2
CONTINUITY MEASUREMENT - CP-100C • Measuring range: 0 to 120 . • Measuring current: - 200 mA if R 2 , 20 mA otherwise. - 20 mA (Eco mode enabled) for R from 0 to 120 Ω. • Programmable conformity threshold (BEEP): - 1 or 2 Ω. • Standard: IEC 61557-4. Voltage alert INSULATION MEASUREMENT - CP-100B • Range: 10 kto 999 M. • Configurable voltages: 50 V DC, 100 V DC, 250 V DC, 500 V DC, 1 000 V DC. • Rated measuring current: 1mA. • Adjustable conformity threshold: OFF, 0.25 M, 0.5 M, 1 M, 2 M, 100 M. • Standards: IEC 61557-2. TRMS VOLTAGE MEASUREMENT - CP-100B • Voltage types: AC, DC, AC+DC. • Bandwidth: signal 45Hz to 66Hz + harmonics up to 1Khz. Resistance range ± 20 V to 1 500 V DC ± 20 V to 400 V 50/60 Hz AC Resolution 1 V 2 V Accuracy 5% ±5 digits 5% ± 5 digits SPECIFICATIONS CONTENTS ACCESSORIES OPTIONS Central unit + Controller CP-100 • controller CP-100C , • central unit CP-100B, • red IP2X lead 2 m - bent/straight - male/male, • black IP2X lead 2 m - bent/straight - male/male, • red IP2X test lead point, • black IP2X test lead point, • green alligator clip, • CP-100C and CP-100B calibration certificate*, • main unit straps, • quick startup guide CP-100C and CP-100B, • batteries included and fitted inside the devices. Controller CP-100C • tester CP-100C, • calibration certificate* CP-100C , • quick startup guide CP-100C , • batteries included and fitted inside the device. Central unit CP-100B • central unit CP-100B, • red IP2X lead 2 m - bent/straight - male/male, • black IP2X lead 2 m - bent/straight - male/male, • red IP2X test lead point, • black IP2X test lead point, • green alligator clip, • calibration certificate* CP-100B , • main unit straps, • quick startup guide CP-100B , • batteries included and fitted inside the device. E P by CATU 10/20 Avenue Jean-Jaurès 92220 Bagneux Phone: +33 (0) 1 42 31 46 00 Fax : +33 (0) 1 42 31 46 31 www.pontarlier-electronique.fr Central unit Controller Operating temperature -10 to +45°C -10 to +45°C Storage temperature -25 to +70°C -25 to +70°C Maximum relative humidity 80% 80% Dimensions 244.5 x 132.6 x 85.8 231.1 x 56.9 x 36 Weight of the device (with batteries) 907.45 g 289.70 g Pollution degree 2 2 Installation category III 600V III 600V with cap II 600V without cap IP, IK IK 06 IP 40 IK 06 IP 40 Battery type 4 * Alkaline LR06 2 * Alkaline LR06 Fuse type 500V 500mA 6.3 x 32mm Breaking current 50 kA NA Double insulated Yes Yes Electrical safety EN 61010-1 EN 61010-1 EMC EN 61326-1 61326-2 EN 61326-1 61326-2 Wireless EN 300220-1 et -2 EN 300220-1 et -2 Wireless device category CAT 2 CAT 2 Wireless power 10mW 10mW Wireless standard EN 300220-1 and -2 Wireless frequency Band ISM433 MHz (433.075 to 434.775) Altitude < 2000 m < 2000 m Central unit CP-100B Main unit / Tester unlocking Battery compartment Insulation testing connection terminals Controller CP-100C Controller set CP-100 Red lead CS-1156 Magnetic tips CS-2001 and CS-2002 Schuko earth electrode CS-4118 Reel ERL-3-30-P (30 m PVC) Reel ERL-3-30-S (30 m silicone) Handling Kit KML-002 Rod CS-4915 Adapter DCL CS-4915DCL Black lead CS-1157 Red and black test-lead points CS-4005 and CS-4006 Carrying bag for CP-100C STP-007 Green alligator clip CS-4117 No contractual photographs. Design / layout: ComST 04/2015 Resistance range 0.01 to 4.00 4.1 to 120.0 Resolution 0.01 0.1 Accuracy ±5% ±5 digits ±5% ± 5 digits Resistance range ±1V to ±99.99 V AC or DC ±100V to ±999 V AC or DC Resolution 0.01 V 0.1 V Accuracy 2% ± 2 digits 2% ± 2 digits * COFRAC calibration certificate upon request.

Upload: others

Post on 27-Jun-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Mise en page 1 - catuelec.com- 20 mA (Eco mode enabled) for R from 0 Ω to 120 Ω. • Programmable conformity threshold (BEEP): - 1 Ω or 2 Ω. • Standard: IEC 61557-4. Voltage

CONTINUITY MEASUREMENT - CP-100C

• Measuring range: 0 Ω to 120 Ω. • Measuring current: - 200 mA if R ≤ 2 Ω, 20 mA otherwise.- 20 mA (Eco mode enabled) for R from 0 Ω to 120 Ω.

• Programmable conformity threshold (BEEP):- 1 Ω or 2 Ω.

• Standard: IEC 61557-4.

Voltage alert

INSULATION MEASUREMENT - CP-100B

• Range: 10 kΩ to 999 MΩ.• Configurable voltages: 50 V DC, 100 V DC, 250 V DC, 500 V DC, 1 000 V DC.

• Rated measuring current: ≥ 1mA.• Adjustable conformity threshold: OFF, 0.25 MΩ, 0.5 MΩ, 1 MΩ, 2 MΩ, 100 MΩ.

• Standards: IEC 61557-2.

TRMS VOLTAGE MEASUREMENT - CP-100B• Voltage types: AC, DC, AC+DC.

• Bandwidth: signal 45Hz to 66Hz + harmonics up to 1Khz.

Resistance range ± 20 V to 1500 V DC ± 20 V to 400 V 50/60 Hz AC

Resolution 1 V 2 V

Accuracy 5% ±5 digits 5% ± 5 digits

SPECIFICATIONS CONTENTS

ACCESSORIES

OPTIONS

Central unit +Controller CP-100

• controller CP-100C ,• central unit CP-100B,• red IP2X lead 2 m - bent/straight- male/male,

• black IP2X lead 2 m -bent/straight - male/male,

• red IP2X test lead point,• black IP2X test lead point,• green alligator clip,• CP-100C and CP-100Bcalibration certificate*,

• main unit straps,• quick startup guide CP-100C and CP-100B,

• batteries included and fittedinside the devices.

Controller CP-100C

• tester CP-100C,• calibration certificate* CP-100C ,• quick startup guide CP-100C , • batteries included and fitted inside the device.

Central unit CP-100B

• central unit CP-100B,• red IP2X lead 2 m - bent/straight - male/male,• black IP2X lead 2 m - bent/straight - male/male,• red IP2X test lead point,• black IP2X test lead point,• green alligator clip,• calibration certificate* CP-100B ,• main unit straps,• quick startup guide CP-100B ,• batteries included and fitted inside the device.

EEPP by

CATU

10/20 Avenue Jean-Jaurès 92220 Bagneux

Phone: +33 (0) 1 42 31 46 00

Fax : +33 (0) 1 42 31 46 31

www.pontarlier-electronique.fr

Central unit Controller

Operating temperature -10 to +45°C -10 to +45°C

Storage temperature -25 to +70°C -25 to +70°C

Maximum relative humidity 80% 80%

Dimensions 244.5 x 132.6 x 85.8 231.1 x 56.9 x 36

Weight of the device (with batteries) 907.45 g 289.70 g

Pollution degree 2 2

Installation category III 600VIII 600V with cap

II 600V without cap

IP, IK IK 06 IP 40 IK 06 IP 40

Battery type 4 * Alkaline LR06 2 * Alkaline LR06

Fuse type 500V 500mA 6.3 x 32mm Breaking current 50 kA

NA

Double insulated Yes Yes

Electrical safety EN 61010-1 EN 61010-1

EMC EN 61326-1 61326-2 EN 61326-1 61326-2

Wireless EN 300220-1 et -2 EN 300220-1 et -2

Wireless device category CAT 2 CAT 2

Wireless power ≤ 10mW ≤ 10mW

Wireless standard EN 300220-1 and -2

Wireless frequency Band ISM433 MHz (433.075 to 434.775)

Altitude < 2000 m < 2000 m

Central unitCP-100B

Main unit / Tester unlocking

Battery compartment

Insulation testingconnection terminalsController

CP-100C

Controller set CP-100

Red lead CS-1156

Magnetic tips

CS-2001 and CS-2002

Schuko earth electrode

CS-4118

Reel ERL-3-30-P (30 m PVC)Reel ERL-3-30-S (30 m silicone)

Handling Kit KML-002

Rod CS-4915 Adapter DCL CS-4915DCL

Black lead CS-1157Red and black test-lead pointsCS-4005 and CS-4006

Carrying bag for CP-100C STP-007 Green alligator clip CS-4117

No contractual photographs. Design / layout: ComST 04/2015

Resistance range 0.01 Ω to 4.00 Ω 4.1 Ω to 120.0 Ω

Resolution 0.01 Ω 0.1 Ω

Accuracy ±5% ±5 digits ±5% ± 5 digits

Resistance range ±1V to ±99.99 V AC or DC ±100V to ±999 V AC or DC

Resolution 0.01 V 0.1 V

Accuracy 2% ± 2 digits 2% ± 2 digits

* COFRAC calibration certificate upon request.

doc_c diag_GB 22/04/2015 08:59 Page1

Page 2: Mise en page 1 - catuelec.com- 20 mA (Eco mode enabled) for R from 0 Ω to 120 Ω. • Programmable conformity threshold (BEEP): - 1 Ω or 2 Ω. • Standard: IEC 61557-4. Voltage

Voltagemeasurement

The “C’DIAG TOUCH”associated with the mainunit can perform TRMSvoltage tests, both AC andDC.

Holding system easy to install

CONTINUITY TESTER

CP-100CThe "C’DIAG TOUCH" continuity tester belongs to a new generationof measuring devices specifically designed for taking measurementsfor the compulsory tests of low voltage facilities in the tertiary andindustrial sectors.

ERGONOMIC DESIGN FOR PROFESSIONAL APPLICATIONS

With its integrated test-lead point, this lightweight, compact device acts as anextension to the user's hand.

Thanks to the ergonomic design, the test-lead points can be held single-handedly.

The direct value reading reduces test time.

A complete set of accessories (lead, handling kit, test-lead points, reel) makes the deviceperfectly compatible with most test situations.

HARD WIRED CONNECTIONThe tester is used as an enhanced test-lead point with a display.

WIRELESS CONNECTIONThe two devices can be connected via a wireless connection to freeup the user's hands and guarantee safety by triggering remotemeasurement.

The right performance levelFor measurements, the TFT colour screen makes valuereading simple and immediately available forinterpretation, as the colour switches from green to redwhen the continuity resistance exceeds the conformitythreshold (measurement range from 0 to 120 Ohms,refer to the specifications table).

Unrivalled operating timeThe “C’DIAG TOUCH” continuity tester is powered bytwo 1.5 V batteries and its innovative design provides anoutstanding operating time of up to 3,000 tests beforereplacing the batteries.

SafetyAn audible signal and a dangerous voltage indicator onthe earth circuit warn the user, who can then take all thenecessary precautionary measures.

TFT screen with clear display of readings

Test-lead pointbuilt into the tester

Intuitive function keys:direct access to functions

Direct access to activate or deactivate the BEEP

Battery-powered, longoperating time up to3000 tests

Compact/lightweight unit (290 g),robust and easy to handle

Can be used anywhere with the HANDLING KITfor intensive use or use with universal rods.

Use with a rod and reel.

20 mA

90.2 Ω

200 mA

1.50 Ω

ADDITIONAL MAIN UNIT FOR INSULATION TESTING

CP-100B

IP2X connection terminals

Shock absorbingbumpers

Insulation resistance indications directly on the CP-100C tester

Central unit designed tohouse and protect thecontinuity tester

Configuration of voltage levelsfrom 50 V to 1 000 V DC to accommodate any installation

The use of the central unit savesthe continuity tester's battery lifeCP-100C in insulation mode

Safe interlocksystem

500 V

0.2 MΩ

MΩ Ω V

500 VMΩ Ω V

1.5 MΩ