im 05805008 k
TRANSCRIPT
-
8/18/2019 Im 05805008 k
1/14
IM05805008K
Effective June 2004
Instructions for EATON Cutler-Hammer Microprocessor Based Remote Alarm Panels
-
8/18/2019 Im 05805008 k
2/14
-
8/18/2019 Im 05805008 k
3/14
IM05805008K
Effective June 2004
TABLE OF CONTENTS
1. INSTALLATION AND MOUNTING OF THE CONTROLLER ................................................... 1
2. ELECTRICAL CONNECTIONS ....................................................................................................... 1
2.1 ELECTRICAL CHECKOUT INSTRUCTIONS ……………………………………………………………22.2 ELECTRICAL ALARM PANELS (FULL SERVICE) .................................................................................. 2
2.2.1 'Pump Operating' check…………………………………………………………………………. 22.2.2 'Common Alarm' check ……………………………………………………………………………2
2.2.3 'Phase Failure' check …………………………………………………………………………….. 2
2.3 DIESEL ALARM PANELS.................................................................................................................... 2
2.3.1 'Engine Run' & 'Controller in OFF mode' check ……………………………………………. 22.3.2 'Engine Trouble' check ……………………………………………………………………………2
2.3.3 'Pump Room Trouble' check ……………………………………………………………………...2
2.4 OPERATION ................................................................................................................................... 32.4.1 Lamp Test Button …………………………………………………………………………………..3
2.4.2 Supervisory and Backup Voltage ………………………………………………………………...3
2.4.3 Audible Alarm ………………………………………………………………………………………3
2.4.4 Silence Pushbutton …………………………………………………………………………………32.4.5 Supervisory Power Normal Light………………………………………………………………...3
2.4.6 Output Contacts ……………………………………………………………………………………3
2.4.7 Output Relays……………………………………………………………………………………….3
3. FIGURE 1: ELECTRIC DIMENSIONS & SHIPPING WEIGHTS ............................................... 4
4. FIGURE 2: DIESEL DIMENSIONS & SHIPPING WEIGHTS ..................................................... 5
5. FIGURE 3: ELECTRIC WIRING SCHEMATIC ............................................................................ 6
6. FIGURE 4: DIESEL WIRING SCHEMATIC .................................................................................. 7
7. FIGURE 5: ELECTRIC LOCAL WIRING SCHEMATIC ............................................................. 8
Page i
-
8/18/2019 Im 05805008 k
4/14
-
8/18/2019 Im 05805008 k
5/14
IM05805008K Page 1
Effective June 2004
INSTALLATION & MAINTENANCE
MANUAL FOR REMOTE ALARM
PANELS
In order to familiarize yourself with the Remote Alarm Panel, please read the instruction manual thoroughly andcarefully. Retain the manual for future reference.
1. Installation and Mounting of theController
Carefully unpack the controller and inspect
thoroughly.
The controller is not free standing and must be bolted
securely to a wall. For dimensional and weight data
please refer to the respective data sheets for theRemote Alarm Panels.
Figure #1 - Electric Remote Alarm PanelFigure #2 - Diesel Remote Alarm Panel
2. Electrical Connections
All electrical connections should meet national
and local electrical codes and standards.
The controller should be located or so protected that
they will not be damaged by water escaping from
pumps or pump connections. Current carrying parts
of controllers shall be a minimum of 12 inches (305mm) above the floor level.
• Prior to starting, verify all data on the nameplate
such as, catalog number and AC line voltage.
• Inspect all electrical connections, componentsand wiring for any visible damage and correct as
necessary. Ensure that all electrical connections
are tightened before energization.
• Install necessary conduit using proper methodsand tools.
• Incoming supervisory power and backup power
connections are clearly marked L and N and are
located on the upper right side of themicroprocessor board.
• Ensure selector switches are set correctly to
correspond to the incoming supply voltage – (120V or 240V).
-
8/18/2019 Im 05805008 k
6/14
Page 2 IM05805008K
Effective June 2004
2.1 Electrical Checkout Instructions (For Use with Eaton Cutler-Hammer Remote Alarm
Panels)
WARNING: The following procedures should be carried out by a qualified electrician familiar with the electrical
safety procedures associated with this product and its associated equipment.
2.2 Electric Remote Alarm Panels (Full Service) – For Electrical Schematic Refer to Figure #3
Note: The alarm buzzer can be silenced by pressing the ‘Silence Alarm’ pushbutton on the front of the controller.
2.2.1 - Turn power on to the Fire Pump Controller and to the Remote Alarm Panel
- In the Fire Pump Controller press the ‘Local Start’ pushbutton, the controller will start
- The ‘Pump Operating’ light should illuminate and the alarm will sound on the Alarm Panel- Press the ‘Stop’ pushbutton on the front of the fire pump controller
2.2.2 - Move the disconnect handle on the Fire Pump Controller to the ‘OFF’ Position
- The ‘Common Alarm’ and ‘Phase Failure’ lights should illuminate and the alarm will sound on the Alarm Panel- Move the disconnect handle back to the ‘ON’ Position
2.2.3 - Move dip switch #4 in the Fire Pump Controller, located on the top left hand corner of the main board, to the
opposite direction- The ‘Common Alarm’ and ‘Phase Reversal’ lights should illuminate and the alarm will sound on the Alarm
Panel
- Move the dip switch back to the original position
2.3 Diesel Remote Alarm Panels – For Electrical Schematic Refer to Figure #4
Note: The alarm buzzer can be silenced by pressing the ‘Silence Alarm’ pushbutton on the front of the controller.
2.3.1 - Turn power on to the Fire Pump Controller and to the Remote Alarm Panel
- Place the controller in the ‘AUTO’ mode by depressing the “AUTO” button
- Start the controller either by jumpering the remote start (Terminal #11 & #28) or by dropping the pressure in
the Fire Pump Controller - The ‘Engine Run’ light should illuminate and the alarm will sound on the alarm panel
- Place the controller in the ‘OFF’ mode by depressing the “OFF” button
- The ‘Controller in OFF Mode’ light will illuminate and the alarm will sound on the alarm panel
2.3.2 - Place the controller in the ‘AUTO’ mode by depressing the “AUTO” button
- Start the controller either by jumpering the remote start (Terminal #11 & #28) or by dropping the pressure in the Fire Pump Controller
- Place a jumper between Terminal #4 & #11 in the Fire Pump Controller (Low Oil Pressure)
- The ‘Engine Trouble’ light should illuminate and the alarm will sound on the alarm panel
- Place the controller in the ‘OFF’ mode by depressing the “OFF” button
2.3.3 - Place the controller in the ‘MANUAL’ mode by depressing the “MANUAL” button
- Place a jumper between Terminal #21 & #11 in the Fire Pump Controller (Low Room Temp.)- The ‘Pump Room Trouble’ light should illuminate and the alarm will sound on the alarm panel
- Place the controller in the ‘OFF’ mode by depressing the “OFF” button
-
8/18/2019 Im 05805008 k
7/14
IM05805008K Page 3
Effective June 2004
2.4 Operation
2.4.1 Lamp Test ButtonEach remote alarm panel is equipped with a
Lamp Test button that fully tests all lights and
audible alarm buzzer when pressed. Operatingthe lamp test button will not change the state of
the internal output relays
2.4.2 Supervisory and Backup Supply VoltageThe remote alarm panels will accept both 120
volt 50/60Hz and 240 volt 50/60Hz power
supply on either of the supervisory and backupsource inputs. If the supervisory source of
supply is lost, the panel will automatically
switch to the backup source. Both the
supervisory and backup sources must be
independent of each other.
2.4.3 Audible Alarm
When any alarm conditions are present, theaudible alarm will sound. It will continue to
sound until either the silence pushbutton is
pressed, or the alarm condition is satisfied.
2.4.4 Silence Pushbutton
An audible alarm silencing pushbutton is
provided that silences all active alarms when
pressed. Pressing the button has no effect onthe associated alarm light(s). Should a second
alarm condition occur after the silence
pushbutton has been pressed, the audible alarmwill re-sound until the silence pushbutton is
pressed again, or the alarm condition has beensatisfied.
2.4.5 Supervisory Power Normal Light
The supervisory power normal light indicates whe
supervisory power is available and will turn owhen the controller switches to the backup powe
source. An audible alarm will sound whe
supervisory power is not available and will remaiON until supervisory power is restored, or th
silence pushbutton is pressed.
2.4.6 Output ContactsThe FDAP-M electric remote alarm panel has five
alarm outputs to indicate supervisory power norma
pump operating, phase reversal, phase failure and
common alarm. The DFDAP-M diesel remotealarm panel also has five alarm outputs that indicat
supervisory power normal, engine running, engine
trouble, pump room trouble and controller in OFFmode. An additional Common Alarm relay output
consisting of two Form-C contacts, is provided tha
energizes under any alarm condition. Three
additional alarm outputs are provided to indicatespecific alarm conditions within the fire pump
controller.
2.4.7 Output Relays
The alarm panel relays are printed circuit boardstyle that plug into sockets mounted on the alarm
panel main circuit board. They are rated for 8 amp
/ 250VAC. They are de-energized under normalconditions regardless of input status selected.
2.4.7 Alarm InputsEach controller is equipped with seven user
selectable alarm inputs. Each can be selected asnormally open (N.O.) or normally closed (N.C.) by
the use of jumpers on the microprocessor board.
-
8/18/2019 Im 05805008 k
8/14
Page 4 IM05805008K
Effective June 2004
ELECTRIC REMOTE ALARM PANEL – FDAP-M
Figure #1
-
8/18/2019 Im 05805008 k
9/14
IM05805008K Page 5
Effective June 2004
DIESEL ENGINE REMOTE ALARM PANEL – DFDAP-M
Figure #2
-
8/18/2019 Im 05805008 k
10/14
Page 6 IM05805008K
Effective June 2004
WIRING SCHEMATIC – ELECTRIC REMOTE ALARM PANEL – FDAP-M
Figure #3
-
8/18/2019 Im 05805008 k
11/14
IM05805008K Page 7
Effective June 2004
WIRING SCHEMATIC – DIESEL REMOTE ALARM PANEL – DFDAP-M
Figure #4
-
8/18/2019 Im 05805008 k
12/14
Page 8 IM05805008K
Effective June 2004
WIRING SCHEMATIC – ELECTRIC LOCAL ALARM PANEL
Figure #5
-
8/18/2019 Im 05805008 k
13/14
IM05805008K Page 9
Effective June 2004
-
8/18/2019 Im 05805008 k
14/14
EATON
Cutler-Hammer
403 East Lake Blvd., Airdrie, Alberta, T4A 2G1Canadatel: 403-948-7955fax: 403-948-6967www.chfire.com
© 2004 Eaton Corporation All Rights ReservedPrinted in CanadaPublication No.: IM05805008KJune 2004