high tension low sag conductors technical data … · 2020. 8. 11. · high tension low sag...
TRANSCRIPT
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
www.emtaaccc.com
www.emtaconductor.com
Manufactured under licence by
Inductive Reactance 0,245
Capacitive Reactance 0,214
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
AC Current Rating at Given Temp. Amperes458
673
GMR (estimated) 0,01
AC Nominal Resistance at 25°C 0,2335
AC Nominal Resistance at 75°C 0,2795
AC Nominal Resistance at 180°C 0,3762
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,2286
Temperature Coefficient of Resistance 0,00403
Frequency 50
No. of Layers 2
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
1,64E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 68,1
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 54
Conductor Nominal Mass per Unit Length 393,3
Aluminum Nominal Mass per Unit Length 339,9
Nominal Cross-Sectional Area of the Conductor 150,7
Ultimate Tensile Strength of Conductor 67,4
Rate Strength of Core - 313ksi (2158 MPa) 60,4
Nominal Diameter of Composite Core 5,97
Nominal Cross-Sectional Area of Core 28,0
Overall Diameter of Conductor 14,35
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEET
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
CODE NAME ACCC® SilvassaSTANDARD ASTM B 957 / B 609 or EN 50540
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 122,7
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Electrical Specifications
0,00403Temperature Coefficient of Resistance
519
765
Mechanical Specifications
Stranding Configuration
471,2
Rate Strength of Core - 313ksi (2158 MPa)
AmperesAC Current Rating at Given Temp.
Core Nominal Mass per Unit Length
Frequency 50
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 66,5
AC Nominal Resistance at 25°C 0,1902
54
Nominal Aluminum Cross-Sectional Area
Nominal Diameter of Composite Core
Conductor Nominal Mass per Unit Length
AC Nominal Resistance at 180°C 0,3064
0,1862
1,74E-05
AC Nominal Resistance at 75°C 0,2277
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS
150,6
5,97
28,0
68,9Ultimate Tensile Strength of Conductor
Nominal Cross-Sectional Area of Core
Nominal Cross-Sectional Area of the Conductor 178,6
60,4
15,65
0,210
Aluminum Nominal Mass per Unit Length 471,2
Maximum Continuous Operating Temperature of Conductor
Coefficient of Linear Expansion Above Thermal Kneepoint
180
1,61E-06
Maximum Allowable Emergency Temperature of Conductor 200
Manufactured under licence by
No. of Layers
No. of Trapezoidal Wires in First Layer
No. of Trapezoidal Wires in Second Layer
2
Capacitive Reactance
8
12
GMR (estimated)
Inductive Reactance
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME
STANDARD
ACCC® Helsinki
ASTM B 957 / B 609 or EN 50540
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
0,01
0,676
Overall Diameter of Conductor
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
www.emtaaccc.com
www.emtaconductor.com
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
Inductive Reactance 0,233
Capacitive Reactance 0,201
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
www.emtaaccc.com
AC Current Rating at Given Temp. Amperes656
971
GMR (estimated) 0,007
AC Nominal Resistance at 25°C 0,1301
AC Nominal Resistance at 75°C 0,1557
AC Nominal Resistance at 180°C 0,2094
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,1272
Temperature Coefficient of Resistance 0,00403
Frequency 50
No. of Layers 2
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
1,88E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 64,1
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 54
Conductor Nominal Mass per Unit Length 661,0
Aluminum Nominal Mass per Unit Length 607,0
Nominal Cross-Sectional Area of the Conductor 247,9
Ultimate Tensile Strength of Conductor 72,8
Rate Strength of Core - 313ksi (2158 MPa) 60,4
219,9
Nominal Diameter of Composite Core 5,97
Nominal Cross-Sectional Area of Core 28,0
Overall Diameter of Conductor 18,29
www.emtaconductor.com
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Copenhagen
STANDARD ASTM B 957 / B 609 or EN 50540
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
Inductive Reactance 0,231
Capacitive Reactance 0,199
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
www.emtaaccc.com
AC Current Rating at Given Temp. Amperes665
986
GMR (estimated) 0,008
AC Nominal Resistance at 25°C 0,1285
AC Nominal Resistance at 75°C 0,1537
AC Nominal Resistance at 180°C 0,2067
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,1256
Temperature Coefficient of Resistance 0,00403
Frequency 50
No. of Layers 2
No. of Trapezoidal Wires in First Layer 6
No. of Trapezoidal Wires in Second Layer 10
1,75E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 66,2
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 76
Conductor Nominal Mass per Unit Length 693,6
Aluminum Nominal Mass per Unit Length 617,6
Nominal Cross-Sectional Area of the Conductor 262,8
Ultimate Tensile Strength of Conductor 98,3
Rate Strength of Core - 313ksi (2158 MPa) 85,7
223,1
Nominal Diameter of Composite Core 7,11
Nominal Cross-Sectional Area of Core 39,7
Overall Diameter of Conductor 18,82
www.emtaconductor.com
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Reykjavik
STANDARD ASTM B 957 / B 609 or EN 50540
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
Inductive Reactance 0,228
Capacitive Reactance 0,197
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
www.emtaaccc.com
AC Current Rating at Given Temp. Amperes692
1027
GMR (estimated) 0,008
AC Nominal Resistance at 25°C 0,1211
AC Nominal Resistance at 75°C 0,1449
AC Nominal Resistance at 180°C 0,1949
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,1184
Temperature Coefficient of Resistance 0,00403
Frequency 50
No. of Layers 2
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
1,71E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 67,0
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 86
Conductor Nominal Mass per Unit Length 731,3
Aluminum Nominal Mass per Unit Length 645,3
Nominal Cross-Sectional Area of the Conductor 283,8
Ultimate Tensile Strength of Conductor 115,0
Rate Strength of Core - 313ksi (2158 MPa) 101,7
236,7
Nominal Diameter of Composite Core 7,75
Nominal Cross-Sectional Area of Core 47,1
Overall Diameter of Conductor 19,53
www.emtaconductor.com
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Glasgow
STANDARD ASTM B 957 / B 609 or EN 50540
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
Inductive Reactance 0,226
Capacitive Reactance 0,194
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
www.emtaaccc.com
AC Current Rating at Given Temp. Amperes754
1120
GMR (estimated) 0,008
AC Nominal Resistance at 25°C 0,1049
AC Nominal Resistance at 75°C 0,1255
AC Nominal Resistance at 180°C 0,1686
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,1024
Temperature Coefficient of Resistance 0,00403
Frequency 50
No. of Layers 2
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
1,83E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 64,9
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 76
Conductor Nominal Mass per Unit Length 834,4
Aluminum Nominal Mass per Unit Length 758,4
Nominal Cross-Sectional Area of the Conductor 313,3
Ultimate Tensile Strength of Conductor 101,1
Rate Strength of Core - 313ksi (2158 MPa) 85,7
273,6
Nominal Diameter of Composite Core 7,11
Nominal Cross-Sectional Area of Core 39,7
Overall Diameter of Conductor 20,50
www.emtaconductor.com
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Casablanca
STANDARD ASTM B 957 / B 609 or EN 50540
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Monte Carlo
STANDARD ASTM B 957 / B 609 or EN 50540
228,5
Nominal Diameter of Composite Core 10,54
Nominal Cross-Sectional Area of Core 87,3
Nominal Cross-Sectional Area of the Conductor 315,8
Overall Diameter of Conductor 20,78
Ultimate Tensile Strength of Conductor 201,2
Rate Strength of Core - 313ksi (2158 MPa) 188,3
Core Nominal Mass per Unit Length 164
Conductor Nominal Mass per Unit Length 798,7
Aluminum Nominal Mass per Unit Length 634,7
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
1,39E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 73,0
Stranding Configuration
No. of Layers 2
No. of Trapezoidal Wires in First Layer 12
No. of Trapezoidal Wires in Second Layer 16
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,1230
Temperature Coefficient of Resistance 0,00403
Frequency 50
AC Nominal Resistance at 25°C 0,1257
AC Nominal Resistance at 75°C 0,1504
AC Nominal Resistance at 180°C 0,2024
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
AC Current Rating at Given Temp. Amperes691
1027
GMR (estimated) 0,009
www.emtaaccc.com
www.emtaconductor.com
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
Inductive Reactance 0,222
Capacitive Reactance 0,194
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
Inductive Reactance 0,222
Capacitive Reactance 0,191
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
www.emtaaccc.com
AC Current Rating at Given Temp. Amperes823
1227
GMR (estimated) 0,009
AC Nominal Resistance at 25°C 0,0910
AC Nominal Resistance at 75°C 0,1088
AC Nominal Resistance at 180°C 0,1461
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0887
Temperature Coefficient of Resistance 0,00403
Frequency 50
No. of Layers 2
No. of Trapezoidal Wires in First Layer 6
No. of Trapezoidal Wires in Second Layer 10
1,88E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 64,1
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 76
Conductor Nominal Mass per Unit Length 947,6
Aluminum Nominal Mass per Unit Length 871,6
Nominal Cross-Sectional Area of the Conductor 355,2
Ultimate Tensile Strength of Conductor 103,4
Rate Strength of Core - 313ksi (2158 MPa) 85,7
315,5
Nominal Diameter of Composite Core 7,11
Nominal Cross-Sectional Area of Core 39,7
Overall Diameter of Conductor 21,79
www.emtaconductor.com
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Lisbon
STANDARD ASTM B 957 / B 609 or EN 50540
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
Inductive Reactance 0,220
Capacitive Reactance 0,189
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
www.emtaaccc.com
AC Current Rating at Given Temp. Amperes828
1234
GMR (estimated) 0,009
AC Nominal Resistance at 25°C 0,0911
AC Nominal Resistance at 75°C 0,1091
AC Nominal Resistance at 180°C 0,1469
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0893
Temperature Coefficient of Resistance 0,00403
Frequency 50
No. of Layers 2
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
1,70E-05
Final Modulus of Elasticity Above Thermal Kneepoint 116,0
Final Modulus of Elasticity Below Thermal Kneepoint 67,4
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,45E-06
Core Nominal Mass per Unit Length 113
Conductor Nominal Mass per Unit Length 980,2
Aluminum Nominal Mass per Unit Length 867,2
Nominal Cross-Sectional Area of the Conductor 374,1
Ultimate Tensile Strength of Conductor 147,9
Rate Strength of Core - 313ksi (2158 MPa) 130,2
313,8
Nominal Diameter of Composite Core 8,76
Nominal Cross-Sectional Area of Core 60,3
Overall Diameter of Conductor 22,40
www.emtaconductor.com
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Oslo
STANDARD ASTM B 957 / B 609 or EN 50540
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
Inductive Reactance 0,217
Capacitive Reactance 0,186
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
www.emtaaccc.com
AC Current Rating at Given Temp. Amperes907
1355
GMR (estimated) 0,010
AC Nominal Resistance at 25°C 0,0784
AC Nominal Resistance at 75°C 0,0936
AC Nominal Resistance at 180°C 0,1256
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0762
Temperature Coefficient of Resistance 0,00403
Frequency 50
No. of Layers 2
No. of Trapezoidal Wires in First Layer 7
No. of Trapezoidal Wires in Second Layer 11
1,88E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 64,2
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 86
Conductor Nominal Mass per Unit Length 1101,6
Aluminum Nominal Mass per Unit Length 1015,6
Nominal Cross-Sectional Area of the Conductor 414,5
Ultimate Tensile Strength of Conductor 122,4
Rate Strength of Core - 313ksi (2158 MPa) 101,7
367,4
Nominal Diameter of Composite Core 7,75
Nominal Cross-Sectional Area of Core 47,1
Overall Diameter of Conductor 23,55
www.emtaconductor.com
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Amsterdam
STANDARD ASTM B 957 / B 609 or EN 50540
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
Inductive Reactance 0,213
Capacitive Reactance 0,183
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
www.emtaaccc.com
AC Current Rating at Given Temp. Amperes1145
1506
GMR (estimated) 0,010
AC Nominal Resistance at 25°C 0,0710
AC Nominal Resistance at 75°C 0,0848
AC Nominal Resistance at 180°C 0,1138
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0690
Temperature Coefficient of Resistance 0,00403
Frequency 50
No. of Layers 2
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
1,62E-05
Final Modulus of Elasticity Above Thermal Kneepoint 146,7
Final Modulus of Elasticity Below Thermal Kneepoint 71,2
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 7,51E-07
Core Nominal Mass per Unit Length 128
Conductor Nominal Mass per Unit Length 1253,6
Aluminum Nominal Mass per Unit Length 1125,6
Nominal Cross-Sectional Area of the Conductor 477,7
Ultimate Tensile Strength of Conductor 207,1
Rate Strength of Core - 313ksi (2158 MPa) 184,2
406,4
Nominal Diameter of Composite Core 9,53
Nominal Cross-Sectional Area of Core 71,3
Overall Diameter of Conductor 25,14
www.emtaconductor.com
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® ULS Liepzig (ULS Brussels Ice)
STANDARD ASTM B 957 / B 609 or EN 50540
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
Inductive Reactance 0,213
Capacitive Reactance 0,183
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
www.emtaaccc.com
AC Current Rating at Given Temp. Amperes987
1479
GMR (estimated) 0,010
AC Nominal Resistance at 25°C 0,0687
AC Nominal Resistance at 75°C 0,0820
AC Nominal Resistance at 180°C 0,1099
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0666
Temperature Coefficient of Resistance 0,00403
Frequency 50
No. of Layers 2
No. of Trapezoidal Wires in First Layer 7
No. of Trapezoidal Wires in Second Layer 12
1,89E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 64,0
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 98
Conductor Nominal Mass per Unit Length 1264,8
Aluminum Nominal Mass per Unit Length 1166,8
Nominal Cross-Sectional Area of the Conductor 473,3
Ultimate Tensile Strength of Conductor 135,7
Rate Strength of Core - 313ksi (2158 MPa) 112,0
421,4
Nominal Diameter of Composite Core 8,13
Nominal Cross-Sectional Area of Core 51,9
Overall Diameter of Conductor 25,15
www.emtaconductor.com
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Brussels
STANDARD ASTM B 957 / B 609 or EN 50540
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
Inductive Reactance 0,210
Capacitive Reactance 0,180
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
www.emtaaccc.com
AC Current Rating at Given Temp. Amperes1049
1576
GMR (estimated) 0,011
AC Nominal Resistance at 25°C 0,0625
AC Nominal Resistance at 75°C 0,0746
AC Nominal Resistance at 180°C 0,0999
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0605
Temperature Coefficient of Resistance 0,00403
Frequency 50
No. of Layers 2
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 1,40E+01
1,86E-05
Final Modulus of Elasticity Above Thermal Kneepoint 116,0
Final Modulus of Elasticity Below Thermal Kneepoint 64,7
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,45E-06
Core Nominal Mass per Unit Length 113
Conductor Nominal Mass per Unit Length 1394,3
Aluminum Nominal Mass per Unit Length 1281,3
Nominal Cross-Sectional Area of the Conductor 523,6
Ultimate Tensile Strength of Conductor 156,3
Rate Strength of Core - 313ksi (2158 MPa) 130,2
463,3
Nominal Diameter of Composite Core 8,76
Nominal Cross-Sectional Area of Core 60,3
Overall Diameter of Conductor 26,40
www.emtaconductor.com
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Stockholm 2L
STANDARD ASTM B 957 / B 609 or EN 50540
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Overall Diameter of Conductor 26,40
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Stockholm 3L
STANDARD ASTM B 957 / B 609 or EN 50540
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 453,7
Nominal Diameter of Composite Core 8,76
Nominal Cross-Sectional Area of Core 60,3
Nominal Cross-Sectional Area of the Conductor 514,0
Ultimate Tensile Strength of Conductor 155,7
Rate Strength of Core - 313ksi (2158 MPa) 130,2
Core Nominal Mass per Unit Length 113
Conductor Nominal Mass per Unit Length 1367,8
Aluminum Nominal Mass per Unit Length 1254,8
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,45E-06
1,85E-05
Final Modulus of Elasticity Above Thermal Kneepoint 116,0
Final Modulus of Elasticity Below Thermal Kneepoint 64,8
Stranding Configuration
No. of Layers 3
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
16
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0617
Temperature Coefficient of Resistance 0,00403
Frequency 50
AC Nominal Resistance at 25°C 0,0637
AC Nominal Resistance at 75°C 0,0760
AC Nominal Resistance at 180°C 0,1019
AC Current Rating at Given Temp. Amperes1039
1560
GMR (estimated) 0,011
Inductive Reactance 0,210
Capacitive Reactance 0,180
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
www.emtaaccc.com
www.emtaconductor.com
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
14
Inductive Reactance 0,207
Capacitive Reactance 0,177
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
AC Current Rating at Given Temp. Amperes1112
1673
GMR (estimated) 0,011
ACCC® is produced with 1350 O-tempered aluminum
AC Nominal Resistance at 25°C 0,0573
AC Nominal Resistance at 75°C 0,0683
AC Nominal Resistance at 180°C 0,0914
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0553
Temperature Coefficient of Resistance 0,00403
Frequency 50
No. of Layers 3
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 11
1,89E-05
Final Modulus of Elasticity Above Thermal Kneepoint 116,0
Final Modulus of Elasticity Below Thermal Kneepoint 64,2
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,45E-06
Core Nominal Mass per Unit Length 113
Conductor Nominal Mass per Unit Length 1519,8
Aluminum Nominal Mass per Unit Length 1406,8
Nominal Cross-Sectional Area of the Conductor 567,8
Ultimate Tensile Strength of Conductor 158,7
Rate Strength of Core - 313ksi (2158 MPa) 130,2
Nominal Diameter of Composite Core 8,76
Nominal Cross-Sectional Area of Core 60,3
Overall Diameter of Conductor 27,72
www.emtaaccc.com
www.emtaconductor.com
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Warsaw
STANDARD ASTM B 957 / B 609 or EN 50540
507,5
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
Inductive Reactance 0,206
Capacitive Reactance 0,176
AC Current Rating at Given Temp. Amperes1136
1711
GMR (estimated) 0,011
AC Nominal Resistance at 25°C 0,0553
AC Nominal Resistance at 75°C 0,0660
AC Nominal Resistance at 180°C 0,0883
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0534
Temperature Coefficient of Resistance 0,00403
Frequency 50
No. of Layers 2
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 14
1,86E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 64,5
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 132
Conductor Nominal Mass per Unit Length 1583,0
Aluminum Nominal Mass per Unit Length 1451,0
Nominal Cross-Sectional Area of the Conductor 595,8
Ultimate Tensile Strength of Conductor 183,3
Rate Strength of Core - 313ksi (2158 MPa) 153,8
524,5
Nominal Diameter of Composite Core 9,53
Nominal Cross-Sectional Area of Core 71,3
Overall Diameter of Conductor 28,14
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Dublin
STANDARD ASTM B 957 / B 609 or EN 50540
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
www.emtaaccc.com
www.emtaconductor.com
GMR (estimated) 0,012
Inductive Reactance 0,205
Capacitive Reactance 0,175
AC Nominal Resistance at 180°C 0,0855
AC Current Rating at Given Temp. Amperes1160
1748
Frequency 50
AC Nominal Resistance at 25°C 0,0536
AC Nominal Resistance at 75°C 0,0639
14
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0517
Temperature Coefficient of Resistance 0,00403
No. of Layers 3
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
1,87E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 64,3
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 132
Conductor Nominal Mass per Unit Length 1643,2
Aluminum Nominal Mass per Unit Length 1511,2
Nominal Cross-Sectional Area of the Conductor 614,8
Ultimate Tensile Strength of Conductor 184,4
Rate Strength of Core - 313ksi (2158 MPa) 153,8
Nominal Diameter of Composite Core 9,53
Nominal Cross-Sectional Area of Core 71,3
Overall Diameter of Conductor 28,62
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Kolkata
STANDARD ASTM B 957 / B 609 or EN 50540
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 543,5
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
www.emtaaccc.com
www.emtaconductor.com
GMR (estimated) 0,012
Inductive Reactance 0,206
Capacitive Reactance 0,175
AC Nominal Resistance at 180°C 0,0850
AC Current Rating at Given Temp. Amperes1163
1752
Frequency 50
AC Nominal Resistance at 25°C 0,0534
AC Nominal Resistance at 75°C 0,0636
14
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0514
Temperature Coefficient of Resistance 0,00403
No. of Layers 3
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
1,91E-05
Final Modulus of Elasticity Above Thermal Kneepoint 116,0
Final Modulus of Elasticity Below Thermal Kneepoint 63,8
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,45E-06
Core Nominal Mass per Unit Length 113
Conductor Nominal Mass per Unit Length 1626,9
Aluminum Nominal Mass per Unit Length 1513,9
Nominal Cross-Sectional Area of the Conductor 606,7
Ultimate Tensile Strength of Conductor 160,9
Rate Strength of Core - 313ksi (2158 MPa) 130,2
Nominal Diameter of Composite Core 8,76
Nominal Cross-Sectional Area of Core 60,3
Overall Diameter of Conductor 28,62
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Hamburg
STANDARD ASTM B 957 / B 609 or EN 50540
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 546,4
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
www.emtaaccc.com
www.emtaconductor.com
GMR (estimated) 0,012
Inductive Reactance 0,205
Capacitive Reactance 0,174
AC Nominal Resistance at 180°C 0,0818
AC Current Rating at Given Temp. Amperes1191
1797
Frequency 50
AC Nominal Resistance at 25°C 0,0514
AC Nominal Resistance at 75°C 0,0612
16
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0494
Temperature Coefficient of Resistance 0,00403
No. of Layers 3
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
1,93E-05
Final Modulus of Elasticity Above Thermal Kneepoint 116,0
Final Modulus of Elasticity Below Thermal Kneepoint 63,6
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,45E-06
Core Nominal Mass per Unit Length 113
Conductor Nominal Mass per Unit Length 1686,1
Aluminum Nominal Mass per Unit Length 1573,1
Nominal Cross-Sectional Area of the Conductor 628,0
Ultimate Tensile Strength of Conductor 162,1
Rate Strength of Core - 313ksi (2158 MPa) 130,2
Nominal Diameter of Composite Core 8,76
Nominal Cross-Sectional Area of Core 60,3
Overall Diameter of Conductor 29,10
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Milan
STANDARD ASTM B 957 / B 609 or EN 50540
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 567,7
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
www.emtaaccc.com
www.emtaconductor.com
GMR (estimated) 0,012
Inductive Reactance 0,203
Capacitive Reactance 0,173
AC Nominal Resistance at 180°C 0,0785
AC Current Rating at Given Temp. Amperes1225
1850
Frequency 50
AC Nominal Resistance at 25°C 0,0494
AC Nominal Resistance at 75°C 0,0588
16
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0474
Temperature Coefficient of Resistance 0,00403
No. of Layers 3
No. of Trapezoidal Wires in First Layer 9
No. of Trapezoidal Wires in Second Layer 12
1,90E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 63,8
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 132
Conductor Nominal Mass per Unit Length 1773,8
Aluminum Nominal Mass per Unit Length 1641,8
Nominal Cross-Sectional Area of the Conductor 663,8
Ultimate Tensile Strength of Conductor 187,1
Rate Strength of Core - 313ksi (2158 MPa) 153,8
Nominal Diameter of Composite Core 9,53
Nominal Cross-Sectional Area of Core 71,3
Overall Diameter of Conductor 29,89
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Rome
STANDARD ASTM B 957 / B 609 or EN 50540
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 592,5
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
www.emtaaccc.com
www.emtaconductor.com
GMR (estimated) 0,012
Inductive Reactance 0,202
Capacitive Reactance 0,172
AC Nominal Resistance at 180°C 0,0738
AC Current Rating at Given Temp. Amperes1269
1918
Frequency 50
AC Nominal Resistance at 25°C 0,0466
AC Nominal Resistance at 75°C 0,0554
16
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0445
Temperature Coefficient of Resistance 0,00403
No. of Layers 3
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
1,96E-05
Final Modulus of Elasticity Above Thermal Kneepoint 115,9
Final Modulus of Elasticity Below Thermal Kneepoint 63,1
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,45E-06
Core Nominal Mass per Unit Length 113
Conductor Nominal Mass per Unit Length 1852,3
Aluminum Nominal Mass per Unit Length 1739,3
Nominal Cross-Sectional Area of the Conductor 689,5
Ultimate Tensile Strength of Conductor 165,6
Rate Strength of Core - 313ksi (2158 MPa) 130,2
Nominal Diameter of Composite Core 8,76
Nominal Cross-Sectional Area of Core 60,3
Overall Diameter of Conductor 30,42
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Vienna
STANDARD ASTM B 957 / B 609 or EN 50540
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 629,2
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
www.emtaaccc.com
www.emtaconductor.com
GMR (estimated) 0,013
Inductive Reactance 0,200
Capacitive Reactance 0,170
AC Nominal Resistance at 180°C 0,0697
AC Current Rating at Given Temp. Amperes1318
1996
Frequency 50
AC Nominal Resistance at 25°C 0,044
AC Nominal Resistance at 75°C 0,0523
16
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0420
Temperature Coefficient of Resistance 0,00403
No. of Layers 3
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
1,94E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 63,2
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 132
Conductor Nominal Mass per Unit Length 1983,9
Aluminum Nominal Mass per Unit Length 1851,9
Nominal Cross-Sectional Area of the Conductor 739,6
Ultimate Tensile Strength of Conductor 191,4
Rate Strength of Core - 313ksi (2158 MPa) 153,8
Nominal Diameter of Composite Core 9,53
Nominal Cross-Sectional Area of Core 71,3
Overall Diameter of Conductor 31,50
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Budapest
STANDARD ASTM B 957 / B 609 or EN 50540
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 668,3
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
Manufactured under licence by
www.emtaaccc.com
www.emtaconductor.com
GMR (estimated) 0,013
Inductive Reactance 0,199
Capacitive Reactance 0,169
AC Nominal Resistance at 180°C 0,0681
AC Current Rating at Given Temp. Amperes1336
2025
Frequency 50
AC Nominal Resistance at 25°C 0,0431
AC Nominal Resistance at 75°C 0,0511
18
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0410
Temperature Coefficient of Resistance 0,00403
No. of Layers 3
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
1,94E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 63,1
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 132
Conductor Nominal Mass per Unit Length 2034,9
Aluminum Nominal Mass per Unit Length 1902,9
Nominal Cross-Sectional Area of the Conductor 756,7
Ultimate Tensile Strength of Conductor 192,4
Rate Strength of Core - 313ksi (2158 MPa) 153,8
Nominal Diameter of Composite Core 9,53
Nominal Cross-Sectional Area of Core 71,3
Overall Diameter of Conductor 31,77
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEET
CODE NAME ACCC® Mumbai
STANDARD ASTM B 957 / B 609 or EN 50540
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 685,4
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Manufactured under licence by
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
www.emtaaccc.com
www.emtaconductor.com
GMR (estimated) 0,013
Inductive Reactance 0,199
Capacitive Reactance 0,169
AC Nominal Resistance at 180°C 0,0676
AC Current Rating at Given Temp. Amperes1340
2032
Frequency 50
AC Nominal Resistance at 25°C 0,0428
AC Nominal Resistance at 75°C 0,0508
16
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0407
Temperature Coefficient of Resistance 0,00403
No. of Layers 3
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
1,98E-05
Final Modulus of Elasticity Above Thermal Kneepoint 116,0
Final Modulus of Elasticity Below Thermal Kneepoint 62,7
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,45E-06
Core Nominal Mass per Unit Length 113
Conductor Nominal Mass per Unit Length 2029,8
Aluminum Nominal Mass per Unit Length 1916,8
Nominal Cross-Sectional Area of the Conductor 751,0
Ultimate Tensile Strength of Conductor 169,1
Rate Strength of Core - 313ksi (2158 MPa) 130,2
Nominal Diameter of Composite Core 8,76
Nominal Cross-Sectional Area of Core 60,3
Overall Diameter of Conductor 31,77
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEET
CODE NAME ACCC® Prague
STANDARD ASTM B 957 / B 609 or EN 50540
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 690,7
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
GMR (estimated) 0,013
Inductive Reactance 0,197
Capacitive Reactance 0,167
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
AC Nominal Resistance at 180°C 0,0638
AC Current Rating at Given Temp. Amperes1392
2113
Frequency 50
AC Nominal Resistance at 25°C 0,0405
AC Nominal Resistance at 75°C 0,0480
16
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0384
Temperature Coefficient of Resistance 0,00403
Stranding Configuration
No. of Layers 3
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
1,96E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 62,8
Aluminum Nominal Mass per Unit Length 2037,5
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Rate Strength of Core - 313ksi (2158 MPa) 153,8
Core Nominal Mass per Unit Length 132
Conductor Nominal Mass per Unit Length 2169,5
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 733,2
Nominal Diameter of Composite Core 9,53
Nominal Cross-Sectional Area of Core 71,3
Overall Diameter of Conductor 32,85
ACCC® is produced with 1350 O-tempered aluminum
www.emtaaccc.com
www.emtaconductor.com
Manufactured under licence by
Nominal Cross-Sectional Area of the Conductor 804,5
Ultimate Tensile Strength of Conductor 195,0
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Munich
STANDARD ASTM B 957 / B 609 or EN 50540
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
GMR (estimated) 0,013
Inductive Reactance 0,196
Capacitive Reactance 0,166
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
AC Nominal Resistance at 180°C 0,0616
AC Current Rating at Given Temp. Amperes1424
2164
Frequency 50
AC Nominal Resistance at 25°C 0,0391
AC Nominal Resistance at 75°C 0,0464
16
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0370
Temperature Coefficient of Resistance 0,00403
Stranding Configuration
No. of Layers 3
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
1,96E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 62,9
Aluminum Nominal Mass per Unit Length 2105,1
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Rate Strength of Core - 313ksi (2158 MPa) 162,1
Core Nominal Mass per Unit Length 143
Conductor Nominal Mass per Unit Length 2248,1
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 759,0
Nominal Diameter of Composite Core 9,78
Nominal Cross-Sectional Area of Core 75,1
Overall Diameter of Conductor 33,40
ACCC® is produced with 1350 O-tempered aluminum
www.emtaaccc.com
www.emtaconductor.com
Manufactured under licence by
Nominal Cross-Sectional Area of the Conductor 834,1
Ultimate Tensile Strength of Conductor 204,8
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® London
STANDARD ASTM B 957 / B 609 or EN 50540
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
GMR (estimated) 0,014
Inductive Reactance 0,195
Capacitive Reactance 0,165
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
AC Nominal Resistance at 180°C 0,0576
AC Current Rating at Given Temp. Amperes1480
2254
Frequency 50
AC Nominal Resistance at 25°C 0,0368
AC Nominal Resistance at 75°C 0,0435
18
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0345
Temperature Coefficient of Resistance 0,00403
Stranding Configuration
No. of Layers 3
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
Coefficient of Linear Expansion Above Thermal Kneepoint 1,45E-06
2,03E-05
Final Modulus of Elasticity Above Thermal Kneepoint 116,0
Final Modulus of Elasticity Below Thermal Kneepoint 62,0
Aluminum Nominal Mass per Unit Length 2252,4
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Rate Strength of Core - 313ksi (2158 MPa) 130,2
Core Nominal Mass per Unit Length 113
Conductor Nominal Mass per Unit Length 2365,4
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 813,7
Nominal Diameter of Composite Core 8,76
Nominal Cross-Sectional Area of Core 60,3
Overall Diameter of Conductor 34,16
ACCC® is produced with 1350 O-tempered aluminum
www.emtaaccc.com
www.emtaconductor.com
Manufactured under licence by
Nominal Cross-Sectional Area of the Conductor 874,0
Ultimate Tensile Strength of Conductor 176,0
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Paris
STANDARD ASTM B 957 / B 609 or EN 50540
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
GMR (estimated) 0,014
Inductive Reactance 0,192
Capacitive Reactance 0,162
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
AC Nominal Resistance at 180°C 0,0531
AC Current Rating at Given Temp. Amperes1560
2381
Frequency 50
AC Nominal Resistance at 25°C 0,0340
AC Nominal Resistance at 75°C 0,0402
18
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0318
Temperature Coefficient of Resistance 0,00403
Stranding Configuration
No. of Layers 3
No. of Trapezoidal Wires in First Layer 10
No. of Trapezoidal Wires in Second Layer 14
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
1,96E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 62,9
Aluminum Nominal Mass per Unit Length 2602,2
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Rate Strength of Core - 313ksi (2158 MPa) 188,3
Core Nominal Mass per Unit Length 164
Conductor Nominal Mass per Unit Length 2766,2
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 880,9
Nominal Diameter of Composite Core 10,54
Nominal Cross-Sectional Area of Core 87,3
Overall Diameter of Conductor 35,76
ACCC® is produced with 1350 O-tempered aluminum
www.emtaaccc.com
www.emtaconductor.com
Manufactured under licence by
Nominal Cross-Sectional Area of the Conductor 968,2
Ultimate Tensile Strength of Conductor 237,9
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Bordeaux
STANDARD ASTM B 957 / B 609 or EN 50540
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
No. of Trapezoidal Wires in Fourth Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
GMR (estimated) 0,015
Inductive Reactance 0,190
Capacitive Reactance 0,161
AC Nominal Resistance at 180°C 0,0498
AC Current Rating at Given Temp. Amperes1623
2483
Frequency 50
AC Nominal Resistance at 25°C 0,0321
AC Nominal Resistance at 75°C 0,0378
16
Electrical Specifications
Nominal Resistivity of Aluminum at 20°C, DC 63% IACS 0,0297
Temperature Coefficient of Resistance 0,00403
20
No. of Layers 4
No. of Trapezoidal Wires in First Layer 9
No. of Trapezoidal Wires in Second Layer 12
2,02E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 62,0
Stranding Configuration
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
Core Nominal Mass per Unit Length 143
Conductor Nominal Mass per Unit Length 2759,1
Aluminum Nominal Mass per Unit Length 2616,1
Nominal Cross-Sectional Area of the Conductor 1020,0
Ultimate Tensile Strength of Conductor 215,3
Rate Strength of Core - 313ksi (2158 MPa) 162,1
Nominal Diameter of Composite Core 9,78
Nominal Cross-Sectional Area of Core 75,1
Overall Diameter of Conductor 36,85
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Antwerp
STANDARD ASTM B 957 / B 609 or EN 50540
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 944,9
www.emtaaccc.com
www.emtaconductor.com
Manufactured under licence by
ACCC® is produced with 1350 O-tempered aluminum
ACCC® exhibit lay length (ratios) that conform to ASTM B 857 or EN 50540
Minimum tensile strength of annealed aluminum conform to ASTM B 609 and EN 50540
Conditions: 0,61 m/s (2 ft/s) wind, 0 m (0 ft) elevation, 0,5 emis., 0,5 absorp. 40°C ambient temp., 1033 W/m2 (96 W/ft2) sun radiation
mailto:[email protected]://www.emtaaccc.com/http://www.emtaconductor.com/
-
mm2
mm
mm2
mm
mm2
kN
kN
kg/km
kg/km
kg/km
°C
°C
/°C
Coefficient of Linear Expansion Below Thermal Kneepoint /°C
Gpa
GPa
pcs.
pcs.
pcs.
No. of Trapezoidal Wires in Third Layer pcs.
No. of Trapezoidal Wires in Fourth Layer pcs.
Ω/km
/°C
Hz
Ω/km
Ω/km
Ω/km
@ 100°C & 50 Hz
@180°C & 50 Hz
m
Ω/km
MΩ-km
EMTA KABLO SANAYI VE TİCARET A.Ş.
İstasyon Mahallesi İbişağa Caddesi No:4 34940 Tuzla, İstanbul/TURKEY
Tel: +90 216 446 66 06 / Fax: +90 216 446 43 93
Overall Diameter of Conductor 38,20
HIGH TENSION LOW SAG CONDUCTORS
TECHNICAL DATA SHEETCODE NAME ACCC® Madrid
STANDARD ASTM B 957 / B 609 or EN 50540
Alu
min
ium
Co
nd
uct
or
Co
mp
osi
te C
ore
Mechanical Specifications
Nominal Aluminum Cross-Sectional Area 1013,1
Nominal Diameter of Composite Core 9,78
Nominal Cross-Sectional Area of Core 75,1
Nominal Cross-Sectional Area of the Conductor 1088,2
Ultimate Tensile Strength of Conductor 219,1
Rate Strength of Core - 313ksi (2158 MPa) 162,1
Core Nominal Mass per Unit Length 143
Conductor Nominal Mass per Unit Length 2947,8
Aluminum Nominal Mass per Unit Length 2804,8
Maximum Continuous Operating Temperature of Conductor 180
Maximum Allowable Emergency Temperature of Conductor 200
Coefficient of Linear Expansion Above Thermal Kneepoint 1,61E-06
2,04E-05
Final Modulus of Elasticity Above Thermal Kneepoint 112,3
Final Modulus of Elasticity Below Thermal Kneepoint 61,8
Stranding Configuration
No. of Layers 4
No. of Trapezoidal Wires in First Layer 8
No. of Trapezoidal Wires in Second Layer 12
16
20
Ele