  • 8/12/2019 NetSure701 R48-3200-DataSheet

    1/212012.09

    DC Power for

    Business-Critical Continuity

    RectifierR48-3200

    Key Features

    n3200 watt rectifier

    designed for -48V DC

    power applications

    n

    Optimized depth reduced footprint allows

    installation in short-depth

    racks and cabinets

    nDSP (Digital Signaling

    Processor) means fewer

    components, optimized

    operation and active load

    sharing for increased

    reliability

    n

    Compliant with globalstandards delivers quality,

    performance and reliability no

    matter what the application

    or location demands

    nHigh efficiency, up to 92%,

    reduces power consumption

    for lower operating costs

    nHot pluggable facilitates

    future extensions

    nWide input voltage range

    operates in the most

    demanding environments

    where input voltage changes

    nWide temperature operating

    range (-40C / -40F to +75C /

    167F) meets the harshest

    climatic environment

    requirements

    The reliable and efficient R48-3200 rectifier reducespower consumption, lowering operating cost.

    Description

    The 3200 watt rectifier (R48-3200) is designed to convert standard AC supply volt-

    ages into stable nominal -48V DC voltage that is adjustable to application needs.The R48-3200 is a constant power rectifier designed with the latest patented

    switch-mode technology using DSP (Digital Signaling Processor) functionality for

    efficient operation.

    For a higher load capacity, rectifiers can be connected in parallel, and intelligent

    control can be added with the help of a separate controller.

  • 8/12/2019 NetSure701 R48-3200-DataSheet

    2/22012.092

    Rectifier R48-3200

    EmersonNetworkPower.com/EnergySystems (North America)

    EmersonNetworkPower.eu/EnergySystems (EMEA)

    Emerson Network Power Energy Systems North America 2012.

    Business-Critical Continuity, Emerson Network Power, the Emerson Network Power logo, Emersonand Consider it Solved are service marks and trademarks of Emerson Electric Co.

    EnergyMaster , eSure, NetPerform, NetReach, NetSpan, NetSureand NetXtendare trademarks of Emerson Network Power Energy Systems North America.

    DiagramsTechnical SpecificationsAC Input

    Input Voltage, Nominal 200 to 250 V AC

    Input Voltage, Permitted Variation 85 to 290 V AC

    Line Frequency 45 to 55 Hz

    Max Input Current 20A

    Power Factor 0.99

    THD (Total Harmonic Distortion) 48VDC

    Output Power, Derated for Input

    VoltageSee diagram

    Output Current 67A

    Output Current Limit Set Point 0 to 67A

    Efficiency 92%

    Psophometric Noise (system)