SmartAire™ C/T
R0 SmartAire T Controlled Automatic VAV Damper: 17350 ,
7510 Montevideo Road © 2012 Tate Access Floors, Inc. Jessup, MD 20794 Tel (410)799-4200 1
SPECIFICATIONS
General Information Allows For 0-22.1kW Supported IT Loads
2226 Cfm at 0.1” Static Pressure
Fail Closed Operation For 100% Closed for Minimum Hot Aisle Leakage.
Zero Maintenance
20 Gauge Steel Construction
Powder Coat Finish
User Input for 0-10VDC Control Signal or Daisy Chain Signal from SmartAire™ T or P
Six Vane Automatic Damper Design
Damper Control Infinitely Variable 0-100%
Tool less Roll Form Stringer Attachment or Flexible Cable Hangers
23.1”X26.7”X6.2” For Use in >12” FFH
19W/VA Peak – 5W/VA Typical
INCLUDED COMPONENTS
4 X Tool less Roll Form Stringer Hangers
4 X Alternative Corner Lock Hangers
4 X Corner Sealing Shrouds Installed
REQUIRED COMPONENTS
DirectAire™, or DirectAire™ X2
4 Or 16 Unit AC Power Supply
SmartAire Power Cable (Green)
Power/Control Cable (Blue) (1 per ea. SmartAire™ C/T Unit(s) in Daisy Chain Configuration)
UNDERSTRUCTURE OPTIONS
24” Bolted Steel System
24” Wood Core Systems
60cm Bolted Steel System
Flexible Alternative Hanging Method For Corner Lock Hanging
Daisy Chain Connection to SmartAire T Via Power/Control
Cable
Heavy Duty Gear Driven Damper Control For High Reliability
Client Input Switch Phoenix Type Screw Terminal Connector Input
Automatic
Dampers
Fail Open Actuator and
High Speed Controller Tool less
Stringer Hanger
0-10 Input For Client Control- Phoenix
Type Screw Terminal Connector
SmartAire™ C/T
R0 SmartAire T Controlled Automatic VAV Damper: 17350 ,
7510 Montevideo Road © 2012 Tate Access Floors, Inc. Jessup, MD 20794 Tel (410)799-4200 2
PERFORMANCE
SmartAire™ Paired with DirectAire™ CFM @ Static Pressure (in.
wc)
Hanger Install Corner Lock Install
100 % Open Closed 100 % Open Closed
0.02 945 51 1077 164
0.03 1146 63 1312 204
0.04 1313 73 1509 239
0.05 1460 83 1682 271
0.06 1592 91 1838 299
0.08 1824 106 2114 349
0.1 2026 119 2355 394
0.12 2208 131 2573 435
0.14 2373 141 2771 472
0.16 2527 152 2956 508
0.18 2672 162 3130 542
0.2 2807 171 3293 573 For PN: XXXXX Performance refer to SmartAire-T Drawing
INSTALLATION – 24” STEEL WELDED
Tool less
Stringer
Attachment
24VAC Input
(Green)
26.7”
6.2”
23.1”
24 VAC/Control
Output
(Blue/Green)
SmartAire™ C/T
R0 SmartAire T Controlled Automatic VAV Damper: 17350 ,
7510 Montevideo Road © 2012 Tate Access Floors, Inc. Jessup, MD 20794 Tel (410)799-4200 3
INSTALLATION – 60 CM STEEL WELDED
INSTALLATION – 24” WOODCORE
Alternative
Corner Lock
Hangers
Rivet-on Hanger Adapter
(Order Separately)
SmartAire™ C/T
R0 SmartAire T Controlled Automatic VAV Damper: 17350 ,
7510 Montevideo Road © 2012 Tate Access Floors, Inc. Jessup, MD 20794 Tel (410)799-4200 4
WIRING DIAGRAM
SA-PSmartAire-T
SA-PSmartAire-C/T
SA-PSmartAire-C/T
Rack
Rack
Rack
Rack
Rack
Rack
Rack
Rack
Rack
Rack
Rack
Rack
Power/Control
Cable (Blue)
(Order Separately)
Power Module
(Order
Separately)
Hot Aisle ContainAire
(Order Separately)
User Activated Trigger
W/ Cable (By Other)
Hot Aisle
Temperature
Sensor
Power Cable
(Green) (Order
Separately)
Phoenix Type
Terminal
Connector
DirectAire X2
DirectAire X2
DirectAire
(Order Separately)
(Order Separately)