herzlich willkommen bienvenue welcome general basics …€¦ · herzlich willkommen bienvenue...
TRANSCRIPT
2General Presentation JUMO Screen Recorders
� This presentation shows important functions of JUMO-
Screen Recoders and demonstrates their application
� The exemplifying description of configuration and
operation applies for the LOGOSCREEN 500 cf
Advices for the presentation
� Both – LOGOSCREEN 500 cf and LOGOSCREEN nt offer
the functions described
� Configuration and operation are slightly different from
those of the LOGOSCREEN nt
� Most of the explanations are based on concrete
examples
3General Presentation JUMO Screen Recorders
Application Example
� Two temperatures (PT100 each) and a pressure (4…20
mA = 0…500 mBar) shall be recorded
� Basicly the measured values shall be recorded every 20s.
If the temperature 1 is > 100°C, the values shall be
recorded every second.
� If a potential-free contact is closed (binary input 1) , the
following text shall be adopted in the event list: „ Ready
for operation“
4General Presentation JUMO Screen Recorders
Connection Screen RecordersExample LOGOSCREEN 500 cf – Analogue inputs
5General Presentation JUMO Screen Recorders
Connection Screen RecordersExample LOGOSCREEN 500 cf – Binary inputs
ETHERNET
6General Presentation JUMO Screen Recorders
Connection Screen RecordersLOGOSCREEN 500 cf – Binary outputs, Interface
8General Presentation JUMO Screen Recorders
Device designation, Language
Device name:
This name appearslater with theevaluation of therecorded data
Language:
Please select thelanguage for the text in the device.
10General Presentation JUMO Screen Recorders
Configuration Inputs
Within the setup-program please go to the submenu „analogue inputs“. There your are
requested to proceed as follows:
Select the input you want to configure; in our example we use the inputs 1-3.
Under input 1 and 2 (menu item: sensor) – please select „resistance thermometer“. The
thermometer is connected in 3-wire circuit; please take the corresponding adjustment.
The correct temperature for all common resistance thermometers and thermocouples is
automatically built on the basis of the measured resistance values or voltages. For a PT100 you
can keep the basic adjustments under menu item „linearization“.
Our signal shall be recorded within a range of 0…200°C; please put in the relevant limit under
menu item „Range“.
Configuration Input 1-2
11General Presentation JUMO Screen Recorders
Configuration of the inputs
Configuration Input 3
20 mA equals 500
4 mA equals 0
12General Presentation JUMO Screen Recorders
RecordingHow to assign temperatures and pressure signal to the channels
� our devices offer a certain number of analogue- and binary channels
� in our example the signals of the analogue inputs 1-3 are assigned to the analogue
channels 1-3
� the channels 4-6 are disconnected (input signal: no signal):
Dispaly at the deviceConfiguration
13General Presentation JUMO Screen Recorders
Recording
Signal binary input 1 (ready for operation) assign event trace
� Binary input 1 is assigned to the event trace
� The event traces 2-6 are disconnected:
Configuration Display at the device
14General Presentation JUMO Screen Recorders
Recording
Normal operation
� Normally the screen recorder shall record a measured value every 20 s; in the submenu
„Normal operation“ we put in the corresponding specifications
Normal operation is required – memory status„on“
Storage cycle for the measured value shall be20s
15General Presentation JUMO Screen Recorders
� The screen recorder scans the input signals every 250 ms (in 20 s 80 samplingrates)
• Under „Memory value“ you can define which of these 80 sampling rates shall bestored:
The mean value of the 80 signals
The instantanenous value
The minimum value of the 80 signals
The maximum value of the 80 signals
The maximum and the minimum of the 80 signals (peak value)
Recording
Normal operation – Memory values
16General Presentation JUMO Screen Recorders
Recording
Event Operation and Alarms
� If a binary signal is active, the recorder can be changed into event operation
� In this case memory value and –cycle can be changed
In our example the recorder changes into event
operation, if there is a high alarm at input 1.
Peak values are still stored; however, thestorage cycle for the measured values is 1 s
17General Presentation JUMO Screen Recorders
Recording
High-Alarm
� In our example we change into the event operation, if there is a high alarm at analogue
input 1
� In order to configure the alarm, we must select the used channel:
Text 1 is defined in the menu „texts“
18General Presentation JUMO Screen Recorders
Effects at the device
Alarm changes into event operation, text indicated in event list
If the limit of 100 °C is exceeded, an alarm occurs
The Signal „Max-Alarm 1“ changes the device from normal operation(Storage in the example every 20 s) to the event operation (in the examplethe measured value is stored every second). In the event operation thecolour of the chart speed display changes to orange
The configured text is taken over in the event list
19General Presentation JUMO Screen Recorders
Recording
Time operation
� If – e.g. the storage cycle – is changed for a certain period of time, the timed operation
applies
� In our example during the time from 20:00 hh until 06:hh the value shall be recorded every
180 s only
� Please make the following adjustments:
20General Presentation JUMO Screen Recorders
Recording
Priorities, event operation, timed operation, normal operation
If all three kinds of operation apply, the recorders are working as follows:
� Actual time not within the timed operation, control signal for the event operation is not
active � Normal operation
� Actual time within the timed operation, control signal for the event operation is not active
� Timed operation
� Control signal for the event operation is active � Recorders work in the event operation
� The event operation has top priority
21General Presentation JUMO Screen Recorders
External Texts
Take-over of a text as result of the binary signal
� If binary input 1 closes, the text „ready“ shall be taken over in the event list:
Indicate the number of the customer text which shall be taken over in the event list in the event of a positive or negative edge at binary input 1
Define customer text
Event list of the device:
22General Presentation JUMO Screen Recorders
Data transfer to the device
Transfer via interface
� In our example new data (configuration) are transferred to the device
� A new configuration for the LOGOSCREEN 500 cf is created
alternatively
23General Presentation JUMO Screen Recorders
Operation
Change of the diagram views
� Change of diagram views is possible with the push-button „channel display“;
the following views are possible:
Diagram (without
headline)
Diagram with digital display
Diagram with bargraphDiagram with scaling
Digital display - large
24General Presentation JUMO Screen Recorders
Operation
How to show and/or remove the event traces
� Event traces can be shown or removed with the push-button
Event traces
25General Presentation JUMO Screen Recorders
Operation
Calling the event list
� you can reach the event list by two possibilties:
1. Selection by push-button:
2. Menu navigation Button menu
26General Presentation JUMO Screen Recorders
Data Memory
Explanation I/II
To help you to understand history and operating principle of the menu Compact-Flash-Card,
the following pages will provide you with important explanations about the data storage:
� The recorder has a flash memory which work as a ring buffer
� If a block of 4 Kilobyte is completed, a copy of these datais stored on the external CF-Card
27General Presentation JUMO Screen Recorders
Data Memory
Explanation II/II
� The memory range with the copied data isconsidered as free memory
� The part of free memory is displayed on thescreen for your information:
28General Presentation JUMO Screen Recorders
Operation
History Function
Data in the main memory can be checked with the history function:
Scroll buttonsZoom is possible
The diagram can bescrolled to certainpoint of time
29General Presentation JUMO Screen Recorders
Operation
Data memory on CF-Card
� As mentioned already, the data are automatically copied from the internal memory to the
external CF card
� However, this done only, if one data block is completed with 4 kB
� If you want to make sure that all data are on the CF-card before removing the card, please
select the corresponding submenu in the menu CompactFlash-Card:
30General Presentation JUMO Screen Recorders
Further Functions
� Now the recoder works acc. to the requested configuration
� On the following pages further functions of the screen recorders
are described
� The data of the CF-Card can be evaluated with the evaluation
software PCA3000
31General Presentation JUMO Screen Recorders
Configuration Transfer with CF-Card
� A configuration by setup can – alternatively –
be transferred with the CF-Card:
� Read-in of the configuration in to the recoder as follows:
Menu � CompactFlash-Card �“CF-Card → Config-Data“
32General Presentation JUMO Screen Recorders
Configuration Transfer with CF-Card
� The code can be changed with the setup program:
� Before the menu starts, the
corresponding code must be put in:
33General Presentation JUMO Screen Recorders
Relay Outputs
� Screen recorders can be equipped with relay outputs
� A multiplicity of functions can be assigned to the outputs
Example: A high alarm at input 1 occurs
���� Relay 1 switches
34General Presentation JUMO Screen Recorders
Mathematics / Logic
Mathematics - Principle
Max. 70 digits
35General Presentation JUMO Screen Recorders
Mathematics/ Logic
JUMO-Screen recorders offer a mathematics/logic function (option with costs). With the
setup-program several mathematics- and logic formula can be defined.
In the formula-editor (left) you can find the variables which can be integrated in the formula.
The allowed operators are indicated in the right window.
All mentioned terms can be imported into the formula with „Adding“. In our example we will
use the mathematics formula to create the mean value of the signals at analogue input 1 and
analogue input 2.
With the logic formula you can realize logic functions (Example: Logic 1 shall be active, if the
binary inputs 1 and 2 are active).
36General Presentation JUMO Screen Recorders
Mathematics / Logic
Mathematics – how to enable?
Mathematics/Logic for JUMO screen recorders can be releasedafterwards:
Enter enable code (Release)
Generate the code number
37General Presentation JUMO Screen Recorders
Record Mathematics
� In the registration the maths value is
assigned to a channel:
� Display of the maths result at the
recorder:
38General Presentation JUMO Screen Recorders
Configuration from the device front
� Configuration of the JUMO-Screen recorders can be realized in a big scope from the front
of the device
� Adjustments are to be made in the menu „Configuration“:
Works adjustment 9200; please refer in
the setup to submenu „instrument data“
39General Presentation JUMO Screen Recorders
Display switch-off
� The display switch-off is energy-saving (a good portion of the power consumption is
allotted to the display) and saves the display.
� There are two possibilities:
If the user does not tap a key, the display will be switched off after a defined period (here 5 min.). After pressing a key, the display will be switched on again.
As long as the control signal is activated (here binary input 1), the display is switched off.
40General Presentation JUMO Screen Recorders
Time Synchronisation
� In the menu „Extras“ a new time for the screen recorder can be defined:
� If the time is changed, a new
configuration is created
� Due to a binary signal the recorders can be synchronised on the clock minute:
� The synchronisation signals occurs on the clock minute
� If the time of the recorder is in the second half of the minute,
the time is set ahead to the clock minute
� If the time of the recorder is ahead up to half a minute,
the time is reset to the clock minute
� Time synchronisation does not create a new
configuration!
41General Presentation JUMO Screen Recorders
Overview LOGOSCREEN 500 cf
� Available with 3 or 6 analogue inputs for thermocouples
resistance thermometers, voltage and current, min./max
supervision of the signals
� 4 Binary inputs for logic functions (Change of operating
mode, event counter etc.)
� 3 Relay outputs
� 5“ – STN- Colour screen, 320 x 240 Pixel, 27 colours
� 6 Event traces
� 6 Channels for mathematics- and logic functions
� 6 Channels – optionally for counter, integrators or operating
time counter
� Event list
� External Texts
42General Presentation JUMO Screen Recorders
Overview LOGOSCREEN 500 cf
� Normal operation, Event operation, Time operation
� Memory cycle: min 1s (internal scanning rate 250ms)
� Data memory:
- internal memory (Flash) for app. 350.000 meas. values
- external memory (CompactFlash-Carte – Industrial Grade,
alternatively with max. 2 GB)
� Interface ETHERNET and selectable RS 232/RS 485
� Configuration via setup program and device front
� Overview – important options:
260 Integrators and Counters
Mathematics- / Logic-module
261 Serial interface RS232/RS485
4 Binary inputs
3 Relay ouputs
008 ETHERNET interface
Auf Wiedersehen
Au revoir
Good Bye
JUMO GmbH & Co. KG
MANFRED SCHLEICHER
Dipl. Ing. (FH)
Head of Training
Tel.: +49 661 6003-396
E-Mail:[email protected]