  • CURSO CURSO NORMAS Y PROCEDIMIENTOS NORMAS Y PROCEDIMIENTOS

    PARAPARA MANTENIMIENTO ELECTRICO DE MANTENIMIENTO ELECTRICO DE SUBESTACIONES SUBESTACIONES

    Mdulo 1 CONCEPTOS BSICOS DE SUBESTACIONES

    1.3 EQUIPOS DE PATIO

    1.3.2 INTERRUPTORES DE POTENCIA1.3.2 INTERRUPTORES DE POTENCIA

  • INTERRUPTORES

    Un interruptor es un dispositivo cuya funcin es interrumpir y restablecer lacontinuidad en un circuito elctrico. Si la operacin se efecta sin carga (corriente),el interruptor recibe el nombre de desconectador o cuchilla desconectadora.

    Sin embargo si la operacin de apertura o de cierre la efecta con carga (corrientenominal) o con corriente de corto circuito (en caso de alguna perturbacin) elinterruptor recibe el nombre de disyuntor o interruptor de potencia.

    Los interruptores en caso de apertura, deben asegurar el aislamiento elctrico delcircuito.

    Los interruptores de potencia, como ya se mencion, interrumpen y restablecen lacontinuidad de un circuito elctrico. La interrupcin la deben efectuar con carga ocorriente de corto circuito y se construyen en dos tipos generales:

    Interruptores de aceite.Interruptores neumticos.

  • FUNCIN DE LOS INTERRUPTORES

    Se utilizan para:

    Establecer o interrumpir la corriente permanente de un circuito

    Interrumpir las corrientes de falla de un circuito

    Su funcin principal es conectar y desconectar los circuitos

    Proceso de corte:

    Separacin de contactos Arco elctrico

    Extincin del arco elctrico

    Reforzamiento dielctrico del espacio entre contactos Tensin de restablecimiento

  • FUNCIN DE LOS INTERRUPTORES

  • FUNCIN DE LOS INTERRUPTORES

  • Interruptor automtico Cmara de corte

  • DEFINICIONES

    Arco elctrico

    Corriente que se desarrolla entre los contactos del interruptor

    despus de estar separados

    Tensin de arco

    Tensin entre contactos cuando existe arco elctrico

    Tensin transitoria de recuperacin TTR

    Tensin transitoria que aparece entre los contactos despus de lainterrupcin del arco

    Tensin de encendido

    Tensin requerida entre los contactos para el encendido del arco

  • TIPOS

    Segn el sitio de la instalacin

    Interiores: Comunes en tensiones 4,6< Um< 34,5 kV

    Exteriores: Para tensiones Um > 34,5 kV, y estospueden ser:

  • TIPOS

    Segn el sitio de la instalacin (cont.)

    Exteriores:

    Tanque vivo: el mecanismo deinterrupcin se encuentra enpequeas cmaras, las que seubican en soportes aislantes

    Caractersticas:

    Ocupan menos espacio

    Son menos costosos

    Utilizan menos medios deextincin

  • Segn el sitio de la instalacin (cont.)

    Exteriores:

    Tanque muerto: consiste en untanque con el mecanismo deinterrupcin que se conecta a laalta tensin mediante bujes

    TIPOS

    Caractersticas:

    Los transformadores de corriente se

    pueden instalar en los bujes

    Se comportan mejor ante sismos

  • Segn el medio de extincin

    Aceite: los contactos seencuentran sumergidos enaceite el cual tiene la funcin derefrigerar y de extinguir el arco

    TIPOS

    VENTAJAS:- Comparativamente usan una menorcantidad de aceite (5%).- Menor tamao y peso en comparacin alos de granvolumen.- Menor costo.- Pueden emplearse tanto en formamanual comoautomtica.- Fcil acceso a los contactos.

    DESVENTAJAS-Peligro de incendio y explosin aunque enmenor grado.- No pueden usarse con reconexinautomtica.- Requieren un mantenimiento frecuente yreemplazos peridicos de aceite.- Sufren de mayor dao los contactosprincipales.

  • Segn el medio de extincin (cont.)

    Interruptores en airecomprimido: El arco elctrico essoplado por aire comprimido enla cmara de extincin.

    TIPOS

    VENTAJAS- No hay riesgos de incendio oexplosin.- Operacin muy rpida.- Pueden emplearse en sistemas conreconexin automtica.- Alta capacidad de ruptura.- La interrupcin de corrientesaltamente capacitivas no presentamayores dificultades.- Menor dao a los contactos.- Fcil acceso a los contactos.- Comparativamente menor peso.

    VENTAJAS- Poseen una compleja instalacindebido a la red de aire comprimido,que incluye motor, compresor,tuberas, etc.,- Construccin ms compleja,- Mayor costo.- Niveles de ruido altos al operar.

  • Segn el medio de extincin :(cont.)

    Interruptores en SF6: El SF6 esun gas que se encuentra apresin dentro de la cmara deextincin y es el que produce elsoplado del arco.

    TIPOS

    VENTAJAS- Alta rigidez dielctrica que hace que seaun excelente aislante.- Altamente estable, inerte, inodoro.- No hay riesgos de incendio o explosin.- Son menos pesados.- Bajo mantenimiento.- Bajo nivel de ruido.

    DESVENTAJAS- El SF6 es 2.500 veces ms potente queel CO2 para producir efecto Invernadero.- Pueden generar productos altamentetxicos durante la extincin del arco, sinembargo dada su alta estabilidad estosproductos tienen poca vida.

  • Segn el medio de extincin : (cont.)

    Vaco: Esta tecnologa aparece enlos aos 60. Los contactos estndentro de una botella especial enlas que se ha hecho el vacio casiabsoluto. Se usan principalmenteen sistemas de baja y mediatensin.

    TIPOS

    VENTAJAS- Tiempo de operacin muy rpida, engeneral la corriente se anula a la primerapasada por cero.- No hay riesgos de incendio o explosin.- Son menos pesados y ms baratos.- Prcticamente no requierenmantenimiento y tienen una vida tilmucho mayor a los interruptoresconvencionales.- Rigidez dielctrica entre los contactos serestablece rpidamente impidiendo lareignicin del arco.

    DESVENTAJAS- Dificultad para mantener la condicin devaco.- Generan sobre-tensiones producto delelevado di/dt.- Tienen capacidad de interrupcinlimitada.

  • Segn el mecanismo de operacin:

    Resortes: la energa se almacena en resortes. Requiere motor para cargar elresorte

    Neumtico: la energa se almacena en aire comprimido. Requiere un moto-compresor para mantener la presin constante

    Hidrulico: La energa se almacena en aceite a presin. Se requiere una bombapara mantener la presin de aceite.

    TIPOS

  • RELACIN ENTRE TENSIONES NOMINALES Y TIPO DE INTERRUPTOR

  • Clasificacin segn IEC

    Segn su durabilidad elctrica: clase E1 E2

    Segn su desempeo ante corrientes capacitivas: clase C1 C2

    Segn su durabilidad mecnica: clase M1 M2

    TIPOS

  • CLASIFICACIN DE ACUERDO CON IEC

    Segn la durabilidad elctrica

    Clase E2: diseados con durabilidad elctrica extendida, es decir, las partes de

    interrupcin del contacto principal no requieren mantenimiento

    Clase E1: no clasificados en Clase E2

  • CLASIFICACIN DE ACUERDO CON IEC

    Segn su desempeo ante corrientes capacitivas

    Clase C1: con baja probabilidad de recebado (restablecimiento del arco

    despus de separados los contactos)

    Clase C2: con muy baja probabilidad de recebado

  • CLASIFICACIN DE ACUERDO CON IEC

    Segn su durabilidad mecnica

    Clase M1: con durabilidad mecnica normal (2.000 operaciones sin

    mantenimiento). No catalogados en clase M2

    Clase M2: con durabilidad mecnica extendida (10.000 operaciones sin

    mantenimiento)

  • NORMAS TCNICAS

    IEC 62271-100 - High-voltage switchgear and control gear - part 100: alternating-

    current circuit-breakers

    IEC 60376 - Specification of technical grade Sulfur Hexafluoride (SF6) for use in

    electrical Equipment (Especificaciones para Hexafluoruro de Azufre (SF6) de

    calidad tcnica para uso en equipos elctricos)

    IEC 60427 - Synthetic Testing of High-Voltage Alternating Current Circuit-Breakers

  • NORMAS TCNICAS

    IEC 62271-100 - HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR - PART 100: ALTERNATING-CURRENT CIRCUIT-BREAKERS

    Scope:

    This International Standard is applicable to a.c. circuit-breakers designed for indoor or outdoor installation and for operation at

    frequencies of 50 Hz and 60 Hz on systems having voltages above 1 000 V.

    It is only applicable to three-pole circuit-breakers for use in three-phase systems and single-pole circuit-breakers for use in single

    phase systems. Two-pole circuit-breakers for use in single-phase systems and application at frequencies lower than 50 Hz are

    subject to agreement between manufacturer and user.

    This standard is also applicable to the operating devices of circuit-breakers and to their auxiliary equipment. However, a circuit

    breaker with a closing mechanism for dependent manual operation is not covered by this standard, as a rated short-circuit

    making-current cannot be specified, and such dependent manual operation may be objectionable because of safety

    considerations.

    This standard does not cover circuit-breakers intended for use on motive power units of electrical traction equipment; these are

    covered by IEC 60077 [4].

    Generator circuit-breakers installed between generator and step-up transformer are not within the scope of this standard.

    Switching of inductive loads is covered by IEC 61233.

    Circuit-breakers with an intentional non-simultaneity between the poles, with the exception of circuit-breakers providing single

    pole auto-reclosing, are not within the scope of this standard.

    This standard does not cover self-tripping circuit-breakers with mechanical tripping devices or devices which cannot be made

    inoperative.

    By-pass circuit-breakers installed in parallel with line series capacitors and their protective equipment are not within the scope of

    this standard, these are covered by IEC 60143-2 [6].

    NOTE Tests to prove the performance under abnormal conditions should be subject to agreement between manufacturer and

    user. Such abnormal conditions are, for instance, cases where the voltage is higher than the rated voltage of the circuit-breaker,

    conditions which may occur due to sudden loss of load on long lines or cables.

  • NORMAS TCNICAS

    IEC 60376 Specification of technical grade sulfur hexafluoride (SF6) for use in electrical equipment.

    This International Standard defines the quality requirements and properties for technical grade sulfur hexafluoride (SF6) for

    use in electrical equipment. It covers the properties and methods of test applicable to SF6 when this substance is supplied

    for use in connection with any electrical equipment. This second edition differs widely from the first one. The focus is now

    on the specification of the gas needed for electrical applications. As a consequence, the term employed to name this gas is

    'technical grade' in place of 'new'. Based on experience, the acceptable impurity levels have been increased. However, the

    gas as defined in this new second edition has the same performance in electrical equipment as the gas previously defined in

    the first edition. The analytical methods for the SF6 analysis have been removed as it has been found confusing to prescribe

    methods that can become obsolete very rapidly.

  • NORMAS TCNICAS

    IEC 60427 - Synthetic Testing of High-Voltage Alternating Current Circuit-Breakers

    Scope:

    This International Standard applies to a.c. circuit-breakers within the scope of IEC 60056. It provides the general rules fortesting a.c. circuit-breakers, for making and breaking capacities over the range of test-duties described in 6.102 to 6.111 ofIEC 60056, by synthetic methods.

    NOTE Circuits for the test duties described in 6.111 have not yet been standardized. However, present methods are given in annex GG.

    The methods and techniques described are those in general use. The purpose of this standard is to establish criteria for synthetic testing and for the proper evaluation of results. Such criteria will establish the validity of the test method withoutimposing restraints on innovation of test circuitry

  • Accesorios

    Dispositivos para igualar tensiones:

    Se utilizan condensadores en paralelo con los contactos

    Resistencias de pre-insercin:

    Se instalan en paralelo con los contactos, sirven para reducir las sobretensiones

    Conectores de alta tensin y para puesta a tierra

    Indicador de posicin

  • FENMENO DE INTERRUPCIN MANIOBRA: CIERRE

    Posicin cerrado

    Posicin abierto

    Aparicin del arco

    (todos los polos)Energizacin bobina

    de cierre

    Cierre del contacto

    (todos los polos)

    T ( armado)

    T ( cierre)

    T ( pre-arco)

    Con resistencia de

    pre-insercin Flujo de corriente

  • FENMENO DE INTERRUPCIN MANIOBRA: APERTURA

    Posicin cerrado

    Posicin abierto

    Aparicin del arco

    (todos los polos)Energizacin bobina

    de aperturaExtincin del arco

    (todos los polos)

    T ( apertura)

    T ( desarmado)

    T ( arco)

    Flujo de corriente

  • CARACTERSTICAS TCNICAS

    Tensin transitoria de recuperacin (TTR)

    Es el valor de la tensin transitoria que aparece entre los contactos del interruptor cuando se extingue el arco

    Para fallas terminales

    Fallas en lneas cortas

    Interrupcin de pequeas corrientes capacitivas

    Interrupcin de pequeas corrientes inductivas

    Recierre de lneas

  • FENMENO DE INTERRUPCIN : FALLA

    Corriente

    Tensin

    Separacin

    contactoInicio separacin

    contactoSeparacin

    contactoInicio separacin

    contacto

    Ur

    TTR / TRV

    TTR/TRV IDEAL TTR/TRV REAL

    TTR: Tensin transitoria de recuperacin

    TRV: Transient recovery voltage

  • CARACTERSTICAS TCNICAS QUE SE ESPECIFICAN

    Tiempo de apertura:

    Puede ser en ciclos o en ms: valores tpicos

    Para 245 kV: 2,5 ciclos o 40 ms

    Para 500 kV: 3 ciclos o 50 ms

    Secuencia de maniobra asignada

    O - t - CO - t- CO

    t: 3 min cuando no se requiere recierre rpido

    t: 0,3 s para recierres rpidos

    t: 3 minutos

    O - t - CO

    t: 15 s

  • CARACTERSTICAS TCNICAS

    Poder de corte asignado en cortocircuito: Valor mas alto de la corriente de cortocircuito que el interruptor debe ser capaz de abrir Ik

    Poder de cierre asignado en cortocircuito: Valor pico de corriente de cortocircuito que el interruptor debe poder cerrar, 2,6 x Ik

  • CARACTERSTICAS TCNICAS QUE SE ESPECIFICAN

    Tensin asignada

    Niveles de aislamiento

    Corriente asignada en servicio continuo

    Frecuencia asignada

    Duracin asignada del cortocircuito

    Lnea de fuga

    Tensin asignada para la alimentacin de los circuitos de apertura y cierre

    Presin asignada del gas para operacin o interrupcin

    Factor de primer polo

  • PRUEBAS

    Pruebas de rutina

    Tensin aplicada a frecuencia industrial, en seco, en el circuito principal

    Tensin aplicada en los circuitos auxiliares y de control

    Medida de la resistencia del circuito principal

    Funcionamiento mecnico

    Verificacin visual

  • PRUEBAS

    Pruebas tipo

    Pruebas dielctricas:

    Impulso tipo rayo

    Impulso tipo maniobra

    Tensin soportada a frecuencia industrial

    Descargas parciales

    Pruebas en circuitos auxiliares y de control

  • PRUEBAS

    Pruebas tipo

    Tensin de radio interferencia (r.i.v.)

    Incremento de temperatura

    Medida de la resistencia del circuito principal

    Pruebas de corrientes pico y de corto tiempo

    Pruebas mecnicas y ambientales

  • PRUEBAS

    Pruebas tipo

    Pruebas de interrupcin y cierre de corrientes de corto circuito

    Corrientes crticas

    Interrupcin de corto circuito monofsico

    Interrupcin de fallas kilomtricas

    Apertura y cierre de corrientes fuera de fase

    Maniobra de corrientes capacitivas

    Maniobra de corrientes de magnetizacin y de pequeas corrientes inductivas

  • 1.3.2 INTERRUPTORES DE POTENCIA1.3.2 INTERRUPTORES DE POTENCIA