lab1 eps fina

Upload: jorge-nelson

Post on 12-Oct-2015

172 views

Category:

Documents


0 download

DESCRIPTION

lab eps

TRANSCRIPT

  • 5/21/2018 Lab1 EPS Fina

    1/13

    LAB 1: Transmission and Distribution Systems

    NURUL SHAFINA BT RAZALI

    EA11053(SECTION: 03)

    DATE: 22 APRIL (SEM 2 2013/14)

    [email protected]

    ABSTRACT Electric-power transmission is the

    bulk transfer of electrical energy, from

    generati ng power plants to electr ical substations

    located near demand centers. Thi s is distinct f rom

    the local wir ing between high-voltage substations

    and customers, which is typical ly referred to as

    electric power distribution. Transmission lines,

    when interconnected with each other, become

    transmission networks. The combined

    transmission and distr ibution network i s known

    as the " power gr id" in the Uni ted States, or just

    " the grid" . In the Uni ted Kingdom, the network is

    known as the " National Grid"

    INTRODUCTION

    Distribution is a part of the electrical utility system

    between the bulk power source and the consumersservice switches and normally operated below 100

    kV.

    Sub transmission system deliver energy from bulk

    power sources to the distribution substations. The

    voltage is about between 34.5 and 138 kV. Thedistribution substation reduces the sub

    transmission voltage to a lower primary system

    voltage for local distribution (using power

    transformer)

    There are three basic types of distribution system

    designs that is Radial, Loop, or Network.

    We can use combinations of these three systems,and this is frequently done.

    Electric utilities aim to provide service tocustomers at a specific voltage level, for example,

    220V or 240V. However, due to Kirchhoff's Laws,

    the voltage magnitude and thus the service voltageto customers will in fact vary along the length of a

    conductor such as a distribution feeder.

    Jn order to maintain voltage within tolerance unchanging load conditions, various types of devi

    are traditionally employed

    a load tap changer (LTC) at the substat

    transformer, which changes the turns ratio

    response to load current and thereby adjusts voltage supplied at the sending end of the feeder

    voltage regulators, which are essentia

    transformers with tap changers to adjust

    voltage along the feeder, so as to compensate the voltage drop over distance; and

    capacitors, which reduce the voltage drop alo

    the feeder by reducing current flow to lo

    consuming reactive power.

    Radial Distr ibut ion Systems

    The Radial distribution system is the cheapestbuild, and is widely used in sparsely popula

    areas. A radial system has only one power soufor a group of customers. A power failure, shcircuit, or a downed power line would interr

    power in the entire line which must be fixed bef

    power can be restored.

    Electricity suppliers normally use rad

    distribution in rural areas where the load

    randomly distributed, separated by areas with lior no habitation, and back up supplies are norma

    not available. The length of feeder is typica

    limited to 500 m or less. In the radial distributsystem, feeders supplying the consumers are all from a central point (the substation) as shown

    Figure 1. There is no looping of the feeders.

  • 5/21/2018 Lab1 EPS Fina

    2/13

    FIGURE 1

    Ring Di str ibution Systems

    A loop system, as the name implies, loopsthrough the service area and returns to the original

    point. The loop is usually tied into an alternatepower source. By placing switches in strategic

    locations, the utility can supply power to the

    customer from either direction.

    If one source of power fails, switches are thrown

    (automatically or manually), and power can be fedto customers from the other source.

    The loop system provides better continuity ofservice than the radial system, with only short

    interruptions for switching. In the event of power

    failures due to faults on the line, the utility hasonly to find the fault and switch around it to restore

    service. The fault itself can then be repaired with a

    minimum of customer interruptions.

    The loop system is more expensive than the radial

    because more switches and conductors are

    required, but the resultant improved system

    reliability is often worth the price.

    This is commonly used in urban areas with high

    housing density. In such a system, LV cables from

    neighbouring distribution substations are either

    looped together or are terminated very close to oneanother where an interconnection of cables can be

    made. This system is normally used when a high

    degree of reliability of load supply is required andback up substations is made available. Figure 2

    shows a schematic diagram for a ring distribut

    network.

    FIGURE 2

    Voltage Regulation

    Voltage regulation is a measure of change in

    voltage magnitude between the sending

    receiving end of a component, such astransmission or distribution line. Volt

    regulation describes the ability of a system

    provide near constant voltage over a wide range

    load conditions.

    A voltage phasor diagram can be drawn for equivalent circuit as shown in Figure 3,

    considering the current, I, to be equal to the sum

    two currents, Ip and Iq, that are at right angles

    each other. Ip is in phase with Vr and Iq lags Vr900.

    Figure 3: Generator Feeding a Large Pow

    System

  • 5/21/2018 Lab1 EPS Fina

    3/13

    The resulting phasor diagram for a lagging p.f.

    load is shown in Figure 4.

    Figure 4: Resulting Phasor Diagram for a lagging

    p.f load

    From this diagram,

    222

    qprs VVVV (1.1)

    If is small,

    rs VV = qpp XIRIV (1.2)

    And, therefore,

    r

    qp

    pV

    QIPIV

    (1.3)

    If the load is capacitive or leading p.f. load, the

    plus sign becomes a minus sign. Similarly, it is

    seen that:

    r

    qpqV

    QRPXRIXIV

    (1

    Thus, if X/R > 1, the flow of reactive power

    determines the voltage drop and the flow of powP, determines the transmission angle and th

    statements are substantially independent of e

    other.

    The objectives for this Lab 1 are to investig

    the effect of loading and feeder length on

    voltage regulation in a radial distribution netwfeeding a resistive load, to investigate the eff

    that the inductive and capacitive loads have up

    the voltage regulation of a radial feeder andinvestigate the voltage regulation for a simple r

    distribution network when it supplies resisti

    inductive and capacitive loads. Also, to mak

    comparison between the results obtained with

    corresponding results for the radial network.

    I. PROCEDURE

    Experiment 1: Single-Phase Radial Netw

    Feeding a Resistive Load

    Procedure A: One Section of the Feeder

    1)

    One phase of the supply line and the neu

    line is connected to one phase of resistive loas shown in Appendix A. Ensure that

    secondary of the CT is short-circuited.2) CB1 and CB2 have been closed to connect

    circuit.3)

    The Neutral Switch has been closedconnect the circuit to the ground

    4) The supply is switched on and the load is se

    25%. This should give the load current roug1.25A. The readings for load (receive) volt

    Vr, supply voltage Vs and load current, I h

    been taken.5) Step (3) is repeated for 50%, 75% and 10

    and recorded it in Table 1.

    Procedure B: Two Section of the Feeder

    1) Procedure A is repeated, but with two secti

    of the line 1 connected in series and the t

  • 5/21/2018 Lab1 EPS Fina

    4/13

    sections of the Neutral line are connected in

    series as shown in Appendix B. The resultsare recorded in Table 2.

    Experiment 2: Single-Phase Radial Network

    Feeding I nductive and Capaciti ve Loads

    Procedure A: Inductive Load

    1) On the three-phase circuit of the trainer, two

    sections of the red phase and the neutral linesare connected to one phase of the inductive

    load as shown in Appendix C. Ensure that the

    secondary of the CT is short-circuited.2)

    CB1 and CB2 are closed to connect thecircuit.

    3) The Neutral Switch has been closed to connect

    the circuit to the ground4)

    The supply is switched on and the load is set

    to 25%. The readings for load (receive)voltage Vr, supply voltage Vsand load current,

    Ihave been taken.5) Step (3) is repeated, for 50%, 75% and 100%

    and recorded it in Table 3.

    Procedure B: Capacitive Load

    1) A blank table is created as in Table 3 and

    replaced the inductive load by a capacitiveload, repeat Procedure A.

    Experiment 3: Ring Distribution Network

    Supplying Resistive, Inductive and Capacitive

    Loads

    Procedure A: Resistive Load

    1)

    A resistive load is connected to the midpoint(TP4) of the red phase sections that are fed

    from the two points (TP2) and (TP3) as shown

    in Appendix D.2)

    Temporarily disconnected the load, the supply

    is switched on and no load receive voltage

    (VnL) reading has been taken. CB1 and CB2 are

    closed to connect the circuit.3) The load is reconnected and the load is set to

    25%. The readings for load (receive) voltage

    Vr, supply voltage Vs and load current, I h

    been taken.4) Step (3) is repeated, for 50%, 75% and 10

    and recorded it in Table 4. The central mete

    used to measure Vr.

    Procedure B: Inductive Load

    1) A blank table is created as in Table 4.

    2) The resistive load is replaced with an induct

    load and Procedure A is repeated.

    Procedure C: Capacitive Load

    1) A blank table is created as in Table 4.

    2)

    The inductive load is replaced with a capacitload and steps (3) and (4) in Procedure A

    repeated.

    II. RESULTS

    Experiment 1: Single-Phase Radial Netw

    Feeding a Resistive Load

    Table 1: One Section of the Feeder.

    Load I

    25% 132.10 V 131.26 V 1441.5 m

    50% 131.76 V 130.03 V 2.81 A

    75% 131.05 V 128.23 V 4.29 A

    100% 130.52 V 127.09 V 5.58 A

    Table 2: Two Sections of the Feeder in

    Series.

    Load I

    25% 132.17 V 130.89 V 1429.0 m

    50% 131.43 V 128.67 V 2.754 A

    75% 130.85 V 125.90 V 4.213 A

    100% 130.30 V 123.79 V 5.423 A

  • 5/21/2018 Lab1 EPS Fina

    5/13

    R

    Generator

    1 2

    X21

    Resis

    Load

    Experiment 2: Single-Phase Radial Network

    Feeding I nductive and Capaciti ve Loads

    Table 3A: Inductive Load.

    Load I

    25% 132.44 V 127.11 V 1202.5 mA

    50% 132.35 V 120.96 V 2.396 A

    75% 132.17 V 114.93 V 3.581 A

    100% 130.01 V 111.00 V 4.418 A

    Table 3B: Capacitive Load.

    Load I

    25% 133.88 V 140.48 V 1525.5 mA

    50% 133.30 V 149.28 V 3.285 A

    75% 133.47 V 145.69 V 5.232 A

    100% 133.67 V 150.64 V 7.385 A

    Experiment 3: Ring Distribution Network

    Supplying Resistive, Inductive and Capacitive

    Loads

    Table 4A: Ring Network with Resistive Load.

    = 132.05 V

    Load I%

    Regulation

    25%132.36

    V

    130.68

    V

    143.5

    mA0.26

    50%131.93

    V

    130.48

    V

    2783.8

    mA0.41

    75%131.13

    V

    128.65

    V

    4270.0

    mA1.84

    100%130.65

    V

    127.31

    V5.557A 2.91

    Table 4B: Ring Network with Inductive Load.

    = 132.41 V

    Load I%

    Regulation

    25%132.77

    V

    129.96

    V

    1234.6

    mA1.89

    50%132.51

    V

    126.38

    V

    2519.4

    mA4.77

    75%132.28

    V

    123.09

    V

    3839.8

    mA7.57

    100%132.09

    V

    120.67

    V

    4.828

    A9.73

    Table 4C: Ring Network with Capacitive Loa

    =133.10 V

    Load I%

    Regulati

    25%133.21

    V136.92

    V1492.8

    mA2.79

    50% 133.34V

    141.10V

    3080.4mA

    5.67

    75%133.71

    V145.43

    V4.781

    A8.48

    100%133.89

    V

    149.55

    V

    6.594

    A10.99

    III. DISCUSSIONS

    Experiment 1: Single-Phase Radial NetwFeeding a Resistive Load

    Procedure A: One Section of the Feeder

    Circuit diagram obtained from the connection

    Appendix A;

  • 5/21/2018 Lab1 EPS Fina

    6/13

    The percentage regulation using the Equation 1.5

    for each load setting;

    % Regulation = 100

    r

    rs

    V

    VV (1.5)

    For load: 25%

    For load: 50%

    For load: 75%

    For load: 100%

    The percentage regulation against load cur rent;

    Graph 1.1

    As we can see from the Graph 1.1, the

    percentage regulation is increases due to the load

    current increases. Regarding to Ohms Law, V=IR

    it states that current flowing is directlyproportional to the voltage and inversely

    proportional to the resistance. Therefore, if the

    voltage is increased, the current will increase if the

    resistance of the circuit does not change. Sa

    goes to the increasing resistance of the circuit wlower the current flow if the voltage is

    changed. This formula shows that there

    relationship between this three variable.

    Procedure B: Two Section of the Feeder

    The circuit diagram obtained from the connectio

    in Appendix B;

    The percentage regulation using the Equation

    for each load setting;

    For load: 25%

    For load: 50%

    For load: 75%

    For load: 100%

    0

    2

    4

    6

    0 1 2 3 4 5 6Percentageregulation(%)

    Load current (A)

    Percentage Regulation against load current for one

    section of the feeder

  • 5/21/2018 Lab1 EPS Fina

    7/13

    X2

    1 2

    R

    Generator

    1 2

    X21

    R221

    Inductive

    Load

    The percentage regulation against load current;

    Graph 1.2

    Compar ison of the regulation- load current

    curves obtained when one section and two

    sections of the feeder are used to supply the load;

    Graph 1.3

    In the Graph 1.3, the line curve percentageregulation for two sections of the feeder is higher

    than line curve percentage regulation for onesection of the feeder. Based on the Ohms Law. the

    voltage will be higher as the impedance is increase

    and that will lead to the higher percentageregulation. In this experiment, the impedances for

    two feeders, are higher rather than one feeder,

    Based on the results, current is one of

    factors that determine the voltage regulation . the percentage of load current is negative,

    percentage regulation will be increase. Length

    the feeder also one of the factors that will affect

    voltage regulation. The percentage regulation wbe increase if we increase the length of the feede

    So, we can see the effect of loading feeder length on the voltage regulation in a rad

    distribution network feeding a resistive load.

    Experiment 2: Single-Phase Radial Netw

    Feeding I nductive and Capaciti ve Loads

    Procedure A: Inductive Load

    The circuit diagram obtained from the connectio

    in Appendix C;

    The percentage regulation using the Equation 1.for each load setting.

    % Regulation = 100

    r

    rs

    V

    VV (1.6)

    For load: 25%

    For load: 50%

    For load: 75%

    0

    1

    2

    3

    4

    5

    6

    0 1 2 3 4 5 6

    Percentageregulation(%)

    Load current(A)

    Percentage Regulation against load current for two

    section of the feeder

    0

    2

    4

    6

    0 1 2 3 4 5 6Percentageregulation(%)

    Load current(A)

    Percentage regulation against load current for one and

    two section of the feeder.

    one section of

    the feeder

    two sections of

    the feeder

  • 5/21/2018 Lab1 EPS Fina

    8/13

    For load: 100%

    Graph 2.1

    Compar ison of the regulati on- load cur rentcurves obtained for inductive load and resistive

    load;

    Graph 2.2

    As we can see in Graph 2.2, inductive l

    having higher percentage regulation than resistload. It is show that inductive load has m

    voltage loss when compared to resistive load.

    Procedure B: Capacitive Load

    The percentage regulation using the Equation 1.for each load setting.

    For load: 25%

    For load: 50%

    For load: 75%

    For load: 100%

    0

    2

    4

    68

    10

    12

    14

    16

    18

    20

    0 1 2 3 4 5

    Percentageregulation(%)

    Load currents(A)

    Percentage regulation against load current for inductive

    load

    0

    2

    4

    6

    8

    10

    12

    14

    16

    18

    20

    0 1 2 3 4 5 6

    Percentage

    regulation(%)

    Load current (A)

    Percentage regulation against load current for inductive

    load and resistive load

    inductive load

    resistive load

    0

    2

    4

    6

    8

    10

    12

    0 2 4 6 8

    Percentageregulation(%)

    Load current (A)

    Percentage regulation against load current for capacitive

    load

  • 5/21/2018 Lab1 EPS Fina

    9/13

    X2

    1

    2

    R

    Generator1

    2

    X

    2

    1

    R2

    2

    1

    Resistive

    Load

    Graph 2.3

    Compar ison of the regulati on- load cur rent

    curves obtained for capacitive load and inductive

    load;

    Graph 2.4

    Based on calculation, capacitive load actually

    having negative percentage regulation. So,

    theoretically, the percentage regulation for

    capacitive load is less than inductive load.

    For the inductor, assume the current through is

    it same as resistor, and the voltage across theinductor is

    which transforms to the phasor,

    but , and , thus

    showing that the voltage has a magnitude of

    and a phase of The voltage and current

    are out of phase. Specifically, the current lthe voltage by .

    For the capacitor, assume the voltage acros

    is while the current throuthe capacitor is

    And by referring to steps as we took for inductor, we obtain

    showing that the current and voltage are ouphase. To be specific, the current leads the volt

    by . And this explain why capacitive loresults in less voltage regulation than induct

    loads.

    Experiment 3: Ring Distribution Netw

    Supplying Resistive, Inductive and Capaci

    Loads

    Procedure A: Resistive Load

    The circuit diagram obtained from the connect

    in Appendix D (for resistive load);

    The percentage regulation for each load using expression;

    % Regulation = 100

    r

    rnL

    V

    VV (1.7

    0

    2

    4

    6

    8

    10

    12

    14

    16

    18

    20

    0 2 4 6 8

    Percentageregulation(%)

    Load current (A)

    Percentage regulation against load current for capacitive

    load and inductive load

    inductive

    capacitive

    load

  • 5/21/2018 Lab1 EPS Fina

    10/13

    InductiveLoadGenerator

    2

    1

    1

    2

    X2

    1

    2

    R R2

    2

    1

    X

    For load: 25%

    For load: 50%

    For load: 75%

    For load: 100%

    Comparison results for the voltage regulation

    with the corr esponding resul ts obtained from the

    radial feeder in Experiment 1;

    Graph 3.1

    As can be seen in Graph 3.1, radial feeder

    curve is slightly different than ring feeder. Thepercentage regulation are almost the same for the

    second , third and fourth point of the radial and

    ring network.

    Procedure B: Inductive Load

    The circuit diagram obtained from the connect

    in Appendix D (for inductive load);

    The percentage regulation for each load using

    expression 1.6;

    For load: 25%

    For load: 50%

    For load: 75%

    For load: 100%

    Comparison results for the voltage regulat

    with the corresponding resul ts obtained from

    radial feeder in Experiment 2;

    0

    0.5

    1

    1.5

    2

    2.5

    3

    3.5

    0 1 2 3 4 5 6

    Percentageregulation(%)

    load current (A)

    Percentage regulation against load current for radial

    network resistive load and radial network resistive load

    radial

    network

    resistive load

    ring network

    resistive load

  • 5/21/2018 Lab1 EPS Fina

    11/13

    CapacitiveLoadGenerator

    2

    1

    1

    2

    X2

    1

    2

    R R2

    2

    1

    X

    Graph 3.2

    Referring to Graph 3.2, radial feeder curve

    regulation-load current is rising higher than ring

    feeder for each point.

    Procedure C: Capacitive Load

    The circuit diagram obtained from the connection

    in Appendix D (for capacitive load);

    The percentage regulation for each load using the

    expression 1.6;

    For load: 25%

    For load: 50%

    For load: 75%

    For load: 100%

    Comparison results for the voltage regulat

    with the corresponding resul ts obtained from radial feeder in Experiment 2;

    Graph 3.3

    The effect of load power factor upon volta

    regulation for each of resistive, inductive a

    capacit ive loads;

    0

    2

    4

    6

    8

    1012

    14

    16

    18

    20

    0 2 4 6

    Percentageregula

    tion(%)

    Load current (A)

    Percentage regulation against load current for inductive

    load in radial and ring feeder

    radial

    networkinductive

    load

    ring network

    inductive

    load

    0246810

    12141618202224

    0 2 4 6 8

    Percentageregulation(%)

    Load current (A)

    Percentage regulation against load current for capacitive

    load in radial and ring feeder

    radial

    network

    capacitive

    load

    ring netwo

    capacitive

    load

  • 5/21/2018 Lab1 EPS Fina

    12/13

    Graph 3.4

    In this experiment, we can calculate the"power factor", which is defined as the cosine of

    this angle based on the phase difference betweenthe voltage and current signals. In an electricpower system, a load with a low power factor

    draws more current than a load with a high power

    factor for the same amount of useful power

    transferred. The higher currents increase theenergy lost in the distribution system, and require

    larger wires and other equipment. Because of the

    costs of larger equipment and wasted energy,electrical utilities will usually charge a higher cost

    to industrial or commercial customers where there

    is a low power factor.

    Linear loads with low power factor (such as

    induction motors) can be corrected with a passive

    network of capacitors or inductors. Non-linearloads, such as rectifiers, distort the current drawn

    from the system. In such cases, active or passive

    power factor correction may be used to counteractthe distortion and raise the power factor. The

    devices for correction of the power factor may be

    at a central substation, spread out over a

    distribution system, or built into power-consumingequipment.

    In a purely resistive AC circuit, voltage and

    current waveforms are in step (or in phase),changing polarity at the same instant in each cycle.

    All the power entering the load is consumed (or

    dissipated). Where reactive loads are present, suchas with capacitors or inductors, energy storage in

    the loads results in a time difference between the

    current and voltage waveforms.

    If a load had a capacitive value, induct

    (also known as reactors in this context) connected to correct the power factor. In

    electricity industry, inductors are said to consu

    reactive power and capacitors are said to supply

    even though the energy is just moving back forth on each AC cycle.

    When the load is inductive, the inducta

    tends to oppose the flow of current, storing ene

    then releasing it later in the cycle. The currwaveform lags behind the voltage wavefo

    When the load is capacitive, the opposite occu

    and the current waveform leads the volt

    waveform.

    So, lagging and leading is another way o

    saying the net reactance is either inductive or

    capacitive.

    IV. CONCLUSION

    As a conclusion, we can say since the volt

    drop for the ring network is lower than radnetwork, it means that the ring distribution netw

    is better than radial network. All the objectives

    this experiment are achieved as we assure

    managed to investigate the effect of loading

    feeder length on the voltage regulation in a raddistribution network feeding a resistive load,

    effect that the inductive and capacitive loads hupon the voltage regulation of a radial feeder,

    the voltage regulation for a simple ring distribut

    network when it supplies resistive, inductive a

    capacitive loads. Other than that, we also mcomparison between ring and radial networks.

    V. REFERENCES

    1. http://en.wikipedia.org/wiki/Power_f

    or

    2. http://www.allaboutcircuits.com/vol_2

    pt_11/3.html

    3.

    http://en.wikipedia.org/wiki/Electric_p

    er_transmission

    0

    12

    3

    4

    5

    6

    7

    0 2 4 6 8

    Percentageregulations(%)

    Load current (A)

    Percentage regulation against load current for resistive,

    inductive and capacitive load

    resistive load

    inductive load

    capacitive

    load

    http://en.wikipedia.org/wiki/Power_factorhttp://en.wikipedia.org/wiki/Power_factorhttp://en.wikipedia.org/wiki/Power_factorhttp://en.wikipedia.org/wiki/Power_factorhttp://en.wikipedia.org/wiki/Power_factorhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://en.wikipedia.org/wiki/Electric_power_transmissionhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://www.allaboutcircuits.com/vol_2/chpt_11/3.htmlhttp://en.wikipedia.org/wiki/Power_factorhttp://en.wikipedia.org/wiki/Power_factor
  • 5/21/2018 Lab1 EPS Fina

    13/13

    4. http://epb.apogee.net/foe/home.asp

    5. http://yourelectrichome.blogspot.com

    http://epb.apogee.net/foe/home.asphttp://epb.apogee.net/foe/home.asphttp://yourelectrichome.blogspot.com/http://yourelectrichome.blogspot.com/http://yourelectrichome.blogspot.com/http://epb.apogee.net/foe/home.asp