lab1 eps fina
DESCRIPTION
lab epsTRANSCRIPT
-
5/21/2018 Lab1 EPS Fina
1/13
LAB 1: Transmission and Distribution Systems
NURUL SHAFINA BT RAZALI
EA11053(SECTION: 03)
DATE: 22 APRIL (SEM 2 2013/14)
ABSTRACT Electric-power transmission is the
bulk transfer of electrical energy, from
generati ng power plants to electr ical substations
located near demand centers. Thi s is distinct f rom
the local wir ing between high-voltage substations
and customers, which is typical ly referred to as
electric power distribution. Transmission lines,
when interconnected with each other, become
transmission networks. The combined
transmission and distr ibution network i s known
as the " power gr id" in the Uni ted States, or just
" the grid" . In the Uni ted Kingdom, the network is
known as the " National Grid"
INTRODUCTION
Distribution is a part of the electrical utility system
between the bulk power source and the consumersservice switches and normally operated below 100
kV.
Sub transmission system deliver energy from bulk
power sources to the distribution substations. The
voltage is about between 34.5 and 138 kV. Thedistribution substation reduces the sub
transmission voltage to a lower primary system
voltage for local distribution (using power
transformer)
There are three basic types of distribution system
designs that is Radial, Loop, or Network.
We can use combinations of these three systems,and this is frequently done.
Electric utilities aim to provide service tocustomers at a specific voltage level, for example,
220V or 240V. However, due to Kirchhoff's Laws,
the voltage magnitude and thus the service voltageto customers will in fact vary along the length of a
conductor such as a distribution feeder.
Jn order to maintain voltage within tolerance unchanging load conditions, various types of devi
are traditionally employed
a load tap changer (LTC) at the substat
transformer, which changes the turns ratio
response to load current and thereby adjusts voltage supplied at the sending end of the feeder
voltage regulators, which are essentia
transformers with tap changers to adjust
voltage along the feeder, so as to compensate the voltage drop over distance; and
capacitors, which reduce the voltage drop alo
the feeder by reducing current flow to lo
consuming reactive power.
Radial Distr ibut ion Systems
The Radial distribution system is the cheapestbuild, and is widely used in sparsely popula
areas. A radial system has only one power soufor a group of customers. A power failure, shcircuit, or a downed power line would interr
power in the entire line which must be fixed bef
power can be restored.
Electricity suppliers normally use rad
distribution in rural areas where the load
randomly distributed, separated by areas with lior no habitation, and back up supplies are norma
not available. The length of feeder is typica
limited to 500 m or less. In the radial distributsystem, feeders supplying the consumers are all from a central point (the substation) as shown
Figure 1. There is no looping of the feeders.
-
5/21/2018 Lab1 EPS Fina
2/13
FIGURE 1
Ring Di str ibution Systems
A loop system, as the name implies, loopsthrough the service area and returns to the original
point. The loop is usually tied into an alternatepower source. By placing switches in strategic
locations, the utility can supply power to the
customer from either direction.
If one source of power fails, switches are thrown
(automatically or manually), and power can be fedto customers from the other source.
The loop system provides better continuity ofservice than the radial system, with only short
interruptions for switching. In the event of power
failures due to faults on the line, the utility hasonly to find the fault and switch around it to restore
service. The fault itself can then be repaired with a
minimum of customer interruptions.
The loop system is more expensive than the radial
because more switches and conductors are
required, but the resultant improved system
reliability is often worth the price.
This is commonly used in urban areas with high
housing density. In such a system, LV cables from
neighbouring distribution substations are either
looped together or are terminated very close to oneanother where an interconnection of cables can be
made. This system is normally used when a high
degree of reliability of load supply is required andback up substations is made available. Figure 2
shows a schematic diagram for a ring distribut
network.
FIGURE 2
Voltage Regulation
Voltage regulation is a measure of change in
voltage magnitude between the sending
receiving end of a component, such astransmission or distribution line. Volt
regulation describes the ability of a system
provide near constant voltage over a wide range
load conditions.
A voltage phasor diagram can be drawn for equivalent circuit as shown in Figure 3,
considering the current, I, to be equal to the sum
two currents, Ip and Iq, that are at right angles
each other. Ip is in phase with Vr and Iq lags Vr900.
Figure 3: Generator Feeding a Large Pow
System
-
5/21/2018 Lab1 EPS Fina
3/13
The resulting phasor diagram for a lagging p.f.
load is shown in Figure 4.
Figure 4: Resulting Phasor Diagram for a lagging
p.f load
From this diagram,
222
qprs VVVV (1.1)
If is small,
rs VV = qpp XIRIV (1.2)
And, therefore,
r
qp
pV
QIPIV
(1.3)
If the load is capacitive or leading p.f. load, the
plus sign becomes a minus sign. Similarly, it is
seen that:
r
qpqV
QRPXRIXIV
(1
Thus, if X/R > 1, the flow of reactive power
determines the voltage drop and the flow of powP, determines the transmission angle and th
statements are substantially independent of e
other.
The objectives for this Lab 1 are to investig
the effect of loading and feeder length on
voltage regulation in a radial distribution netwfeeding a resistive load, to investigate the eff
that the inductive and capacitive loads have up
the voltage regulation of a radial feeder andinvestigate the voltage regulation for a simple r
distribution network when it supplies resisti
inductive and capacitive loads. Also, to mak
comparison between the results obtained with
corresponding results for the radial network.
I. PROCEDURE
Experiment 1: Single-Phase Radial Netw
Feeding a Resistive Load
Procedure A: One Section of the Feeder
1)
One phase of the supply line and the neu
line is connected to one phase of resistive loas shown in Appendix A. Ensure that
secondary of the CT is short-circuited.2) CB1 and CB2 have been closed to connect
circuit.3)
The Neutral Switch has been closedconnect the circuit to the ground
4) The supply is switched on and the load is se
25%. This should give the load current roug1.25A. The readings for load (receive) volt
Vr, supply voltage Vs and load current, I h
been taken.5) Step (3) is repeated for 50%, 75% and 10
and recorded it in Table 1.
Procedure B: Two Section of the Feeder
1) Procedure A is repeated, but with two secti
of the line 1 connected in series and the t
-
5/21/2018 Lab1 EPS Fina
4/13
sections of the Neutral line are connected in
series as shown in Appendix B. The resultsare recorded in Table 2.
Experiment 2: Single-Phase Radial Network
Feeding I nductive and Capaciti ve Loads
Procedure A: Inductive Load
1) On the three-phase circuit of the trainer, two
sections of the red phase and the neutral linesare connected to one phase of the inductive
load as shown in Appendix C. Ensure that the
secondary of the CT is short-circuited.2)
CB1 and CB2 are closed to connect thecircuit.
3) The Neutral Switch has been closed to connect
the circuit to the ground4)
The supply is switched on and the load is set
to 25%. The readings for load (receive)voltage Vr, supply voltage Vsand load current,
Ihave been taken.5) Step (3) is repeated, for 50%, 75% and 100%
and recorded it in Table 3.
Procedure B: Capacitive Load
1) A blank table is created as in Table 3 and
replaced the inductive load by a capacitiveload, repeat Procedure A.
Experiment 3: Ring Distribution Network
Supplying Resistive, Inductive and Capacitive
Loads
Procedure A: Resistive Load
1)
A resistive load is connected to the midpoint(TP4) of the red phase sections that are fed
from the two points (TP2) and (TP3) as shown
in Appendix D.2)
Temporarily disconnected the load, the supply
is switched on and no load receive voltage
(VnL) reading has been taken. CB1 and CB2 are
closed to connect the circuit.3) The load is reconnected and the load is set to
25%. The readings for load (receive) voltage
Vr, supply voltage Vs and load current, I h
been taken.4) Step (3) is repeated, for 50%, 75% and 10
and recorded it in Table 4. The central mete
used to measure Vr.
Procedure B: Inductive Load
1) A blank table is created as in Table 4.
2) The resistive load is replaced with an induct
load and Procedure A is repeated.
Procedure C: Capacitive Load
1) A blank table is created as in Table 4.
2)
The inductive load is replaced with a capacitload and steps (3) and (4) in Procedure A
repeated.
II. RESULTS
Experiment 1: Single-Phase Radial Netw
Feeding a Resistive Load
Table 1: One Section of the Feeder.
Load I
25% 132.10 V 131.26 V 1441.5 m
50% 131.76 V 130.03 V 2.81 A
75% 131.05 V 128.23 V 4.29 A
100% 130.52 V 127.09 V 5.58 A
Table 2: Two Sections of the Feeder in
Series.
Load I
25% 132.17 V 130.89 V 1429.0 m
50% 131.43 V 128.67 V 2.754 A
75% 130.85 V 125.90 V 4.213 A
100% 130.30 V 123.79 V 5.423 A
-
5/21/2018 Lab1 EPS Fina
5/13
R
Generator
1 2
X21
Resis
Load
Experiment 2: Single-Phase Radial Network
Feeding I nductive and Capaciti ve Loads
Table 3A: Inductive Load.
Load I
25% 132.44 V 127.11 V 1202.5 mA
50% 132.35 V 120.96 V 2.396 A
75% 132.17 V 114.93 V 3.581 A
100% 130.01 V 111.00 V 4.418 A
Table 3B: Capacitive Load.
Load I
25% 133.88 V 140.48 V 1525.5 mA
50% 133.30 V 149.28 V 3.285 A
75% 133.47 V 145.69 V 5.232 A
100% 133.67 V 150.64 V 7.385 A
Experiment 3: Ring Distribution Network
Supplying Resistive, Inductive and Capacitive
Loads
Table 4A: Ring Network with Resistive Load.
= 132.05 V
Load I%
Regulation
25%132.36
V
130.68
V
143.5
mA0.26
50%131.93
V
130.48
V
2783.8
mA0.41
75%131.13
V
128.65
V
4270.0
mA1.84
100%130.65
V
127.31
V5.557A 2.91
Table 4B: Ring Network with Inductive Load.
= 132.41 V
Load I%
Regulation
25%132.77
V
129.96
V
1234.6
mA1.89
50%132.51
V
126.38
V
2519.4
mA4.77
75%132.28
V
123.09
V
3839.8
mA7.57
100%132.09
V
120.67
V
4.828
A9.73
Table 4C: Ring Network with Capacitive Loa
=133.10 V
Load I%
Regulati
25%133.21
V136.92
V1492.8
mA2.79
50% 133.34V
141.10V
3080.4mA
5.67
75%133.71
V145.43
V4.781
A8.48
100%133.89
V
149.55
V
6.594
A10.99
III. DISCUSSIONS
Experiment 1: Single-Phase Radial NetwFeeding a Resistive Load
Procedure A: One Section of the Feeder
Circuit diagram obtained from the connection
Appendix A;
-
5/21/2018 Lab1 EPS Fina
6/13
The percentage regulation using the Equation 1.5
for each load setting;
% Regulation = 100
r
rs
V
VV (1.5)
For load: 25%
For load: 50%
For load: 75%
For load: 100%
The percentage regulation against load cur rent;
Graph 1.1
As we can see from the Graph 1.1, the
percentage regulation is increases due to the load
current increases. Regarding to Ohms Law, V=IR
it states that current flowing is directlyproportional to the voltage and inversely
proportional to the resistance. Therefore, if the
voltage is increased, the current will increase if the
resistance of the circuit does not change. Sa
goes to the increasing resistance of the circuit wlower the current flow if the voltage is
changed. This formula shows that there
relationship between this three variable.
Procedure B: Two Section of the Feeder
The circuit diagram obtained from the connectio
in Appendix B;
The percentage regulation using the Equation
for each load setting;
For load: 25%
For load: 50%
For load: 75%
For load: 100%
0
2
4
6
0 1 2 3 4 5 6Percentageregulation(%)
Load current (A)
Percentage Regulation against load current for one
section of the feeder
-
5/21/2018 Lab1 EPS Fina
7/13
X2
1 2
R
Generator
1 2
X21
R221
Inductive
Load
The percentage regulation against load current;
Graph 1.2
Compar ison of the regulation- load current
curves obtained when one section and two
sections of the feeder are used to supply the load;
Graph 1.3
In the Graph 1.3, the line curve percentageregulation for two sections of the feeder is higher
than line curve percentage regulation for onesection of the feeder. Based on the Ohms Law. the
voltage will be higher as the impedance is increase
and that will lead to the higher percentageregulation. In this experiment, the impedances for
two feeders, are higher rather than one feeder,
Based on the results, current is one of
factors that determine the voltage regulation . the percentage of load current is negative,
percentage regulation will be increase. Length
the feeder also one of the factors that will affect
voltage regulation. The percentage regulation wbe increase if we increase the length of the feede
So, we can see the effect of loading feeder length on the voltage regulation in a rad
distribution network feeding a resistive load.
Experiment 2: Single-Phase Radial Netw
Feeding I nductive and Capaciti ve Loads
Procedure A: Inductive Load
The circuit diagram obtained from the connectio
in Appendix C;
The percentage regulation using the Equation 1.for each load setting.
% Regulation = 100
r
rs
V
VV (1.6)
For load: 25%
For load: 50%
For load: 75%
0
1
2
3
4
5
6
0 1 2 3 4 5 6
Percentageregulation(%)
Load current(A)
Percentage Regulation against load current for two
section of the feeder
0
2
4
6
0 1 2 3 4 5 6Percentageregulation(%)
Load current(A)
Percentage regulation against load current for one and
two section of the feeder.
one section of
the feeder
two sections of
the feeder
-
5/21/2018 Lab1 EPS Fina
8/13
For load: 100%
Graph 2.1
Compar ison of the regulati on- load cur rentcurves obtained for inductive load and resistive
load;
Graph 2.2
As we can see in Graph 2.2, inductive l
having higher percentage regulation than resistload. It is show that inductive load has m
voltage loss when compared to resistive load.
Procedure B: Capacitive Load
The percentage regulation using the Equation 1.for each load setting.
For load: 25%
For load: 50%
For load: 75%
For load: 100%
0
2
4
68
10
12
14
16
18
20
0 1 2 3 4 5
Percentageregulation(%)
Load currents(A)
Percentage regulation against load current for inductive
load
0
2
4
6
8
10
12
14
16
18
20
0 1 2 3 4 5 6
Percentage
regulation(%)
Load current (A)
Percentage regulation against load current for inductive
load and resistive load
inductive load
resistive load
0
2
4
6
8
10
12
0 2 4 6 8
Percentageregulation(%)
Load current (A)
Percentage regulation against load current for capacitive
load
-
5/21/2018 Lab1 EPS Fina
9/13
X2
1
2
R
Generator1
2
X
2
1
R2
2
1
Resistive
Load
Graph 2.3
Compar ison of the regulati on- load cur rent
curves obtained for capacitive load and inductive
load;
Graph 2.4
Based on calculation, capacitive load actually
having negative percentage regulation. So,
theoretically, the percentage regulation for
capacitive load is less than inductive load.
For the inductor, assume the current through is
it same as resistor, and the voltage across theinductor is
which transforms to the phasor,
but , and , thus
showing that the voltage has a magnitude of
and a phase of The voltage and current
are out of phase. Specifically, the current lthe voltage by .
For the capacitor, assume the voltage acros
is while the current throuthe capacitor is
And by referring to steps as we took for inductor, we obtain
showing that the current and voltage are ouphase. To be specific, the current leads the volt
by . And this explain why capacitive loresults in less voltage regulation than induct
loads.
Experiment 3: Ring Distribution Netw
Supplying Resistive, Inductive and Capaci
Loads
Procedure A: Resistive Load
The circuit diagram obtained from the connect
in Appendix D (for resistive load);
The percentage regulation for each load using expression;
% Regulation = 100
r
rnL
V
VV (1.7
0
2
4
6
8
10
12
14
16
18
20
0 2 4 6 8
Percentageregulation(%)
Load current (A)
Percentage regulation against load current for capacitive
load and inductive load
inductive
capacitive
load
-
5/21/2018 Lab1 EPS Fina
10/13
InductiveLoadGenerator
2
1
1
2
X2
1
2
R R2
2
1
X
For load: 25%
For load: 50%
For load: 75%
For load: 100%
Comparison results for the voltage regulation
with the corr esponding resul ts obtained from the
radial feeder in Experiment 1;
Graph 3.1
As can be seen in Graph 3.1, radial feeder
curve is slightly different than ring feeder. Thepercentage regulation are almost the same for the
second , third and fourth point of the radial and
ring network.
Procedure B: Inductive Load
The circuit diagram obtained from the connect
in Appendix D (for inductive load);
The percentage regulation for each load using
expression 1.6;
For load: 25%
For load: 50%
For load: 75%
For load: 100%
Comparison results for the voltage regulat
with the corresponding resul ts obtained from
radial feeder in Experiment 2;
0
0.5
1
1.5
2
2.5
3
3.5
0 1 2 3 4 5 6
Percentageregulation(%)
load current (A)
Percentage regulation against load current for radial
network resistive load and radial network resistive load
radial
network
resistive load
ring network
resistive load
-
5/21/2018 Lab1 EPS Fina
11/13
CapacitiveLoadGenerator
2
1
1
2
X2
1
2
R R2
2
1
X
Graph 3.2
Referring to Graph 3.2, radial feeder curve
regulation-load current is rising higher than ring
feeder for each point.
Procedure C: Capacitive Load
The circuit diagram obtained from the connection
in Appendix D (for capacitive load);
The percentage regulation for each load using the
expression 1.6;
For load: 25%
For load: 50%
For load: 75%
For load: 100%
Comparison results for the voltage regulat
with the corresponding resul ts obtained from radial feeder in Experiment 2;
Graph 3.3
The effect of load power factor upon volta
regulation for each of resistive, inductive a
capacit ive loads;
0
2
4
6
8
1012
14
16
18
20
0 2 4 6
Percentageregula
tion(%)
Load current (A)
Percentage regulation against load current for inductive
load in radial and ring feeder
radial
networkinductive
load
ring network
inductive
load
0246810
12141618202224
0 2 4 6 8
Percentageregulation(%)
Load current (A)
Percentage regulation against load current for capacitive
load in radial and ring feeder
radial
network
capacitive
load
ring netwo
capacitive
load
-
5/21/2018 Lab1 EPS Fina
12/13
Graph 3.4
In this experiment, we can calculate the"power factor", which is defined as the cosine of
this angle based on the phase difference betweenthe voltage and current signals. In an electricpower system, a load with a low power factor
draws more current than a load with a high power
factor for the same amount of useful power
transferred. The higher currents increase theenergy lost in the distribution system, and require
larger wires and other equipment. Because of the
costs of larger equipment and wasted energy,electrical utilities will usually charge a higher cost
to industrial or commercial customers where there
is a low power factor.
Linear loads with low power factor (such as
induction motors) can be corrected with a passive
network of capacitors or inductors. Non-linearloads, such as rectifiers, distort the current drawn
from the system. In such cases, active or passive
power factor correction may be used to counteractthe distortion and raise the power factor. The
devices for correction of the power factor may be
at a central substation, spread out over a
distribution system, or built into power-consumingequipment.
In a purely resistive AC circuit, voltage and
current waveforms are in step (or in phase),changing polarity at the same instant in each cycle.
All the power entering the load is consumed (or
dissipated). Where reactive loads are present, suchas with capacitors or inductors, energy storage in
the loads results in a time difference between the
current and voltage waveforms.
If a load had a capacitive value, induct
(also known as reactors in this context) connected to correct the power factor. In
electricity industry, inductors are said to consu
reactive power and capacitors are said to supply
even though the energy is just moving back forth on each AC cycle.
When the load is inductive, the inducta
tends to oppose the flow of current, storing ene
then releasing it later in the cycle. The currwaveform lags behind the voltage wavefo
When the load is capacitive, the opposite occu
and the current waveform leads the volt
waveform.
So, lagging and leading is another way o
saying the net reactance is either inductive or
capacitive.
IV. CONCLUSION
As a conclusion, we can say since the volt
drop for the ring network is lower than radnetwork, it means that the ring distribution netw
is better than radial network. All the objectives
this experiment are achieved as we assure
managed to investigate the effect of loading
feeder length on the voltage regulation in a raddistribution network feeding a resistive load,
effect that the inductive and capacitive loads hupon the voltage regulation of a radial feeder,
the voltage regulation for a simple ring distribut
network when it supplies resistive, inductive a
capacitive loads. Other than that, we also mcomparison between ring and radial networks.
V. REFERENCES
1. http://en.wikipedia.org/wiki/Power_f
or
2. http://www.allaboutcircuits.com/vol_2
pt_11/3.html
3.
http://en.wikipedia.org/wiki/Electric_p
er_transmission
0
12
3
4
5
6
7
0 2 4 6 8
Percentageregulations(%)
Load current (A)
Percentage regulation against load current for resistive,
inductive and capacitive load
resistive load
inductive load
capacitive
load
http://en.wikipedia.org/wiki/Power_factorhttp://en.wikipedia.org/wiki/Power_factorhttp://en.wikipedia.org/wiki/Power_factorhttp://en.wikipedia.org/wiki/Power_factorhttp://en.wikipedia.org/wiki/Power_factorhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://en.wikipedia.org/wiki/Power_factorhttp://en.wikipedia.org/wiki/Power_factor -
5/21/2018 Lab1 EPS Fina
13/13
4. http://epb.apogee.net/foe/home.asp
5. http://yourelectrichome.blogspot.com
http://epb.apogee.net/foe/home.asphttp://epb.apogee.net/foe/home.asphttp://yourelectrichome.blogspot.com/http://yourelectrichome.blogspot.com/http://yourelectrichome.blogspot.com/http://epb.apogee.net/foe/home.asp