displays: PF%.
-
8/12/2019 Electric Calc Pro
13/68
Users Guide 11
[HPth] Horsepower (Theoretical)Enters or calculates theoretical horse-
power (based on Amps, VA, watts,efficiency%, PF%, and/or volts). 1.0HPth correlates to 746 watts at 100%efficiency. Displays: HPth.
[Set] [HPth] EfficiencyEnters or calculates the percent ratiobetween real power (watts) and theo-retical horsepower. Default: 100%.Entered or calculated efficienciesgreater than 100% will result in an er-ror. Displays: EFF%.
Motor Horsepower FunctionsThe ElectriCalc Pro can be used todetermine motor full-load current(amps) based on entries for motorhorsepower (HP), phase and voltage.
You can also find an equivalent motorhorsepower if you have entered voltageand full load current values. Only HPand voltage entries as defined by NECTables 430-148 and 430-150 can beused to determine motor loads.
-
8/12/2019 Electric Calc Pro
14/68
12 ElectriCalc Pro
[Set] [8] Induction/Synchronous Motor Toggle
Toggles between induction and syn-chronous motor types. Displays: SYNC(synchronous) or IND (induction - de-fault).
[HPmotor] Motor HorsepowerEnters or calculates motor horsepower.Displays: SYNC HP (synchronous) orHP IND (induction - default).
Ampacity Tables
The ElectriCalc Pro uses NEC Table310-16 (310-17 for Free Air) to find wiresizes and ampacity ratings of wires.The calculator uses the following datato calculate wire size: 1) insulationtemperature rating (60C, 75C and90C); 2) wire material (copper or alu-
minum); and 3) ambient temperature.Only standard AWG wire sizes areused by the ElectriCalc Pro .
NOTE: 1/0, 2/0, 3/0 and 4/0 wires are
entered using the [0] key (i.e., 0, 00,000 and 0000).
[WireSz] Wire Size/AmpacityEnters or calculates wire size based on
ampacity and voltage drop, if a voltagedrop length has been entered.
-
8/12/2019 Electric Calc Pro
15/68
Users Guide 13
First Press If a wire length has been entered, the
first press will show the larger of theampacity or voltage drop derived wiresize. The calculator will use the largervalue when calculations require a wiresize. If no voltage drop length has beenentered, the calculator will display thecalculated ampacity rated wire size.
Second Press If a wire length has been entered, thesecond press displays the smaller ofthe two wire sizes. If not solving forvoltage drop wire size, then displaysthe maximum ampacity.
Third Press If a wire length has been entered, dis-plays the minimum wire ampacity rat-ing.
[Set] [WireSz] 125% AmpacityUsed for motor wire sizing when thewire must not exceed 80% of its rated
ampacity (125%A). This keystrokecalculates wire size based on 125% ofthe entered or calculated amps value.Displays: 125%.
-
8/12/2019 Electric Calc Pro
16/68
14 ElectriCalc Pro
[ParSz] Parallel SizeUsed to find the size of parallel conduc-
tors using amperage and an enteredquantity of wires. Parallel wire sizecomputations smaller than 1/0 are dis-played as none (display showsnonE ) as the NEC does not allow
parallel wire runs smaller than 1/0.
First Press When preceded by a number, calcu-lates the applicable wire size for thatquantity of wires in parallel.Displays: PAR WIRE SIZE.
Second Press
Displays the maximum adjusted am-pacity of the calculated parallel wiresize. Displays: WIRE A.
NOTE: No adjustments are made for deration.
[Set] [ParSz] Derated Wire SizeUsed to calculate derated wire sizesand allowable ampacity based on theentered quantity of wires, NEC Table310-16 and NEC Table 310-15(b)(2)(a).Derated wire sizes are not calculatedwhen there are less than 4 wires, or
when the unit is in Free Air mode.
-
8/12/2019 Electric Calc Pro
17/68
Users Guide 15
First Press Calculates the derated wire size, if you
have entered the number of wires, forexample, 4 [Set] [ParSz]).Displays: D/R WIRE SIZE.
Second Press Displays the maximum adjusted am-pacity of the derated wire size.Displays: D/R WIRE A.
Third Press Displays the derated adjustment factorper the NEC Table 310-15(b)(2)(a).Displays: ADJ %.
Voltage Drop Solutions
The ElectriCalc Pro will calculatemaximum lengths, minimum wire sizesor actual voltage drops given the othertwo values. Voltage drop solutions arebased on the DC resistance valuesfound in NEC Chapter 9, Table 8.
NOTE: Voltage drop solutions may vary slightly from actual AC circuit values as the calculator does not incorporatefactors such as inductive reactance,skin effect, raceway material, etc.
-
8/12/2019 Electric Calc Pro
18/68
16 ElectriCalc Pro
[VD%] Percent Voltage DropUsed to enter or calculate voltage drop.
The default voltage drop is 3%. If wiresize or wire length values are not avail-able, nonE will display since the volt-age drop cannot be found.
First Press Enters a maximum allowable voltagedrop percentage ( Displays: V DROP%) or calculates actual voltage drop(Displays: V DROP ).
Second Press Calculates actual percent voltage drop.Displays: V DROP %.
[Length] LengthEnters or calculates the length of a runfor voltage drop computation.Displays: FEET or MET.
NOTE: Units of length can be set to Feet or Meters by use of the Prefer- ence function ( [Set] [] ).
[Set] [Length] Wire ResistanceDisplays the actual resistance per1,000 feet of the wire size in [WireSz]based on NEC Chapter 9, Table 8.
Displays: OHMS WIRE.
-
8/12/2019 Electric Calc Pro
19/68
Users Guide 17
Ground Function Keys
[Grnd] GroundAn output-only key used to find thegrounding electrode conductor size forAC systems based on NEC Table250-66 and an entered or calculatedservice-entrance conductor (largestsize). Only actual wire sizes are con-sidered valid entries.
First Press Calculates the copper grounding elec-trode conductor size if you have en-tered a valid wire size.Displays: GRND CU WIRE SIZE.
Second Press Displays the aluminum grounding elec-trode conductor size.Displays: GRND AL WIRE SIZE.
Third Press Displays the circular mil area used tocalculate the grounding electrode con-
ductor size. Displays: CMIL WIRE.
-
8/12/2019 Electric Calc Pro
20/68
18 ElectriCalc Pro
[Set] [Grnd] Equipment Ground (EqGrnd)
This function uses NEC Table 250-122to compute the minimum equipmentgrounding conductor size, given anentered amperage rating or setting for aover-current device up line (i.e., 300
[Set] [Grnd]).
NOTE: This function deviates from the NEC Table 250-122 in that 1250 MCM AL is used instead of 1200 as specified in NEC Table 250-122.
First Press Displays the copper grounding conduc-
tor size for the entered amp rating.Displays: EQPG WIRE SIZE CU.
Second Press Displays the aluminum grounding con-ductor size.Displays: EQPG WIRE SIZE AL.
-
8/12/2019 Electric Calc Pro
21/68
Users Guide 19
Fuse/Breaker Keys
The ElectriCalc Pro has special keysthat automatically calculate the Ampratings of the following over-currentprotection devices: Dual Element Fuses(Time Delay), Single Element Fuses(Non-Time Delay), Instantaneous TripBreakers (Type 1), Inverse TimeBreakers (Type 2), and OverloadProtection Devices.
These fuse and circuit breaker sizesare derived using the Percent of Full-Load Current multipliers listed in NECTable 430-152.
You can also calculate the full voltagestarter size for non-plugging and non-
jogging duty motors based on phase,voltage, motor HP and NEMA table
specifications.If a parameter is missing or invalid, thecalculator will display nonE .
[Set] [O-Load] Motor TypeBased on NEC Table 430-152, this keyselects the motor type used to definethe percent factors for breakers/fuses.Once set, the motor type remains fixeduntil you change it or perform an allclear ( [Set] [x] ).
-
8/12/2019 Electric Calc Pro
22/68
20 ElectriCalc Pro
First Press Displays the current motor type. Note
there is no motor type in single-phasemode.
Second Press In three-phase mode only, subsequent
presses of [O-Load] will select anddisplay the next motor type from thislist: SQ-C non-E (Squirrel Cage, non-Design E), SQ-C E (Squirrel Cage,Design E), SYNC no codE (Synchro-nous), WND no codE (Wound Rotor).
[DEFuse] Dual Element Fuse
First Press Calculates the minimum amp rating fora Dual Element Fuse.Displays: AMPS dE.
Second Press Displays the full-load current percentmultiplier used to determine fuse size.Displays: %FLC.
[Set] [DEFuse] Single Element Fuse (SEFuse)
First Press Displays the minimum amp ratingbased on phase, motor type, and am-perage. Displays: AMPS SE.
-
8/12/2019 Electric Calc Pro
23/68
Users Guide 21
Second Press Displays the full-load current percent
multiplier value used to determine fusesize. Subsequent presses repeat thiscycle. Displays: %FLC.
[Set] [InvTime] InstantaneousTrip Circuit Breaker
First PressDisplays the minimum amp rating foran Instantaneous Trip Circuit Breaker,based on the phase, motor type, andamperage. Displays: AMPS b1.
Second Press
Displays the full-load current percentmultiplier value used to determinebreaker size. Displays: %FLC.
[InvTime] Inverse Time Breaker
First Press Calculates the minimum amp rating foran Inverse Time Breaker, based on the
phase, motor type, and amperage.Displays: AMPS b2.
Second Press Displays the full-load current percentmultiplier value used to determinebreaker size. Displays: %FLC.
-
8/12/2019 Electric Calc Pro
24/68
22 ElectriCalc Pro
[O-Load] Overload Protection
First Press
Displays the overload amperage re-quirement based on the full-load cur-rent shown on the motor nameplate.Multiplies the entered motor nameplatefull-load current (stored in the [Amps]registers) by 115% or the value youenter. Conforms to NEC Section 430-32 (a)(1) value of 115% unless youenter another value. For example, en-
tering 125 [O-Load] would calculateoverload protection based on 125% ofthe entered amperage. Displays:AMPS ol.
Second Press Displays the full-load current percentmultiplier value used to determine theoverload current protection size. Sub-sequent presses of [O-Load] repeat the
cycle. Displays: %FLC.[Set] [HPmotor] Starter SizeDisplays the starter size (from NEMApublication ICS 2-1988 Tables 2-327-1
and 2-327-2) based on the phase, volt-age, and motor horsepower settings.Displays: STAR SIZE.
NOTE: Horsepower values not identi- fied in NEMA tables will cause the cal- culator to round up to the next larger starter size in the table.
-
8/12/2019 Electric Calc Pro
25/68
Users Guide 23
Conduit Sizing Keys
The ElectriCalc Pro calculates conduitsize using NEC Tables 1, 3, 4, and 5 ofChapter 9 (given insulation type, wiresize, and quantity of wires). It will alsocalculate the number of wires of a
specified insulation type and wire sizethat will fit in a defined conduit size.Acceptable conduit sizes (dependingon the type of conduit used) are asfollows: 1/2, 3/4, 1, 1-1/4, 1-1/2, 2,2-1/2, 3, 3-1/2, 4 5 and 6. Conduitsizes are entered using decimal equiva-lents (i.e., 1-1/2 is entered as 1.5, 3/4is entered as .75, etc.).
[#THW], [#XHHW], [#THHN] Number of WiresUsed to enter or calculate the numberof wires in a raceway and calculatecross-sectional wire area.
First Press Enters number of wires or calculatesmaximum number of wires in conduit.Displays: TTL WIRES (calculated) orWIRES (entered).
Second Press Shows total cross-sectional area for allentered wires. Displays: WIRE AREA
(entered) or TTL WIRE AREA (calcu-lated).
-
8/12/2019 Electric Calc Pro
26/68
24 ElectriCalc Pro
Third Press Shows total cross-sectional area of all
entered wires of the selected wire insu-lation. Displays: TTL WIRE AREA.
[CondSz] Conduit SizeUsed to find conduit sizes based on the
total area of the entered wire types andsizes (up to 15 at one time). If thequantity and insulation type has notbeen entered, the calculator will as-sume 2 THHN wires for single-phase or3 THHN wires for three-phase calcula-tions.
First Press Enters or calculates conduit size.Displays: COND SIZE.
NOTE: If a wire size has not been en- tered or calculated, or an invalid con- duit size is entered, the calculator will display nonE .
Second Press Shows total number of wires in the
conduit for calculated conduit size.Shows the conduit internal area for anentered conduit. Displays: TTL WIRES(calculated) or CONDAREA (entered).
NOTE: Third through fifth presses dis- play only for calculated conduit sizes.
-
8/12/2019 Electric Calc Pro
27/68
Users Guide 25
Third Press Shows fill percentage for the calculated
conduit size as determined by Table 1,Chapter 9. Displays: COND FILL %.
Fourth Press Shows the total wire area for all entered
wires. Displays: FILL TTL WIRE AREA.Fifth Press
Shows remaining fill area. This valuemay be negative if all wires are thesame size due to Note 7 in NEC Chap-ter 9, Table 1.Displays: REM WIRE AREA.
[Set] [CondSz] Conduit Type
First Press Displays the currently selected conduittype.
Second Press
Subsequent presses will display andselect the next conduit type from thislist: 1) EMT 2) ENT 3) FMC 4) IMC5) LFNB 6) LFNA 7) LFMC 8) RMC9) P-80 10) P-40 11) P-A 12) P- EB.To select a specific conduit type, enterthe corresponding number of the con-duit and then press [Set] [CondSz]. Ifyou press this keystroke without enter-
ing a number, the calculator will switchto the next conduit type on the list.
-
8/12/2019 Electric Calc Pro
28/68
26 ElectriCalc Pro
Preference SettingsYour calculator has the following Pref-erence Settings that you can accessand change at any time.
Reach the Preference Function bypressing [Set] [] . Then, to accesseach category, press the [] key untilthe desired setting is reached. Within each category , press the [+] or [-] keysto toggle between individual selections(note: the [+] will advance, the [-] willback-up).
You can change these settings at anytime by repeating the above, and set-
ting in a new preference. NOTE: Toclear preferences, you must either reset using keystrokes below, or perform an All-Clear ( [Set] [x] ).
The Preference Settings are (defaultsettings shown first):
To Set 1999 or 1996 NEC Code:[Set] [] (1st press of []) CODE 99
[+] CODE 96To Set Ambient Temp. to C or F:[] (2nd press of []) AMB30 C[+] AMB86 FTo Set Length to Feet or Meter:[] (3rd press of []) FEET 1.[+] MET 1.
-
8/12/2019 Electric Calc Pro
29/68
Users Guide 27
Default SettingsWhen you first receive your calculator,it is pre-set to the default settings listedbelow. You can always return yourcalculator to these default values withan All-Clear ( [Set] [x] ).
Ambient Temperature 30C
Insulation Rating 60C
Material Copper (Cu)
Phase 3
Volts 240 V
Efficiency 100%Power Factor 100%
Length Units Feet
Voltage Drop Percent 3%Wire Environment Raceway(vs Free Air)
-
8/12/2019 Electric Calc Pro
30/68
28 ElectriCalc Pro
Basic Math OperationsThis calculator uses standard chaininglogic, which simply means that youenter your first value, the operator (+, ,x, ), the second value and then theequals sign (=).
A. 3 [+] 2 [=] 5B. 3 [] 2 [=] 1C. 3 [x] 2 [=] 6D. 3 [] 2 [=] 1.5
Percent CalculationsThe percent key [%] can be used forfinding a given percentage of a numberor for working add-on, discount or divi-sion percentage calculations.
355 [x] 15 [%] 53.25250 [+] 6.5 [%] 266.2525 [] 5 [%] 23.75100 [] 50 [%] 200.
The percent key also allows you tochange percentages to decimals (e.g.,25 [%] 0.25).
-
8/12/2019 Electric Calc Pro
31/68
Users Guide 29
Memory FunctionsWhenever the [Stor] [0] (M+) keys arepressed, the displayed value will beadded to memory. A list of memorykeystrokes/functions is provided below:
Function KeystrokesAdd to memory [Stor] [0]Display total in memory [Rcl] [0]Display & clear memory [Rcl] [Rcl]
Clear memory, no display [Set] [Rcl]Replace memory withdisplayed value [Set] [Rcl] [Stor] [0]
The memory is semi-permanent; it willbe cleared when you:
1) turn off the calculator;2) press [Rcl] [Rcl] ;3) press [Set] [Rcl] ;
4) press [Set] [x] (all clear).
How To Use Memory Functions:
Steps Keystrokes Display
Reset calculator [On/C] 0.Add to M+ 355 [Stor] [0] 355. MAdd to M+ 255 [Stor] [0] 255. MRecall total M+ [Rcl] [0] 610. MSub. from M+ 745 [Set]
[Stor] [0] 745. MRecall & clear [Rcl] [Rcl] 135.
-
8/12/2019 Electric Calc Pro
32/68
30 ElectriCalc Pro
Kerchoffs LawThe ElectriCalc Pro utilizes KerchoffsLaw in finding volts, amps, volt-amps,watts, horsepower (theoretical), effi-ciency and power factor.
Finding VoltageFind the voltage supply to a single-phase load drawing 14,605 volt-ampsand 115 amps.
Steps Keystrokes Display
Clear calculator [On/C] [On/C] 0.Set to 1-phase [Set] [1] 1 PH
Enter VA 14605 [VA] 14,605. VAEnter amps 115 [Amps] 115. AMPSSolve for volts [Volts] 127. VOLT
Finding Amps
What is the current (amps) for a loaddrawing 8,250 volt-amps on a 240 volt,three-phase circuit?
Steps Keystrokes DisplayClear calculator [On/C] [On/C] 0.Set to 3-phase [Set] [3] 3 PHEnter VA 8250 [VA] 8,250. VAEnter volts 240 [Volts] 240. VOLTSolve for amps [Amps] 19.846416 AMPS
-
8/12/2019 Electric Calc Pro
33/68
Users Guide 31
Finding Current Load
A building with 120/240 volt 1 servicehas the following loads:
Range = 7,800 VA Heating = 15,100 VADryer = 5,100 VA Appliances = 8,900 VALighting = 6,470 VA
What is the service load (amps) of thecircuit supplying this building?
Steps Keystrokes Display
Clear calculator [On/C] [On/C] 0.Set to 1-phase [Set] [1] 1 PHAdd VA loads: 7,800 + 15,100 +
5,100 + 8,900 +
6,470 [=] 43,370.Enter as VA [VA] 43,370. VAEnter volts 240 [Volts] 240. VOLTSolve for amps [Amps] 180.70833 AMPS
Finding Amps from Kilowatts
What is the amperage for a 75 kW loadconnected in a 120/208 volt, 3 circuit?
Steps Keystrokes DisplayClear calculator [On/C] [On/C] 0.Set to 3-phase [Set] [3] 3 PHEnter kilowatts 75 [kilo-] [Watts] 75. KWEnter volts 208 [Volts] 208. VOLTSolve for amps [Amps] 208.17918 AMPS
-
8/12/2019 Electric Calc Pro
34/68
32 ElectriCalc Pro
Finding Volt-Amps
What is the VA rating for a 120 volt, 22amp, 1 circuit? What is the kVA rat-ing?
Steps Keystrokes Display
Clear calculator [On/C] [On/C] 0.Set to 1-phase [Set] [1] 1 PHEnter volts 120 [Volts] 120. VOLTEnter amps 22 [Amps] 22. AMPS
Solve volt-amps [VA] 2,640. VASolve for kVA [kilo-] [VA] 2.64 KVA
Finding kVA Rating
What is the kVA rating for a 120/208volt, three-phase 65 amp transformer?
Steps Keystrokes Display
Reset calculator [Set] [x] [On/C] 0.Enter volts 208 [Volts] 208. VOLTEnter amps 65 [Amps] 65. AMPSSolve for kVA [kilo-] [VA] 23.417327 KV
-
8/12/2019 Electric Calc Pro
35/68
Users Guide 33
Finding Wattage
A 120 volt single-phase 45 amp electri-cal motor has an 87% power factor.What is its wattage?
Steps Keystrokes Display
Clear calculator [On/C] [On/C] 0.Set to 1-phase [Set] [1] 1 PHEnter volts 120 [Volts] 120. VOLTSet power fact % 87 [Set] [Watts] 87. PF%
Enter amps 45 [Amps] 45. AMPSSolve for watts [Watts] 4,698. WATT
Finding kW Rating
Whats the kW rating for a 90 amp, 208volt, three-phase broiler with 100%power factor?
Steps Keystrokes DisplayClear calculator [On/C] [On/C] 0.Set to 3-phase [Set] [3] 3 PHSet power factor 100 [Set] [Watts] 100. PF%Enter amps 90 [Amps] 90. AMPSEnter volts 208 [Volts] 208. VOLTSolve for kW [kilo-] [Watts] 32.423991 KW
-
8/12/2019 Electric Calc Pro
36/68
34 ElectriCalc Pro
Motor HorsepowerThe ElectriCalc Pro can calculate thefull load current (amps) of a motor,based on phase, voltage and motor(synchronous or induction). It usesNEC Tables 430-148 and 430-150 to
determine the motor full load current. (Ifyou enter a value for HP or voltage thatdoes not correspond to these tables,the unit will display Error 8).
The ElectriCalc Pro can also calculatean equivalent horsepower for either aninduction or a synchronous motorbased on a voltage, phase and full loadcurrent. When calculating motor HPfrom an entered amperage, a result notdirectly matching a value in NEC Table430-148 or 430-150 will cause the cal-culator to choose the next higher table
value for motor horsepower.
-
8/12/2019 Electric Calc Pro
37/68
Users Guide 35
Finding Single-Phase Full LoadCurrent
A 2 HP induction motor operates on 230volt, single-phase power. What is the fullload current for this motor?
Steps Keystrokes Display
Reset calculator [On/C] 0.Set to 1-phase [Set] [1] 1 PHEnter volts 230 [Volts] 230. VOLTEnter HPind 2 [HPmotor] 2. HP INDFind full load amps [Amps] 12. FLC A
Finding Motor Wire Size andAmpacity
Find the wire size required to connect acontinuous run, 3, 3 HP inductionmotor into a 230V circuit.
Steps Keystrokes Display
Reset calculator [Set] [x] [On/C] 0.Enter volts 230 [Volts] 230. VOLTEnter HPind 3 [HPmotor] 3. HP INDFind load current [Amps] 9.6 FLC A
Find 125% A size [Set] [WireSz] 14 CU AWWIRE SIZE 125%
Find max ampacity [WireSz] 14 20.0WIRE A125%
NOTE: Display will show wire size in the upper left when displaying wire ampacity rating.
-
8/12/2019 Electric Calc Pro
38/68
36 ElectriCalc Pro
Finding Synchronous MotorHorsepower
A synchronous motor is defined ashaving a 27 amp load on a 240 volt, 3circuit. What is its horsepower?
Steps Keystrokes Display
Reset calculator [On/C] 0.Set to synch. [Set] [8] 0. SYNCEnter volts 240 [Volts] 240. VOLT
Enter amps 27 [Amps] 27. AMPSSolve for Hp [HPmotor] 25. HP SYNC
Ampacity Wire SizingThe required wire size of a serviceconductor can be determined based onthe specified electrical requirementsand the [WireSz] key. The wire size isautomatically recalculated wheneverthe wire insulation (temperature) ratingsor wire material (copper or aluminum)types are revised. Wire sizing is based
on the requirements defined in NECTables 310-16 and 310-17.
-
8/12/2019 Electric Calc Pro
39/68
Users Guide 37
Wire Sizing Basedon Insulation Rating
Wiring is being installed in a 240 volt,single-phase system rated at 30 kVA.What is the wire size needed if you use60C copper wire?
Steps Keystrokes Display
Clear calculator [On/C] [On/C] 0.Set to 1-phase [Set] [1] 1 PHSet to 60C [Set] [6] 1 60 Cu 1 PHEnter kVA 30 [kilo-] [VA] 30. KVAEnter volts 240 [Volts] 240. VOLTFind amps [Amps] 125. AMPSFind CU wire size [WireSz] 0 CU
AWG WIRE SIZE
Re-sizing Wire Based onDifferent Insulation Ratings
What wire size is required for a 75Ccopper branch circuit carrying a load of260 amps? What would the wire size beif 90C copper is used?
Steps Keystrokes Display
Reset calculator [Set] [x] [On/C] 0.Set to 75C [Set] [7] 3 75 Cu 0.Enter amps 260 [Amps] 260. AMPSFind wire size [WireSz] 300 CU
AWG WIRE SIZEChange to 90 [Set] [9] 0000 CUAWG WIRE SIZE
-
8/12/2019 Electric Calc Pro
40/68
38 ElectriCalc Pro
Wire Sizing Basedon Ambient Temperature
Find the 90C aluminum wire sizeneeded to connect a 47,700 volt-ampload to a 240 volt, single-phase source.What is the adjusted wire size, if theambient temperature rating is changedfrom the default 30C to 40C?
Steps Keystrokes Display
Clear calculator [On/C] [On/C] 0.Set to 1-phase [Set] [1] 1 PHSet to 90C [Set] [9] 1 90 Cu 1 PHSet toAl [Set] [4] 1 90 Al 1 PHEnter VA 47700 [VA] 47,700. VAEnter volts 240 [Volts] 240. VOLTFind amps [Amps] 198.75 AMPSFind wire size [WireSz] 0000 AL
AWG WIRE SIZE
Change ambienttemperature 40 [Set] [2] AMB 40.CFind adjustedwire size [WireSz] 250 AL
AWG WIRE SIZE
Reset amb. temp 30 [Set] [2] AMB 30.C
*NOTE: Ambient temperature will re- main at 40C unless you change it or perform an ALL CLEAR ( [Set] [x] ).
-
8/12/2019 Electric Calc Pro
41/68
Users Guide 39
Wire Sizing Based onMaterial Type
Find the wire size for a 75C copperwire carrying a 3 load of 265 amps.What is the equivalent aluminum wiresize?
Steps Keystrokes Display
Reset calculator [Set] [x] [On/C] 0.Set to 75C [Set] [7] 3 75 Cu 0.
Enter amps 265 [Amps] 265. AMPSFind wire size [WireSz] 300 CU
AWG WIRE SIZEChange to alum. [Set] [4] 400 AL
AWG WIRE SIZE
Sizing Parallel Conductors
What size 60C insulated copper wire is
required for a single conductor carryinga 500 amp load in a Free Air environ-ment (30C amb. temp.)? What size for2 parallel conductors? For 3 conduc-tors?
-
8/12/2019 Electric Calc Pro
42/68
40 ElectriCalc Pro
(Contd)Steps Keystrokes Display
Reset calculator [Set] [x] [On/C] 0.Set free air mode [Set] [5] 3 60 FrAir Cu 0.Enter amps 500 [Amps] 500. AMPSFind 1 wire size [WireSz] 500 CU
AWG WIRE SIZEFind 2 wire size 2 [ParSz] 000 CU
PAR WIRE SIZEFind 3 wire size 3 [ParSz] 0 CU
PAR WIRE SIZE
NOTE: Parallel wire sizes smaller than 1/0 will be displayed as nonE.
Finding Derated Wire Size
What is the derated wire size requiredfor nine 75C copper wires, each carry-ing a maximum load of 65 amps?
Steps Keystrokes Display
Reset calculator [Set] [x] [On/C] 0.Set to 75C [Set] [7] 3 75 Cu 0.Enter amps 65 [Amps] 65. AMPSFind normalwire size [WireSz] 6 CU
AWG WIRE SIZEFind derated
wire size 9 [Set] [ParSz] 3 CUD/R WIRE SIZE
-
8/12/2019 Electric Calc Pro
43/68
Users Guide 41
Sizing Temperature-AdjustedDerated Wires
A circuit was built with 90C aluminumwire connecting a 47,650 volt-amp loadto a 240 volt, single-phase source.Ambient temperature is 50C. What isthe derated wire size required if eightcurrent-carrying THHN wires were in-stalled in the raceway?
Steps Keystrokes DisplayReset calculator [On/C] 0.Set to 1-phase [Set] [1] 1 PHSet to 90C [Set] [9] 1 90 Cu 1 PHToggle to alum. [Set] [4] 1 90 Al 1 PHEnter volt-amps 47650 [VA] 47,650. VAEnter volts 240 [Volts] 240. VOLTSet to 50C amb 50 [Set] [2] AMB 50 CFind adjst wire sz. [WireSz] 300 AL
AWG WIRE SIZEFind derated 8 [Set] [ParSz] 500 ALwire size D/R WIRE SIZE
NOTE: Ambient temperature should be
changed back to 30C to avoid conflicts in answers through out the rest of this manual.
Reset to 30C 30 [Set] [2] AMB 30 C
-
8/12/2019 Electric Calc Pro
44/68
42 ElectriCalc Pro
Voltage DropThe reduction in voltage between thepower source and the load can be de-termined by entering the phase, volts,amps, wire material, voltage drop wiresize and length of run. The calculator
determines resistance and then thevoltage reduction. Voltage drop can bedisplayed as volts dropped, or as apercent reduction of potential load.
This calculator also finds voltage dropwire size once you have entered orcalculated the phase, volts, amps,length, wire type, and allowable VDpercentage. It will solve for the distance([Length]) once you have entered orcalculated the phase, volts, amps, wiretype, voltage drop wire size, and allow-able VD percentage. The ElectriCalc
Pro uses resistance values found inNEC Table 8 to determine voltage drop.
NOTE: Voltage drop solutions may vary slightly from actual AC circuit meas- urements as the calculator does notincorporate factors such as inductive reactance, skin effect, raceway mate- rial, etc. In most situations, the DC Voltage Drop calculation is sufficient to meet safety standards.
-
8/12/2019 Electric Calc Pro
45/68
Users Guide 43
IMPORTANT NOTE ONVOLTAGE DROP CALCULATIONS
The ElectriCalc Pro calculates voltagedrop and wire size using DC resistanceas defined by the 2002 NEC. To findthe voltage drop for a specific wire size,you must first enter amps and the one-
way wire length (and other requiredvariables), entering the specific wiresize last . Otherwise, for your safety thecalculator will recalculate the wire sizesbased on the 99 NEC Ampacity Tablesand maximum allowable voltage drop.
Finding Single-PhaseVoltage Drop
You are installing 175 feet of 75C, #8THW branch circuit copper conductorsto supply an 11A load on a 208V 1system. What is the source voltagedrop at the load?
Steps Keystrokes Display
Reset calculator [Set] [x] [On/C] 0.Set to 1-phase [Set] [1] 1 PH
Set to 75C [Set] [7] 1 75 Cu 1 PHEnter amps 11 [Amps] 11. AMPSEnter volts 208 [Volts] 208. VOLTEnter length 175 [Length] 175. FEETEnter wire size 8 [WireSz] 8 CU
AWG WIRE SIZESolve volt. drop [VD%] 3.0 DROP VSolve % v.drop [VD%] 1.4 DROP V %
-
8/12/2019 Electric Calc Pro
46/68
44 ElectriCalc Pro
Finding Three-PhaseVoltage Drop
A 20-amp three-phase load is being fedby a 230-volt source located 150 feetaway. The installation specificationsrequire 75C #10 THW stranded copperconduc-tor. What is the voltage drop onthis branch circuit?
Steps Keystrokes Display
Reset calculator [Set] [x] [On/C] 0.Set to 75C [Set] [7] 3 75 Cu 0.Enter amps 20 [Amps] 20. AMPSEnter volts 230 [Volts] 230. VOLTEnter length(feet) 150 [Length] 150. FEETEnter VD wire size10[WireSz] 10 CU
AWG WIRE SIZESolve volt. drop [VD%] 6.4 DROP VSolve % v.drop [VD%] 2.8 DROP V %
-
8/12/2019 Electric Calc Pro
47/68
Users Guide 45
Finding Voltage Drop Wire Size
A 20-amp single-phase 208-volt load willbe located 175 feet away from thesource. Assuming a 3% allowable volt-age drop, what is the size of 75C con-ductor re-quired for this branch circuit?
Steps Keystrokes Display
Reset calculator [On/C] 0.Set to 75C [Set] [7] 3 75 Cu 0.
Set to 1-phase [Set] [1] 1 PHEnter amps 20 [Amps] 20. AMPSEnter volts 208 [Volts] 208. VOLTEnter distance 175 [Length] 175. FEETEnter allow. VD% 3 [VD%] 3.0 DROP V %Find wire size [WireSz] 8 CU
AWG VD WIRE SIZEFind actualvoltage drop [VD%] 5.4 DROP V
Find % v.drop [VD%] 2.6 DROP V %
-
8/12/2019 Electric Calc Pro
48/68
46 ElectriCalc Pro
Finding Voltage Drop Distance
How far from a single-phase 240-voltsource can you install a 15 amp loadusing 60C #10 Al branch circuit con-ductors? Assume a 3% allowable volt-age drop.
Steps Keystrokes Display
Reset calculator [Set] [x] [On/C] 0.Set to 1-phase [Set] [1] 1 PH
Set to aluminum [Set] [4] 1 60 Al 1 PHEnter amps 15 [Amps] 15. AMPSEnter volts 240 [Volts] 240. VOLTEnter wire size 10 [WireSz] 10 AL
AWG WIRE SIZEEnter 3% VD 3 [VD%] 3.0 DROP V %Find distance [Length] 123.77387 FEETFind actualvoltage drop [VD%] 7.2 DROP AL V
Find % v.drop [VD%] 3.0 DROP AL V %NOTE: The calculator automatically makes adjustments for resistance using NEC Chap 9, Table 8, if the insulation
type is other than 75C.
-
8/12/2019 Electric Calc Pro
49/68
Users Guide 47
Finding Voltage DropResistance
What is the resistance of 85 feet of #290C copper conductor?
Steps Keystrokes Display
Reset calculator [Set] [x] [On/C] 0.Set to 90C mode [Set] [9] 3 90 Cu 0.Enter wire size 2 [WireSz] 2 CU
AWG WIRE SIZE
Find resistance [Set] [Length] 0.2033993OHMS WIRE
Find 85 ft resist* [] 1000 [x] 85 [=] 0.0172889
*NOTE: Given resistance per 1000 feet,divide by 1000 to get a per foot resis- tance, then multiply by 85.
Finding DC Resistance
What is the equivalent resistance of a12 volt DC circuit pulling 5 amps?
Steps Keystrokes Display
Reset calculator [On/C] 0.Enter voltage 12 [Volts] 12. VOLTEnter amps 5 [Amps] 5. AMPSFind resistance [Set] [Volts] 2.4 OHMS
-
8/12/2019 Electric Calc Pro
50/68
48 ElectriCalc Pro
Ground Conductor Wire SizeYou can use single or multiple serviceentrance conductor(s) to find thegrounding electrode conductor for ACsystems. When using multiple conduc-tors, the ElectriCalc Pro uses the
equivalent circular mils to find thegrounding electrode conductor (basedon NEC Table 250-66).
Find the grounding electrode conductorwire size required when 2/0 is the larg-est 3-phase 75C copper service-entrance conductor being used. Whatis the equivalent aluminum size? Whatis the equivalent circular mils?
Steps Keystrokes Display
Reset calculator [On/C] 0.Set cond. temp. [Set] [7] 3 75 Cu 0.Enter wire size 00 [WireSz] 00 CU
AWG WIRE SIZEFind grnd wire sz [Grnd] 4 CU
GRND WIRE SIZEFind alum size [Grnd] 2 AL
GRND WIRE SIZEFind circular mils [Grnd] 133,100.
CMIL WIRE
-
8/12/2019 Electric Calc Pro
51/68
Users Guide 49
Equip. Grounding ConductorWire SizeThe [Set] [Grnd] keystroke can be usedto find the grounding conductor size forraceways and over-current devices incircuit ahead equipment. The calcula-
tor uses the displayed amperage valueto solve for the equipment groundingconductor based on NEC Table250-122.
Find the equipment grounding conduc-tor size required when the circuit-breaker is rated at 45 amps and 90copper is being used in the installation.
What is the equivalent aluminum size?
Steps Keystrokes Display
Reset calculator [On/C] 0.Set cond. temp. [Set] [9] 3 90 Cu 0.Enter amp rating 45 [Amps] 45. AMPSFind equip. grnd.wire size [Set] [Grnd] 10 CU
EQPG WIRE SIZE
Find alum size [Grnd] 8 ALEQPG WIRE SIZE
-
8/12/2019 Electric Calc Pro
52/68
50 ElectriCalc Pro
Fuse and Circuit Breaker SizeWhat is the computed dual elementand single element fuse size for a 230volt, 3-phase, 50 HP induction motor?What are the Instantaneous Trip andInverse Time Circuit Breaker require-
ments?
Steps Keystrokes Display
Reset calculator [On/C] 0.Enter volts 230 [Volts] 230. VOLTEnter hp 50 [HPmotor] 50. HP INDFind full current [Amps] 130. FLC AFind DE fuse size [DEFuse] 227.5
dE AMPS
Display % used [DEFuse] 175. %FLCFind SE fuse size [Set] [DEFuse] 390.SE AMPS
Display % used [DEFuse] 300. %FLCFind inv. time brkr [InvTime] 325. b2 AMPSDisplay % used [InvTime] 250. %FLCFind ins. tripbreaker sz. [Set] [InvTime] 1,040.
b1 AMPSDisplay % used [InvTime] 800. %FLC
-
8/12/2019 Electric Calc Pro
53/68
Users Guide 51
Starter SizeWhat NEMA size starter is required fora 575 volt, 3, 20 HP induction motor?
Steps Keystrokes Display
Reset calculator [On/C] 0.
Enter volts 575 [Volts] 575. VOLTEnter hp 20 [HPmotor] 20. HP INDSolve forstarter size [Set] [HPmotor] 2
STAR SIZE
Overload Protection SizeWhat overload protection device size isrequired for a 460 volt, 3-phase, 15 HP
induction motor with a nameplate cur-rent rating of 19.2 amps and a 1.0 ser-vice factor? What is the required over-load rating at 125% (for a 1.15 servicefactor)?
Steps Keystrokes Display
Reset Calculator [On/C] 0.Enter volts 460 [Volts] 460. VOLTEnter horsepower 15 [HPmotor] 15. HP INDEnter nameplatecurrent 19.2 [Amps] 19.2 AMPS
Find overload size [O-Load] 22.08 ol AMPSDisplay % used [O-Load] 115. %FLCFind 125% load 125 [O-Load] 24.
ol AMPSDisplay % used [O-Load] 125 %FLC
-
8/12/2019 Electric Calc Pro
54/68
52 ElectriCalc Pro
Conduit SizeThe ElectriCalc Pro can calculate thesize of conduit required when runningsingle or multiple wires using the[CondSz] key and the calculators inter-nal tables. The calculator uses NEC
values for area of THW, THHN, andXHHW wires. When using the actualwire areas (and following the guidelinesin NEC Chapter 9, Tables 1, 3, 4 and5), the calculator can calculate a con-duit size based on the conduit type andthe same or different wire types andsizes.
To select a specific conduit type, enterthe corresponding number of the con-duit and then press [Set] [CondSz]. Thenumbers and types are:
1) EMT 2) ENT 3) FMC 4) IMC5) LFNB 6) LFNA 7) LFMC 8) RMC9) P-80 10) P-40 11) P-A 12) P-EB
When you enter a new conduit type orscroll through the types, you will seethe updated conduit size (if you haveentered the wire type and quantity).
-
8/12/2019 Electric Calc Pro
55/68
Users Guide 53
Finding Motor Branch-CircuitWire Size & Conduit Size
Same Wire Type & SizeWhat size THHN copper wire & RMCconduit are needed to connect a 10 HP1 induction motor to a 115 volt source?
Steps Keystrokes Display
Reset calculator [Set] [x] [On/C] 0.Set to 1-phase [Set] 1 1 PHEnter volts 115 [Volts] 115. VOLTEnter horsepower 10 [HPmotor] 10. HP INDEnter cond. type 8 [Set] [CondSz] nonE
RMCDisplay full load
amps [Amps] 100. FLC AFind wire size [Set] [WireSz] 0 CUAWG WIRE SIZE 125%
Find wire ampacity [WireSz] 0 125.0*WIRE A125%
Find conduit size [CondSz] 1.25 inRMC COND SIZE
Find total # wires [CondSz] 2. TTL WIRESFind conduit fill % [CondSz] 24.3
FILL COND %Find act. fill area [CondSz] 0.3710
FILL TTL WIRE AREAFind rem. area [CondSz] 0.1021
REM WIRE AREA
NOTE: Display will also show wire size in upper left when displaying maximum ampacity rating.
-
8/12/2019 Electric Calc Pro
56/68
54 ElectriCalc Pro
NOTE: If a wire size has been calculated or stored, and the wire type/quantity is not defined,
the calculator will assume 2 THHN wires for 1 and 3 THHN wires for 3 when calculatingconduit size.
Finding Conduit Sizes for Multi-ple Conductors Same WireType & Size
Find the minimum IMC conduit size for
eleven #6 THHN copper wires.
Steps Keystrokes Display
Clear calculator [On/C] [On/C] 0.Enter cond. type 4 [Set] [CondSz] nonE
IMCEnter wire size 6 [WireSz] 6 CU
AWG WIRE SIZEEnter # THHN 11 [#THHN] 11.
THHN WIRESFind conduit size [CondSz] 1.25 inIMC COND SIZE
-
8/12/2019 Electric Calc Pro
57/68
Users Guide 55
Finding Number of Wires in Ex-isting Conduit Same Size,
Various TypesFind the maximum number of #10THHN copper wires that can be pulledthrough an existing 3 EMT conduit.How many XHHW wires? How manyTHW wires?
Steps Keystrokes Display
Clear calculator [On/C] [On/C] 0.Enter cond. type 1 [Set] [CondSz] EMT
nonE CONDEnter wire size 10 [WireSz] 10 CU
AWG WIRE SIZE
Enter conduit size 3 [CondSz] 3.00 inEMT COND SIZEFind max THHN # [#THHN] 167.
THHN TTL WIRESFind max XHHW# [#XHHW] 145.
XHHW TTL WIRESFind max THW # [#THW] 145.
THW TTL WIRES
Finding Conduit Size - MultipleConductors Different Wire Sizes& Types
Three 1/0 THWN 75C conductors andone #2 XHHW 75C copper conductorare to connect to a panel board using asingle conduit. What is the cross-
-
8/12/2019 Electric Calc Pro
58/68
-
8/12/2019 Electric Calc Pro
59/68
Users Guide 57
Error CodesThe error codes for the ElectriCalc Pro are listed below (Note: To clear anerror, simply press any key):
Error Description1 Display register overflow
(Answer too large to fit display) 2 Invalid or out-of-scale entry
3 PF or EFF calculated above 100%
4 Conduit Size beyond limits of table5 Unable to calculate VDWire Size
(Amps/Length too high)
8 Invalid HP entry per NEC table
9 Entered or calculated more than 15different wires sizes
11 Temperature setting out of range forwire computation.
Battery InformationThe calculator is powered by a single 3-Volt Lithium CR-2032 battery. Thisshould last upwards of 800 hours ofactual use (1 year plus for most peo-ple). If the display becomes very dim orerratic, replace the battery.
NOTE: Please use caution when dis- pos-ing of your old batteries as theycontain hazardous chemicals.
-
8/12/2019 Electric Calc Pro
60/68
58 ElectriCalc Pro
2002 NEC ReferencesTable 250-66Table 250-122Table 310-15(b)(2)(a)Table 310-16Table 310-17
Chapter 9, Table 1, 4, 5 and 8Section 430-32Table 430-148Table 430-150Table 430-152Appendix C
Updating Future Code
RevisionsThis model is updateable for futureNEC Editions. For information on 2005and 2008 Codes, contact the dealer
where this calculator was purchased oryou may contact Calculated Industries,Inc. in the fall of the year prior.
-
8/12/2019 Electric Calc Pro
61/68
Users Guide 59
Settings
Permanent Values/Settings
Values and settings maintained in per-manent memory can only be changed(1) by pressing [Set] [x] (resets calcula-tor to default settings), or (2) by chang-ing each one or all of these settings.The following are permanent values:
(1) Selectable (60C/75C/90C) insula-tion ratings and CU/AL wire type rat-ings
(2) Phase setting (1/3)(3) The entered values for volts, volt-
age drop %, power factor % andefficiency %
Semi-Permanent Values
The following semi-permanent valuesare cleared to default settings when thecalculator is shut off:
(1) Independent User Memory(2) Free Air mode
-
8/12/2019 Electric Calc Pro
62/68
60 ElectriCalc Pro
Warranty
Warranty Repair Service U.S.A.Calculated Industries, Inc. (CI) war-rants this product against defects inmaterials and workmanship for a period
of one (1) year from the date of originalconsumer purchase in the U.S. If adefect exists during the warranty pe-riod, CI at its option will either repair(using new or remanufactured parts) orreplace (with a new or remanufacturedunit) the product at no charge.
THE WARRANTY WILL NOT APPLY TOTHE PRODUCT IF IT HAS BEEN DAM-AGED BY MISUSE, ALTERA-TION, ACCIDENT, IMPROPER HAN-DLING OR OPERATION, OR IF UN-AUTHORIZED REPAIRS ARE AT-TEMPTED OR MADE. SOME EXAM-PLES OF DAMAGES NOT COVEREDBY WARRANTY INCLUDE, BUT ARENOT LIMITED TO, BATTERY LEAK-AGE, BENDING, OR VISIBLE CRACK-
ING OF THE LCD, WHICH ARE PRE-SUMED TO BE DAMAGES RESULT-ING FROM MISUSE OR ABUSE.
To obtain warranty service in the U.S.,
ship the product postage paid to the CIAuthorized Service Provider listed onthe back page of the Users Guide.
-
8/12/2019 Electric Calc Pro
63/68
Users Guide 61
Please provide an explanation of theservice requirement, your name, ad-
dress, day phone number and datedproof of purchase (typically a salesreceipt). If the product is over 90 daysold, include payment of $6.95 for returnshipping and handling within the con-
tiguous 48 states. (Outside the contigu-ous 48 states, please call CI for returnshipping costs.)
A repaired or replacement product
assumes the remaining warranty of theoriginal product or 90 days, whicheveris longer.
Non-Warranty Repair Service U.S.A.Non-warranty repair covers servicebeyond the warranty period or servicerequested due to damage resulting
from misuse or abuse.
Contact the CI Authorized Service Pro-vider listed on the back page of theUsers Guide to obtain current productrepair information and charges. Repairsare guaranteed for 90 days.
-
8/12/2019 Electric Calc Pro
64/68
62 ElectriCalc Pro
Repair Service Outside the U.S.A.
Not all countries have CI AuthorizedService Providers or the same warrantyand service policies. To obtain warrantyor non-warranty repair service for goodspurchased outside the U.S., contact thedealer through which you initially pur-chased the product. If you cannot rea-sonably have the product repaired inyour area, you may contact CI to obtain
current product repair information andcharges, including freight and duties.
Disclaimer
CI MAKES NO WARRANTY OR REP-RESENTATION, EITHER EXPRESSOR IMPLIED, WITH RESPECT TOTHE PRODUCTS QUALITY, PER-FORMANCE, MERCHANTABILITY,
OR FITNESS FOR A PARTICULARPURPOSE. AS A RESULT, THISPRODUCT, INCLUDING BUT NOTLIMITED TO, KEYSTROKE PROCE-DURES, MATHEMATICAL ACCU-
RACY AND PREPROGRAMMED MA-TERIAL, IS SOLD AS IS, AND YOUTHE PURCHASER ASSUME THEENTIRE RISK AS TO ITS QUALITYAND PERFORMANCE.
IN NO EVENT WILL CI BE LIABLEFOR DIRECT, INDIRECT, SPECIAL,
-
8/12/2019 Electric Calc Pro
65/68
Users Guide 63
INCIDENTAL, OR CONSEQUENTIALDAMAGES RESULTING FROM ANYDEFECT IN THE PRODUCT OR ITSDOCUMENTATION.
The warranty, disclaimer, and remediesset forth above are exclusive and re-
place all others, oral or written, ex-pressed or implied. No CI dealer,agent, or employee is authorized tomake any modification, extension, oraddition to this warranty.
Some states do not allow the exclusionor limitation of implied warranties orliability for incidental or consequentialdamages, so the above limitation orexclusion may not apply to you. Thiswarranty gives you specific rights, andyou may also have other rights, whichvary, from state to state.
FCC Class BThis equipment has been certified tocomply with the limits for a Class B
computing device, pursuant to SubpartJ of Part 15 of FCC rules.
-
8/12/2019 Electric Calc Pro
66/68
64 ElectriCalc Pro
Legal NoticesSoftware copyrighted and licensed toCalculated Industries, Inc. by SpecialtyCalculator Technologies, LLC, 2002.
Users Guide is copyrighted by Calcu-
lated Industries, Inc., 2002.
ElectriCalc and Calculated Industries are registered trademarks of CalculatedIndustries, Inc.
ALL RIGHTS RESERVED
Calculated Industries, Inc.4840 Hytech Drive
Carson City, NV 89706 U.S.A775/885-4975 o Fax: 775/885-4949E-mail: [email protected]
http://www.calculated.com
File: 5060-UG-B
-
8/12/2019 Electric Calc Pro
67/68
-
8/12/2019 Electric Calc Pro
68/68