kele control dif presion aire

2
PRESSURE PSI KELE • www.kele.com USA 901-937-4900 • International 901-382-6084 KELE • www.kele.com USA 901-937-4900 • International 901-382-6084 PRESSURE CONTROLLER MODEL PCM Supply voltage 24 VDC +15%,-10% @ 75 mA max Accuracy ±2% of range including non-linearity and hysteresis Output 4-20 mA sourcing Output resolution 255 steps Output burden 650max Port connections 3/16'' dia suitable for 1/4'' OD polyethylene tubing Max overpressure 800% of the pressure range Temp Operating 32° to 125°F (0° to 52°C) Humidity Limit 0% to 90% noncondensing Local set point input Built-in three-wire potentio- meter (factory setting) Remote set point input 4-20 mA, 1-5 VDC Weight 1.3 lb (0.61 kg) DESCRIPTION The Model PCM Pressure Controller is a low-air pres- sure transducer combined with a microprocessor-based proportional or Proportional plus Integral (PI) controller. The compact size and ease of installation and setup makes this unit ideal for standard HVAC applications. Ranges are available from 0" to 2", 3", or 5'' W.C. The set point adjustment knob is clearly marked with the appropriate scale for ease of use. All setup and tuning is easily accomplished by DIP switches and bottle plug jumpers. Mounting is a snap with the convenient mount- ing tabs or with the DIN rail mounting option. Remote set point is also possible with voltage or milliamp signals. The Model PCM can be configured for direct or reverse acting control. FEATURES Proportional or PI control Easy setup DIP switch/jumper setup and tuning Selectable proportional band Selectable integral reset rate Direct or reverse acting Optional DIN rail mounting Compact size Position insensitive APPLICATIONS Controlling duct pressures Isolation rooms VAV systems Inlet guide vanes and VFDs Paint booths Relief damper control Pressure bypass damper control 1.5 (3.81) 4.8 (12.19) 2.9 (7.37) 4.0 (10.16) 3.4 (8.64) 0.7 (1.78) 4.6 (11.68) 2.0 (5.08) 2.75 (6.99) Mounting Slots for Optional DIN Rail Adapter Set Point Knob High Pressure Port Low Pressure Port Pressure Ports in (cm) DIMENSIONS SPECIFICATIONS

Upload: carlos-enrique-godoy-sifontes

Post on 14-Sep-2015

11 views

Category:

Documents


4 download

DESCRIPTION

catalogo sensor diferencial de presion de aire

TRANSCRIPT

  • PRESSURE PSI

    KELE www.kele.com USA 901-937-4900 International 901-382-6084KELE www.kele.com USA 901-937-4900 International 901-382-6084

    PRESSURE CONTROLLERMODEL PCM

    Supply voltage 24 VDC +15%,-10% @75 mA max

    Accuracy 2% of range includingnon-linearity and hysteresis

    Output 4-20 mA sourcingOutput resolution 255 stepsOutput burden 650 maxPort connections 3/16'' dia suitable for

    1/4'' OD polyethylene tubing

    Max overpressure 800% of the pressure rangeTemp

    Operating 32 to 125F (0 to 52C)Humidity

    Limit 0% to 90% noncondensingLocal set point input Built-in three-wire potentio-

    meter (factory setting) Remote set point input 4-20 mA, 1-5 VDCWeight 1.3 lb (0.61 kg)

    DESCRIPTIONThe Model PCM Pressure Controller is a low-air pres-sure transducer combined with a microprocessor-basedproportional or Proportional plus Integral (PI) controller.The compact size and ease of installation and setupmakes this unit ideal for standard HVAC applications.Ranges are available from 0" to 2", 3", or 5'' W.C. Theset point adjustment knob is clearly marked with theappropriate scale for ease of use. All setup and tuning iseasily accomplished by DIP switches and bottle plugjumpers. Mounting is a snap with the convenient mount-ing tabs or with the DIN rail mounting option. Remote setpoint is also possible with voltage or milliamp signals.The Model PCM can be configured for direct or reverseacting control.

    FEATURES

    Proportional or PI control Easy setup DIP switch/jumper setup and tuning Selectable proportional band Selectable integral reset rate Direct or reverse acting Optional DIN rail mounting Compact size Position insensitive

    APPLICATIONS Controlling duct pressures Isolation rooms VAV systems Inlet guide vanes and VFDs Paint booths Relief damper control Pressure bypass damper control

    1.5(3.81)

    4.8(12.19)

    2.9(7.37)

    4.0(10.16)

    3.4(8.64)

    0.7(1.78)

    4.6(11.68)

    2.0(5.08)

    2.75(6.99)

    Mounting Slotsfor Optional

    DIN RailAdapter

    Set Point Knob

    High Pressure PortLow Pressure Port

    Pressure Ports

    in(cm)

    DIMENSIONS

    SPECIFICATIONS

  • PRESSURE PSI

    KELE www.kele.com USA 901-937-4900 International 901-382-6084

    PWM INPUTPWM INPUT

    REM SPT INPUT

    LOC SPT POT +

    LOC SPT INPUT

    LOC SPT POT

    FEEDBK INPUT24 PWR

    COMMONMA SIG

    OUTPUT

    LOCA

    LSE

    T PO

    INT

    FEED

    BACK

    REM

    OTE

    SE

    T PO

    INT

    B

    A1 2 3 4 5 6 7 8

    1 2 3 4 5 6 7 8

    4-20 mA Sourcing Output Signal toControlled Device

    +

    PCM DIP SWITCH SETTINGS1=ON 0=OFF

    PCM JUMPER POSITIONS

    A1 0 1A2 1 0

    Local Set Point Remote Set Point

    A3 0 1Reverse Acting Direct Acting

    Reset Per Minute Rate

    Proportional Throttling Range Settings

    OFF 0.5 1.0 2.0A4 0 0 1 1A5 0 1 0 1

    This Unit'sRange Is:0-2''W.C.0-3''W.C.0-5''W.C.

    10% 20% 35% 50% 65% 80% 90% 100%A6 0 0 0 0 1 1 1 1A7 0 0 1 1 0 0 1 1A8 0 1 0 1 0 1 0 1

    All B switches should be in the off positionLocal Set Point Jumper Positions 1, 8, & 11For Remote Set Point: Voltage Input Jumper Positions 2, 8, & 11 Current Input Jumper Positions 1, 8, & 11

    ON

    ON

    12

    3456

    78910

    + 24 VDC Power

    1112

    Remote Set Point Input 4-20 mA or 1-5VRemote Set Point

    +

    Common

    Optional Remote Set Point Wiring4-20 mA or 1-5 VDC

    1. Switch A1 off and switch A2 on.2. Set jumper positions to 1, 8, and 11.3. Set switch A3 in the on position for direct acting con-

    trol and in the off position for reverse acting control.4. Set switches A4 and A5 in the off position.5. Set switches A6, A7, and A8 in the on position. This

    will set the proportional band at 100%. 6. Set all B switches to the off position.

    7. All systems will require a fine-tuning process. Startthe tuning process by decreasing the proportionalband in increments through switches A6 through A8until the system begins to hunt. Then, return to theDIP switch settings before the system started to hunt.

    8. Switches A4 and A5 are used to select the integralreset rate. This feature corrects the offset that isinherent with proportional-only controllers. If it isdetermined that the integral reset is needed, increasethe rate until this offset is corrected and still maintainsstability.

    PRESSURE CONTROLLERMODEL PCM

    WIRING

    ORDERING INFORMATION

    SETUP FOR LOCAL SET POINT OPERATION (FACTORY SETTINGS)

    MODEL DESCRIPTIONPCM Pressure Set Point Controller

    PRESSURE RANGE020 0" to 2'' W.C.030 0" to 3'' W.C.050 0" to 5'' W.C.

    OPTIONS47 DIN rail mounting (must be factory installed)

    PCM 47020 Example: PCM-020-47 Pressure controller for a0" to 2'' W.C. range with DIN rail mounting