    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 17/30

    6. PROTECTION SETTING RANGES

    6.1 Distance Protection

    6.1.1 Line Settings

    Setting Range Step size

    Length of line (Ln) 0.3 - 1000 km0.2 - 625 miles

    0.010 km0.005 miles

    Positive sequence angle (-1) 90 - 90 0.1

    In = 1 A In = 5 A

    Setting Range Step size Range Step size

    Positive sequence impedance(Z

    1)

    0.001 - 500 : 0.001 : 0.002 -

    199,8 :0.002:

    6.1.2 Zones settings

    Setting In = 1 A In = 5 A

    Range Step size Range Step size

    Impedance reaches(Zone 1, Zone 2, Zone 3, Zone P,Zone 4)

    0.001 - 500 : 0.001 : 0.0002 -

    100 :0.0002:

    Resistive reaches for phase -earth faults(Zone 1, Zone 2, Zones 3 & 4,Zone P)

    0 - 400 : 0.01 : 0 - 80 : 0.002 :

    Resistive reaches for phase -

    earth faults(Zone 1, Zone 2, Zones 3 & 4,Zone P)

    0 - 400 : 0.01 : 0 - 80 : 0.002 :

    Setting Range Step size

    Residual compensation angles(Zone 1, Zone 2, Zones 3 & 4,Zone P)

    180-180 0.1

    Residual compensation factors(Zone 1, Zone 2, Zones 3 & 4,Zone P)

    0 - 7 0.001

    Timer for zone 1/1X 0 - 10s 0.002s

    Timers for zone 2, Zone 3,Zone P, Zone 4

    0 - 10s 0.01s

  • 7/27/2019 MICOM P441

    2/2

    P44x/EN TD/E33 Technical Data

    Page 18/30 MiCOM P441/P442 & P444

    6.1.3 Power-swing settings

    In = 1 A In = 5 A

    Setting Range Step size Range Step size

    Powerswing detection boundaries:Delta R

    Delta X

    0 - 400 :

    0 - 400 :

    0.01 :

    0.01 :

    0 - 80 :

    0 - 80 :

    0.002 :

    0.002 :

    Setting Range Step size

    Imax line In - 20 In 0.01 In

    IN threshold 10 - 100 % Imax 1%Imax

    I2 threshold 10 - 100 % Imax 1%Imax

    Trip mode Single/Three pole -

    Unblocking time delay 0 - 30s 0.1s

    Power-swing detection boundary 0 - 25:

    0.01:

    Block zones Bit 0: Z1&Z1X-Block, Bit 1: Z2 blockBit 2: Z3 block, Bit 3: Zp block, Bit 4:Z4block

    6.2 Distance protection schemes

    Basic scheme functions: Instantaneous zone 1 tripping

    Time delayed tripping for all zones

    Directional earth fault protection

    Zero sequence Power protection (since B1.0)

    Switch on to fault logic

    Trip on reclose logicLoss of load logic

    Conversion to three pole tripping

    Channel-aided distance schemes: Permissive Overreach Protection withOverreaching Zone 1 (POP Z1)

    Permissive Overreach Protection withOverreaching Zone 2 (POP Z2)

    Permissive Underreach Protection, AcceleratingZone 2 (PUP Z2)

    Permissive Underreach Protection Tripping viaForward Start (PUP Fwd)

    Blocking Overreach Protection with OverreachingZone 1 (BOP Z1)

    Blocking Overreach Protection with OverreachingZone 2 (BOP Z2)

    Permissive Scheme Unblocking Logic

    Permissive Overreach Schemes Weak InfeedFeatures

    Permissive Overreach Schemes Current ReversalGuard

    Blocking Scheme Current Reversal Guard