POLYPANEL Polypanel is a tested and proven alternative to sheet metal ducting and components. It is widely accepted and currently in use in major domestic and commercial projects throughout the world. (In the United Arab Emirates, the location of highest rate of building development per capita, Pre insulated Aluminium board has taken over in excess of 50% market share in last 4 years) Comprising closed cell polyisocyanurate foam enclosed in two layers of aluminium textured sheet, this product offers superior features and benefits to both the installer and end user, including light weight, strength, ease of fabrication, low vapour permeability and superior hygiene characteristics. Polypanel Ducting Can be fitted closer to ceilings than galvanised sheet as no space need be left for insulation cladding. This saves on ceiling cavity height. Can be fitted to fibrous cement and suspended ceilings due to light weight. Minor adjustments can often be made on site without the need to fabricate a new section in the factory. This saves both time and money. Requires less machinery to position in place due to light weight. Where can you use Polypanel? • Hospitals Commercial high rise buildings • Wineries Domestic buildings and apartments • Pharmaceutical Cleanrooms • Factories/ Commercial Offices Anywhere where indoor air quality is important and/or when you have installation, schedule and cost constraints. ALUMINIUM EXTERIOR OF THE DUCT Embossed aluminium creates a sturdy exterior which will protect against impact. The lacquer coating increases corrosion resistance. PIR (Polyisocyanurate) Board Durable, light & good insulation. ALUMINIUM INTERIOR OF THE DUCT Coated with transluscent lacquer providing low vapour permeability and preventing air pollution within the duct. Comparison Chart Properties Steel Duct Polypanel Remarks Insulation Additional insulation required at extra cost to fabricate and install Pre-insulation sandwich between two aluminium sheets. No extra process required Pre-insulated Polypanel has better insulation consistency and good vapour barrier Weight 0.8 gauge: 6.5kg/m² 1.0 gauge: 8.1kg/m² Polypanel 20/35 = 1.10kg/m² Polypanel 20/45 = 1.30kg/m² Polypanel 30/35 = 1.85kg/m² Polypanel is less than 25% of steel duct weight. Requires less machinery and manpower to install Noise High noise generation and transfer Limited reverberation effect GI duct hard surfaces promote sound propagation and resonance. Polypanel tends to absorb rather than reflect sound Corrosion By water vapour in air Not affected by water vapour Corrosion in GI ducts is even more common in coastal regions Chemical Rapid corrosion by chemical reaction in air Strong chemical resistance External aluminium surface of Polypanel is coated with lacquer Installation Hard to cut, bend and install East, light & fast to install Fast fabrication and installation of Polypanel ducts Maintenance Difficult, requires tradesmen and equipment Easy, Simple tools and simple process to repair, renew or adjust Blanket insulation for steel ducts may be easily damaged and is difficult & expensive to repair or replace Durability About 10 years Semi-permanent Polypanel, though lightweight, is remarkably stable Cost Expensive More effective Price-Quality relationship than GI duct and insulation Overall Polypanel system is cheaper than GI plus insulation CFC HCFC FREE

Upload: polyaire

Post on 25-Jul-2016

222 views

Category:

Documents


2 download

DESCRIPTION

 

TRANSCRIPT

Page 1: Polyaire polypanelflyer

POLYPANEL

Polypanel is a tested and proven alternative to sheet metal ducting and components.It is widely accepted and currently in use in major domestic and commercial projects throughout the world. (In the United Arab Emirates, the location of highest rate of building development per capita, Pre insulated Aluminium board has taken over in excess of 50% market share in last 4 years)Comprising closed cell polyisocyanurate foam enclosed in two layers of aluminium textured sheet, this product offers superior features and benefits to both the installer and end user, including light weight, strength, ease of fabrication, low vapour permeability and superior hygiene characteristics. Polypanel Ducting• Can be fitted closer to ceilings than galvanised sheet as no space need be left for insulation cladding. This saves on ceiling cavity height.• Can be fitted to fibrous cement and suspended ceilings due to light weight.• Minor adjustments can often be made on site without the need to fabricate a new section in the factory. This saves both time and money.• Requires less machinery to position in place due to light weight. Where can you use Polypanel?• Hospitals• Commercial high rise buildings• Wineries• Domestic buildings and apartments• Pharmaceutical Cleanrooms• Factories/ Commercial Offices• Anywhere where indoor air quality is important and/or when you have installation, schedule and cost constraints.

ALUMINIUM EXTERIOR OF THE DUCT Embossed aluminium creates a sturdy exterior which will protect against impact. The lacquer coating increases corrosion resistance.

PIR (Polyisocyanurate) BoardDurable, light & good insulation. ALUMINIUM INTERIOR OF THE DUCT Coated with transluscent lacquer providing low vapour permeability and preventing air pollution within the duct.

Comparison ChartProperties Steel Duct Polypanel Remarks

Insulation Additional insulation required at extra cost to fabricate and install

Pre-insulation sandwich between two aluminium sheets. No extra process required

Pre-insulated Polypanel has better insulation consistency and good vapour barrier

Weight 0.8 gauge: 6.5kg/m² 1.0 gauge: 8.1kg/m²

Polypanel 20/35 = 1.10kg/m² Polypanel 20/45 = 1.30kg/m² Polypanel 30/35 = 1.85kg/m²

Polypanel is less than 25% of steel duct weight. Requires less machinery and manpower to install

Noise High noise generation and transfer Limited reverberation effect GI duct hard surfaces promote sound propagation and resonance. Polypanel tends to absorb rather than reflect sound

Corrosion By water vapour in air Not affected by water vapour Corrosion in GI ducts is even more common in coastal regions

Chemical Rapid corrosion by chemical reaction in air Strong chemical resistance External aluminium surface of Polypanel is coated with lacquer

Installation Hard to cut, bend and install East, light & fast to install Fast fabrication and installation of Polypanel ducts

Maintenance Difficult, requires tradesmen and equipment Easy, Simple tools and simple process to repair, renew or adjust

Blanket insulation for steel ducts may be easily damaged and is difficult & expensive to repair or replace

Durability About 10 years Semi-permanent Polypanel, though lightweight, is remarkably stable

Cost Expensive More effective Price-Quality relationship than GI duct and insulation

Overall Polypanel system is cheaper than GI plus insulation

CFC HCFC FREE

Page 2: Polyaire polypanelflyer

POLYPANEL

©2016 Polyaire™ Pty Ltd. The manufacturer reserves the right to alter product specifications without notice. E. & O.E. Conditions Apply. PBN_PANEL_15

Polyaire Head Office [email protected]

11-13 White Rd GEPPS CROSS SA 5094

Ph: (08) 8349 8466Fax: (08) 8349 8446

New South Wales [email protected]

Unit 2/167 Prospect HwySEVEN HILLS NSW 2147

Unit 2/6 Church RoadMOOREBANK NSW 2170

Unit 10/33 Maddox StreetALEXANDRIA NSW 2015

70 Mitchell RoadCARDIFF NSW 2285

22 Schiller StreetWAGGA WAGGA NSW 2650

4 Young StreetDUBBO NSW 2830

107 North Street ALBURY NSW 2640

Ph: (02) 8811 1333Fax: (02) 9620 8088

Ph: (02) 9600 8799Fax: (02) 9600 8115

Ph: (02) 9557 6948Fax: (02) 9557 6954

Ph: (02) 4954 6677Fax: (02) 4954 6033

Ph: (02) 6921 7606Fax: (02) 6921 1987

Ph: (02) 6884 4328Fax: (02) 6884 4362

Ph: (02) 6021 7206 Fax: (02) 6041 2090

ACTUnit 17/1 Pirie StreetFYSHWICK ACT 2609

Ph: (02) 6126 3600Fax: (02) 6228 1338

Queensland [email protected]

81-89 Northlink PlaceVIRGINIA QLD 4014

3/60 Dulacca StreetACACIA RIDGE QLD 4110

2/3 Anisar Court MOLENDINAR QLD 4214

Ph: (07) 3866 8700Fax: (07) 3256 8718

Ph: (07) 3273 8043Fax: (07) 3273 6104

Ph: (07) 5656 1900Fax: (07) 5597 5985

South Australia [email protected]

11-13 White RoadGEPPS CROSS SA 5094

1590 Main North RoadBRAHMA LODGE SA 5109

9 Somerset Circuit LONSDALE SA 5160

Ph: (08) 8349 5959Fax: (08) 8349 6659

Ph: (08) 8182 3347Fax: (08) 8182 3348

Ph: (08) 8326 7063 Fax: (08) 8186 1069

Western Australia [email protected]

1 Booth PlaceBALCATTA WA 6021

15 Opportunity StreetWANGARA WA 6065

11 Spencer StreetCOCKBURN CENTRAL WA 6164

Ph: (08) 6241 0555Fax: (08) 9240 1484

Ph: (08) 9303 4506Fax: (08) 9302 5420

Ph: (08) 9414 1723Fax: (08) 9417 9329

Victoria [email protected]

76 Northgate DriveTHOMASTOWN VIC 3074

9-15 Arkwright DriveDANDENONG STH VIC 3175

1 Grace Court SUNSHINE WEST VIC 3020

106 Barwon Terrace SOUTH GEELONG VIC 3220

6/100 New Street RINGWOOD VIC 3134

Ph: (03) 9465 8022Fax: (03) 9465 5484

Ph: (03) 9793 1611 Fax: (03) 9792 0501

Ph: (03) 9311 5679 Fax: (03) 9311 9571

Ph: (03) 5221 7644 Fax: (03) 5221 8299

Ph: (03) 9876 0633 Fax: (03) 9879 2233

United KingdomUnit 9, Baron Avenue Telford Way Industrial EstateKettering, Northants ENGLAND NN16 8UW

Ph: 01536 519 922Fax: 01536 519 949

Asia102, Jalan Dua, Kawasan Perindustrian Olak Lempit42700 Banting, SelangorWEST MALAYSIA

Ph: +603 3149 4100Fax: +603 3149 4101

www.polyaire.com.auPolyaire Locations

Distributed by:

PBN_PANEL_04©2008 Polyaire™ Pty Ltd. Themanufacturerreservestherighttoalterproductspecificationswithoutnotice.E.&O.E.ConditionsApply.

ACT Unit21/1PirieStFYSHWICKACT

Ph: (02) 6126 3600Fax:(02)62281338

Victoria 72-76NissanDriveDANDENONGVIC

Ph: (03) 8710 7000Fax:(03)97692799

108-110NorthgateDrvTHOMASTOWNVIC

Ph:(03)94658022Fax:(03)94655484

Western Australia 1 Booth PlaceBALCATTAWA

Ph: (08) 6241 0555Fax:(08)92401484

United Kingdom Unit 17 Enterprise Court ParkFarmIndustrialEstateWellingboroughNorthantsENGLANDNN86UW

Ph:(44)1933402666Fax:(44)1933402777

Asia 102,JalanDua,KawasanPerindustrianOlakLempit42700 Banting, SelangorWESTMALAYSIA

Ph:+60331494100Fax:+60331494101

Internet www.polyaire.com.au

HEAD OFFICE 11-13WhiteRdGEPPSCROSSSA

Ph:(08)83498466Fax:(08)83498446

SALES OFFICES

New South Wales Unit6/167ProspectHwySEVENHILLSNSW

Ph: (02) 8811 1333Fax:(02)96208088

Unit2/6ChurchRdMOOREBANKNSW

Ph:(02)96008799Fax:(02)96008115

Unit10/33MaddoxStALEXANDRIANSW

Ph:(02)95576948Fax:(02)95576954

70MitchellRdCARDIFFNSW

Ph:(02)49546677Fax:(02)49546033

299CoplandStWAGGAWAGGANSW

Ph:(02)69217606Fax:(02)69211987

4YoungStDUBBONSW

Ph: (02) 6884 4328Fax:(02)68844362

Queensland 81-89NorthlinkPlaceVIRGINIAQLD

Ph: (07) 3866 8700Fax:(07)32568718

14LedaDrvANDREWSQLD

Ph:(07)55768955Fax:(07)55768975

South Australia 5WhiteRoadGEPPSCROSSSA

Ph:(08)83495959Fax:(08)83496659

POLYPANEL

Technical SpecificationDESCRIPTION Polypanel 20 Polypanel 24 Polypanel 36

DIMENSION

Length (±7mm Tolerances) 3.0m 3.0m 3.0m

Width (±3mm Tolerances) 1.2m 1.2m 1.2m

Thickness (+1.5, -1mm Tolerances) 20mm 24mm 36mm

Skin Material Centesimal Aluminium

Thickness of Aluminium Foil (micron) 60 60 60

Outer Surface Protection ProtectantLaquer

Water Permeability Aluminium more than 50 micron thick is a good vapour barrier

THERMAL PROPERTIES

Insulating material Polyisocyanurate(PIR)

Expanding Agent CFCandHCFCfree(ZeroODP)

Closed Cell (%) 95%

Thermal Conductivity @ 23ºC (W/mK) 0.0240 0.0240 0.0240

Thermal Conductance (W/m²K) 1.227 1.000 0.667

R-Value (m²K/W) 0.815 1.0 1.5

Service Temperature Range (ºC) -40 to +80

Co-efficient of linear thermal expansion (mm/mmK) 40 x 10

COMPOSITE MECHANICAL PROPERTIES

Density (kg/m³) 35 ± 2 35 ± 2 35 ± 2

Compressive Strength (kg/cm²) 3.0 ± 0.5 3.0 ± 0.5 3.0 ± 0.5

Water Absorption < 1.5% in weight

FIRE SAFETY AS4254-2000*

Flame Ignitability Index = 0

Flame Spread Index = 0 0

Heat Evolved Index = 0

Smoke Developed Index = 0-1 <3

DUCT SERVICE PROPERTIES

Max Duct Pressure (Pa) 1,000 1,100 1,400

Permissable Velocity in Duct (m/s) <15

-6

+

Note + TestcriteriaasdefinedinAS/NZS1530.3:1999,CSIROCertificateofTestReportNo:FNE8133 * LimitsasdefinedinAS/NZS4254-2000Clause#2.7.2,CSIROCertificateofTestReportNo.:FND0160 ‘ThermalResistanceMeasurementofanInsulationProduct’BRANZTestReportNo.:EC1087#

#

#