SmartAire™ C/T R0 SmartAire T Controlled Automatic VAV Damper: 17350 , 7510 Montevideo Road © 2012 Tate Access Floors, Inc. Jessup, MD 20794 Tel (410)799-4200 1 SPECIFICATIONS General Information Allows For 0-22.1kW Supported IT Loads 2226 Cfm at 0.1” Static Pressure Fail Closed Operation For 100% Closed for Minimum Hot Aisle Leakage. Zero Maintenance 20 Gauge Steel Construction Powder Coat Finish User Input for 0-10VDC Control Signal or Daisy Chain Signal from SmartAireT or P Six Vane Automatic Damper Design Damper Control Infinitely Variable 0-100% Tool less Roll Form Stringer Attachment or Flexible Cable Hangers 23.1”X26.7”X6.2” For Use in >12” FFH 19W/VA Peak 5W/VA Typical INCLUDED COMPONENTS 4 X Tool less Roll Form Stringer Hangers 4 X Alternative Corner Lock Hangers 4 X Corner Sealing Shrouds Installed REQUIRED COMPONENTS DirectAire, or DirectAireX2 4 Or 16 Unit AC Power Supply SmartAire Power Cable (Green) Power/Control Cable (Blue) (1 per ea. SmartAireC/T Unit(s) in Daisy Chain Configuration) UNDERSTRUCTURE OPTIONS 24” Bolted Steel System 24” Wood Core Systems 60cm Bolted Steel System Flexible Alternative Hanging Method For Corner Lock Hanging Daisy Chain Connection to SmartAire T Via Power/Control Cable Heavy Duty Gear Driven Damper Control For High Reliability Client Input Switch Phoenix Type Screw Terminal Connector Input Automatic Dampers Fail Open Actuator and High Speed Controller Tool less Stringer Hanger 0-10 Input For Client Control- Phoenix Type Screw Terminal Connector

Upload: dodiep

Post on 12-Aug-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

SmartAire™ C/T

R0 SmartAire T Controlled Automatic VAV Damper: 17350 ,

7510 Montevideo Road © 2012 Tate Access Floors, Inc. Jessup, MD 20794 Tel (410)799-4200 1

SPECIFICATIONS

General Information Allows For 0-22.1kW Supported IT Loads

2226 Cfm at 0.1” Static Pressure

Fail Closed Operation For 100% Closed for Minimum Hot Aisle Leakage.

Zero Maintenance

20 Gauge Steel Construction

Powder Coat Finish

User Input for 0-10VDC Control Signal or Daisy Chain Signal from SmartAire™ T or P

Six Vane Automatic Damper Design

Damper Control Infinitely Variable 0-100%

Tool less Roll Form Stringer Attachment or Flexible Cable Hangers

23.1”X26.7”X6.2” For Use in >12” FFH

19W/VA Peak – 5W/VA Typical

INCLUDED COMPONENTS

4 X Tool less Roll Form Stringer Hangers

4 X Alternative Corner Lock Hangers

4 X Corner Sealing Shrouds Installed

REQUIRED COMPONENTS

DirectAire™, or DirectAire™ X2

4 Or 16 Unit AC Power Supply

SmartAire Power Cable (Green)

Power/Control Cable (Blue) (1 per ea. SmartAire™ C/T Unit(s) in Daisy Chain Configuration)

UNDERSTRUCTURE OPTIONS

24” Bolted Steel System

24” Wood Core Systems

60cm Bolted Steel System

Flexible Alternative Hanging Method For Corner Lock Hanging

Daisy Chain Connection to SmartAire T Via Power/Control

Cable

Heavy Duty Gear Driven Damper Control For High Reliability

Client Input Switch Phoenix Type Screw Terminal Connector Input

Automatic

Dampers

Fail Open Actuator and

High Speed Controller Tool less

Stringer Hanger

0-10 Input For Client Control- Phoenix

Type Screw Terminal Connector

terri.davis
Tate Airflow

SmartAire™ C/T

R0 SmartAire T Controlled Automatic VAV Damper: 17350 ,

7510 Montevideo Road © 2012 Tate Access Floors, Inc. Jessup, MD 20794 Tel (410)799-4200 2

PERFORMANCE

SmartAire™ Paired with DirectAire™ CFM @ Static Pressure (in.

wc)

Hanger Install Corner Lock Install

100 % Open Closed 100 % Open Closed

0.02 945 51 1077 164

0.03 1146 63 1312 204

0.04 1313 73 1509 239

0.05 1460 83 1682 271

0.06 1592 91 1838 299

0.08 1824 106 2114 349

0.1 2026 119 2355 394

0.12 2208 131 2573 435

0.14 2373 141 2771 472

0.16 2527 152 2956 508

0.18 2672 162 3130 542

0.2 2807 171 3293 573 For PN: XXXXX Performance refer to SmartAire-T Drawing

INSTALLATION – 24” STEEL WELDED

Tool less

Stringer

Attachment

24VAC Input

(Green)

26.7”

6.2”

23.1”

24 VAC/Control

Output

(Blue/Green)

terri.davis
Tate Airflow

SmartAire™ C/T

R0 SmartAire T Controlled Automatic VAV Damper: 17350 ,

7510 Montevideo Road © 2012 Tate Access Floors, Inc. Jessup, MD 20794 Tel (410)799-4200 3

INSTALLATION – 60 CM STEEL WELDED

INSTALLATION – 24” WOODCORE

Alternative

Corner Lock

Hangers

Rivet-on Hanger Adapter

(Order Separately)

terri.davis
Tate Airflow

SmartAire™ C/T

R0 SmartAire T Controlled Automatic VAV Damper: 17350 ,

7510 Montevideo Road © 2012 Tate Access Floors, Inc. Jessup, MD 20794 Tel (410)799-4200 4

WIRING DIAGRAM

SA-PSmartAire-T

SA-PSmartAire-C/T

SA-PSmartAire-C/T

Rack

Rack

Rack

Rack

Rack

Rack

Rack

Rack

Rack

Rack

Rack

Rack

Power/Control

Cable (Blue)

(Order Separately)

Power Module

(Order

Separately)

Hot Aisle ContainAire

(Order Separately)

User Activated Trigger

W/ Cable (By Other)

Hot Aisle

Temperature

Sensor

Power Cable

(Green) (Order

Separately)

Phoenix Type

Terminal

Connector

DirectAire X2

DirectAire X2

DirectAire

(Order Separately)

(Order Separately)