hướng dẫn sử dụng màn hình pro-face |pro-face gp4201 manual, pro-face gp4301 manual,...

Upload: nguyen-van-dung

Post on 07-Feb-2018

244 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    1/240

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    2/240

    2

    The information provided in this documentation contains general descriptions and/or

    technical characteristics of the performance of the products contained herein. This

    documentation is not intended as a substitute for and is not to be used for

    determining suitability or reliability of these products for specific user applications. It

    is the duty of any such user or integrator to perform the appropriate and complete

    risk analysis, evaluation and testing of the products with respect to the relevant

    specific application or use thereof. Neither Pro-face nor any of its affiliates or

    subsidiaries shall be responsible or liable for misuse of the information that is

    contained herein. If you have any suggestions for improvements or amendments or

    have found errors in this publication, please notify us.

    No part of this document may be reproduced in any form or by any means, electronic

    or mechanical, including photocopying, without express written permission of Pro-

    face.

    All pertinent state, regional, and local safety regulations must be observed when

    installing and using this product. For reasons of safety and to help ensure

    compliance with documented system data, only the manufacturer should perform

    repairs to components.

    When devices are used for applications with technical safety requirements, the

    relevant instructions must be followed.

    Failure to use Pro-face software or approved software with our hardware products

    may result in injury, harm, or improper operating results.

    Failure to observe this information can result in injury or equipment damage.

    Copyright 2013. 8 Digital Electronics Corporation. All Rights Reserved.

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    3/240

    3

    GP4000 Series Hardware Manual

    Table of Contents

    Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    Chapter 1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11GP unit Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    Certifications and Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    GP Series of Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    Chapter 2 Device Connectivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    Chapter 3 Parts Identification and Functions . . . . . . . . . . . . . . . . . 31Parts Identification and Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    Chapter 4 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434.1 GP-4200 Series. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    Electrical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

    Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    Structural Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    Display Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    Memory, Clock, and Touch Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Interface Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

    Specifications of Serial Interface COM1 . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    Specifications of Serial Interface COM2 . . . . . . . . . . . . . . . . . . . . . . . . . . 57

    Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

    4.2 GP-4300 Series. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

    Electrical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

    Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

    Structural Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

    Display Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

    Memory, Clock, and Touch Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

    Interface Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

    Specifications of Serial Interface COM1 . . . . . . . . . . . . . . . . . . . . . . . . . . 73

    Specifications of Serial Interface COM2 . . . . . . . . . . . . . . . . . . . . . . . . . . 75

    Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

    4.3 GP-4400 Series. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

    Electrical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

    Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

    Structural Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

    Display Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

    Memory, Clock, and Touch Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

    Interface Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89

    Specifications of Serial Interface COM1 . . . . . . . . . . . . . . . . . . . . . . . . . . 90

    Specifications of Serial Interface COM2 . . . . . . . . . . . . . . . . . . . . . . . . . . 92Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    4/240

    4

    4.4 GP-4500 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97

    Electrical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

    Environmental Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

    Structural Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

    Display Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

    Memory, Clock, and Touch Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

    Interface Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104Specifications of Serial Interface COM1 . . . . . . . . . . . . . . . . . . . . . . . . . 105

    Specifications of Serial Interface COM2 . . . . . . . . . . . . . . . . . . . . . . . . . 107

    Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

    4.5 GP-4600 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117

    Electrical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118

    Environmental Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

    Structural Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120

    Display Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122

    Memory, Clock, and Touch Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

    Interface Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124

    Specifications of Serial Interface COM1 . . . . . . . . . . . . . . . . . . . . . . . . . 125Specifications of Serial Interface COM2 . . . . . . . . . . . . . . . . . . . . . . . . . 127

    Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129

    Chapter 5 Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 1355.1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136

    Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136

    5.2 Wiring Principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141

    Connecting the AC Power Cord. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142

    Connecting the DC Power Cord. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144

    Connecting the Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147

    Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149

    5.3 SD Card Insertion/Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150

    Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151Inserting the SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152

    Before Removing the SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154

    Removing the SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155

    SD Card Data Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156

    5.4 USB Cable Clamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157

    USB Cable Clamp for USB (Type A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158

    USB Holder for USB (mini-B). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160

    Chapter 6 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163Regular Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164

    Replacing the Installation Gasket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165

    Periodic Check Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167Replacing the Primary Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168

    Chapter 7 Rear Mount Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172

    Certifications and Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173

    Options/Maintenance Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175

    Parts Identification and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176

    Structural Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182

    Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184

    Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    5/240

    5

    GP4000 Series Hardware Manual

    Safety Information

    Important Information

    NOTICE

    Read these instructions carefully, and look at the equipment to become familiar with

    the device before trying to install, operate, or maintain it. The following special

    messages may appear throughout this documentation or on the equipment to warn

    of potential hazards or to call attention to information that clarifies or simplifies aprocedure.

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    6/240

    6

    PLEASE NOTE

    Electrical equipment should be installed, operated, serviced, and maintained only by

    qualified personnel. No responsibility is assumed by Pro-face for any consequences

    arising out of the use of this material.

    A qualified person is one who has skills and knowledge related to the construction

    and operation of electrical equipment and its installation, and has received safetytraining to recognize and avoid the hazards involved.

    Model Name Format

    The following describes the format of model names.

    Digit Possible Values Description

    A 2 GP-4200 Series (3.5-inch, 320 x 240 dots (QVGA))

    3 GP-4300 Series (5.7-inch, 320 x 240 dots (QVGA))

    4 GP-4400 Series

    (7.5-inch, 640 x 480 dots (VGA))

    (7.0-inch, 800 x 480 dots (WVGA))

    5 GP-4500 Series (10.4-inch, 640 x 480 dots (VGA))

    6 GP-4600 Series (12.1-inch, 800 x 600 dots (SVGA))

    B 01 RS-232C and RS-422/RS-485 are available.

    On GP-4201T, either RS-232C or RS-422/485 is available.

    03 RS-232C and RS-485 (isolation) are available.

    On GP-4203T, one serial interface RS-485 (isolation) is

    available.

    C T TFT color LCD

    W Wide TFT color LCD

    D A Analog Touch Panel

    M Matrix Touch Panel

    E A AC type power supply

    D DC type power supply

    F W GP-4201TW/GP-4301TW/GP-4401WW/GP-4501TW

    C Coating model

    WC Coating model of GP-4201TW/GP-4301TW/GP-4401WW/GP-

    4501TW

    R Rear Mount Model

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    7/240

    GP4000 Series Hardware Manual

    7

    GP4000 Series Model Names

    Thank you for purchasing Pro-faces GP4000 Series unit (hereafter referred to as

    the "GP unit").

    *1 Please see "GP-4100 Series Hardware Manual" for details.

    *2 Please see "GP-4201TM/4301TM Hardware Manual" for details.

    Series Model Name Model

    GP4000 Series GP-4100 Series*1

    GP-4104 GP4104G1DGP4104W1D

    GP-4105 GP4105G1D

    GP4105W1D

    GP-4106 GP4106G1D

    GP4106W1D

    GP-4107 GP4107G1D

    GP4107W1D

    GP-4200 Series GP-4201T PFXGP4201TAD

    GP-4201TM (Modular

    Type) *2PFXGM4201TAD

    GP-4201TW PFXGP4201TADW

    GP-4203T PFXGP4203TAD

    GP-4300 Series GP-4301T PFXGP4301TAD

    PFXGP4301TADC

    PFXGP4301TADR

    GP-4301TM (Modular

    Type) *2PFXGM4301TAD

    GP-4301TW PFXGP4301TADW

    PFXGP4301TADWC

    GP-4303T PFXGP4303TAD

    GP-4400 Series GP-4401T PFXGP4401TAD

    PFXGP4401TADR

    GP-4401WW PFXGP4401WADW

    GP-4500 Series GP-4501T (Analog

    Touch Panel)

    PFXGP4501TAA

    PFXGP4501TAAC

    PFXGP4501TAD

    PFXGP4501TADC

    PFXGP4501TADR

    GP-4501T (Matrix

    Touch Panel)

    PFXGP4501TMA

    PFXGP4501TMD

    GP-4501TW PFXGP4501TADW

    GP-4503T PFXGP4503TAD

    GP-4600 Series GP-4601T (Analog

    Touch Panel)

    PFXGP4601TAA

    PFXGP4601TAAC

    PFXGP4601TAD

    PFXGP4601TADC

    PFXGP4601TADR

    GP-4601T (Matrix

    Touch Panel)

    PFXGP4601TMD

    PFXGP4601TMA

    GP-4603T PFXGP4603TAD

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    8/240

    8

    Global Code

    A global code is assigned to every Pro-face product as a universal model number.

    For more information on product models and their matching global codes, please

    refer to the following URL.

    http://www.pro-face.com/product/globalcode.html

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    9/240

    9

    GP4000 Series Hardware Manual

    About the Book

    At a Glance

    Document Scope

    This document describes how to use the GP unit.

    Validity NoteThis document is valid for the GP unit with GP-Pro EX version 3.0 or later.

    The technical characteristics of the device(s) described in this manual also appear

    online at http://www.pro-face.com/otasuke/.

    The characteristics presented in this manual should be the same as those that

    appear online. In line with our policy of constant improvement we may revise content

    over time to improve clarity and accuracy. In the event that you see a difference

    between the manual and online information, use the online information as your

    reference.

    Related Documents

    You can download these technical publications and other technical information from

    our website "Otasuke Pro!" at http://www.pro-face.com/otasuke/.

    Product Related Information

    Title of Documentation

    GP-Pro EX Reference Manual

    GP-Pro EX Maintenance/Troubleshooting Manual

    GP-Pro EX Device/PLC Connection Manual

    WARNINGUNINTENDED EQUIPMENT OPERATION

    The application of this product requires expertise in the design and programming

    of control systems. Only persons with such expertise should be allowed to

    program, install, alter, and apply this product.

    Follow all local and national safety standards.

    Failure to follow these instruct ions can result in death, serious injury , or

    equipment damage.

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    10/240

    10

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    11/240

    11

    GP4000 Series Hardware Manual

    1

    GP4000Series Hardware anual

    Overview

    KanpaiHardwareManual 10/2011

    Overview

    Overview

    This chapter describes the GP unit panels and general topics such as package

    contents and standards.

    What Is in This Chapter?

    This chapter contains the following topics:

    Topic Page

    GP unit Package Contents 12

    Certifications and Standards 13

    GP Series of Panels 15

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    12/240

    Overview

    12

    GP unit Package Contents

    Note:

    For information on the package contents for the rear mount model, refer to

    Package Contents (see page 172).

    Overview

    Verify all items listed here are present in your package:

    1 GP unit: 1

    2 Installation gasket: 1 (attached to the GP unit)

    3 Installation fasteners: 4 per set

    4 DC power supply connector: 1 (only for DC type)*15 USB cable clamp Type A: 1 set (1 clip and 1 tie)

    6 GP4000 Series Installation Guide: 1

    7 Warning/Caution information: 1

    This unit has been carefully packed with special attention to quality. However,

    should you find anything damaged or missing, please contact your local distributor.

    *1You can use the DC power supply connector for GP-4200/4300/4400 series to

    supply power to GP-4500/4600 series. However the reverse is not possible. You

    cannot use the DC power supply connector for GP-4500/4600 series on GP-

    4200/4300/4400 series.

    RevisionYou can identify the product revision from the product label on the GP unit. The

    following diagram is a representation of Revision A. The product label indicates

    Revision A with an asterisk (*) in the "A" position.

    REV * B C D E F G H I J K L M N O P Q R S T U V W X Y Z 1 2 3 4 5

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    13/240

    GP4000 Series Hardware Manual

    13

    Certifications and Standards

    Note:

    For information on the certifications and standards of the rear mount model, refer

    to Certifications and Standards (see page 173).

    Introduction

    Pro-face submitted this product for independent testing and qualification by third-

    party listing agencies. These agencies have certified this product as meeting the

    following standards.

    Agency Certi ficat ions

    The GP unit is manufactured in accordance with:

    UL 508 and CSA C22.2 n142 for Industrial Control Equipment

    Standard ANSI/ISA - 12.12.01 and CSA C22.2 n213 for Electrical Equipment for

    Use in Class I, Division 2 Hazardous Locations

    Note:

    For use in Pollution Degree 2 environments.

    For use on a flat surface of a Type 1, Type 4X (Indoor Use Only) or Type 13

    Enclosure.

    24 Vdc input panel must be used with a Class 2 power supply.

    Suitable for use in Class I, Division 2 Groups A, B, C, and D Hazardous

    Locations.

    Hazardous Substances

    The GP is a device for use in factory systems. When using the GP in a system, thesystem should comply with the following standards in regards to the installation

    environment and handling:

    WEEE, Directive 2012/19/EU

    RoHS, Directive 2011/65/EU

    RoHS China, Standard SJ/T 11363-2006

    CE Markings

    This product conforms to the necessary requirements of the following Directives for

    applying the CE label:

    2006/95/EC Low Voltage Directive

    2004/108/EC EMC DirectiveThis conformity is based on compliance with EN61000-6-4, EN61000-6-2 (DC

    model, AC model)

    This conformity is based on compliance with EN60950-1 (AC model)

    For information on Standards and Regulations, such as certified models and

    certificates, see the following.

    http://www.pro-face.com/worldwide.html

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    14/240

    Overview

    14

    KC Markings

    DANGERPOTENTIAL FOR EXPLOSION

    Verify that the power, input and output (I/O) wiring are in accordance with Class

    I, Division 2 wiring methods.

    Substitution of any component may impair suitability for Class I, Division 2. Do not connect or disconnect equipment unless power has been switched off or

    the area is known to be non-hazardous.

    Securely lock externally connected units and each interface before turning on

    the power supply.

    Do not use, connect, or disconnect USB cable unless area is known to be non-

    hazardous.

    Do not disconnect while circuit is live or unless the area is known to be free of

    ignitable concentrations.

    Potential electrostatic charging hazard: wipe the front panel of the terminal with

    a damp cloth before turning ON.

    Failure to follow these instructions will result in death or serious injury.

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    15/240

    GP4000 Series Hardware Manual

    15

    GP Series of Panels

    Critical systems, alarms and handling Requirements

    Critical alarm indicators and system functions require independent and redundant

    protection hardware and/or mechanical interlocks.

    When you cycle power, wait at least 10 seconds before restoring the power to the

    GP unit after it has been turned off. If GP unit is restarted too quickly, it may not

    operate correctly.

    In the event the screen cannot be properly read, for example, if the backlight is not

    functioning, it may be difficult or impossible to identify a function. Functions that may

    present a hazard if not immediately executed, such as a fuel shut-off, must be

    provided independently of the GP unit. The machines control system design must

    take into account the possibility of the backlight no longer functioning and the

    operator being unable to control the machine or making mistakes in the control of

    the machine.

    For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines

    for the Application, Installation, and Maintenance of Solid State Control" and toNEMA ICS 7.1 (latest edition), "Safety Standards for Construction and Guide for

    Selection, Installation and Operation of Adjustable-Speed Drive Systems" or their

    equivalent governing your particular location.

    WARNINGLOSS OF CONTROL

    The designer of any control scheme must consider the potential failure modes

    of control paths and, for certain critical control functions, provide a means to

    achieve a safe state during and after a path failure. Examples of critical control

    functions are emergency stop and overtravel stop, power outage and restart.

    Separate or redundant control paths must be provided for critical control

    functions.

    System control paths may include communication links. Consideration must be

    given to the implications of unanticipated transmission delays or failures of the

    link. Observe all accident prevention regulations and local safety guidelines.

    Each implementation of this equipment must be individually and thoroughly

    tested for proper operation before being placed into service.

    The machine control system design must take into account the possibility of the

    backlight no longer functioning and the operator being unable to control the

    machine, or making errors in the control of the machine.

    Failure to follow these instruct ions can result in death, serious injury , or

    equipment damage.

    WARNINGUNINTENDED EQUIPMENT OPERATION

    Do not use this equipment as the only means of control for critical system

    functions such as motor start/stop or power control.

    Do not use this equipment as the only notification device for critical alarms, such

    as device overheating or overcurrent.

    Failure to follow these instruct ions can result in death, serious injury , or

    equipment damage.

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    16/240

    Overview

    16

    Handling the LCD panel

    The following characteristics are specific to the LCD panel and are considered

    normal behavior:

    LCD screen may show unevenness in the brightness of certain images or may

    appear different when seen from outside the specified viewing angle. Extended

    shadows, or crosstalk may also appear on the sides of screen images. LCD screen pixels may contain black and white colored spots and color display

    may seem to have changed.

    When the same image is displayed on the screen for a long period, an afterimage

    may appear when the image is changed.

    NOTE: Change the screen image periodically and try not to display the same image

    for a long period of time.

    If the panel is damaged and any liquid comes in contact with your skin, immediately

    rinse the area with running water for at least 15 minutes. If the liquid gets in your

    eyes, immediately rinse your eyes with running water for at least 15 minutes and

    consult a doctor.

    CAUTIONSERIOUS EYE AND SKIN INJURY

    The liquid in the LCD panel contains an irritant:

    Avoid direct skin contact with the liquid.

    Wear gloves when you handle a broken or leaking unit.

    Do not use sharp objects or tools in the vicinity of the LCD touch panel.

    Handle the LCD panel carefully to prevent puncture, bursting, or cracking of the

    panel material.

    Failure to follow these instructions can result in in jury or equipment damage.

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    17/240

    17

    GP4000 Series Hardware Manual

    2

    GP4000Series Hardware Manual

    Connectivity

    KanpaiHardwareManual 10/2011

    Device Connectivity

    Introduction

    This chapter presents the equipment you can connect to the GP unit.

    What Is in This Chapter?

    This chapter contains the following topics:

    Topic PageSystem Design 18

    Accessories 27

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    18/240

    Connectivity

    18

    System Design

    Introduction

    The following diagrams represent equipment you can connect to the GP unit.

    COM1 COM2

    GP-4201T RS-232C or RS-422/RS-485

    (see page 19)

    GP-4201TW RS-232C (see page 19) RS-422/RS-485 (see page 23)

    GP-4203T RS-485 (isolation) (see page 22)

    GP-4301T RS-232C (see page 19) RS-422/RS-485 (see page 23)

    GP-4301TW RS-232C (see page 19) RS-422/RS-485 (see page 23)

    GP-4303T RS-232C (see page 19) RS-485 (isolation)

    (see page 24)

    GP-4401T RS-232C (see page 19) RS-422/RS-485 (see page 23)

    GP-4401WW RS-232C (see page 19) RS-422/RS-485 (see page 23)

    GP-4501T RS-232C (see page 19) RS-422/RS-485 (see page 23)

    GP-4501TW RS-232C (see page 19) RS-422/RS-485 (see page 23)

    GP-4503T RS-232C (see page 19) RS-485 (isolation)

    (see page 24)

    GP-4601T RS-232C (see page 19) RS-422/RS-485 (see page 23)

    GP-4603T RS-232C (see page 19) RS-485 (isolation)

    (see page 24)

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    19/240

    GP4000 Series Hardware Manual

    19

    RUN Mode Peripherals - COM1: RS-232C

    NOTE: For instructions on how to connect to other devices, always refer to the GP-

    Pro EX Device/PLC Connection Manual.

    *1When connecting the CA3-ISO232-01, the COM ports pin 9 setting should be

    VCC. You can define COM port settings in GP-Pro EX or in the GP units offline

    menu.

    *2The RS-232C Isolation Unit corresponds to onlyRS-422/485 (4 wire)

    communication.

    *3The RS-232C Isolation Unit does not correspond to Serial Multilink

    communication.

    GP unit

    Host ControllerPLC etc.

    Serial Interface (COM1:RS-232C mode)

    Serial Interface (COM1:RS-232C mode)

    Serial Interface (COM1:RS-422 mode)

    RS-232C CableCA3-CBL232/5M-01

    Mitsubishi PLC Q-Series Link CableCA3-CBLLNKMQ-01

    Omron PLC SYSMAC Link CableCA3-CBLSYS-01

    Mitsubishi PLC Q-Series Connection Cable

    CA3-CBLQ-01

    Siemens TTY Converter CableCA6-CBLTTY/5M-01

    RS-232C Port

    RS-232C Port

    RS-232C Port

    RS-232C Port

    PG Port

    RS-232C CableCA3-CBL232/5M-01

    Mitsubishi PLC Q-Series Link CableCA3-CBLLNKMQ-01

    Omron PLC SYSMAC Link CableCA3-CBLSYS-01

    Mitsubishi PLC Q-Series Connection Cable

    CA3-CBLQ-01

    Siemens TTY Converter CableCA6-CBLTTY/5M-01

    RS-232C Port

    RS-232C Port

    RS-232C Port

    RS-232C Port

    PG Port

    RS-422 Port

    RS-422 Port

    RS-232CIsolation UnitCA3-ISO232-01*1

    Switch setting:RS-232C

    RS-232CIsolation UnitCA3-ISO232-01*1,2,3

    Switch setting:RS-422

    RS-422 CableCA3-CBL422-01

    COM PortConversion

    Adapter

    CA3-ADPCOM-01 RS-422 Cable(Prepared by user)

    Terminal BlockConversion AdapterCA3-ADPTRM-01

    RS-422 Port

    Mitsubishi PLC A, QnA,

    FX Series' 2 Port Adapter IIGP070-MD11

    2 PortAdapter CablePFXZCBCBMD1

    Programming

    Console Port

    Mitsubishi PLC A, QnA,FX Series' 2 Port Adapter IIGP070-MD11

    2 PortAdapter CableCA3-MDCB11

    Programming

    Console Port

    RS-422 CableCA3-CBL422/5M-01

    RS-422 Terminal BlockConversion AdapterPFXZCBADTM1

    RS-422 Port

    RS-422 Cable(Prepared by user)

    RS-422 PortMulti-Link CablePFXZCBCBML1

    RS-422 PortMulti-Link Cable

    CA3-CBLMLT-01

    Mitsubishi PLCA-Series Connection CableCA3-CBLA-01

    Mitsubishi PLCFX-Series Connection CableCA3-CBLFX/1M-01CA3-CBLFX/5M-01

    Programming

    Console Port

    Programming

    Console Port

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    20/240

    Connectivity

    20

    RUN Mode Peripherals - COM1: RS-232C or RS-422/RS-485

    NOTE: For instructions on how to connect to other devices, always refer to the GP-

    Pro EX Device/PLC Connection Manual.

    GP unit

    Host ControllerPLC etc.

    Serial Interface (COM1:RS-232C mode)

    Serial Interface (COM1:RS-232C mode)

    Serial Interface (COM1:RS-422 mode)

    RS-232C CableCA3-CBL232/5M-01

    Mitsubishi PLC Q-Series Link CableCA3-CBLLNKMQ-01

    Omron PLC SYSMAC Link CableCA3-CBLSYS-01

    Mitsubishi PLC Q-Series Connection CableCA3-CBLQ-01

    Siemens TTY Converter CableCA6-CBLTTY/5M-01

    RS-232C Port

    RS-232C Port

    RS-232C Port

    RS-232C Port

    PG Port

    RS-232C CableCA3-CBL232/5M-01

    Mitsubishi PLC Q-Series Link CableCA3-CBLLNKMQ-01

    Omron PLC SYSMAC Link CableCA3-CBLSYS-01

    Mitsubishi PLC Q-Series Connection CableCA3-CBLQ-01

    Siemens TTY Converter CableCA6-CBLTTY/5M-01

    RS-232C Port

    RS-232C Port

    RS-232C Port

    RS-232C Port

    PG Port

    RS-422 Port

    RS-422 Port

    RS-232C

    Isolation UnitCA3-ISO232-01 *1

    Switch setting:RS-232C

    RS-232CIsolation UnitCA3-ISO232-01 *1,2,3

    Switch setting:RS-422

    RS-422 CableCA3-CBL422-01

    COM PortConversion

    AdapterCA3-ADPCOM-01

    RS-422 Cable(Prepared by user)

    Terminal BlockConversion AdapterCA3-ADPTRM-01

    continued to the next page

    RS-422 Port

    Mitsubishi PLC A, QnA,FX Series' 2 Port Adapter IIGP070-MD11

    2 PortAdapter CablePFXZCBCBMD1

    Programming

    Console Port

    Mitsubishi PLC A, QnA,FX Series' 2 Port Adapter IIGP070-MD11

    2 PortAdapter Cable

    CA3-MDCB11

    Programming

    Console Port

    RS-422 CableCA3-CBL422/5M-01

    RS-422 Terminal Block

    Conversion AdapterPFXZCBADTM1

    RS-422 Port

    RS-422 Cable

    (Prepared by user)

    RS-422 PortMulti-Link CablePFXZCBCBML1

    RS-422 PortMulti-Link Cable

    CA3-CBLMLT-01

    Mitsubishi PLCA-Series Connection CableCA3-CBLA-01

    Mitsubishi PLCFX-Series Connection CableCA3-CBLFX/1M-01CA3-CBLFX/5M-01

    Programming

    Console Port

    Programming

    Console Port

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    21/240

    GP4000 Series Hardware Manual

    21

    *1When connecting the CA3-ISO232-01, the COM ports pin 9 setting should be

    VCC. You can define COM port settings in GP-Pro EX or in the GP units offline

    menu.

    *2The RS-232C Isolation Unit corresponds to onlyRS-422/485 (4 wire)

    communication.

    *3The RS-232C Isolation Unit does not correspond to Serial Multilink

    communication.

    Host ControllerPLC etc.

    Mitsubishi PLCA-Series Connection CableCA3-CBLA-01

    Mitsubishi PLCFX-Series Connection Cable

    CA3-CBLFX/1M-01CA3-CBLFX/5M-01

    MPI CableST03-A2B-MPI21-PFE

    RS-422 Port

    RS-485 Port

    RS-422 Port

    RS-422 Port

    Programming

    Console Port

    ProgrammingConsole Port

    Serial Interface(COM1:RS-422 mode)

    RS-422 CableCA3-CBL422-01

    Mitsubishi PLC A, QnA,FX Series' 2 Port Adapter IIGP070-MD11

    RS-422 CableCA3-CBL422/5M-01

    2 PortAdapter CableCA3-MDCB11

    COM PortConversion

    AdapterCA3-ADPCOM-01

    Programming

    Console Port

    RS-422 Port

    RS-422 Cable(Prepared by user)

    Terminal BlockConversion AdapterCA3-ADPTRM-01

    RS-422 Port

    Mitsubishi PLC A, QnA,FX Series' 2 Port Adapter IIGP070-MD11

    2 PortAdapter CablePFXZCBCBMD1

    Programming

    Console Port

    Multi-Link Cable

    CA3-CBLMLT-01

    Multi-Link CablePFXZCBCBML1

    RS-422 Terminal BlockConversion AdapterPFXZCBADTM1

    RS-422 Port

    RS-422 Cable(Prepared by user)

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    22/240

    Connectivity

    22

    RUN Mode Peripherals - COM1: RS-485 (isolation)

    NOTE: For instructions on how to connect to other devices, always refer to the GP-

    Pro EX Device/PLC Connection Manual.

    GP unit

    Host ControllerPLC etc.

    Serial Interface (COM1: RS-485 (isolation) mode)

    PROFIBUS Cable

    (Prepared by user)

    RS-485 Cable

    (Prepared by user)

    MPI Cable

    CA3-MPI-PG1-PFE

    CA3-MPI-PGN-PFE

    RS-485 (isolation) Port

    RS-485 (isolation) Port

    RS-485 (isolation) Port

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    23/240

    GP4000 Series Hardware Manual

    23

    RUN Mode Peripherals - COM2: RS-422/RS-485

    NOTE: For instructions on how to connect to other devices, always refer to the GP-

    Pro EX Device/PLC Connection Manual.

    Host ControllerPLC etc.

    Mitsubishi PLCA-Series Connection CableCA3-CBLA-01

    Mitsubishi PLCFX-Series Connection CableCA3-CBLFX/1M-01CA3-CBLFX/5M-01

    MPI CableST03-A2B-MPI21-PFE

    RS-422 Port

    RS-485 Port

    RS-422 Port

    RS-422 Port

    Programming

    Console Port

    Programming

    Console Port

    Serial Interface(COM2:RS-422 mode)

    RS-422 CableCA3-CBL422-01

    Mitsubishi PLC A, QnA,FX Series' 2 Port Adapter IIGP070-MD11

    RS-422 CableCA3-CBL422/5M-01

    2 PortAdapter CableCA3-MDCB11

    COM PortConversion

    AdapterCA3-ADPCOM-01

    Programming

    Console Port

    RS-422 Port

    RS-422 Cable(Prepared by user)

    Terminal BlockConversion AdapterCA3-ADPTRM-01

    RS-422 Port

    Mitsubishi PLC A, QnA,FX Series' 2 Port Adapter IIGP070-MD11

    2 PortAdapter CablePFXZCBCBMD1

    Programming

    Console Port

    Multi-Link CableCA3-CBLMLT-01

    Multi-Link Cable

    PFXZCBCBML1

    GP unit

    RS-422 Terminal BlockConversion AdapterPFXZCBADTM1

    RS-422 Port

    RS-422 Cable(Prepared by user)

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    24/240

    Connectivity

    24

    RUN Mode Peripherals - COM2: RS-485 (isolation)

    NOTE: For instructions on how to connect to other devices, always refer to the GP-

    Pro EX Device/PLC Connection Manual.

    RUN Mode Peripherals - Ethernet Communication

    GP unit

    Host ControllerPLC etc.

    Serial Interface (COM2: RS-485 (isolation) mode)

    PROFIBUS Cable(Prepared by user)

    RS-485 Cable(Prepared by user)

    MPI Cable CA3-MPI-PG1-PFE CA3-MPI-PGN-PFE

    RS-485 (isolation) Port

    RS-485 (isolation) Port

    RS-485 (isolation) Port

    GP unit

    Ethernet Interface

    (10BASE-T/100BASE-TX)

    Twisted Pair Cable

    (commercial type)

    Hub

    (commercial type)

    To an Ethernet Network

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    25/240

    GP4000 Series Hardware Manual

    25

    RUN Mode Peripherals - USB Type A / min i-B Interface

    *1For supported models, refer to Pro-faces support site Otasuke Pro!

    (http://www.pro-face.com/otasuke/). You can connect to this site in GP-Pro EX: fromthe [Help (H)] menu, click [Connect to Support Site Otasuke Pro! (C)].

    GP unit

    USB (Type A) Interface

    Bar-Code Reader*1

    (Commercial type)

    Printer*1

    (Commercial type)

    External Device (RS-422/485)

    USB Cable

    FP-US00 or

    Commercial type

    USB-to-IEEE1284

    Conversion Cable

    (Commercial type)

    USB-Serial (RS-232C)Conversion Cable

    CA6-USB232-01

    USB/RS-422/485

    Conversion Adapter

    PFXZCBCBCVUSR41

    EZ Illuminated Switch

    PFXZCCEUSG1

    EZ Fingerprint Recognition UnitPFXZCCEUSS1

    USB Hub

    (Commercial type)

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    26/240

    Connectivity

    26

    Edit Mode Peripherals

    *1For supported models, refer to Pro-faces support site Otasuke Pro!

    (http://www.pro-face.com/otasuke/). You can connect to this site in GP-Pro EX: from

    the [Help (H)] menu, click [Connect to Support Site Otasuke Pro! (C)]

    *2There are certain types and models of PCs that are not supported. Please refer

    to the GP-Pro EX Reference Manual for the softwares operating environment

    requirements.

    GP unit

    USB (Type A) Interface

    Ethernet Interface

    (10BASE-T/100BASE-TX)

    To an Ethernet Network

    USB Memory Strage*1

    (Commercial type)

    Modem*1

    (Commercial type)

    USB Port

    Personal Computer

    (Commercial type) *2Screen Editor&

    Logic Program Software

    GP-Pro EX

    USB Transfer Cable

    CA3-USBCB-01

    USB (mini B) Interface

    SD Card Interface

    USB Port

    USB Port

    SD Card Slot

    USB Data Transfer Cable

    (USB A/mini-B)

    ZC9USCBMB1

    or Commercial type

    USB Transfer Cable

    (USB A/mini-B)

    ZC9USCBMB1 or

    Commercial Type

    USB Panel-mount

    Extension Cable

    (USB mini-B)

    ZC9USEXMB1

    SD Memory Card (4GB)

    PFXZCBSD4GC41

    or Commercial type

    SD Card Reader

    (Commercial type)

    SD Memory Card (4GB)

    PFXZCBSD4GC41

    or Commercial type

    USB-Serial (RS-232C)

    Conversion Cable

    CA6-USB232-01

    Telephone lines

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    27/240

    GP4000 Series Hardware Manual

    27

    Accessor ies

    Serial Interface Items

    Product Name Product Number Description

    RS-232C Cable (5m) CA3-CBL232/5M-01 Connects a host controller to the GP unit.(RS-232C)

    RS-422 Cable (5m) CA3-CBL422/5M-01 Connects a host controller to the GP unit.

    (RS-422 / Socket Type)

    Mitsubishi PLC Q-Series Link

    Cable (5m)

    CA3-CBLLNKMQ-01 Connects Mitsubishi PLC Q-Series (or other

    host controller) to the GP unit. (RS-232C)

    Omron PLC SYSMAC Link Cable

    (5m)

    CA3-CBLSYS-01 Connects Omron PLC SYSMAC Series unit

    (or other host controller) to the GP unit. (RS-

    232C)

    Mitsubishi PLC A-Series

    Connection Cable (5m)

    CA3-CBLA-01 Connects Mitsubishi PLC A or QnA Series

    programming console I/F to GP unit.

    (Simultaneous use of programming consolesis not possible.)

    Mitsubishi PLC Q-Series

    Connection Cable (5m)

    CA3-CBLQ-01 Connects Mitsubishi PLC Q-Series

    programming console I/F to GP unit.

    (Simultaneous use of programming consoles

    is not possible.)

    Mitsubishi PLC FX-Series

    Connection Cable

    CA3-CBLFX/1M-01 (1m)

    CA3-CBLFX/5M-01 (5m)

    Connects Mitsubishi PLC FX-Series

    programming console I/F and GP unit.

    (Simultaneous use of programming consoles

    is not possible.)

    RS-422 Cable (5m) CA3-CBL422-01 Connects a host controller to the GP unit.

    (RS-422 / Plug Type)

    2 Port Adapter Cable (5m) CA3-MDCB11 Connects Mitsubishi PLC to the GP unit using

    2 port adapter II (RS-422). Please see "GP-

    Pro EX Device/PLC Connection Manual" for

    how to connect the cable.

    PFXZCBCBMD1 Connects Mitsubishi PLC directly to the GP

    unit (D-sub 9 pin plug) using 2 port adapter II

    (RS-422).

    Mitsubishi PLC A, QnA, FX Series

    2 Port Adapter II

    GP070-MD11 Enables simultaneous use of a GP unit and a

    Mitsubishi PLC A, QnA, or FX Series

    peripheral device.

    Terminal Block Conversion

    Adapter

    CA3-ADPTRM-01 Connects output from a GP units Serial

    Interface (D-sub 9 pin plug) directly with anRS-422 terminal block.

    RS-422 Terminal Block

    Conversion Adapter

    PFXZCBADTM1 Connects output from a GP units Serial

    Interface (D-sub 9 pin plug) directly with an

    RS-422 terminal block.

    COM Port Conversion Adapter CA3-ADPCOM-01 Connects optional RS-422 communication

    items to GP units Serial Interface.

    Multi-Link Cable (5m) CA3-CBLMLT-01 Connects a host controller to the GP unit for

    multi-link (n:1) communication. Please see

    "GP-Pro EX Device/PLC Connection Manual"

    for how to connect the cable.

    PFXZCBCBML1 Connects a host controller directly to the GPunit (D-sub 9 pin plug) for multi-link (n:1)

    communication.

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    28/240

    Connectivity

    28

    USB Interface Items

    *1For supported models, refer to Pro-faces support site Otasuke Pro!

    (http://www.proface.com/otasuke/). You can connect to this site in GP-Pro EX: from

    the [Help (H)] menu, click [Connect].

    9-pin-to-25-pin RS-232C

    Conversion Cable (0.2m)

    CA3-CBLCBT232-01 Connects a standard RS-232C cable (D-Sub

    25-pin socket) to the GP unit (D-sub 9-pin

    plug).

    RS-422 9/25-pin Conversion

    Cable (0.2m)

    PFXZCBCBCVR41 Connects a standard RS-422 cable (D-sub

    25-pin socket) to the GP unit (D-sub 9 pinplug).

    Siemens TTY Converter Cable

    (5m)

    CA6-CBLTTY/5M-01 Connects Siemens PLC S5 Series to the GP

    unit.

    MPI Cable (3.5m) ST03-A2B-MPI21-PFE

    CA3-MPI-PG1-PFE

    CA3-MPI-PGN-PFE

    Connects a host controller to the GP unit for

    MPI communication.

    RS-232C Isolation Unit CA3-ISO232-01 Connects a host controller to the GP unit and

    provides isolation. (RS-232C and RS-422 are

    switchable.)

    Product Name Product Number Description

    Product Name Product Number Description

    USB Transfer Cable (2m) CA3-USBCB-01 Downloads project data created with the

    Screen Editor & Logic Program Software

    via the GP units USB I/F.

    USB Cable (5m) FP-US00 Connects a USB printer. (TYPE-B)

    USB Front Cable (1m) CA5-USBEXT-01 Extension cable attaching USB interface to

    front panel.

    USB-Serial (RS-232C) Conversion

    Cable (0.5m)

    CA6-USB232-01 Cable for converting a GP units USB

    interface into a serial interface (RS-232C).

    Allows connection to modems*1or bar codereaders*1that support RS-232C.

    USB/RS-422/485 Conversion

    Adapter

    PFXZCBCBCVUSR41 Adapter for connecting a GP unit (USB

    Type A) with an external device (RS-

    422/RS-485).

    USB Transfer Cable (USB Type

    A/mini-B) (1.8 m)

    ZC9USCBMB1 Cable for transferring screen data from a

    PC (USB Type A) to the GP unit (USB mini-

    B).

    USB Panel-mount Extension Cable

    (USB mini-B) (1 m)

    ZC9USEXMB1 Extension cable that attaches to the USB

    (mini-B) interface on the front side of the

    operation panel.

    USB Clamp mini-B (1 port) ZC9USCLMB1 Clamp to prevent disconnection of USBcable (USB/mini-B, 1 port, 5 clamps/set)

    EZ Illuminated Switch PFXZCCEUSG1 A unit of 5 illuminated switches with

    multiple color LED easily connected with

    GP unit via USB.

    EZ Fingerprint Recognition Unit PFXZCCEUSS1 Fingerprint recognition unit easily

    connected with GP unit via USB.

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    29/240

    GP4000 Series Hardware Manual

    29

    SD Card Items

    Option Items

    *1Please use "12.1-inch Environment Cover" for GP-4501TW (10.4-inch model).

    *2These options cannot be used with the rear mount model. For information on the

    option items dedicated for use with the rear mount model, refer to Option Items /

    Maintenance Options (see page 175).

    Product Name Product Number Description

    SD Memory Card (4 GB) PFXZCBSD4GC41 SD Memory Card (4 GB, CLASS4)

    Product Name Product Number Corresponding GP

    unit

    Description

    12.1-inch Screen Protection Sheet CA7-DFS12-01 GP-4600 Series*2 Disposable, dirt-resistant sheet

    for the GP unit screen (5

    sheets/set)10.4-inch Screen Protection Sheet PFXZCBDS101 GP-4500 Series*2

    7.5-inch Screen Protection Sheet PFXZCBDS71 GP-4401T*2

    7.0-inch Wide Screen Protection

    Sheet

    PFXZCBDS72 GP-4401WW

    5.7-inch Screen Protection Sheet PFXZCBDS61 GP-4300 Series*2

    3.5-inch Screen Protection Sheet CA6-DFS4-01 GP-4200 Series

    12.1-inch Environment Cover PFXZCBOP121 GP-4600 Series*2

    GP-4501TW

    Disposable, environment cover

    for the GP unit screen (1

    sheet/set)10.4-inch Environment Cover PFXZCBOP101 GP-4500 Series*1*2

    7.0/7.5-inch Environment Cover PFXZCBOP71 GP-4400 Series*2

    5.7-inch Environment Cover PFXZCBOP61 GP-4300 Series*2

    3.5-inch Environment Cover PFXZCBOP41 GP-4200 Series

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    30/240

    Connectivity

    30

    Maintenance Options

    *1Does not include GP-4100 Series, GP-4201TM, or GP-4301TM.

    *2These options cannot be used with the rear mount model. For information on the

    option items dedicated for use with the rear mount model, refer to Option Items /

    Maintenance Options (see page 175).

    Product Name Product Number Corresponding GP

    unit

    Description

    Installation Fastener PFXZCBAF1 GP4000 Series*1*2 Used to install the GP unit into a

    solid panel (4 pieces/ set)

    10.4-inch TW models & 12.1-inch

    Installation Gasket

    PFXZCBWG121 GP-4600 Series*2

    GP-4501TW

    Provides dust and moisture

    resistance when GP unit is

    installed into a solid panel (1

    piece)10.4-inch Installation Gasket PFXZCBWG101 GP-4500 Series*2

    (except GP-

    4501TW)

    7.0-inch Wide & 7.5-inch Installation

    Gasket

    PFXZCBWG71 GP-4400 Series*2

    5.7-inch Installation Gasket PFXZCBWG61 GP-4300 Series*2

    3.5-inch Installation Gasket PFXZCBWG41 GP-4200 Series

    USB Clamp TypeA (1 port) PFXZCBCLUSA1 GP4000 Series*1

    Clamp to prevent disconnectionof USB cable (USB/A, 1 port, 5

    clamps/set)

    DC Power Supply Connector PFXZCBCNDC1 GP-4400 Series

    GP-4300 Series

    GP-4200 Series

    Connector to connect DC power

    supply cables (5 pcs/set)

    DC Power Supply Connector (Right-

    angle)

    PFXZCBCNDC2 GP-4600 Series

    GP-4500 Series

    Right-angle connector to

    connect DC power supply

    cables (5 pcs/set)

    Battery for Memory Backup PFXZCBBT1 GP-4600 Series

    GP-4500 Series

    GP-4400 Series

    GP-4300 Series(except GP-

    4301TW)

    Primary battery for memory and

    time data backup (1)

    Panel Cutout Adapter CA4-ATM10-01 GP-4500 Series

    (except Rear Mount

    Models)

    Panel cutout adapter for

    mounting GP-4500 Series in

    cutout for GP-2500/2600 series.

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    31/240

    31

    GP4000 Series Hardware Manual

    3

    GP4000Series Hardware anual

    Parts/Functions

    KanpaiHardwareManual 10/2011

    Parts Identification and Functions

    Parts Identification and Functions

    GP-4200 Series Parts Identif ication

    Side GP-4200 Series

    Front

    Rear

    Bottom

    Part Name Description

    A Status LED *1

    B USB (mini-B) Interface Conforms to USB2.0 (mini-B) x 1.

    Communication Distance: 5 m (16.4 ft) or

    less.

    A

    B C

    GP-4201T/4203T

    GP-4201TW

    F E D

    F G D

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    32/240

    Parts/Functions

    32

    *1Status LED operations are as shown below:

    *2Ethernet LED operations are as shown below.

    C USB (Type A) Interface Conforms to USB2.0 (Type A) x 1. Power

    supply voltage: 5Vdc+/-5%. Output Current:

    500 mA or less. Maximum communication

    distance: 5 m (16.4 ft).

    D Serial Interface (COM1) GP-4201T: RS-232C/422/485 SerialInterface. (You can switch the

    communication method via software.)

    Connector: D-Sub 9 pin (plug) x 1.

    GP-4201TW: RS-232C Serial Interface.

    Connector: D-Sub 9 pin (plug) x 1.

    GP-4203T: RS-485 (isolation) Serial

    Interface. Connector: D-Sub 9 pin (socket)

    x 1.

    E Ethernet Interface*2 Ethernet transmission interface (10BASE-

    T/100BASE-TX)

    Connector: Modular jack (RJ-45) x 1.

    Ethernet Interface is not attached to GP-

    4201TW.

    F Power Plug Connector -

    G Serial Interface (COM2) GP-4201TW: RS-422/485 Serial Interface.

    Connector: D-Sub 9 pin (plug) x 1.

    Color Indicator Operation Mode

    (Drawing)

    Logic execution mode

    (when logic is enabled)

    Green ON Offline

    In operation RUN

    Flashing In operation STOP

    Orange Flashing Software starting up.

    Red ON Power is turned ON.

    Flashing In operation Major Error

    LED fade

    (Green)

    ON The GP units "Backlight Control" is set to Standby Mode

    and the screen has gone blank.

    - OFF Power is turned OFF.

    Color Indicator Description

    Green (Active) Flashing Data transmission is occurring.

    OFF No data transmission.

    Green (Link) ON Data transmission is available in

    10BASE-T/100BASE-TX.

    OFF No connection or subsequent

    transmission failure.

    Part Name Description

    Link

    Active

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    33/240

    GP4000 Series Hardware Manual

    33

    GP-4300 Series Parts Identif ication

    NOTE:

    If you are using the rear mount model, refer to Parts Identification and Functions

    (see page 176).

    Side GP-4300 Series

    Front

    Right

    Rear

    Bottom

    Part Name Description

    A Status LED *1

    B USB (Type A) Interface Conforms to USB2.0 (Type A) x 1. Power

    supply voltage: 5Vdc+/-5%. Output Current:

    500 mA or less. Maximum communication

    distance: 5 m (16.4 ft).

    C Serial Interface (COM1) RS-232C Serial Interface. Connector: D-Sub 9

    pin (plug) x 1.

    A

    B

    C

    D

    E F

    E G H I

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    34/240

    Parts/Functions

    34

    *1Status LED operations are as shown below:

    *2SD Card Access LED operations are as shown below.

    *3Ethernet LED operations are as shown below.

    D Serial Interface (COM2) GP-4301T/GP-4301TW: RS-422/485 Serial

    Interface. Connector: D-Sub 9 pin (plug) x 1.

    GP-4303T: RS-485 (isolation) Serial Interface.

    Connector: D-Sub 9 pin (socket) x 1.

    E Power Plug Connector -F SD Card Access LED *2 This lamp lights up when SD Card is inserted.

    NOTE: Do not remove or insert the SD Card

    when the LED lamp is on. Doing so may

    damage data on the SD Card.

    G SD Card Interface

    Cover/Replacement Battery

    Insertion Cover

    For information on how to open the cover, and

    insert or remove the SD Card, refer to SD Card

    Insertion / Removal(see page 150).

    For information on how to open the cover and

    replace the battery, refer to Replacing the

    Primary Battery(see page 168).

    NOTE: This cover is not on GP-4301TW

    H USB (mini-B) Interface Conforms to USB2.0 (mini-B) x 1.Communication Distance: 5 m (16.4 ft) or less.

    I Ethernet Interface *3 Ethernet transmission interface (10BASE-

    T/100BASE-TX)

    Connector: Modular jack (RJ-45) x 1.

    Color Indicator Operation Mode

    (Drawing)

    Logic execution mode

    (when logic is enabled)

    Green ON Offline

    In operation RUN

    Flashing In operation STOP

    Orange Flashing Software starting up.

    Red ON Power is turned ON.

    Flashing In operation Major Error

    LED fade

    (Green)

    ON The GP units "Backlight Control" is set to Standby Mode

    and the screen has gone blank.

    - OFF Power is turned OFF.

    Color Indicator Description

    Green (Active) ON The SD Card is inserted.

    OFF The SD Card is not inserted or is not

    being accessed.

    Color Indicator Description

    Green (Active) Flashing Data transmission is occurring.

    OFF No data transmission.

    Green (Link) ON Data transmission is available in

    10BASE-T/100BASE-TX.

    OFF No connection or subsequent

    transmission failure.

    Part Name Description

    Link

    Active

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    35/240

    GP4000 Series Hardware Manual

    35

    GP-4400 Series Parts Identif ication

    NOTE:

    If you are using the rear mount model, refer to Parts Identification and Functions

    (see page 176).

    Side GP-4400 Series

    Front

    Right

    Rear

    A

    A

    GP-4401T

    GP-4401WW

    B

    C

    D

    E F

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    36/240

    Parts/Functions

    36

    *1Status LED operations are as shown below:

    Bottom

    Part Name Description

    A Status LED *1

    B USB (Type A) Interface Conforms to USB2.0 (Type A) x 1. Power

    supply voltage: 5Vdc+/-5%. Output Current:

    500 mA or less. Maximum communication

    distance: 5 m (16.4 ft).

    C Serial Interface (COM1) RS-232C Serial Interface. Connector: D-Sub 9

    pin (plug) x 1.

    D Serial Interface (COM2) RS-422/485 Serial Interface. Connector: D-

    Sub 9 pin (plug) x 1.

    E Power Plug Connector -

    F SD Card Access LED *2 This lamp lights up when SD Card is inserted.

    NOTE: Do not remove or insert the SD Card

    when the LED lamp is on. Doing so may

    damage data on the SD Card.

    G SD Card Interface

    Cover/Replacement Battery

    Insertion Cover

    For information on how to open the cover, and

    insert or remove the SD Card, refer to SD Card

    Insertion / Removal(see page 150).

    For information on how to open the cover andreplace the battery, refer to Replacing the

    Primary Battery(see page 168).

    H USB (mini-B) Interface Conforms to USB2.0 (mini-B) x 1.

    Communication Distance: 5 m (16.4 ft) or less.

    I Ethernet Interface *3 Ethernet transmission interface (10BASE-

    T/100BASE-TX)

    Connector: Modular jack (RJ-45) x 1.

    Color Indicator Operation Mode

    (Drawing)

    Logic execution mode

    (when logic is enabled)

    Green ON Offline

    In operation RUN

    Flashing In operation STOP

    Orange Flashing Software starting up.

    Red ON Power is turned ON.

    Flashing In operation Major Error

    LED fade

    (Green)

    ON The GP units "Backlight Control" is set to Standby Mode

    and the screen has gone blank.

    - OFF Power is turned OFF.

    Side GP-4400 Series

    E G H I

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    37/240

    GP4000 Series Hardware Manual

    37

    *2SD Card Access LED operations are as shown below.

    *3Ethernet LED operations are as shown below.

    Color Indicator Description

    Green (Active) ON The SD Card is inserted.

    OFF The SD Card is not inserted or is not

    being accessed.

    Color Indicator Description

    Green (Active) Flashing Data transmission is occurring.

    OFF No data transmission.

    Green (Link) ON Data transmission is available in

    10BASE-T/100BASE-TX.

    OFF No connection or subsequent

    transmission failure.

    Link

    Active

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    38/240

    Parts/Functions

    38

    GP-4500 Series Parts Ident ification

    NOTE:

    If you are using the rear mount model, refer to Parts Identification and Functions

    (see page 176).

    Side GP-4500 Series

    Front

    Rear

    Bottom

    Part Name Description

    A Status LED *1

    B Power Input Terminal Block

    (AC model), Power Plug

    Connector (DC model)

    -

    C SD Card Access LED *2 This lamp lights up when SD Card is inserted.

    NOTE: Do not remove or insert the SD Card

    when the LED lamp is on. Doing so may

    damage data on the SD Card.

    D Ethernet Interface *3 Ethernet transmission interface (10BASE-

    T/100BASE-TX)

    Connector: Modular jack (RJ-45) x 1.

    E USB (mini-B) Interface Conforms to USB2.0 (mini-B) x 1.Communication Distance: 5 m (16.4 ft) or less.

    A

    B C

    B F E D

    I H G

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    39/240

    GP4000 Series Hardware Manual

    39

    *1Status LED operations are as shown below:

    *2SD Card Access LED operations are as shown below.

    *3Ethernet LED operations are as shown below.

    F SD Card Interface

    Cover/Replacement Battery

    Insertion Cover

    For information on how to open the cover, and

    insert or remove the SD Card, refer to SD Card

    Insertion/Removal(see page 150).

    For information on how to open the cover and

    replace the battery, refer to Replacing the

    Primary Battery(see page 168).

    G Serial Interface (COM2) GP-4501T/GP-4501TW: RS-422/485 Serial

    Interface. Connector: D-Sub 9 pin (plug) x 1.

    GP-4503T: RS-485 (isolation) Serial Interface.

    Connector: D-Sub 9 pin (socket) x 1.

    H Serial Interface (COM1) RS-232C Serial Interface.

    Connector: D-Sub 9 pin (plug) x 1.

    I USB (Type A) Interface Conforms to USB2.0 (Type A) x 1. Power

    supply voltage: 5Vdc+/-5%. Output Current:

    500 mA or less. Maximum communication

    distance: 5 m (16.4 ft).

    Color Indicator Operation Mode

    (Drawing)

    Logic execution mode

    (when logic is enabled)

    Green ON Offline

    In operation RUN

    Flashing In operation STOP

    Orange Flashing Software starting up.

    Red ON Power is turned ON.

    Flashing In operation Major ErrorLED fade

    (Green)

    ON The GP units "Backlight Control" is set to Standby Mode

    and the screen has gone blank.

    - OFF Power is turned OFF.

    Color Indicator Description

    Green (Active) ON The SD Card is inserted.

    OFF The SD Card is not inserted or is not

    being accessed.

    Color Indicator Description

    Green (Active) Flashing Data transmission is occurring.

    OFF No data transmission.

    Green (Link) ON Data transmission is available in

    10BASE-T/100BASE-TX.

    OFF No connection or subsequent

    transmission failure.

    Part Name Description

    Link

    Active

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    40/240

    Parts/Functions

    40

    GP-4600 Series Parts Ident ification

    NOTE:

    If you are using the rear mount model, refer to Parts Identification and Functions

    (see page 176).

    Side GP-4600 Series

    Front

    Rear

    Bottom

    Part Name Description

    A Status LED *1

    B Power Input Terminal Block

    (AC model), Power Plug

    Connector (DC model)

    -

    C SD Card Access LED *2 This lamp lights up when SD Card is inserted.

    NOTE: Do not remove or insert the SD Card

    when the LED lamp is on. Doing so may

    damage data on the SD Card.

    D Ethernet Interface *3 Ethernet transmission interface (10BASE-

    T/100BASE-TX)

    Connector: Modular jack (RJ-45) x 1.

    E USB (mini-B) Interface Conforms to USB2.0 (mini-B) x 1.

    Communication Distance: 5 m (16.4 ft) or less.

    A

    B C

    B I H G

    F E D

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    41/240

    GP4000 Series Hardware Manual

    41

    *1Status LED operations are as shown below:

    *2SD Card Access LED operations are as shown below.

    *3Ethernet LED operations are as shown below.

    F SD Card Interface

    Cover/Replacement Battery

    Insertion Cover

    For information on how to open the cover, and

    insert or remove the SD Card, refer to SD Card

    Insertion/Removal(see page 150).

    For information on how to open the cover and

    replace the battery, refer to Replacing the

    Primary Battery(see page 168).

    G Serial Interface (COM2) GP-4601T: RS-422/485 Serial Interface.

    Connector: D-Sub 9 pin (plug) x 1.

    GP-4603T: RS-485 (isolation) Serial Interface.

    Connector: D-Sub 9 pin (socket) x 1.

    H Serial Interface (COM1) RS-232C Serial Interface. Connector: D-Sub 9

    pin (plug) x 1.

    I USB (Type A) Interface Conforms to USB2.0 (Type A) x 1.

    Power supply voltage: 5Vdc+/-5%.

    Output Current: 500 mA or less.

    Maximum communication distance: 5 m (16.4

    ft).

    Color Indicator Operation Mode

    (Drawing)

    Logic execution mode

    (when logic is enabled)

    Green ON Offline

    In operation RUN

    Flashing In operation STOP

    Orange Flashing Software starting up.

    Red ON Power is turned ON.

    Flashing In operation Major Error

    LED fade

    (Green)

    ON The GP units "Backlight Control" is set to Standby Mode

    and the screen has gone blank.

    - OFF Power is turned OFF.

    Color Indicator Description

    Green (Active) ON The SD Card is inserted.

    OFF The SD Card is not inserted or is not

    being accessed.

    Color Indicator Description

    Green (Active) Flashing Data transmission is occurring.

    OFF No data transmission.

    Green (Link) ON Data transmission is available in

    10BASE-T/100BASE-TX.

    OFF No connection or subsequent

    transmission failure.

    Part Name Description

    Link

    Active

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    42/240

    Parts/Functions

    42

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    43/240

    43

    GP4000 Series Hardware Manual

    4

    GP4000Series Hardware anual

    Specifications

    KanpaiHardwareManual 10/2011

    Specifications

    Overview

    This chapter presents the GP unit specifications.

    What Is in This Chapter?

    This chapter contains the following sections:

    Section Topic Page4.1 GP-4200 Series 44

    4.2 GP-4300 Series 64

    4.3 GP-4400 Series 82

    4.4 GP-4500 Series 97

    4.5 GP-4600 Series 117

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    44/240

    Specifications

    44

    4.1 GP-4200 Series

    What Is in This Section?

    This section contains the following topics:

    Topic Page

    Electrical Specifications 45

    Environmental Specifications 46

    Structural Specifications 47

    Display Specifications 49

    Memory, Clock, and Touch Panel 50

    Interface Specifications 52

    Specifications of Serial Interface COM1 53

    Specifications of Serial Interface COM2 57

    Dimensions 58

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    45/240

    GP4000 Series Hardware Manual

    45

    Electrical Specifications

    PowerSupply

    Rated Input Voltage 24 Vdc

    Input Voltage Limits 19.2...28.8 Vdc

    Voltage Drop 2 ms or less

    Power Consumption 9.6 W or less

    When power is not supplied to

    external devices

    5.2 W or less

    Backlight OFF (Standby Mode) 4.2 W or less

    Backlight Dimmed (Brightness:

    20%)

    4.3 W or less

    In-Rush Current 30 A or less

    Voltage Endurance 1,000 Vac 20 mA for 1 minute

    (between charging and FGterminals)

    Insulation Resistance 500 Vdc, 10 Mor more

    (between charging and FG

    terminals)

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    46/240

    Specifications

    46

    Environmental Specifications

    Ai r qual ity requirements

    Do not operate or store the panel where chemicals evaporate, or where chemicals

    are present in the air:

    Corrosive chemicals: Acids, alkalines, liquids containing salt.

    Flammable chemicals: Organic solvents.

    PhysicalEnvironment

    Surrounding Air

    Temperature

    0...50C (32...122F)

    Storage Temperature -20...60C (-4...140F)

    Surrounding Air and

    Storage Humidity

    10%...90% RH (Non condensing, wet bulb

    temperature 39 C [102.2 F] or less)

    Dust 0.1 mg/m3(10-7oz/ft3) or less (non-conductive

    levels)

    Pollution Degree For use in Pollution Degree 2 environment

    Corrosive Gases Free of corrosive gases

    Atmospheric Pressure

    (Operating Altitude)

    800...1,114 hPa (2,000 m [6,561 ft] or lower)

    MechanicalEnvironmen

    tVibration Resistance IEC/EN 61131-2 compliant

    5...9 Hz Single amplitude 3.5 mm (0.14 in.)

    9...150 Hz Fixed acceleration: 9.8 m/s2

    X, Y, Z directions for 10 cycles (approx. 100 min.)

    Concussion Resistance IEC/EN 61131-2 compliant

    147 m/s2, X, Y, Z directions for 3 times

    ElectricalEn

    vironment

    Noise immunity Noise Voltage: 1,000 Vp-p

    Pulse Width: 1 s

    Rise Time: 1 ns

    Electrostatic DischargeImmunity

    Contact Discharge Method: 6 kV (IEC/EN 61000-4-2 Level 3)

    CAUTIONINOPERATIVE EQUIPMENT

    Do not allow water, liquids, metal, and wiring fragments to enter the panel case.

    Failure to follow these instructions can result in in jury or equipment damage.

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    47/240

    GP4000 Series Hardware Manual

    47

    Structural Specifications

    *1The front face of the GP unit, installed in a solid panel, has been tested using

    conditions equivalent to the standards shown in the specification. Even though the

    GP units level of resistance is equivalent to these standards, oils that should have

    no effect on the GP unit can possibly harm the panel. This can occur in areas where

    either vaporized oils are present, or where low viscosity cutting oils are allowed to

    adhere to the panel for long periods of time. If the GP units front face protection

    sheet peels off, these conditions can lead to the ingress of oil into the GP unit and

    separate protection measures are suggested.

    Also, if non-approved oils are present, they may cause deformation or corrosion of

    the front panels plastic cover. Therefore, prior to installing the GP unit, be sure to

    confirm the type of conditions that will be present in the GP units operating

    environment. If the installation gasket is used for a long period of time, or if the GP

    unit and its gasket are removed from the panel, the original level of protection cannot

    be kept. To maintain the original protection level, be sure to replace the installation

    gasket regularly.

    *2For dimensional tolerance, everything +1/-0 mm (+0.04/-0 in.) and R in angle are

    below R3 (R0.12 in.)

    *3Even if the installation wall thickness is within the recommended range for the

    Panel Cut Dimensions, depending on walls material, size, and installation locationof the GP unit and other devices, the installation wall could warp. To prevent

    warping, the installation surface may need to be strengthened.

    The front face of the panel, installed in a solid panel, has been tested using

    conditions equivalent to the standards shown in the specification.

    Grounding Functional grounding: Grounding resistance

    of 100, 2mm2(AWG 14) or thicker wire, oryour countrys applicable standard. (Same

    for FG and SG terminals)

    Cooling Method Natural air circulation

    Structure *1 IP65F NEMA #250 TYPE 4X/13 (on the front

    panel when properly installed in an

    enclosure)

    External Dimensions W132 x H106 x D42 mm (W5.2 x H4.17 x

    D1.65 in.)

    Panel Cut Dimensions W118.5 x H92.5 mm (W4.67 x H3.64 in.)*2

    Panel thickness area: 1.6...5 mm (0.06...0.2

    in)*3

    Weight 0.4 kg (0.9 lb) or less (main unit only)

    CAUTIONEQUIPMENT DAMAGE

    Ensure that the panel is not in permanent and direct contact with oils.

    Failure to follow these instructions can result in injury or equipment damage.

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    48/240

    Specifications

    48

    NOTICE

    STORAGE AND OPERATION OUTSIDE OF SPECIFICATIONS

    Store the panel in areas where temperatures are within the panels

    specifications.

    Do not restrict or block the panels rear-face ventilation slots.

    Failure to follow these instructions can result in equipment damage.

    NOTICE

    GASKET AGING

    Inspect the gasket periodically as required by your operating environment to

    keep the initial IP level.

    Change the gasket at least once a year, or as soon as scratches or dirt become

    visible.

    Failure to follow these instructions can result in equipment damage.

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    49/240

    GP4000 Series Hardware Manual

    49

    Display Specifications

    *1Please refer to the GP-Pro EX Reference Manual for details on font types and

    character codes.

    *2You can set up other font sizes using the software.

    GP-4201T / GP-4203T GP-4201TW

    Display Type TFT Color LCD

    Display Size 3.5

    Resolution 320 x 240 pixels (QVGA)

    Effective Display Area W70.56 x H52.92 mm (W2.78 x H2.08 in.)

    Display Colors 65,536 colors (No blink) / 16,384 colors (Blink)

    Backlight White LED (Not user replaceable. When

    replacement is required, contact your local

    distributor.)

    Backlight Service Life 50,000 hours or more (continuous operation at 25 C

    [77 F] before backlight brightness decreased to

    50%)Brightness Control 16 levels (Adjusted with

    touch panel or software)

    8 levels (Adjusted with

    touch panel or software)

    Language Fonts*1 Japanese, ASCII, Chinese (Simplified), Chinese

    (Traditional), Korean, Cyrillic, Thai

    Character Sizes Standard font: 8 x 8, 8 x 16, 16 x 16 and 32 x 32 pixel

    fonts

    Stroke font: 6...127 pixel fonts

    Image font: 8...72 pixel fonts

    Font Sizes Standard font: You can expand width up to 8 times,

    and expand height up to 8 times.*2

    Text 8 x 8 pixels 40 characters per row x 30 rows

    8 x 16 pixels 40 characters per row x 15 rows

    16 x 16 pixels 20 characters per row x 15 rows

    32 x 32 pixels 10 characters per row x 7 rows

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    50/240

    Specifications

    50

    Memory, Clock, and Touch Panel

    Memory

    *1Capacity available for user application.

    *2Up to 60,000 steps can be converted in software. However, this reduces

    application memory capacity for screen data by 1 MB.

    NOTE:

    When the message "RAAA051 Low battery" is displayed, supply power to the GP

    unit and fully charge the battery. In 24 hours the battery charges to a level that

    allows backup operation. Completing a full charge requires about 120 hours (5days).

    The lithium batterys lifetime is: 10 years when the batterys ambient temperature

    is 40 C (104 F) or less, 4.1 years when the batterys ambient temperature is 50

    C (122 F) or less, and 1.5 years when the batterys ambient temperature is 60

    C (140 F) or less.

    When used for backup:

    Approximately 100 days, with a fully charged battery.

    Approximately 6 days, with a half-charged battery.

    Clock

    65 seconds per month (deviation at room temperature and power is OFF).Variations in operating conditions and battery life can cause clock deviations from -

    380 to +90 seconds per month.

    For systems where this level of precision is insufficient, the user should monitor and

    make adjustments when required.

    NOTE:

    When the message "RAAA051 Low battery" is displayed, supply power to the GP

    unit and fully charge the battery. In 24 hours the battery charges to a level that

    allows backup operation. Completing a full charge requires about 120 hours (5

    days).

    The lithium batterys lifetime is: 10 years when the batterys ambient temperature

    is 40 C (104 F) or less, 4.1 years when the batterys ambient temperature is 50C (122 F) or less, and 1.5 years when the batterys ambient temperature is 60

    C (140 F) or less.

    GP-4201T / GP-4203T GP-4201TW

    Application Memory *1 FLASH EPROM 16 MB(including the logic

    program area)

    FLASH EPROM 8 MB(including the logic

    program area)

    Logic Program Area FLASH EPROM 132 KB (Equivalent to 15,000

    steps)*2

    Font Area FLASH EPROM 8 MB (when limit exceeded, uses

    application memory)

    Data Backup SRAM 320 KB

    (Rechargeable lithium

    battery for data backup)

    SRAM 128 KB

    (Rechargeable lithium

    battery for data backup)

    Variable Area SRAM 64 KB

    (Rechargeable lithiumbattery for retentive

    variables)

    None

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    51/240

    GP4000 Series Hardware Manual

    51

    When used for backup:

    Approximately 100 days, with a fully charged battery.

    Approximately 6 days, with a half-charged battery.

    Touch Panel

    Touch Panel Type Resistive Film (analog)

    Touch Panel Resolution 1,024 x 1,024

    Touch Panel Service Life 1 million times or more

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    52/240

    Specifications

    52

    Interface Specifications

    Serial Interface COM1

    Serial Interface COM2

    USB Interface

    Ethernet Interface

    NOTE: GP-4201TW does not have an Ethernet interface.

    GP-4201T GP-4201TW GP-4203T

    AsynchronousTransmission

    RS-232C / RS-422 /RS-485

    RS-232C RS-485 (isolation)

    Data Length 7 or 8 bits

    Stop Bit 1 or 2 bits

    Parity None, odd or even

    Data Transmission

    Speed

    2,400...115,200 bps,

    187,500 bps (MPI)

    2,400...115,200 bps 2,400...115,200

    bps, 187,500 bps

    (MPI)

    Connector D-Sub 9 pin (plug) D-Sub 9 pin

    (socket)

    GP-4201TW

    Asynchronous Transmission RS-422 / RS-485

    Data Length 7 or 8 bits

    Stop Bit 1 or 2 bits

    Parity None, odd or even

    Data Transmission Speed 2,400...115,200 bps,

    187,500 bps (MPI)

    Connector D-Sub 9 pin (plug)

    USB (Type A) In ter face USB (m in i-B ) In ter face

    Connector USB 2.0 (Type A) x 1 USB 2.0 (mini-B) x 1

    Power Supply Voltage 5 Vdc 5% -

    Maximum Current

    Supplied

    500 mA -

    Maximum Transmission

    Distance

    5 m (16.4 ft)

    GP-4201T / GP-4203T

    Ethernet (LAN) IEEE802.3i / IEEE802.3u,

    10BASE-T/100BASE-TX

    Connector Modular jack (RJ45) x 1

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    53/240

    GP4000 Series Hardware Manual

    53

    Specifications of Serial Interface COM1

    Introduction

    NOTE: For instructions on how to connect to other devices, always refer to the GP-

    Pro EX Device/PLC Connection Manual.

    The COM1 ports of GP-4201T and GP-4201TW are not isolated. The SG (signal

    ground) and FG (frame ground) terminals are connected inside the GP unit.

    Serial Interface COM1

    GP-4201T: D-Sub 9 pin plug connector via an RS-232C or RS-422/RS-485 cable.

    NOTE: *1You can switch pin #9 between RI and VCC via software.

    DANGERELECTRIC SHOCK

    When using the SG terminal to connect an external device to the panel:

    Verify that a short-circuit loop is not created when you set up the system.

    Connect the #5 SG terminal to remote equipment when the host (PLC) unit is

    not isolated. Connect the #5 SG terminal to a known reliable ground connection

    to reduce the risk of damaging the circuit.Failure to foll ow these instructions will result in death or serious injury.

    Pin Connection Pin

    No.

    RS-232C

    Signal Name Direction Meaning

    1 CD Input Carrier Detect

    2 RD(RXD) Input Receive Data

    3 SD(TXD) Output Send Data

    4 ER(DTR) Output Data Terminal Ready

    5 SG - Signal Ground

    6 DR(DSR) Input Data Set Ready

    7 RS(RTS) Output Request to Send

    8 CS(CTS) Input Send possible

    9 CI(RI)/VCC Input/ Called Status Display

    +5V5% Output 0.25A*1

    Shell FG Frame Ground (Common

    with SG)

    NOTICE

    EQUIPMENT DAMAGE

    Use only the rated current.

    Failure to foll ow these instructions can result in equipment damage.

    9

    6

    5

    1

    (GP unit side)

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    54/240

    Specifications

    54

    Interfit bracket is #4-40 (UNC).

    Recommendations:

    Cable Connector: XM2D-0901 manufactured by OMRON Corporation.

    Cable Cover: XM2S-0913 manufactured by OMRON Corporation.

    Jack Screw (#4-40 UNC): XM2Z-0073 manufactured by OMRON Corporation.

    GP-4201TW: D-Sub 9 pin plug connector via an RS-232C cable.

    NOTE: *1You can switch pin #9 between RI and VCC via software.

    Pin Connection Pin

    No.

    RS-422/RS-485

    Signal Name Direction Meaning

    1 RDA Input Receive Data A (+)

    2 RDB Input Receive Data B (-)

    3 SDA Output Send Data A (+)

    4 ERA Output Data Terminal Ready A (+)

    5 SG - Signal Ground

    6 CSB Input Send Possible B (-)

    7 SDB Output Send Data B (-)

    8 CSA Input Send Possible A (+)

    9 ERB Output Data Terminal Ready B (-)

    Shell FG Frame Ground (Common

    with SG)

    CAUTIONLOSS OF COMMUNICATION

    All connections to the communication ports must not put excessive stress on the

    ports. Securely attach communication cables to the panel wall or cabinet.

    Use only D-Sub 9 pin cables with a locking tab in good condition.

    Failure to follow these instructions can result in in jury or equipment damage.

    Pin Connection Pin

    No.

    RS-232C

    Signal Name Direction Meaning

    1 CD Input Carrier Detect

    2 RD(RXD) Input Receive Data

    3 SD(TXD) Output Send Data

    4 ER(DTR) Output Data Terminal Ready

    5 SG - Signal Ground

    6 DR(DSR) Input Data Set Ready

    7 RS(RTS) Output Request to Send

    8 CS(CTS) Input Send possible

    9 CI(RI)/VCC Input/ Called Status Display

    +5V5% Output 0.25A*1

    Shell FG Frame Ground (Common

    with SG)

    9

    6

    5

    1

    (GP unit side)

    9

    6

    5

    1

    (GP unit side)

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    55/240

    GP4000 Series Hardware Manual

    55

    Interfit bracket is #4-40 (UNC).

    Recommendations:

    Cable Connector: XM2D-0901 manufactured by OMRON Corporation.

    Cable Cover: XM2S-0913 manufactured by OMRON Corporation.

    Jack Screw (#4-40 UNC): XM2Z-0073 manufactured by OMRON Corporation.

    GP-4203T: D-Sub 9 pin socket connector via a RS-485, PROFIBUS, or MPI cable.

    NOTE: *1You can supply power to the Siemens PROFIBUS connector only. You

    cannot supply power to the device/PLC.

    *2The SG and FG terminals are isolated.

    Interfit bracket is #4-40 (UNC).

    Recommendations:

    Cable Connector: XM2A-0901 manufactured by OMRON Corporation.

    Cable Cover: XM2S-0913 manufactured by OMRON Corporation.

    Jack Screw (#4-40 UNC): XM2Z-0073 manufactured by OMRON Corporation.

    NOTICE

    EQUIPMENT DAMAGE

    Use only the rated current.

    Failure to foll ow these instructions can result in equipment damage.

    CAUTIONLOSS OF COMMUNICATION

    All connections to the communication ports must not put excessive stress on theports.

    Securely attach communication cables to the panel wall or cabinet.

    Use only D-Sub 9 pin cables with a locking tab in good condition.

    Failure to follow these instructions can result in injury or equipment damage.

    Pin Connection Pin

    No.

    RS-485 (isolation)

    Signal Name Direction Meaning

    1 NC no connection

    2 NC no connection

    3 Line A Input/Output Data A (+)

    4 RS(RTS) Output Request to Send

    5 SG Signal Ground

    6 VCC +5V5% External Output*1

    7 NC no connection

    8 Line B Input/Output Data B (-)

    9 NC no connection

    Shell FG Frame Ground

    *2

    (Notconnected with SG)

    6

    9

    1

    5

    (GP unit side)

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    56/240

    Specifications

    56

    CAUTIONLOSS OF COMMUNICATION

    All connections to the communication ports must not put excessive stress on the

    ports. Securely attach communication cables to the panel wall or cabinet.

    Use only D-Sub 9 pin cables with a locking tab in good condition.

    Failure to follow these instructions can result in in jury or equipment damage.

  • 7/21/2019 Hng dn s dng mn hnh pro-face |Pro-face GP4201 manual, Pro-face GP4301 manual, GP4401 manual, Pro-

    57/240

    GP4000 Series Hardware Manual

    57

    Specifications of Serial Interface COM2

    Introduction

    NOTE: For instructions on how to connect to other devices, always refer to the GP-

    Pro EX Device/PLC Connection Manual.

    The serial port is not isolated. The SG (signal ground) and FG (frame ground)

    terminals are connected inside the GP unit.

    Serial Interface COM2

    GP-4201TW: D-Sub 9 pin plug connector via an RS-422/485 cable.

    Interfit bracket is #4-40 (UNC).

    Recommendations:

    Cable Connector: XM2D-0901 manufactured by OMRON