piperack presentation
DESCRIPTION
Piperack types and designTRANSCRIPT
-
5/24/2018 Piperack Presentation
1/23
1
WELCOME TO INHOUSE
TRAINING SESSION
DESIGN OF PIPERACK
www.pipingfunda.com
-
5/24/2018 Piperack Presentation
2/23
2
CONTENTS
Introduction & Layout (DAY-1)
Pipe Loading calculations for Pipe rack as per
Specifications
Wind loading calculations as per IS:875-III
Introduction to UBC-94 & its use for Calculation ofLoads for Pipe rack structure.
Load Combinations for Design of Pipe rack
Provisions of Project Specifications
Concrete Design of Pipe rack Members (DAY-2) Introduction about IS:456 & SP:16 Provisions(DAY-3)
-
5/24/2018 Piperack Presentation
3/23
3
Introduction
What is called PIPERACK ?
PIPERACK is a structure whose basic geometry is like a Portal Frame
having Multi-tiers which are provided to support piping , cable trays and
(with) Fin fan coolers or (Without) coolers.
CLASSIFICATION OF PIPERACK
Based on plant layout
ISBL (Inside Bat. Limit) & OSBL(Outside Bat. Limit)
Based on Utilities Supported
Non Fin fan & Fin fan pipe rack
Based on Materials used for Members
Concrete (Pre cast or Cast-insitu) , Steel & Composite(Steel+Concrete)
-
5/24/2018 Piperack Presentation
4/23
4
Introduction & Layout
Following Preliminary Informations required from Piping
Screen dumps or P65 drawings showing C/s OF Piperack with different
tiers & elevations.
Line size , Max. unsupported spacing/span ,Piping class & state(Hot or
Cold), Flow direction i.e supply or Return , Insulation details
Space required for Electrical cable trays.
Fireproofing requirement based on line contents for Steel Pipe rack
-
5/24/2018 Piperack Presentation
5/235
Introduction & Layout
Braced bay location:
Brace bay is nothing but it is bay supporting Piping anchor points.
Location shall be generally provided by Piping Specialist.
For Economy the anchor points for the same line shall be provided at
staggering positions.
Expansion Bay :
Normally to be decided by Civil/Structural specialist. Normally the same
shall be provided at every 40 to 50 Mt.
Longitudinal RC beam Elevations :
Normally to be provided in the center of Two tiers.
Always Larger diameter of Pipes shall be routed near to Columns.
-
5/24/2018 Piperack Presentation
6/23
6
PIPERACK LOADING (REFERENCE : 3PS-CA-001)
For on-plot pipe racks minimum vertical load of 1.7kN/m2 on plan area shall be applied at each pipe
rack level, unless definitive loads are available from
Piping Group. A concentrated load shall be added for
pipes 12 in. dia. or larger.)
For off-plot pipe racks a vertical load of 2.5 kN/m on
plan area shall be applied at each pipe rack level,
unless definitive loads are available from piping group.
Concentrated loads for 14 in. dia. or 16 in. dia. pipes
shall also be considered.
-
5/24/2018 Piperack Presentation
7/23
7
The horizontal friction load applied at each level shall be thegreater of 7.5% of the total pipe weight or 30% of the
operating pipe weight of any number of lines known to be
moving simultaneously in the same direction.
For on-plot pipe racks the longitudinal beam struts shall bedesigned for a vertical load of 50% of the load carried by the
most heavily loaded transverse beam. This load should not
be added to the design load for column or footings. For off-
plot pipe racks, longitudinal beam struts shall be designed
for vertical and horizontal loads imposed by expansionloops, located by piping group.
Introduction contd.
PIPERACK LOADINGS
-
5/24/2018 Piperack Presentation
8/23
8
PIPERACK LOADINGS
All pipe rack longitudinal beam struts shall be designedfor a compression load of 15% of the maximum adjacent
column load at beam level.
The horizontal load on pipe rack anchor bays shall be the
greatest of:-
Anchor force from pipe stress (These shall include start-
up and shutdown conditions). or
7.5% of piping vertical load between expansion joints or
40 kN applied uniformly at each level.
-
5/24/2018 Piperack Presentation
9/23
9
PIPERACK LOADINGS
Pipe rack designs shall be checked, when actualpipe loads, friction and anchor forces are known.
-
5/24/2018 Piperack Presentation
10/23
10
WIND LOADING CALCULATIONS
Wind loads acting on Pipe racks shall be in accordance withIS:875-III-1987
Basic Wind speed : Vb = 50 m/sec
Risk coefficient -K1 = 1.08
Height & Terrain Factor K2 = Cat.2,Class-A,Table-2,IS875 Topographic factor k3 = 1.0
Design Wind speed Vz = Vb x K1 x k2 x k3
Design Wind Pressure Pz = 0.6 x Vz
-
5/24/2018 Piperack Presentation
11/23
11
WIND LOADING CALCULATIONS
Wind force for Pipe rack Individual members
Frame wise
Individual Members
* Column & Beam Members(cl.6.3.3.2(b))Normal force=Cfn x Pz x K x b ..Kn/m
Transverse force=Cft x Pz x K x b ..Kn/m
Cfn , Cft = force coefficients
K= Reduction factor for individual members(Table-25,pg.44)b=width of member across wind direction
-
5/24/2018 Piperack Presentation
12/23
12
WIND LOADING CALCULATIONS
Wind force for Pipe rack Frame wise (CL.6.3.3.3 & 6.3.3.4)
Solidity ratio= area of members in direct exposure/Overall area
Force coefficients(for 1 Frame) = Reference table:28(pg.46)
for more than one frameFrame spacing ratio =c/c dist of frames/least overall dim of
frame measured at right angle to direction of wind
Refer Shielding factor based on solidity ratio & Frame spacing
ratio(Refer Table:29 of Pg. No. 46 of IS:875-III)
-
5/24/2018 Piperack Presentation
13/23
13
WIND LOADING CALCULATIONS
Wind Force on Fin FansF (Total Wind Force) = Cf x Ae x Pz ..Kn
Cf(Max) = Force coefficients =0.95 (Table:4)
Ae = Effective Frontal Area
-
5/24/2018 Piperack Presentation
14/23
14
WIND LOADING CALCULATIONS
WIND LOADINGS FOR PIPES
The transverse wind load on piping shall be applied on a
projected area equal to the diameter of the largest pipe
including insulation where applicable plus 10% of the
usable width of the piperack, where the usable width ofthe piperack is defined as the distance between inside
faces of piperack columns less clearance between
columns and piping.
Where pipe sizes are unknown projected area shall be
based on a 12 in. dia. pipe plus 50mm insulation.
-
5/24/2018 Piperack Presentation
15/23
15
Cable Tray Loads
A minimum cable tray load of 1.0 kN/m2per tray layer
shall be used for electrical/instrument trays.
The transverse wind load on cable trays shall be
applied on a projected area equal to the height of thetray plus 10% of the net width of cable way dedicated
to trays.
-
5/24/2018 Piperack Presentation
16/23
16
Introduction to UBC-94
International Conference of Building Officials(ICBO) Publishes the family
of Uniform Building Codes
There are diff. Types of Uniform codes are available
Uniform Building Code : Volumes- 1,2,3 : The most Widely adoptedmodel Building Code in the United States.
Volume-1 : Administrative , Fire and Life safety , Field Inspectionprovisions
Volume-2 : Structural Engineering Design provisions
Volume-3 : Material , Testing & Installation Standards
S ( C )
-
5/24/2018 Piperack Presentation
17/23
17
Seismic loads(As per UBC-1994)
V = Z x I x C / Rw (For Pipe rack structure)
V= Design Base shear
Z = Seismic Zone factor = for Zone-3 it is 0.3 (Table:16 I) (pg no.34)
I = Importance factor = 1.25 (Table :16 K) (pg. No:35)
C= Numerical Coefficient =1.25 x S / T 2/3 (Need not exceed 2.75)
S=Soil Site Coefficient = 1.0 (Table :16 J)
T= Fundamental period = Ct x hn 3/4Ct = 0.0731 (For RC Mom. Frames),0.0853(Steel MomentFrames),0.0488 for all other buildings
hn = Height in meter above the base
W = Dead & Normal operating gravity loads
Rw = Response Modification Factor depending on OMRF,SMRF &
Braced bay types (Table :16 N)(Pg:37)Vertical distribution of base shear force shall be in accordance withformulas (28-6) ,(28-7) & (28-8) of the UBC,Section-1628
S i i l d (A UBC 1994)
-
5/24/2018 Piperack Presentation
18/23
18
Seismic loads(As per UBC-1994)
If T < 0.7 seconds Ft =0
If T > 0.7 seconds Ft =concentrated force @ top=0.07xTxV OR Need notexceed 0.25 V
Remaining Base shear Force shall be distributed as given below
Fx = (V-Ft) x Wx x Hx / Sum( Wi Hi)
S i i l d (A UBC 1994)
-
5/24/2018 Piperack Presentation
19/23
19
Seismic loads(As per UBC-1994)
V = Z x Ip x Cp x Wp (For Fin Fan )
Fp= Lateral Force
Z = Seismic Zone factor = for Zone-3 it is 0.3 (Table :16 I , Pg. No. 34)
Ip = Importance factor = 1.5 (Table :16K , Pg. No. 35)
Cp= Horizontal Force Factor =0.75 (see note below) (Table :16O,Pg.38)
Wp= Weight of Fin fan or component
NOTE : For flexibly supported fin fans with fundamental period greater than
0.06 seconds , use Cp equal to twice the value as shown.
-
5/24/2018 Piperack Presentation
20/23
20
LOAD COMBINATIONS (FOR RC DESIGN & FOUNDATION)
Erection Condition: (Dont include wt. Of contenets)1. U = 0.9 x D + 1.3 x W (ACI) OR 1.5 x W (IS:456)
2. U = 0.9 x D + 1.43 x W (ACI) OR 1.5 x W (IS:456)
D= Empty load of piping shall be 60% of piping
Test Condition:
U = 1.4 x D + 1.4 x TL + 1.7 x L (ACI) OR 1.5 (D+TL+L) (IS:456)
U = 0.75(1.4D + 1.4 TL+ 1.7 L+0.5x1.7W) (ACI) OR 1.2(D+TL+0.5W)(IS456)
Operating Condition: U = 1.4D + 1.7 L (ACI) OR 1.5(D+L) (IS:456)
U = 0.75(1.4D +1.7 L+1.7W) (ACI) OR 1.2(D+L+W) (IS:456)
U=1.4(D+L+E)(ACI) OR 1.2 (D+L+E)(IS:456)
U=1.4(D+T) (ACI) OR 1.5(D+T) (IS:456)
U=0.75(1.4D+1.4T+1.7L) OR 1.2(D+T+L)
U=0.75(1.4D+1.4T+1.7L+1.7W) (ACI) OR 1.2(D+T+L+W) (IS:456) U=0.75(1.4D+1.4T+1.7L+1.87E)(ACI) OR 1.2(D+T+L+E) (IS:456)
Where U=Reqd. strength to resist factored loads in accoordance withthe ACI-318M & UBC OR IS:456
-
5/24/2018 Piperack Presentation
21/23
21
LOAD COMBINATIONS FOR CONNECTIONS
Connection Design as per UBC 1994 clause 2211.5.1 & 2211.8.3.1
37 or 38) DL + Oper. Load (+/-)3(Rw/8)xSeismic in N/S dir.(+/-)(Rw/8)xSL in E/W dir
39 or 40) DL + Oper. Load (+/-)3(Rw/8)xSeismic in E/W dir(+/-)(Rw/8)xSL in N/S dir
41 or 42) DL+Oper. Load+ 50%Live Load (+/-)3(Rw/8)xSL in N/S(+/-)(Rw/8)xSL in E/W
43 or 44) DL+Oper. Load+ 50%Live Load (+/-)3(Rw/8)xSL in E/W(+/-)(Rw/8)xSL in N/S
Column&Bracing Strength in Compression as per UBC 1994 clause 2211.5.1&2211.8.2.3
45 or 46) DL+Oper. Load+ 0.7xLive Load (+/-)3(Rw/8)xSL in N/S(+/-)(Rw/8)xSL in E/W
47 or 48) DL+Oper. Load+ 0.7xLive Load(+/-)3(Rw/8)xSL in E/W(+/-)(Rw/8)xSL in N/S
-
5/24/2018 Piperack Presentation
22/23
22
LOAD COMBINATIONS FOR CONNECTIONS
Column&Bracing Strength in Tension as per UBC 1994 clause 2211.5.1 & 2211.8.2.3
49 or 50) 0.85xDead Load (+/-)3(Rw/8)xSL in N/S(+/-)(Rw/8)SL in E/W dir
51 or 52) 0.85xDead Load (+/-)3(Rw/8)xSL in E/W(+/-)(Rw/8)SL in N/S
Column&Bracing Strength in Tension as per UBC 1994 clause 2211.5.1&2211.8.2.3
49 or 50) 0.85xDead Load (+/-)3(Rw/8)xSL in N/S(+/-)(Rw/8)SL in E/W dir
51 or 52) 0.85xDead Load (+/-)3(Rw/8)xSL in E/W(+/-)(Rw/8)SL in N/S
Manual Check Requirements as per UBC 1994
1. Slenderness Ratio Check as per clause 2211.8.2.1
2. Bracing Check for reduced permissible stress as per clause 2211.8.4.1.1
Note:Application of seismic force in both direction shall be checked by designer.
-
5/24/2018 Piperack Presentation
23/23
23
Example for strength check as per connection design forces
Column subjected to compression and Bending Moment (Example)
Section Used,
Plate Girder 1200x25 + 400x45 (T&B)
Column member subjected to Compressive force and bending Moment
Maximum Axial compression = 4108.6 kN
Allowable Axial compressive stress = 81.42 N/mm2
Area of the Section Used = 63750 mm2
Taken from STAADPro results
Axial Compressive Strength = 1.7 x Fa x A as per UBC Clause 2211.4.2 = 8823.89kN Hence, Safe
Maximum Bending Moment =4368 kN.m
Flexture Strength = Zp x Fy
Plastic Section Modulus of the section = Zp =2.85E+07mm3
Yield stress of the material = Fy =250 N/mm2
Flexture Strength =7122.50 kN.m Hence, Safe