- P:\2016\16-032 Eglin AFB Freshen's Studio\Eglin AFB Freshen's Studio\Constructs\ELECTRICAL\LEGENDS NOTES AND ABBREVIATIONS.dwg SmSsiLng MEP Engineering w Harold L. Dell Jr 73914 Florida License Number 28404 129 E. Government Street Pensacola, FL 32502 P: 850-332-5687 F: 850-332-6629 Dell Consulting project: 16-032 ELECTRICAL LEGEND ABBREVIATIONS GENERAL ELECTRICAL DEVICES: $ SINGLE POLE LIGHTING SWITCH. MOUNT 48" AFF UNLESS NOTED OTHERWISE. SUBSCRIPT INDICATES AS FOLLOWS: ^ DUPLEX RECEPTACLE NEMA 5-20R. MOUNT 16" AFF UNLESS NOTED OTHERWISE. VERIFY DUPLEX MOUNTING REQUIREMENTS WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. SUBSCRIPT INDICATES AS FOLLOWS: G - GROUND FAULT CIRCUIT INTERRUPTER TYPE. 84" - MOUNTING HEIGHT OF DEVICE AFF. ® DUPLEX RECEPTACLE NEMA 5-20R. MOUNTED IN MILLWORK. -8> SPECIAL NEMA TYPE RECEPTACLE. VERIFY WITH EQUIPMENT BEING SUPPLIED. MOUNTED 10" AFF, UNLESS NOTED OTHERWISE. MISCELLANEOUS EQUIPMENT: 0 JUNCTION BOX. © ELECTRICAL CONNECTION TO EQUIPMENT. VERIFY LOCATION WITH EQUIPMENT PROVIDER. ® ROUGH-IN BOX. MOUNT AT 18" AFF UNLESS SUBSCRIPTED OTHERWISE. PROVIDE 4" SQUARE BY 2-1/8" DEEP BOX WITH 1" CONDUIT TO ABOVE ACCESSIBLE CEILING AND TURNED HORIZONTAL WITH BUSHING AND PULL STRING. DISTRIBUTION & POWER EQUIPMENT: — EXISTING PANELBOARD. OTHER: CIRCUIT RUN CONCEALED ABOVE CEILING OR IN WALL. Y CIRCUIT RUN CONCEALED IN OR BELOW FLOOR SLAB OR UNDERGROUND. III U 2P2-9 -I NEC 110.26(A) WORKING CLEARANCE. EXISTING LOAD DATA IS NOT AVAILABLE FOR PANEL L4L/L4C/L4R. CONTRACTOR SHALL PERFORM A 30-DAY LOAD STUDY IN ACCORDANCE WITH NEC 220.87, EXCEPTION 1 ON THE PANEL PRIOR TO COMMENCING ANY ELECTRICAL WORK. THE CONTRACTOR SHALL SUBMIT THE RESULTS TO THE ENGINEER FOR REVIEW AND APPROVAL. THE REPORT SHALL CONTAIN PEAK DEMAND VALUES RECORDED AT 15-MINUTE INTERVALS OVER THE DURATION OF THE 30-DAY MONITORING PERIOD. TELECOMMUNICATIONS: > ROUGH-IN FOR COMMUNICATIONS OUTLET (CO). MOUNT ON WALL AT 18" AFF UNLESS SUBSCRIPTED OTHERWISE. INCLUDE 1" EMT FROM ROUGH-IN BOX STUBBED ABOVE CEILING. TERMINATE WITH BUSHING AND PROVIDE PULL STRING. ® ROUGH-IN FOR COMMUNICATIONS OUTLET (CO) MOUNTED IN MILLWORK. HOMERUN TO PANELBOARD. ANY CIRCUIT WITHOUT FURTHER DESIGNATION SHALL BE 2#12,#12G,1/2"C. TICK MARKS INDICATE # OF CONDUCTORS (EGC NOT SHOWN). MINIMUM SIZE ON 120V HOMERUNS GREATER THAN 50 FEET SHALL BE #10 AWG. MINIMUM SIZE ON 120V HOMERUNS GREATER THAN 100 FEET SHALL BE #8 AWG. MINIMUM SIZE ON 120V HOMERUNS GREATER THAN 160 FEET SHALL BE #6 AWG. MINIMUM SIZE ON 277V HOMERUNS GREATER THAN 100 FEET SHALL BE #10 AWG. INCREASE CONDUIT SIZE AS REQUIRED PER NEC. UNDERLINED TEXT INDICATES CIRCUIT DESIGNATION. LIGHT FIXTURE IDENTIFICATION TAG. SEE LIGHT FIXTURE SCHEDULE FOR SYMBOLS & DETAILS. 1 > SHEET NOTE TAG. (4LPl) PANELBOARD, SWITCHBOARD, TRANSFORMER & ELECTRICAL EQUIPMENT IDENTIFICATION TAG. d~T LEADERS. PANELBOARD SCHEDULE MARK: L4R EXISTING PROVIDE NEW C/B IN EXISTING PANELBOARD 1.9 TOTAL (kVA)0A 12.9 0B 12.6 0C 12.9 14.4 12.6 12.5 HIGH PHASE (AMPS) TOTAL LOAD (AMPS) CREATE A DIRECTORY TO INDICATE INSTALLED LOADS. INDICATE LOAD TYPE (REC, LTG, AHU-1, ETC.) AND ROOM NUMBERS SERVED FOR EVERY BRANCH CIRCUIT. 120.0 TOTAL CONNECTED LOAD (kVA) 39.9 110.8 PANELBOARD SCHEDULE MARK: L4C EXISTING TOTAL (kVA) 0A 2.6 0B 6.4 0C 5.6 HIGH PHASE (AMPS) TOTAL LOAD (AMPS) CREATE A DIRECTORY TO INDICATE INSTALLED LOADS. INDICATE LOAD TYPE (REC, LTG, AHU-1, ETC.) AND ROOM NUMBERS SERVED FOR EVERY BRANCH CIRCUIT. 53.3 TOTAL CONNECTED LOAD (kVA) 14.5 40.4 CKT # LOAD DESCRIPTION BREAKER PHASE (kVA) PHASE (kVA) BREAKER LOAD DESCRIPTION CKT # P TRIP A B C A B C TRIP P 1 TOASTER 2 20 - 1.3 20* 2 REC RM 160 DROP IN FOOD WARMER 2 3 - 1.3 4 5 REC RM 160,164 HOT HOLDING CABINET 1 20* 0.5 1.4 20* 1 REC RM 160 MAGATOP REFRIGERATOR 6 7 CHEESE WARMER 1 20 - 1.5 20* 1 REC RM 160 FOOD GUARD LTS & U.C. LTS 8 9 LEMONADE 1 20 - 0.4 20* 1 REC RM 160 POINT OF SALE 10 11 MENU BOARD 1 20 - 1.4 20* 1 REC RM 160 NUT. TOUCH SCR., DIGIT. SIGNAL, MEDIA PLAYER 12 13 SIGNS 1 20 - 1.2 20* 1 REC RM 160 BLENDER SOUTH 14 15 CRT MONITOR 1 20 - 1.2 20* 1 REC RM 160 BLENDER NORTH 16 17 U.C. REF. 1 20 - 0.6 20* 1 REC RM 160 FRESHENS 18 19 GAS GRIDDLE 1 20 - 0.5 20* 1 REC RM 160 REFRIG. CORD PAN 20 21 U.C. REF. 1 20 - 1.8 20* 1 REC RM 160 DROP IN WATER 22 23 U.C. REF. 1 20 - 1.2 20* 1 REC RM 160 MICROWAVE 24 25 RECEPTACLE 1 20 - 1.8 30* 2 REC RM 160 26 27 FLY FAN 1 20 - 1.8 CREPE IRON 28 29 FLY FAN 1 20 - 1.8 30* 2 REC ROM 160 30 31 FRY DUMP 1 20 - 1.8 CREPE IRON 32 33 FRYER 1 20 - 4.8 REC RM 160 36 35 REC RM 160 MAGATOP REFRIGERATOR 1 20 1.4 4.8 50* 3 VENTLESS OVEN 38 37 SAUCE WARMER 1 20 - 4.8 40 39 CASH REGISTER 1 20 - 1.3 20 2 DISPOSAL 40 41 AMPLIFIER 1 20 - 1.3 164 42 JGHTING FIXTURES: SEE LIGHTING FIXTURE SCHEDULE FOR SYMBOLS AND DESCRIPTIONS. 2P10 24 WRITE ON THE FRONT OF EACH — WIRING DEVICE THE CORRESPONDING CIRCUIT DESIGNATION SO THAT IT IS NOT VISIBLE WITH THE COVERPLATE ON. LETTERING SHALL BE 1/4" HIGH, FINE POINT PERMANENT FELT TIP BLACK MARKER, BY HAND. USE WHITE MARKER ON BLACK DEVICES. "4L1- A AMPS MH MANHOLE AC ABOVE COUNTER MIN MINIMUM AFF ABOVE FINISHED FLOOR MISC MISCELLANEOUS ARCH ARCHITECT OR ARCHITECTURAL MLO MAIN LUGS ONLY AWG AMERICAN WIRE GAUGE MNT MOUNTING HEIGHT BJ BONDING JUMPER MTG MOUNTING BKR CIRCUIT BREAKER N1 NEMA 1 BLDG BUILDING N/A NOT APPLICABLE BOD BASIS OF DESIGN NEC NATIONAL ELECTRICAL CODE C CONDUIT NESC NATIONAL ELECTRICAL SAFETY CODE C/B CIRCUIT BREAKER NEU NEUTRAL CLG CEILING OCPD OVERCURRENT PROTECTION DEVICE CKT CIRCUIT PBD PANELBOARD DEMO DEMOLISH PF POWER FACTOR DM EXISTING TO BE DEMOLISHED PNL PANELBOARD EC ELECTRICAL CONTRACTOR PWR POWER EGC EQUIPMENT GROUNDING CONDUCTOR REC RECEPTACLE ELEC ELECTRICAL REQD REQUIRED EX EXISTING TO REMAIN RM ROOM EMT ELECTRICAL METALLIC TUBING RGS RIGID GALVANIZED STEEL CONDUIT EQUIP EQUIPMENT RNC RIGID NON-METALLIC CONDUIT FMC FLEXIBLE METAL CONDUIT SCA SHORT CIRCUIT AMPS FLA FULL LOAD AMPS SF SUPPLY FAN FLR FLOOR SPEC SPECIFICATION GFI GROUND FAULT INTERRUPTER TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION G GROUND (OR GFI FOR RECEPTACLE SUBSCRIPT) TYP TYPICAL GND GROUND UL UNDERWRITERS’ LABORATORIES GEC GROUNDING ELECTRODE CONDUCTOR UNO UNLESS NOTED OTHERWISE HP HEAT PUMP OR HORSEPOWER V VOLT HVAC HEATING, VENTILATION & AIR-CONDITIONING VA VOLT-AMPERES IMC INTERMEDIATE METAL CONDUIT W WATTS JB JUNCTION BOX WAO WORK AREA OUTLET k KILO WSR WITHSTAND RATING kAIC KILO-AMPERE INTERRUPTING CAPABILITY XFMR TRANSFORMER kCMIL THOUSAND CIRCULAR MILS PHASE LTG LIGHTING 72° DEGREES LFMC LIQUID TIGHT FLEXIBLE METAL CONDUIT A DELTA MCA MINIMUM CIRCUIT AMPACITY Q OHMS MCM THOUSAND CIRCULAR MILS RECEPTACLE WITH COVERPLATE REMOVED SWITCH WITH COVERPLATE REMOVED 1 WIRING DEVICE LABEL DETAIL © NOT TO SCALE ROOF NOTE: ALL RECESSED FIXTURES SHALL BE WIRED FROM A JUNCTION BOXAS SHOWN ABOVE, INCLUDING FIXTURES SHOWN IN CONTINUOUS ROWS; NO WIRING THROUGH FIXTURES. AT CONTRACTOR'S PPTION, SEVERAL FIXTURES (NOT TO EXCEED 4) MAY BE WIRED TO A COMMON JUNCTION BOX. Æ ^ 3/8" FMC 4 FOOT (MINIMUM) TO 6 FOOT (MAXIMUM) LONG PROVIDE CEILING SUPPORT WIRE CKT LOAD BREAKER PHASE (kVA) PHASE (kVA) BREAKER LOAD CKT # DESCRIPTION P TRIP A B C A B C TRIP P DESCRIPTION # 1 DRINK DISP. 1 20 - - 2 3 ICE DISP 1 20 - - 60 3 SPARE 4 5 SODA DISP 1 20 - - 6 7 ICE TEA DISP. ICE DISP 1 20 - - 8 9 ICE DISP 1 20 - - 100 3 STARBUCKS COFFEE STAND 10 11 SODA DISP 1 20 - - 12 13 COFFEE BREWER 2 40 - - 20 2 STARBUCKS HWH 14 15 "EAST" - - 16 17 COFFEE BREWER 2 40 - - 20 1 STARBUCKS HWH 18 19 "WEST" - - 20 1 VENDOR RECEPT. 20 21 SODA DISP 1 20 - - 20 2 ICE MKR. FOR DRINK DISP. 22 23 ICE DISP. 1 20 - - 24 25 ICETEA DISP. ICE DISP. 1 20 - - 20 2 ICE MKR. FOR DRINK DISP. 26 27 SODA DISP. 1 20 - - 28 29 ICE DISP 1 20 - - 20 2 ICE MKR. FOR DRINK DISP. 30 31 NON CARB. DRINK DISP. 1 20 - - 32 33 OCCUPIED SPACE 2 50 - 4.9 60* 2 REC RM 164 34 35 - 4.9 CONVECTION STEAMER 36 37 REC RM 164 BLENDER 1 20* 1.6 1.0 15* 2 REC RM 164 38 39 REC RM 160 SIGNALS 1 20* 0.5 1.0 BLAST CHILLER 40 41 SPARE 1 20 - 0.7 20* 1 REC RM 164 CONDENSER FOR STEAMER 42 * PROVIDE NEW C/B IN EXISTING PANELBOARD 1.6 0.5 1.0 5.9 5.6 W THIN 6" OF EACH OF FOUR FIXTURE CORNERS RECESSED FLUORESCENT LIGHTING FIXTURE T CONDUIT JUNCTION BOX SECURE TO STEEL JOIST OR PENDANT HUNG WITH THREADED ROD AND REQUIRED HANGERS. D CLIPS TO PREVENT PROVIDED FIXTURE GR FALLING THRU GRID (4 REQ). Y SUSPENDED CEILING © TYPICAL FIXTURE INSTALLATION DETAIL NOT TO SCALE LIGHTING FIXTURE SCHEDULE MARK MANUFACTURER AND CATALOG NUMBER LAMPS TOTAL WATTS VOLTAGE MOUNTING NOTES TYPE # WATTS L4S4 CREE # LS4-40L-40K-10V LED 40K N/A 44W 44W 277V SURFACE 22 GAUGE CONSTRUCTION ACRYLIC LENS EXB PATHWAY LDEXCR EMERGILITE DXN-R-N-DL LITHONIA LES 3 R VOLT EL N SD DL LED 7.1W 9.0W 7.1W 9.0W WALL OR CEILING INDICATED PROVIDE EMERGENCY NICAD BATTERY BACKUP, ARROWS AS PER PLANS, DIE CAST ALUMINUM HOUSING W/BRUSHED ALUMINUM FACEPLATE, SELF DIAGNOSTICS W/LEDS, DOUBLE FACE AS INDICATED ON PLANS. BATTERY PACK BODINE EMERGI-LITE BEGHELLI 277V INSIDE LIGHT FIXTURE 1400 LUMENS FOR 90 MINUTES, UL 924 LISTED MAINTENANCE-FREE NICKEL-CADMIUM BATTERY, TEST SWITCH, LED INDICATING LIGHT, AUTOMATIC CHARGER NOTES SEE SPECIFICATIONS FOR APPROVED BALLAST MANUFACTURERS. FIXTURES WITH HALF FILLED IN CENTER SHALL BE PROVIDE WITH A BATTERY PACK. SEE PLANS FOR QUANTITY. APPROVAL SUBMITTALS FOR MANUFACTURERS NOT LISTED MUST BE SUBMITTED TO THE ENGINEER 14 DAYS PRIOR TO BID DATE FOR REVIEW. MANUFACTURERS NOT LISTED WILL NOT BE ACCEPTED UNLESS APPROVED BY ADDENDUM. O CD O CD o £ O) E o _Q *t/> to D u CD O £ TD CD O u _i _i L_ o 15 o E 'N' LT) o_ =) CD o o CO O +- CN LO o' C CD +- CN i/) Z "d CD L_ 2 (D U on D = *o > LU +- 1c LO Q U CD CD U) LO +- D £ LO •— o _C U u O CO i_ IV o LO D CN CN GO z: LU X GO LU O' o z < g o o ^ o > >- U Q/ Z Ll_ LU 0 rv co 1 < k >- LO LU ^ CO ^ < o Cû o Ü O' O ÛÛ O' o O' O < o w : XCHANGE ARMY & AIR FORCE EXCHANGE SERVICE PROJECT NO: 1611010126 REVISIONS: ISSUE DATE: 06.17.16 / o V-.Pe/X c\c^ < % = •• NO . 73914 = = ★ : ★ = STATE OF \< 3 THIS DRAWING REPRESENTS DESIGNS PREPARED BY WATERMARK DESIGN GROUP LLC FOR SPECIFIC USE ON THIS PROJECT AND IS NOT TO BE COPIED, REPRODUCED, OR ALTERED WITHOUT THE EXPRESS WRITTEN CONSENT OF THE WATERMARK DESIGN GROUP REPRESENTATIVE AUTHORIZED TO APPROVE THIS USE. UNAUTHORIZED USE IS SUBJECT TO LEGAL ACTION UNDER STATE AND FEDERAL LAW. SHEET TITLE: LEGENDS NOTES AND ABBREVIATIONS - ELECTRICAL SHEET NUMBER: E0 0

Upload: others

Post on 13-Jun-2020

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ELECTRICAL LEGEND ABBREVIATIONS CD · 2016-10-31 · 2#12,#12g,1/2"c. tick marks indicate # of conductors (egc not shown). minimum size on 120v homeruns greater than 50 feet shall

- P:

\201

6\16

-032

Eg

lin

AFB

Fres

hen'

s St

udio

\Egl

in

AFB

Fres

hen'

s St

udio

\Con

stru

cts\

ELEC

TRIC

AL\

LEG

END

S NO

TES

AND

AB

BR

EV

IATI

ON

S.d

wg

S m S siLngMEP Engineering w

Harold L. Dell Jr 73914 Florida License Number 28404

129 E. Government Street Pensacola, FL 32502

P: 850-332-5687 F: 850-332-6629 Dell Consulting project: 16-032

ELECTRICAL LEGEND ABBREVIATIONSGENERAL ELECTRICAL DEVICES:

$ SINGLE POLE LIGHTING SWITCH. MOUNT 48" AFF UNLESS NOTED OTHERWISE. SUBSCRIPT INDICATES AS FOLLOWS:

^ DUPLEX RECEPTACLE NEMA 5-20R. MOUNT 16" AFF UNLESS NOTED OTHERWISE. VERIFY DUPLEX MOUNTING REQUIREMENTS WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. SUBSCRIPT INDICATES AS FOLLOWS:

G - GROUND FAULT CIRCUIT INTERRUPTER TYPE.84" - MOUNTING HEIGHT OF DEVICE AFF.

® DUPLEX RECEPTACLE NEMA 5-20R. MOUNTED IN MILLWORK.

-8> SPECIAL NEMA TYPE RECEPTACLE. VERIFY WITH EQUIPMENT BEING SUPPLIED. MOUNTED 10" AFF, UNLESS NOTED OTHERWISE.

MISCELLANEOUS EQUIPMENT:

0 JUNCTION BOX.

© ELECTRICAL CONNECTION TO EQUIPMENT. VERIFY LOCATION WITH EQUIPMENT PROVIDER.

® ROUGH-IN BOX. MOUNT AT 18" AFF UNLESS SUBSCRIPTED OTHERWISE. PROVIDE 4" SQUARE BY 2-1/8" DEEP BOX WITH 1" CONDUIT TO ABOVE ACCESSIBLE CEILING AND TURNED HORIZONTAL WITH BUSHING AND PULL STRING.

DISTRIBUTION & POWER EQUIPMENT:

— EXISTING PANELBOARD.

OTHER:

CIRCUIT RUN CONCEALED ABOVE CEILING OR IN WALL.

Y CIRCUIT RUN CONCEALED IN OR BELOW FLOOR SLAB OR UNDERGROUND.

I I I U

2P2-9 -I

NEC 110.26(A) WORKING CLEARANCE.

EXISTING LOAD DATA IS NOT AVAILABLE FOR PANEL L4L/L4C/L4R. CONTRACTOR SHALL PERFORM A 30-DAY LOAD STUDY IN ACCORDANCE WITH NEC 220.87,

EXCEPTION 1 ON THE PANEL PRIOR TO COMMENCING ANY ELECTRICAL WORK. THE CONTRACTOR SHALL SUBMIT THE RESULTS TO THE ENGINEER FOR REVIEW AND APPROVAL. THE REPORT SHALL CONTAIN PEAK DEMAND VALUES RECORDED AT

15-MINUTE INTERVALS OVER THE DURATION OF THE 30-DAY MONITORING PERIOD.

TELECOMMUNICATIONS:

> ROUGH-IN FOR COMMUNICATIONS OUTLET (CO). MOUNT ON WALL AT 18" AFF UNLESS SUBSCRIPTED OTHERWISE. INCLUDE 1" EMT FROM ROUGH-IN BOX STUBBED ABOVE CEILING. TERMINATE WITH BUSHING AND PROVIDE PULL STRING.

® ROUGH-IN FOR COMMUNICATIONS OUTLET (CO) MOUNTED IN MILLWORK.

HOMERUN TO PANELBOARD. ANY CIRCUIT WITHOUT FURTHER DESIGNATION SHALL BE 2#12,#12G,1/2"C. TICK MARKS INDICATE # OF CONDUCTORS (EGC NOT SHOWN). MINIMUM SIZE ON 120V HOMERUNS GREATER THAN 50 FEET SHALL BE #10 AWG. MINIMUM SIZE ON 120V HOMERUNS GREATER THAN 100 FEET SHALL BE #8 AWG. MINIMUM SIZE ON 120V HOMERUNS GREATER THAN 160 FEET SHALL BE #6 AWG. MINIMUM SIZE ON 277V HOMERUNS GREATER THAN 100 FEET SHALL BE #10 AWG. INCREASE CONDUIT SIZE AS REQUIRED PER NEC. UNDERLINED TEXT INDICATES CIRCUIT DESIGNATION.

LIGHT FIXTURE IDENTIFICATION TAG. SEE LIGHT FIXTURE SCHEDULE FOR SYMBOLS & DETAILS.

1 > SHEET NOTE TAG.

( 4 L P l) PANELBOARD, SWITCHBOARD, TRANSFORMER & ELECTRICAL EQUIPMENT IDENTIFICATION TAG.

d~T LEADERS.

PANELBOARD SCHEDULEMARK: L4R EXISTING

PROVIDE NEW C/B IN EXISTING PANELBOARD 1.9

TOTAL (kVA)0A 12.9 0B 12.6 0C

12.9

14.4

12.6 12.5

HIGH PHASE (AMPS)

TOTAL LOAD (AMPS)

CREATE A DIRECTORY TO INDICATE INSTALLED LOADS. INDICATE LOAD TYPE (REC, LTG, AHU-1, ETC.) AND ROOM NUMBERS SERVED FOR EVERY BRANCH CIRCUIT.

120.0TOTAL CONNECTED LOAD (kVA) 39.9 110.8

PANELBOARD SCHEDULEMARK: L4C EXISTING

TOTAL (kVA) 0A 2.6 0B 6.4 0C 5.6 HIGH PHASE (AMPS)

TOTAL LOAD (AMPS)

CREATE A DIRECTORY TO INDICATE INSTALLED LOADS. INDICATE LOAD TYPE (REC, LTG, AHU-1, ETC.) AND ROOM NUMBERS SERVED FOR EVERY BRANCH CIRCUIT.

53.3TOTAL CONNECTED LOAD (kVA) 14.5 40.4

CKT

#

LOAD

DESCRIPTION

BREAKER PHASE (kVA) PHASE (kVA) BREAKER LOAD

DESCRIPTION

CKT

#P TRIP A B C A B C TRIP P

1 TOASTER 2 20 - 1.3 20* 2 REC RM 160

DROP IN FOOD WARMER

2

3 - 1.3 4

5 REC RM 160,164 HOT HOLDING CABINET 1 20* 0.5 1.4 20* 1 REC RM 160 MAGATOP REFRIGERATOR 6

7 CHEESE WARMER 1 20 - 1.5 20* 1 REC RM 160 FOOD GUARD LTS & U.C. LTS 8

9 LEMONADE 1 20 - 0.4 20* 1 REC RM 160 POINT OF SALE 10

11 MENU BOARD 1 20 - 1.4 20* 1 REC RM 160 NUT. TOUCH SCR., DIGIT. SIGNAL, MEDIA PLAYER 12

13 SIGNS 1 20 - 1.2 20* 1 REC RM 160 BLENDER SOUTH 14

15 CRT MONITOR 1 20 - 1.2 20* 1 REC RM 160 BLENDER NORTH 16

17 U.C. REF. 1 20 - 0.6 20* 1 REC RM 160 FRESHENS 18

19 GAS GRIDDLE 1 20 - 0.5 20* 1 REC RM 160 REFRIG. CORD PAN 20

21 U.C. REF. 1 20 - 1.8 20* 1 REC RM 160 DROP IN WATER 22

23 U.C. REF. 1 20 - 1.2 20* 1 REC RM 160 MICROWAVE 24

25 RECEPTACLE 1 20 - 1.8 30* 2 REC RM 160 26

27 FLY FAN 1 20 - 1.8 CREPE IRON 28

29 FLY FAN 1 20 - 1.8 30* 2 REC ROM 160 30

31 FRY DUMP 1 20 - 1.8 CREPE IRON 32

33 FRYER 1 20 - 4.8 REC RM 160 36

35 REC RM 160 MAGATOP REFRIGERATOR 1 20 1.4 4.8 50* 3 VENTLESS OVEN 38

37 SAUCE WARMER 1 20 - 4.8 40

39 CASH REGISTER 1 20 - 1.3 20 2 DISPOSAL 40

41 AMPLIFIER 1 20 - 1.3 164 42

JGHTING FIXTURES:

SEE LIGHTING FIXTURE SCHEDULE FOR SYMBOLS AND DESCRIPTIONS.

2P10 24

— WRITE ON THE FRONT OF EACH — WIRING DEVICE THE CORRESPONDING CIRCUIT DESIGNATION SO THAT IT IS NOT VISIBLE WITH THE COVERPLATE ON. LETTERING SHALL BE 1/4" HIGH, FINE POINT PERMANENT FELT TIP

BLACK MARKER, BY HAND. USE WHITE MARKER ON BLACK DEVICES.

"4L1-

A AMPS MH MANHOLEAC ABOVE COUNTER MIN MINIMUMAFF ABOVE FINISHED FLOOR MISC MISCELLANEOUSARCH ARCHITECT OR ARCHITECTURAL MLO MAIN LUGS ONLYAWG AMERICAN WIRE GAUGE MNT MOUNTING HEIGHTBJ BONDING JUMPER MTG MOUNTINGBKR CIRCUIT BREAKER N1 NEMA 1BLDG BUILDING N/A NOT APPLICABLEBOD BASIS OF DESIGN NEC NATIONAL ELECTRICAL CODEC CONDUIT NESC NATIONAL ELECTRICAL SAFETY CODEC/B CIRCUIT BREAKER NEU NEUTRALCLG CEILING OCPD OVERCURRENT PROTECTION DEVICECKT CIRCUIT PBD PANELBOARDDEMO DEMOLISH PF POWER FACTORDM EXISTING TO BE DEMOLISHED PNL PANELBOARDEC ELECTRICAL CONTRACTOR PWR POWEREGC EQUIPMENT GROUNDING CONDUCTOR REC RECEPTACLEELEC ELECTRICAL REQD REQUIREDEX EXISTING TO REMAIN RM ROOMEMT ELECTRICAL METALLIC TUBING RGS RIGID GALVANIZED STEEL CONDUITEQUIP EQUIPMENT RNC RIGID NON-METALLIC CONDUITFMC FLEXIBLE METAL CONDUIT SCA SHORT CIRCUIT AMPSFLA FULL LOAD AMPS SF SUPPLY FANFLR FLOOR SPEC SPECIFICATIONGFI GROUND FAULT INTERRUPTER TVSS TRANSIENT VOLTAGE SURGE SUPPRESSIONG GROUND (OR GFI FOR RECEPTACLE SUBSCRIPT) TYP TYPICALGND GROUND UL UNDERWRITERS’ LABORATORIESGEC GROUNDING ELECTRODE CONDUCTOR UNO UNLESS NOTED OTHERWISEHP HEAT PUMP OR HORSEPOWER V VOLTHVAC HEATING, VENTILATION & AIR-CONDITIONING VA VOLT-AMPERESIMC INTERMEDIATE METAL CONDUIT W WATTSJB JUNCTION BOX WAO WORK AREA OUTLETk KILO WSR WITHSTAND RATINGkAIC KILO-AMPERE INTERRUPTING CAPABILITY XFMR TRANSFORMERkCMIL THOUSAND CIRCULAR MILS ♦ PHASELTG LIGHTING 72° DEGREESLFMC LIQUID TIGHT FLEXIBLE METAL CONDUIT A DELTAMCA MINIMUM CIRCUIT AMPACITY Q OHMSMCM THOUSAND CIRCULAR MILS

RECEPTACLE WITH COVERPLATE REMOVED

SWITCH WITH COVERPLATE REMOVED

1 WIRING DEVICE LABEL DETAIL© NOT TO SCALEROOF

NOTE: ALL RECESSED FIXTURES SHALL BE WIRED FROM A JUNCTION BOXAS SHOWN ABOVE, INCLUDING FIXTURES SHOWN IN CONTINUOUS ROWS; NO WIRING THROUGH FIXTURES. AT CONTRACTOR'S PPTION, SEVERAL FIXTURES (NOT TO EXCEED 4) MAY BE WIRED TO A COMMON JUNCTION BOX.

Æ ^

3/8" FMC 4 FOOT (MINIMUM) TO 6 FOOT (MAXIMUM) LONG

PROVIDE CEILING SUPPORT WIRE

CKT LOAD BREAKER PHASE (kVA) PHASE (kVA) BREAKER LOAD CKT

# DESCRIPTION P TRIP A B C A B C TRIP P DESCRIPTION #

1 DRINK DISP. 1 20 - - 2

3 ICE DISP 1 20 - - 60 3 SPARE 4

5 SODA DISP 1 20 - - 6

7 ICE TEA DISP. ICE DISP 1 20 - - 8

9 ICE DISP 1 20 - - 100 3 STARBUCKS COFFEE STAND 10

11 SODA DISP 1 20 - - 12

13 COFFEE BREWER 2 40 - - 20 2 STARBUCKS HWH 14

15 "EAST" - - 16

17 COFFEE BREWER 2 40 - - 20 1 STARBUCKS HWH 18

19 "WEST" - - 20 1 VENDOR RECEPT. 20

21 SODA DISP 1 20 - - 20 2 ICE MKR. FOR DRINK DISP. 22

23 ICE DISP. 1 20 - - 24

25 ICETEA DISP. ICE DISP. 1 20 - - 20 2 ICE MKR. FOR DRINK DISP. 26

27 SODA DISP. 1 20 - - 28

29 ICE DISP 1 20 - - 20 2 ICE MKR. FOR DRINK DISP. 30

31 NON CARB. DRINK DISP. 1 20 - - 32

33 OCCUPIED SPACE 2 50 - 4.9 60* 2 REC RM 164 34

35 - 4.9 CONVECTION STEAMER 36

37 REC RM 164 BLENDER 1 20* 1.6 1.0 15* 2 REC RM 164 38

39 REC RM 160 SIGNALS 1 20* 0.5 1.0 BLAST CHILLER 40

41 SPARE 1 20 - 0.7 20* 1 REC RM 164 CONDENSER FOR STEAMER 42

* PROVIDE NEW C/B IN EXISTING PANELBOARD 1.6 0.5 1.0 5.9 5.6

W THIN 6" OF EACH OF FOUR FIXTURE CORNERS

RECESSED FLUORESCENT LIGHTING FIXTURE

T CONDUIT

JUNCTION BOX SECURE TO STEEL JOIST OR PENDANT HUNG WITH THREADED ROD AND REQUIRED HANGERS.

D CLIPS TO PREVENTPROVIDED FIXTURE GR FALLING THRU GRID (4 REQ).

Y SUSPENDED CEILING

© TYPICAL FIXTURE INSTALLATION DETAILNOT TO SCALE

LIGHTING FIXTURE SCHEDULEMARK MANUFACTURER AND CATALOG NUMBER LAMPS TOTAL

WATTS

VOLTAGE MOUNTING NOTES

TYPE # WATTS

L4S4 CREE # LS4-40L-40K-10V LED

40K

N/A 44W 44W 277V SURFACE 22 GAUGE CONSTRUCTION

ACRYLIC LENS

EXB PATHWAY LDEXCR

EMERGILITE DXN-R-N-DL

LITHONIA LES 3 R VOLT EL N SD DL

LED 7.1W

9.0W

7.1W

9.0W

WALL OR

CEILING

INDICATED

PROVIDE EMERGENCY NICAD BATTERY BACKUP, ARROWS AS PER PLANS,

DIE CAST ALUMINUM HOUSING W/BRUSHED ALUMINUM FACEPLATE,

SELF DIAGNOSTICS W/LEDS, DOUBLE FACE AS INDICATED ON PLANS.

BATTERY

PACK

BODINE

EMERGI-LITE

BEGHELLI

277V INSIDE

LIGHT

FIXTURE

1400 LUMENS FOR 90 MINUTES, UL 924 LISTED

MAINTENANCE-FREE NICKEL-CADMIUM BATTERY, TEST SWITCH,

LED INDICATING LIGHT, AUTOMATIC CHARGER

NOTES SEE SPECIFICATIONS FOR APPROVED BALLAST MANUFACTURERS.

FIXTURES WITH HALF FILLED IN CENTER SHALL BE PROVIDE WITH A BATTERY PACK. SEE PLANS FOR QUANTITY.

APPROVAL SUBMITTALS FOR MANUFACTURERS NOT LISTED MUST BE SUBMITTED TO THE ENGINEER 14 DAYS PRIOR TO BID DATE FOR REVIEW. MANUFACTURERS NOT LISTED WILL NOT BE ACCEPTED UNLESS APPROVED BY ADDENDUM.

O CD

O

CDo

£

O) Eo

_Q *t/>to D uCD O £

TD CD Ou_i_i

L_o

15oE

'N'LT)

o_= ) CD

oo CO

O + - CN LOo' C CD+- CN

• i/)

Z "dCDL_

□2

(DU

on D = *o>LU +- 1c LOQ U CD

CD U) LO+- D£ LO•— o_C Uu O COi_ IV

o LOD CN CN

GOz :LUXGOLUO'

oz<

g o o

^ o >> - U Q /Z L l_ L U

0 rv co

1 <

k > -

LOLU ^CO ^< oCû o

ÜO 'O

ÛÛ

O 'oO'

O

<

o

w

: XCHANGEARMY & AIR FORCE EXCHANGE SERVICE

PROJECT NO: 1611010126

REVISIONS:

ISSUE DATE: 06.17.16

/ o V-.Pe/Xc \c ^ < %

= •• NO . 7 3 9 1 4 • = = ★ : ★ • ★ =

STATE O F

\ < 3

THIS DRAWING REPRESENTS DESIGNS PREPARED BY WATERMARK

DESIGN GROUP LLC FOR SPECIFIC USE ON THIS PROJECT AND IS NOT TO BE COPIED, REPRODUCED, OR ALTERED WITHOUT THE EXPRESS

WRITTEN CONSENT OF THE WATERMARK DESIGN GROUP

REPRESENTATIVE AUTHORIZED TO APPROVE THIS USE.

UNAUTHORIZED USE IS SUBJECT TO LEGAL ACTION UNDER STATE AND

FEDERAL LAW.

SHEET TITLE:

LEGENDS NOTES AND ABBREVIATIONS -

ELECTRICALSHEET NUMBER:

E0 0