ŠESTO SAVJETOVANJE HRVATSKOG OGRANKA MEĐUNARODNE ELEKTRODISTRIBUCIJSKE KONFERENCIJE Opatija, 13. ─ 16. svibnja 2018. INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE „PRAHA“ SNAGE 150 KW U DISTRIBUCIJSKU MREŽU BIH-A MARTINA EZGETA, MAG.ING.EL. PROF .DR.SC. SRETE NIKOLOVSKI MR.SC. DRAGAN MLAKIĆ

Upload: others

Post on 15-Feb-2020

4 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE ... · fotonaponske elektrane „praha“ snage 150 kw u distribucijsku mreŽu bih-a martina ezgeta, mag.ing.el. prof.dr.sc

ŠESTO SAVJETOVANJE

HRVATSKOG OGRANKA MEĐUNARODNE ELEKTRODISTRIBUCIJSKE KONFERENCIJE Opatija, 13. ─ 16. svibnja 2018.

INTEGRACIJA I KOORDINACIJA ZAŠTITE

FOTONAPONSKE ELEKTRANE „PRAHA“

SNAGE 150 KW U DISTRIBUCIJSKU MREŽU

BIH-A

MARTINA EZGETA, MAG.ING.EL.

PROF.DR.SC. SRETE NIKOLOVSKI

MR.SC. DRAGAN MLAKIĆ

Page 2: INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE ... · fotonaponske elektrane „praha“ snage 150 kw u distribucijsku mreŽu bih-a martina ezgeta, mag.ing.el. prof.dr.sc

ŠESTO SAVJETOVANJE

HRVATSKOG OGRANKA MEĐUNARODNE ELEKTRODISTRIBUCIJSKE KONFERENCIJE Opatija, 13. ─ 16. svibnja 2018.

NASLOV REFERATA

Autor(i)

• Prikazana je koordinacija nadstrujnih zaštita za FN elektranu „Praha“ izgrađene na

području Žepča u Bosni i Hercegovini.

• Model je napravljen u programskom paketu EasyPower.

• Postojeći urađeni Elaborat podešenja zaštite je bio manjkav, bez nadstrujnih zaštita

u FN elektrani i mreži.

• Postojale su samo naponske i frekvencijske zaštite invertera1). PODEŠENJE GLAVNOG PREKIDAČA NA AC STRANI

2). PODEŠENJE DIFERENCIJALNE ZAŠTITE NA AC STRANI

3). PODEŠENJE INVERTERA

3.1) PODEŠENJE INVERTERA I.1

3.2) PODEŠENJE INVERTERA I.2

3.3) PODEŠENJE INVERTERA I.3

3.4) PODEŠENJE INVERTERA I.4

3.5) PODEŠENJE INVERTERA I.5

3.6) PODEŠENJE INVERTERA I.6

• Ponukalo je diplomanticu da uradi diplomski više prema uputama HEP ODS-a u

Hrvatskoj

INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE „PRAHA“ SNAGE 150 KW U DISTRIBUCIJSKU

MREŽU BIH-e

Martina Ezgeta, Srete Nikolovski i Dragan Mlakić

Page 3: INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE ... · fotonaponske elektrane „praha“ snage 150 kw u distribucijsku mreŽu bih-a martina ezgeta, mag.ing.el. prof.dr.sc

ŠESTO SAVJETOVANJE

HRVATSKOG OGRANKA MEĐUNARODNE ELEKTRODISTRIBUCIJSKE KONFERENCIJE Opatija, 13. ─ 16. svibnja 2018.

NASLOV REFERATA

Autor(i)

• Urađen je ručni proračun pada napona na AC i DC strani

• Urađen je ručni proračun struja 1FKS i 2KS struja kratkog spoja

• Urađena je ručna provjera efikasnosti zaštitnog uređaja za 1FKS i 2FKS

• U programskom paketu EasyPower je modelirana mreža i FN elektrana i

simulirani 1FKS i 3FKS

• Analizirane su komponente struja KS koje teku kroz zaštitne uređaje

• Korišten Power protector modul za kreiranje vremensko-strujni

karakteristika zaštite

• Provjerena i podešena koordinacija zaštite te sukladno kriterijima

selektivnosti prepodešena zaštita.

• Prikaz jednopolne sheme s analiziranim Kratkim spojevima je dan na slici

1.

INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE „PRAHA“ SNAGE 150 KW U DISTRIBUCIJSKU

MREŽU BIH-e

Martina Ezgeta, Srete Nikolovski i Dragan Mlakić

Page 4: INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE ... · fotonaponske elektrane „praha“ snage 150 kw u distribucijsku mreŽu bih-a martina ezgeta, mag.ing.el. prof.dr.sc

ŠESTO SAVJETOVANJE

HRVATSKOG OGRANKA MEĐUNARODNE ELEKTRODISTRIBUCIJSKE KONFERENCIJE Opatija, 13. ─ 16. svibnja 2018.

NASLOV REFERATA

Autor(i)

Slika 1. Model FNE „Praha“ u EasyPower-u

INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE „PRAHA“ SNAGE 150 KW U DISTRIBUCIJSKU

MREŽU BIH-e

Martina Ezgeta, Srete Nikolovski i Dragan Mlakić

Page 5: INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE ... · fotonaponske elektrane „praha“ snage 150 kw u distribucijsku mreŽu bih-a martina ezgeta, mag.ing.el. prof.dr.sc

ŠESTO SAVJETOVANJE

HRVATSKOG OGRANKA MEĐUNARODNE ELEKTRODISTRIBUCIJSKE KONFERENCIJE Opatija, 13. ─ 16. svibnja 2018.

NASLOV REFERATA

Autor(i)

U> U<

Podešenje

(V)

Test iznos na

(V)

Vrijeme odziva

(s)

Podešenje

(V)

Test iznos

na

(V)

Vrijeme

odziva

(s)

245 276 0.08 221 184 0.150

f> f<

Podešenje

(Hz)

Test iznos na

(Hz)

Vrijeme odziva

(s)

Podešenje

(Hz)

Test iznos na

(Hz)

Vrijeme

odziva

(s)

50.2 50.3 0.07 49,85 49.7 0.08

Tablica 5. Pod/nad naponska i pod/nad frekvencijska zaštita

INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE „PRAHA“ SNAGE 150 KW U DISTRIBUCIJSKU

MREŽU BIH-e

Martina Ezgeta, Srete Nikolovski i Dragan Mlakić

Page 6: INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE ... · fotonaponske elektrane „praha“ snage 150 kw u distribucijsku mreŽu bih-a martina ezgeta, mag.ing.el. prof.dr.sc

ŠESTO SAVJETOVANJE

HRVATSKOG OGRANKA MEĐUNARODNE ELEKTRODISTRIBUCIJSKE KONFERENCIJE Opatija, 13. ─ 16. svibnja 2018.

NASLOV REFERATA

Autor(i)

.5

.5

.6

.6

.8

.8

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

10

10

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

100

100

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

1000

1000

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

10000

10000

.01 .01

.02 .02

.03 .03

.04 .04

.05 .05

.06 .06

.07 .07

.08 .08

.09 .09.1 .1

.2 .2

.3 .3

.4 .4

.5 .5

.6 .6

.7 .7

.8 .8

.9 .91 1

2 2

3 3

4 4

5 5

6 67 78 89 9

10 10

20 20

30 30

40 40

50 50

60 6070 7080 8090 90

100 100

200 200

300 300

400 400

500 500

600 600700 700800 800900 900

1000 1000

CURRENT IN AMPERES X 10 AT 400 VOLTS

CURRENT IN AMPERES X 10 AT 400 VOLTS

TIM

E IN

SE

CO

ND

S

TIM

E IN

SE

CO

ND

S

EasyPower®

TIME-CURRENT CURVES

University ofOsijek

TCC-2

FAULT:

DATE: Sep 08, 2017

BY:

REVISION: 1

MARTINA DIPL V5

BL-1ABB Ekip E LSIGSensor = 40Plug = 40Cur Set = 1 (40A)LT Band = 10 secSTPU = 3 (120A)ST Delay = 0.1ST Delay I²t = OutInst = 6.3 (252A)

NADSTRUJNIABB PR222DS [IEC]Sensor = T4(320)Plug = 320Cur Set = 1 (320A)LT Band = 3STPU = 10 (3200A)ST Delay = 0.1ST Delay I²t = OutInst = 4 (1280A)

FS-2SiemensgL/gG [IEC]3NA3 3425 A

BL-8ABB PR222DS [IEC]Sensor = T5(400)Plug = 400Cur Set = 1 (400A)LT Band = 3STPU = 8.2 (3280A)ST Delay = 0.25ST Delay I²t = InInst = Override (6500A)

Z0AlstomHV Din [IEC]FDw(7.2&12)50A

3944

Slika 2. Koordinacija nadstrujne zaštite s pripadnom strujom kvara za 1FKS i 3FKS na sabirnici IMO

.5

.5

.6

.6

.8

.8

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

10

10

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

100

100

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

1000

1000

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

10000

10000

.01 .01

.02 .02

.03 .03

.04 .04

.05 .05

.06 .06

.07 .07

.08 .08

.09 .09.1 .1

.2 .2

.3 .3

.4 .4

.5 .5

.6 .6

.7 .7

.8 .8

.9 .91 1

2 2

3 3

4 4

5 5

6 67 78 89 9

10 10

20 20

30 30

40 40

50 50

60 6070 7080 8090 90

100 100

200 200

300 300

400 400

500 500

600 600700 700800 800900 900

1000 1000

CURRENT IN AMPERES X 10 AT 400 VOLTS

CURRENT IN AMPERES X 10 AT 400 VOLTS

TIM

E IN

SE

CO

ND

S

TIM

E IN

SE

CO

ND

S

NADSTRUJNIABB PR222DS [IEC]Sensor = T4(320)Plug = 320Cur Set = 1 (320A)LT Band = 3STPU = 10 (3200A)ST Delay = 0.1ST Delay I²t = OutInst = 4 (1280A)

BL-13751A

R-1_A82.2A

R-1_AABB REF 54351N/50N DTDefinite TimeCT Ratio = 50/5Tap Io> = 0.8 (40A)Time Dial = 0.3

R-1_A

INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE „PRAHA“ SNAGE 150 KW U DISTRIBUCIJSKU

MREŽU BIH-e

Martina Ezgeta, Srete Nikolovski i Dragan Mlakić

Page 7: INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE ... · fotonaponske elektrane „praha“ snage 150 kw u distribucijsku mreŽu bih-a martina ezgeta, mag.ing.el. prof.dr.sc

ŠESTO SAVJETOVANJE

HRVATSKOG OGRANKA MEĐUNARODNE ELEKTRODISTRIBUCIJSKE KONFERENCIJE Opatija, 13. ─ 16. svibnja 2018.

NASLOV REFERATA

Autor(i)

Odgovor recenzentima:

1. Opišite gdje se nalazi točka razgraničenja vlasništva između elektrane “Praha“ i

distribucijske mreže te kojim se uređajem vrši odvajanje elektrane od mreže?

FN elektrana je odvojena na 0,4 kV sabirnicama u izvodu pomoću 4-polnog

automatskog prekidača sa mogućnošću daljinskog upravljanja s protokolom

IEC 61850 radi SCADA integracije. Prekidač je postavljen između NN strane

sabirnica i mjernog mjesta na kojem su SMT postavljeni.

2. Kako bi se odredila selektivnost zaštita za slučaj da je struja kratkog spoja veća

od 10 kA, a vrijeme djelovanja zaštita manje od 0,01 s?

Zaštita ne bi bila selektivna jer bi proradile bi sve trenutne I>>> nadstrujne

zaštite na niskonaponskim prekidačima u GMO ormaru i NN izvodu.

INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE „PRAHA“ SNAGE 150 KW U DISTRIBUCIJSKU

MREŽU BIH-e

Martina Ezgeta, Srete Nikolovski i Dragan Mlakić

Page 8: INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE ... · fotonaponske elektrane „praha“ snage 150 kw u distribucijsku mreŽu bih-a martina ezgeta, mag.ing.el. prof.dr.sc

ŠESTO SAVJETOVANJE

HRVATSKOG OGRANKA MEĐUNARODNE ELEKTRODISTRIBUCIJSKE KONFERENCIJE Opatija, 13. ─ 16. svibnja 2018.

NASLOV REFERATA

Autor(i)

3. Da li prikazani program u simulacije može uključiti i prorade naponskih zaštita?

Može ako se program prebaci u Dynamic Stability modul gdje se može obaviti

simulacija u vremenskoj domeni i definirati se naponski i frekvencijski releji

4. Koje zaštite prepoznaju otočni pogon elektrane, tj. isključuju izmjenjivače kod

nestanka mrežnog napona?

Otočni pogon prepoznaje logika u izmjenivaču koja prati parametere

izmjenjivača koji mogu značajno varirati te se detekcija otočnog pogona. To je

detekcija nesimetrije napona koja je podešena na 10 % Un i vrijeme prorade 5

ms. Detekcija maksimalne brzine promjene frekvencije napona df/dt je

podešena na 10 Hz/s i vrijeme prorade 10 ms

INTEGRACIJA I KOORDINACIJA ZAŠTITE FOTONAPONSKE ELEKTRANE „PRAHA“ SNAGE 150 KW U DISTRIBUCIJSKU

MREŽU BIH-e

Martina Ezgeta, Srete Nikolovski i Dragan Mlakić