 Ventilation and Leak Dispersion

in CCGT Enclosures

Patrick Phelps ( Flowsolve )   

andDouglas Wylie (GEC Energy Services)    

I PUC 7 - Luxembourg - May 2000  

Page 2: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 2/70

 Ventilation and Leak Dispersion

in CCGT Enclosures

Industrial Context

Health and Safety Issues

 Application to an Existing Power Station

 Application to New Enclosure Designs

Conclusions Experimental Verification

Page 3: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 3/70

 

Industrial Context - 1

Combined Cycle Gas Turbine (CCGT) Plants 

Gas turbines drive an electricity generator

Engine exhaust waste heat recovered by a

boiler to produce steam.

Steam turbine generates further output.

Page 4: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 4/70

Industrial Context - 2

Turbines are fuelled by gas at very

high pressures

Liquid fuel system as back-up

Turbines are contained within

acoustic enclosures.Enclosures tend to be installation-

specific designs

Page 5: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 5/70

“ Frame 6” Turbine Generator

Page 6: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 6/70

Industrial Context - 3

Each enclosure is divided into a number of

compartments containing

 Auxiliary equipment Gas turbine and exhaust plenum

Reduction gearing and the generation equipment.

 Auxiliary/GT/exhaust compartment is usually self-

contained, with a dedicated ventilation system

Page 7: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 7/70

 Ventilation and Leak Dispersion

in CCGT Enclosures

Page 8: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 8/70

Health and Safety Issues - 1

Enclosure ventilation system removes

some heat from the turbine casing

Enables operatives to carry out readings

and routine maintenance under operating

conditions.

However, enclosures remain a “thermally hostile and noisome” environment .

Page 9: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 9/70

Health and Safety Issues - 2

Gas from leakages can accumulate to

flammable proportions in poorly ventilated

regions of the enclosures - “dead zones” 

OUTCOME - Big Bang 

REMEDY - Use the ventilating air to safely

dilute and disperse any gas leakage.

MOTIVATION - Legislation

Page 10: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 10/70

UK Safety Assessment of

CCGT Enclosures - 1

Identify nature and potential sources of

hazardous material releases

Determine leak frequency and inventory ofreleases

Investigate airflow characteristics

identify "dead zones" Predict dispersion consequences safety-critical

release scenarios

Implement remedial measures

Page 11: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 11/70

UK Safety Assessment of

CCGT Enclosures - 2

Experimental investigation of airflow

characteristics is difficult within the

confines of a turbine generator enclosure,especially under operational conditions.

HSE promote computer simulation as themost appropriate technology in this case.

Page 12: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 12/70

UK Safety Assessment of

CCGT Enclosures - 3

CFD models can

simulate the dispersion consequences of

releases under a variety of operating

conditions

compare the efficiency of alternative

 ventilation strategies, to achieve thedesired dilution / dispersion result 

Page 13: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 13/70

“Safe” Dispersion Criteria - 1

“Santon” Criterion “The ventilation arrangements within the turbine

enclosure must be such as to ensure the safedilution/dispersion of gas releases prior to

activation of mitigation/shutdown systems by the

gas detection system. The criteria to be applied 

are that the envelope of the 50% LELconcentration contour should not occupy more

than 0.1% of the free volume of the enclosure, for 

a gas leak of sufficient magnitude to trigger the

gas detection system.”  

Page 14: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 14/70

“Safe” Dispersion Criteria - 2

G = V * (0.01 * E) * (0.01 * S).

Gas concentration level (S) detected by sensors foractivating emergency response systems (typically 10%)

Lower Explosive Limit (E) for the turbine fuel gas is around

5%.

Maximum undetected leak is thus of magnitude 10% of LEL  For compliance, ensuing flammable envelope (of the 50%

LEL surface) must not exceed 0.1% of “the compartmentfree volume”. 

Page 15: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 15/70

“Safe” Dispersion Criteria - 3“Compartment free volume” 

Page 16: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 16/70

Reference Leak Scenario

Zero momentum leak source

corresponds to jet release impinging

immediately on an obstruction (casing,

flange body}

No net directionality imparted to release.

 A directional release would require

additional assumptions ….. 

Page 17: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 17/70

 Application to an Existing Power

Station - 1

 A CFD-based simulation study

commissioned by

IVO Generation Systems

andRegional Power Generators Ltd

Page 18: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 18/70

 Application to an Existing Power

Station - 2

Page 19: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 19/70

 Application to an Existing Power

Station - 3

Over 100 simulations performed 

Studies to determine

air flow distribution 

 worst case operating condition (hot,cold);

 worst case leak location;efficiency of alternative “retrofit” 

 ventilation strategies, to achieve HSE

compliance

Page 20: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 20/70

 Air flow Distribution at inlet to

Turbine Compartment

Page 21: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 21/70

 Application to an Existing Power

Station

Page 22: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 22/70

 Application to an Existing Power

Station - Parameter Studies

Over 100 simulations performed

Studies to determine

air flow distribution

 worst case operating condition (hot,cold);

 worst case leak location;efficiency of alternative “retrofit”

 ventilation strategies, to achieve HSE

compliance

Page 23: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 23/70

Hot Operating Conditions:

Envelope volume - 0.69%

Page 24: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 24/70

Cold Operating Conditions:

Envelope volume - 2.28%

Page 25: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 25/70

 Application to an Existing Power

Station - Parameter Studies

Over 100 simulations performed

Studies to determine

air flow distribution

 worst case operating condition (hot,cold);

 worst case leak location;efficiency of alternative “retrofit”

 ventilation strategies, to achieve HSE

compliance

Page 26: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 26/70

“Worst Case” Leak Location 

Under both hot and cold conditions,

the worst case leak location was

found to be in the “pit” region, in front

of the lowest combustor flanges

Page 27: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 27/70

 Application to an Existing Power

Station - Parameter Studies

Over 100 simulations performed

Studies to determine

air flow distribution

 worst case operating condition (hot,cold);

 worst case leak location;efficiency of alternative “retrofit”

 ventilation strategies, to achieve HSE

compliance 

Page 28: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 28/70

 Alternative Ventilation Strategies :

1 - Abject failures

Increasing ventilation rate

overhead pendant baffles

twin outlets

blowing air into the pit region

sucking air from the pit region EGT “wavewall” idea 

Page 29: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 29/70

 Alternative Ventilation Strategies :

2 - Heroic failures

Reversed flow system

• air supply through existing outlet

• air extract to TG inlet plenum

Lateral side-gust system

• air supply through side door

• air extract through existing outlet

• other inlets blocked off

Page 30: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 30/70

 Alternative Ventilation Strategies :

3 - Final Success !

The “Corkscrew” Strategy 

Close all existing inlets

plate over grated walkway tops

Single non-symmetric outlet

Two inlet slots , one high, one low, cut inconnecting doors

30-degree deflector plates create

corkscrew effect

Page 31: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 31/70

“Corkscrew” Ventilation Scheme 

Page 32: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 32/70

“Corkscrew” Ventilation Scheme 

Page 33: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 33/70

“Corkscrew” Ventilation Scheme 

Page 34: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 34/70

“Corkscrew” Ventilation Scheme 

Page 35: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 35/70

 And so . . . . . . . . . .

This led on to . . . . . . . . 

Page 36: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 36/70

 Application to New Enclosure

Designs

 A CFD-based simulation study

commissioned by

the Thermal Power Division

of Kvaerner Energy Ltd

A li i N E l

Page 37: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 37/70

 Application to New Enclosure

Designs 

Page 38: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 38/70

Enclosure Geometry - Elevation 

Page 39: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 39/70

Enclosure Geometry - End View 

A li ti t N E l

Page 40: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 40/70

 Application to New Enclosure

Designs

T bi b t fl d

Page 41: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 41/70

Turbine combustor flanges and

associated pipework 

Page 42: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 42/70

Geometry Representation - 1 

Page 43: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 43/70

Geometry Representation - 2

A li ti t N E l

Page 44: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 44/70

 Application to New Enclosure

Designs - Workscope

Over 25 different simulations performed 

Studies to determine sensitivity to:

nodalisation level & distribution;

leak location; 

 ventilating flowrate;presence of internal geometric features;

inlet flow manipulation.

Page 45: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 45/70

Findings - 1

The worst case leakage scenario, under cold

start-up conditions, was a zero-momentum

leakage from the flanges in front of the lowestcan combustor

The flammable gas cloud with the “reference”

 ventilation arrangement was twenty five timeslarger than the target value (11 times larger if the

accessory compartment volume was included)

Page 46: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 46/70

Reference Configuration{Flammable volume: 2.8% TC} 

Page 47: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 47/70

Reference Configuration{Flammable volume: 2.8% TC} 

Page 48: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 48/70

Reference Configuration{Flammable volume: 2.8% TC} 

Page 49: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 49/70

Reference Configuration{Flammable volume: 2.8% TC} 

Page 50: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 50/70

Reference Configuration{Flammable volume: 2.8% TC} 

Application to New Enclosure

Page 51: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 51/70

 Application to New Enclosure

Designs - Workscope

Over 25 different simulations performed

Studies to determine sensitivity to:

nodalisation level & distribution;

leak location;

 ventilating flowrate;presence of internal geometric features;

inlet flow manipulation.

Page 52: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 52/70

Findings - 2

Increasing the ventilating air flowby 25% had little effect on

 ventilation efficiency ( gas leak 

size increased proportionately ).

Application to New Enclosure

Page 53: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 53/70

 Application to New Enclosure

Designs - Workscope

Over 25 different simulations performed

Studies to determine sensitivity to:

nodalisation level & distribution;

leak location;

 ventilating flowrate;presence of internal geometric features;

inlet flow manipulation.

Atomising Air System

Page 54: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 54/70

 Atomising Air System

{Flammable volume: 1.9% TC} 

Atomising Air System

Page 55: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 55/70

 Atomising Air System

{Flammable volume: 1.9% TC} 

Atomising Air System

Page 56: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 56/70

 Atomising Air System

{Flammable volume: 1.9% TC} 

Atomising Air System

Page 57: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 57/70

 Atomising Air System

{Flammable volume: 1.9% TC} 

Atomising Air System

Page 58: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 58/70

 Atomising Air System

{Flammable volume: 1.9% TC} 

Application to New Enclosure

Page 59: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 59/70

 Application to New Enclosure

Designs - Workscope

Over 25 different simulations performed

Studies to determine sensitivity to:

nodalisation level & distribution;

leak location;

 ventilating flowrate;presence of internal geometric features; 

inlet flow manipulation. 

Findings 3 :

Page 60: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 60/70

Findings - 3 :

Inlet Flow Manipulation

Improved results (decrease in flammable

cloud size) obtained by :

adding a “scoop” diverter at inlet ; “throttling” - increasing the inlet velocity ;

concentrating the incoming flow towards the

axial centreline; blocking off the outermost inlet hole(s) on each

side; and

biasing the massflow distribution.

Fi l C fi ti

Page 61: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 61/70

Final Configuration{Flammable Volume: 0.2% TC} 

Fi l C fi ti

Page 62: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 62/70

Final Configuration{Flammable Volume: 0.2% TC} 

Fi l C fi i

Page 63: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 63/70

Final Configuration{Flammable Volume: 0.2% TC}

Fi l C fi ti

Page 64: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 64/70

Final Configuration{Flammable Volume: 0.2% TC}

Fi l C fi ti

Page 65: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 65/70

Final Configuration{Flammable Volume: 0.2% TC} 

C l i

Page 66: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 66/70

Conclusions

Flammable cloud volumes of less than 0.1% of the

free volume of the combined compartments are

attainable (at least conceptually) .

This would satisfy the current UK dispersion

criterion.

Compliance achieved without major structural

changes to enclosure or to air delivery system. 

Future Efforts

Page 67: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 67/70

Future Efforts

Confirm high velocities do not provoke thermal

shock problems in hot operation

Confirm required manipulation of inlet air supply

is technically feasible (!)

Use model to predict likely over-pressures

arising from deflagration of the confined gas

plume.

Page 68: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 68/70

Experimental Verification

No quantitative data available.

Qualitative comparison - video footage of

smoke tests on installations with similarinternal geometries.

Smoke trails confirm magnitude and

direction of airflow in the region in front ofthe can flanges and around the front upper

part of the turbine barrel

Ventilation and Leak Dispersion

Page 69: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 69/70

 Ventilation and Leak Dispersion

in CCGT Enclosures

Thank you for your attention .

“ When I count to three, 

you will awake 

and  

remember nothing …..”    

Page 70: Flowsolve Phelps Gas Leaks

7/27/2019 Flowsolve Phelps Gas Leaks

http://slidepdf.com/reader/full/flowsolve-phelps-gas-leaks 70/70

 Ventilation and Leak Dispersion

in CCGT Enclosures

Patrick Phelps (Flowsolve Ltd)   

and Douglas Wylie (GEC Energy Services)