piperack presentation

Upload: ibson045001256

Post on 13-Oct-2015

53 views

Category:

Documents


14 download

DESCRIPTION

Piperack types and design

TRANSCRIPT

  • 5/24/2018 Piperack Presentation

    1/23

    1

    WELCOME TO INHOUSE

    TRAINING SESSION

    DESIGN OF PIPERACK

    www.pipingfunda.com

  • 5/24/2018 Piperack Presentation

    2/23

    2

    CONTENTS

    Introduction & Layout (DAY-1)

    Pipe Loading calculations for Pipe rack as per

    Specifications

    Wind loading calculations as per IS:875-III

    Introduction to UBC-94 & its use for Calculation ofLoads for Pipe rack structure.

    Load Combinations for Design of Pipe rack

    Provisions of Project Specifications

    Concrete Design of Pipe rack Members (DAY-2) Introduction about IS:456 & SP:16 Provisions(DAY-3)

  • 5/24/2018 Piperack Presentation

    3/23

    3

    Introduction

    What is called PIPERACK ?

    PIPERACK is a structure whose basic geometry is like a Portal Frame

    having Multi-tiers which are provided to support piping , cable trays and

    (with) Fin fan coolers or (Without) coolers.

    CLASSIFICATION OF PIPERACK

    Based on plant layout

    ISBL (Inside Bat. Limit) & OSBL(Outside Bat. Limit)

    Based on Utilities Supported

    Non Fin fan & Fin fan pipe rack

    Based on Materials used for Members

    Concrete (Pre cast or Cast-insitu) , Steel & Composite(Steel+Concrete)

  • 5/24/2018 Piperack Presentation

    4/23

    4

    Introduction & Layout

    Following Preliminary Informations required from Piping

    Screen dumps or P65 drawings showing C/s OF Piperack with different

    tiers & elevations.

    Line size , Max. unsupported spacing/span ,Piping class & state(Hot or

    Cold), Flow direction i.e supply or Return , Insulation details

    Space required for Electrical cable trays.

    Fireproofing requirement based on line contents for Steel Pipe rack

  • 5/24/2018 Piperack Presentation

    5/235

    Introduction & Layout

    Braced bay location:

    Brace bay is nothing but it is bay supporting Piping anchor points.

    Location shall be generally provided by Piping Specialist.

    For Economy the anchor points for the same line shall be provided at

    staggering positions.

    Expansion Bay :

    Normally to be decided by Civil/Structural specialist. Normally the same

    shall be provided at every 40 to 50 Mt.

    Longitudinal RC beam Elevations :

    Normally to be provided in the center of Two tiers.

    Always Larger diameter of Pipes shall be routed near to Columns.

  • 5/24/2018 Piperack Presentation

    6/23

    6

    PIPERACK LOADING (REFERENCE : 3PS-CA-001)

    For on-plot pipe racks minimum vertical load of 1.7kN/m2 on plan area shall be applied at each pipe

    rack level, unless definitive loads are available from

    Piping Group. A concentrated load shall be added for

    pipes 12 in. dia. or larger.)

    For off-plot pipe racks a vertical load of 2.5 kN/m on

    plan area shall be applied at each pipe rack level,

    unless definitive loads are available from piping group.

    Concentrated loads for 14 in. dia. or 16 in. dia. pipes

    shall also be considered.

  • 5/24/2018 Piperack Presentation

    7/23

    7

    The horizontal friction load applied at each level shall be thegreater of 7.5% of the total pipe weight or 30% of the

    operating pipe weight of any number of lines known to be

    moving simultaneously in the same direction.

    For on-plot pipe racks the longitudinal beam struts shall bedesigned for a vertical load of 50% of the load carried by the

    most heavily loaded transverse beam. This load should not

    be added to the design load for column or footings. For off-

    plot pipe racks, longitudinal beam struts shall be designed

    for vertical and horizontal loads imposed by expansionloops, located by piping group.

    Introduction contd.

    PIPERACK LOADINGS

  • 5/24/2018 Piperack Presentation

    8/23

    8

    PIPERACK LOADINGS

    All pipe rack longitudinal beam struts shall be designedfor a compression load of 15% of the maximum adjacent

    column load at beam level.

    The horizontal load on pipe rack anchor bays shall be the

    greatest of:-

    Anchor force from pipe stress (These shall include start-

    up and shutdown conditions). or

    7.5% of piping vertical load between expansion joints or

    40 kN applied uniformly at each level.

  • 5/24/2018 Piperack Presentation

    9/23

    9

    PIPERACK LOADINGS

    Pipe rack designs shall be checked, when actualpipe loads, friction and anchor forces are known.

  • 5/24/2018 Piperack Presentation

    10/23

    10

    WIND LOADING CALCULATIONS

    Wind loads acting on Pipe racks shall be in accordance withIS:875-III-1987

    Basic Wind speed : Vb = 50 m/sec

    Risk coefficient -K1 = 1.08

    Height & Terrain Factor K2 = Cat.2,Class-A,Table-2,IS875 Topographic factor k3 = 1.0

    Design Wind speed Vz = Vb x K1 x k2 x k3

    Design Wind Pressure Pz = 0.6 x Vz

  • 5/24/2018 Piperack Presentation

    11/23

    11

    WIND LOADING CALCULATIONS

    Wind force for Pipe rack Individual members

    Frame wise

    Individual Members

    * Column & Beam Members(cl.6.3.3.2(b))Normal force=Cfn x Pz x K x b ..Kn/m

    Transverse force=Cft x Pz x K x b ..Kn/m

    Cfn , Cft = force coefficients

    K= Reduction factor for individual members(Table-25,pg.44)b=width of member across wind direction

  • 5/24/2018 Piperack Presentation

    12/23

    12

    WIND LOADING CALCULATIONS

    Wind force for Pipe rack Frame wise (CL.6.3.3.3 & 6.3.3.4)

    Solidity ratio= area of members in direct exposure/Overall area

    Force coefficients(for 1 Frame) = Reference table:28(pg.46)

    for more than one frameFrame spacing ratio =c/c dist of frames/least overall dim of

    frame measured at right angle to direction of wind

    Refer Shielding factor based on solidity ratio & Frame spacing

    ratio(Refer Table:29 of Pg. No. 46 of IS:875-III)

  • 5/24/2018 Piperack Presentation

    13/23

    13

    WIND LOADING CALCULATIONS

    Wind Force on Fin FansF (Total Wind Force) = Cf x Ae x Pz ..Kn

    Cf(Max) = Force coefficients =0.95 (Table:4)

    Ae = Effective Frontal Area

  • 5/24/2018 Piperack Presentation

    14/23

    14

    WIND LOADING CALCULATIONS

    WIND LOADINGS FOR PIPES

    The transverse wind load on piping shall be applied on a

    projected area equal to the diameter of the largest pipe

    including insulation where applicable plus 10% of the

    usable width of the piperack, where the usable width ofthe piperack is defined as the distance between inside

    faces of piperack columns less clearance between

    columns and piping.

    Where pipe sizes are unknown projected area shall be

    based on a 12 in. dia. pipe plus 50mm insulation.

  • 5/24/2018 Piperack Presentation

    15/23

    15

    Cable Tray Loads

    A minimum cable tray load of 1.0 kN/m2per tray layer

    shall be used for electrical/instrument trays.

    The transverse wind load on cable trays shall be

    applied on a projected area equal to the height of thetray plus 10% of the net width of cable way dedicated

    to trays.

  • 5/24/2018 Piperack Presentation

    16/23

    16

    Introduction to UBC-94

    International Conference of Building Officials(ICBO) Publishes the family

    of Uniform Building Codes

    There are diff. Types of Uniform codes are available

    Uniform Building Code : Volumes- 1,2,3 : The most Widely adoptedmodel Building Code in the United States.

    Volume-1 : Administrative , Fire and Life safety , Field Inspectionprovisions

    Volume-2 : Structural Engineering Design provisions

    Volume-3 : Material , Testing & Installation Standards

    S ( C )

  • 5/24/2018 Piperack Presentation

    17/23

    17

    Seismic loads(As per UBC-1994)

    V = Z x I x C / Rw (For Pipe rack structure)

    V= Design Base shear

    Z = Seismic Zone factor = for Zone-3 it is 0.3 (Table:16 I) (pg no.34)

    I = Importance factor = 1.25 (Table :16 K) (pg. No:35)

    C= Numerical Coefficient =1.25 x S / T 2/3 (Need not exceed 2.75)

    S=Soil Site Coefficient = 1.0 (Table :16 J)

    T= Fundamental period = Ct x hn 3/4Ct = 0.0731 (For RC Mom. Frames),0.0853(Steel MomentFrames),0.0488 for all other buildings

    hn = Height in meter above the base

    W = Dead & Normal operating gravity loads

    Rw = Response Modification Factor depending on OMRF,SMRF &

    Braced bay types (Table :16 N)(Pg:37)Vertical distribution of base shear force shall be in accordance withformulas (28-6) ,(28-7) & (28-8) of the UBC,Section-1628

    S i i l d (A UBC 1994)

  • 5/24/2018 Piperack Presentation

    18/23

    18

    Seismic loads(As per UBC-1994)

    If T < 0.7 seconds Ft =0

    If T > 0.7 seconds Ft =concentrated force @ top=0.07xTxV OR Need notexceed 0.25 V

    Remaining Base shear Force shall be distributed as given below

    Fx = (V-Ft) x Wx x Hx / Sum( Wi Hi)

    S i i l d (A UBC 1994)

  • 5/24/2018 Piperack Presentation

    19/23

    19

    Seismic loads(As per UBC-1994)

    V = Z x Ip x Cp x Wp (For Fin Fan )

    Fp= Lateral Force

    Z = Seismic Zone factor = for Zone-3 it is 0.3 (Table :16 I , Pg. No. 34)

    Ip = Importance factor = 1.5 (Table :16K , Pg. No. 35)

    Cp= Horizontal Force Factor =0.75 (see note below) (Table :16O,Pg.38)

    Wp= Weight of Fin fan or component

    NOTE : For flexibly supported fin fans with fundamental period greater than

    0.06 seconds , use Cp equal to twice the value as shown.

  • 5/24/2018 Piperack Presentation

    20/23

    20

    LOAD COMBINATIONS (FOR RC DESIGN & FOUNDATION)

    Erection Condition: (Dont include wt. Of contenets)1. U = 0.9 x D + 1.3 x W (ACI) OR 1.5 x W (IS:456)

    2. U = 0.9 x D + 1.43 x W (ACI) OR 1.5 x W (IS:456)

    D= Empty load of piping shall be 60% of piping

    Test Condition:

    U = 1.4 x D + 1.4 x TL + 1.7 x L (ACI) OR 1.5 (D+TL+L) (IS:456)

    U = 0.75(1.4D + 1.4 TL+ 1.7 L+0.5x1.7W) (ACI) OR 1.2(D+TL+0.5W)(IS456)

    Operating Condition: U = 1.4D + 1.7 L (ACI) OR 1.5(D+L) (IS:456)

    U = 0.75(1.4D +1.7 L+1.7W) (ACI) OR 1.2(D+L+W) (IS:456)

    U=1.4(D+L+E)(ACI) OR 1.2 (D+L+E)(IS:456)

    U=1.4(D+T) (ACI) OR 1.5(D+T) (IS:456)

    U=0.75(1.4D+1.4T+1.7L) OR 1.2(D+T+L)

    U=0.75(1.4D+1.4T+1.7L+1.7W) (ACI) OR 1.2(D+T+L+W) (IS:456) U=0.75(1.4D+1.4T+1.7L+1.87E)(ACI) OR 1.2(D+T+L+E) (IS:456)

    Where U=Reqd. strength to resist factored loads in accoordance withthe ACI-318M & UBC OR IS:456

  • 5/24/2018 Piperack Presentation

    21/23

    21

    LOAD COMBINATIONS FOR CONNECTIONS

    Connection Design as per UBC 1994 clause 2211.5.1 & 2211.8.3.1

    37 or 38) DL + Oper. Load (+/-)3(Rw/8)xSeismic in N/S dir.(+/-)(Rw/8)xSL in E/W dir

    39 or 40) DL + Oper. Load (+/-)3(Rw/8)xSeismic in E/W dir(+/-)(Rw/8)xSL in N/S dir

    41 or 42) DL+Oper. Load+ 50%Live Load (+/-)3(Rw/8)xSL in N/S(+/-)(Rw/8)xSL in E/W

    43 or 44) DL+Oper. Load+ 50%Live Load (+/-)3(Rw/8)xSL in E/W(+/-)(Rw/8)xSL in N/S

    Column&Bracing Strength in Compression as per UBC 1994 clause 2211.5.1&2211.8.2.3

    45 or 46) DL+Oper. Load+ 0.7xLive Load (+/-)3(Rw/8)xSL in N/S(+/-)(Rw/8)xSL in E/W

    47 or 48) DL+Oper. Load+ 0.7xLive Load(+/-)3(Rw/8)xSL in E/W(+/-)(Rw/8)xSL in N/S

  • 5/24/2018 Piperack Presentation

    22/23

    22

    LOAD COMBINATIONS FOR CONNECTIONS

    Column&Bracing Strength in Tension as per UBC 1994 clause 2211.5.1 & 2211.8.2.3

    49 or 50) 0.85xDead Load (+/-)3(Rw/8)xSL in N/S(+/-)(Rw/8)SL in E/W dir

    51 or 52) 0.85xDead Load (+/-)3(Rw/8)xSL in E/W(+/-)(Rw/8)SL in N/S

    Column&Bracing Strength in Tension as per UBC 1994 clause 2211.5.1&2211.8.2.3

    49 or 50) 0.85xDead Load (+/-)3(Rw/8)xSL in N/S(+/-)(Rw/8)SL in E/W dir

    51 or 52) 0.85xDead Load (+/-)3(Rw/8)xSL in E/W(+/-)(Rw/8)SL in N/S

    Manual Check Requirements as per UBC 1994

    1. Slenderness Ratio Check as per clause 2211.8.2.1

    2. Bracing Check for reduced permissible stress as per clause 2211.8.4.1.1

    Note:Application of seismic force in both direction shall be checked by designer.

  • 5/24/2018 Piperack Presentation

    23/23

    23

    Example for strength check as per connection design forces

    Column subjected to compression and Bending Moment (Example)

    Section Used,

    Plate Girder 1200x25 + 400x45 (T&B)

    Column member subjected to Compressive force and bending Moment

    Maximum Axial compression = 4108.6 kN

    Allowable Axial compressive stress = 81.42 N/mm2

    Area of the Section Used = 63750 mm2

    Taken from STAADPro results

    Axial Compressive Strength = 1.7 x Fa x A as per UBC Clause 2211.4.2 = 8823.89kN Hence, Safe

    Maximum Bending Moment =4368 kN.m

    Flexture Strength = Zp x Fy

    Plastic Section Modulus of the section = Zp =2.85E+07mm3

    Yield stress of the material = Fy =250 N/mm2

    Flexture Strength =7122.50 kN.m Hence, Safe