extended range metering utility benefits - landis+gyr · current transformers and meter are tested...
TRANSCRIPT
Higher System Accuracy
Current transformers and meter are tested and calibrated at the same time
Secondary burden is fixed and the effect is calibrated out
Calibrated on light load at 5 amperes as compared to thetransfer rated meter (calibrated at 10 amperes)
Installation CostSingle Phase
TransformerForm 4S meter6 terminal meter socket2 CTsWires and connectors2 hours/technician$335†
K-BaseFOCUS™ meterK-4 meter mounting device1/2 hour/technician$250†
Landis+Gyr extends the range of self-contained electricity metering with the introduction of the solidstate FOCUS™ and S4e meters for both the residential and commercial & industrial markets. K-Base metering is the metering of continuous electrical loads greater than 320 amperes, using self-containedwatthour meters and no external current transformers. This includes 400 ampere continuous duty and480 continuous/600 ampere maximum duty meters.
Why K-Base Metering?
Competitive pressure of deregulation and retail wheeling are major industry forces demanding reducedcosts, increased profits and improved relationships with utility customers. Many of these requirementsare being fulfilled through the use of K-Base metering.
When an electrical load exceeds 320 amperes, there are two ways of metering these loads: One is by theage-old, costly method of using current transformers, housed in large, special enclosures, consisting ofmultiple wire connections. The other alternative is safe, lower cost, more accurate K-Base metering.
600
500
400
300
200
100
01934 1948 1969 1976 1993
MET
ER C
LASS
YEARS
SOCKET BASE
K-BASE
LO
WER
CO
ST, LES
S T
ES
TIN
G, M
OR
E V
ALU
E Utility BenefitsGREATER ACCURACY
Current transformer is part of meter. Inaccuracies can be compensated for during meter calibrationFixed burden, no problems associated with CTsecondary burdens and accuracy classesStarting watts for 480 ampere installation is approximately 1/3 of the amount of power required to start the meter compared to transformer rated installationsHigh end load curve performance is more accurate compared to transformer rated installation
REDUCED LABOR AND MATERIAL COSTSNo external current transformers, eliminates material and CT testing timeEliminates secondary wiring expenseAllows using a lower labor classification of meterman to install and test the meterMeter is a true self-contained unit, reducing periodic calibration testing required compared to transformer rated meters
AESTHETICSNeater, cleaner-looking installationsLess bulky equipment usedEnclosure can be adapted to become a CT cabinet should the installation load grow
FLEXIBLE AMR TECHNOLOGYPLCRadio FrequencyWireless MeshModemPager
REDUCED CHANCE FOR CURRENT DIVERSIONAsymmetrical baseplate design prevents meter from being turned upside downNo current transformer secondaries to be short circuited or voltage connections to be open circuited
SAFE INSTALLATIONS/FEWER ERRORSField proven for over 35 yearsHigher fault current withstand capability, up to 4 times that of conventional self-contained metersHigh fault current rating allows circuit breaker or fuseto clear fault without causing structural damage within the mounting deviceMounting devices are listed by Underwriters Laboratories*No meter multipliersEasier to wireFewer connections, less than one-half the connections compared to transformer rated installationsAdded optional safety mounting device accessories such as Lexan® safety shield, insulated T-handle wrench and others
REDUCED OPERATING COSTSContractor may purchase and install self-contained mounting devices to help reduce utility’s costInventory carry costs are less because of less inventory of current transformers, cabinets, brackets and test switchesMeters use standard components (covers, registers,etc.) and are calibrated the same - no additional training is requiredNo current transformer testingEliminates engineering costs associated with CT installations
CT ENCLOSURE K-BASE INSTALLATION
SELF CONTAINED - METER CLASS AVAILABILITY
EMBEDDED COIL CURRENT SENSOR
S4/S4e CLASS 480 FOCUS CLASS 480
2006
†Dollar amounts are an approximation
Extended Range Metering
Installation CostPolyphase
TransformerForm 9S meter13 terminal meter socketTest switchTransformer enclosure3 CTsWires and connectors5 hours/technician$769†
K-BaseForm 16K meterK-7 meter mounting device2 hours/technician$522†
ERROR PRONE • CONFUSING • EXPENSIVE47 CONNECTIONS • 3 PHASE
SIMPLE • CLEAN • LOW COST9 CONNECTIONS • 3 PHASE
*The K-type meter mounting device may also be listed by Underwriters Laboratories, which allows the homeowner and contractor to be responsiblefor the installation of the mounting device. On a current transformer installation, the utility typically installs the current transformers and the second-ary wiring from the current transformer to the test switch and the meter terminal block.
L+G_kbase_brochure_091906_FINAL.qxp 9/25/2006 9:20 AM Page 1
2800 Duncan RoadLafayette, IN 47904Phone: 765.742.1001Fax: 765.742.0936www.landisgyr.us
The primary current conductors of K-Basemeters are asymmetrical. This prevents themeters from being installed upside downand reduces the risk of current diversion.
More Advantages of K-Base
Test board adapters are available to convert the K-Base to Socket-Base, whichallows the K-Base meters to be tested onconventional test boards. Field testadapters are also available.
The “K”single phase meter baseplates have aspecial potential disconnect link configuration.This configuration allows the installation tobe top fed or bottom fed. By changing thepolarity of the potential circuit with respectto the current, the line side terminals may bewired at either thetop or bottom ofthe socket blockassembly.Thisflexibility is helpful in retrofitinstallationswhere the service entrance isupgraded and theline conductorsare not longenough to reachthe top terminalsof the socket.
The “K” metering system is designed to provide an out-of-service storage positionfor the watthour meter allowing utilities tostore the meter in the socket when it istaken out of service. This saves onremove/set orders and associated paper-work, and eliminates the need to bring themeter back to the meter shop and retest itbefore it goes back into service.
When the meter is stored in the out-of-service position, it is connected to the linebus, thus keeping the meter potential coilenergized to generate heat and keep moisture out of the meter. If it is a time-of-
use meter, it keeps the time clockgoing without the need to go onbattery carry-over. If an AMRmodule is installed, it will alsoremain powered. A sliding plateon the meter socket cover withthe words “Out of Service” printedon it alerts meter men and meterreaders that the meter is out ofservice.
“K” mounting devices can be bypassed withmanual bypass devices. The bypass clampsbridge from the line to the load bus andare capable of carrying 480 amperes continuously. The insulated handles on thebypasses prevent the enclosure cover frombeing installed with the bypass in place.Other types of bypasses are also available.
If the load increases beyond the 400 or 480amperes respectively, current transformersmay be mounted in the K-Base enclosureby removing the existing block and usingan adapter kit.
CUSTOMER SERVICE APPLICATION TABLE - METER/MOUNTING DEVICE
CLASSRATING
SERVICECONFIGURATION
CURRENT RATINGS (AMPS)CONTINUOUS INTERMITTENT
METERMODEL
METERFORM
MOUNTINGDEVICE
SINGLE PHASE:480480
POLYPHASE:400
480
3-WIRE3-WIRE
3-WIRE4-WIRE WYE
4-WIRE DELTA3-WIRE
4-WIRE WYE4-WIRE DELTA
480480
400
480
600600
400
600
ALTIMUS, FOCUSS4, S4e
MT-K
S4, S4e
2K12k
12K14K, 16K
15K12K16K15K
K-4K-5
K-5K-7K-7K-5K-7K-7
PRODUCT SPECIFICATIONSMOUNTING DEVICES
SPECIFICATIONVOLTAGEAMPACITYMAX. CONDUCTOR SIZE
ENCLOSURE
TERMINALS
K-4300 VAC400 OR 480/600-ONE 800 MCM PER PHASE-TWO 500 MCM PER PHASE-THREE 250 MCM PER PHASE-14 GAUGE GALVANIZED STEEL-POLYESTER POWDER PAINT-STAINLESS STEEL LATCHES-1/2” - 20 STUDS WITH NUTS AND CAPTIVE BELLEVILLE WASHERS-WIDE VARIETY OF DIRECT OR SIDE-ENTRY LUGS AVAILABLE
K-7600 VAC400 OR 480/600
METERS
SPECIFICATIONSTARTING LOADBURDENCLASS*
ALTIMUS - K, FOCUS - K213 mA.860.5%
S4, S4e K-BASE120 mA<0.25 VA0.5%
*TEST RACK STANDARDIZATION MUST BE TAKEN INTO CONSIDERATION
MO
RE A
DVAN
TAG
ES
OF K
-BAS
EL+G_kbase_brochure_091906_FINAL.qxp 9/25/2006 9:20 AM Page 2