SALESPRESENTATION
COMMERCIALE RANGE 2014
Document title 2
GAMME VRF 2014
⊙Combinaison maximum : Max 48HP with 3
modules
Possibility to connect maximum 64 units
3
Outdoor unit VRF
4
Outside Limit temperature
50
40
30
20
10
0
-10
-20
Cooling
Heating
46℃℃℃℃
DB
-15℃℃℃℃
DB
24℃℃℃℃
WB
-15℃℃℃℃
WB
Cooling : de -15 ℃℃℃℃ à +46℃℃℃℃
Heating: de -15 ℃℃℃℃ à +24 ℃℃℃℃
DB : Dry bulbWB : Wet bulb
5
10 à 48 HP VRF
VRF INVENTER RANGE:
• 10 to 48 HP (10 à 135 KW)
• Maximum 64 unit for one system
• Dimensions optimisées
• Assemblage modulaire jusqu’à 3 groupes
• 1 compressor Inverter for 10 hp
• 1 compressor Inverter + 1 compressor fixe for 14 and16 HP
6
Abundance
The Outdoor units should be selected between 80 and 130% of the total cooling capacities from the indoo r units
Each competitor announce this values as us, but in in a safe and practical way we must selected between 90 and 110% (t be secure in front of exceptional clima tic conditions)
7
Outdoor fan speed
Static pressure80 PA
Efficient Structure--Big diameter « aviation » fan, reduce air loss, air resistance, increase heat exchange efficiency-4 way air return, compressors and condenser are placed in separated compartment for a lower sound level
Hélice grand
diamétre,
concept «
aviation »
8
Low sound level and « Night » mode
• The compartment compressor is totally separated from the air condenser. Design with insulated casing for a big attenuation of the compressors sound level.
•The setting of the night mode is from the Outdoor unit. Sound attenuation up to -8 dBA
9
Back -Up
Function Auto back up
Compresseurs Inverter Fixe Puissance
Alarme Inverter 0%
Alarme Fixe 67%
1 Groupe 2 Compresseurs
Compresseurs Module 2 Module 3 Puissance
Alarme Inverter 33 ou 67 %
Alarme Fixe 80%
Module 1
3 Groupes Extérieurs
Document title 10
Automatic Back up
• Backup 24h.
Document title 11
EER And COP
0
0,5
1
1,5
2
2,5
3
3,5
4
4,5
5
8HP 10HP 12HP
3,9
3,5 3,44
4,6
4,23,9
EER
COP
Document title 12
COMPRESSOR VRF
• Compressor Mitsubishi Electric for all product:
DC FAN MOTOR
AND COMPRESSOR
Document title 13
DRV SOUFFLAGE FRONTALE 6HP ET 10HP
VRF YCV ODU 6 HP AIRWELL 7SP14H009AWAU-YCV180-
H13
VRF
NEWYCV
Front DODU 10 HP AIRWELL 7SP14H011
AWAU-
YCVFD280-H13
Possibilités de connecter maximum: 16 unités intérieures
Document title 14
Easy installation for Our new Product 10HP
Document title 15
Easy maintenance
• Easy maintenance:Maintenance
From the top
Maintenance
From the top
Hinge designHinge design
Document title 16
New front discharge 10HP
• High performance and very easy for installation
Document title 17
Indoor unit VRF 2014
cassetteFloor and
ceiling
High
pressure
ducted
High wallHigh
pressure
ducted
ConsoleMiddle
pressure
ducted
Low pressure
ducted
Middle
pressure
ducted
Indoor units 2014
Document title 18
Low pressure ducted
• Ducted Low pressure:
Possibility connect drain pump.
Static pressure maximum: 20Pa
Wired remote with Just function timer :RWV01
Slim Design (220 mm)
DAV IDU 9
DAV IDU 12
DAV IDU 16
–Wired control as a standard, infra redoptional
–G3 Filter
Document title 19
Ducted middle pressure
• Ducted middle pressure:
Drain pump included in standard
Static pressure : 50 Pa
Static pressure maximum: 96 Pa
Wired remote standard RCWV01
DBV IDU 18
DBV IDU 24
DBV IDU 28
DBV IDU 38
Document title 20
High pressure ducted
• High pressure ducted
Possibility to connect drain pump
Static pressure standard:100 Pa
Static pressure maximum: 196 Pa
Wired remote standard RCWV01DCV IDU 48
DCV IDU 72
DCV IDU 96
Document title 21
Cassette 600*600 et 900*900
• Cassette 600*600 and 900*900
CBV IDU 9
CBV IDU 12
CBV IDU 16
CCV IDU 18
CCV IDU 24
CCV IDU 30
CCV IDU 48
Indoor unit compact with design
unique
Drain pump standard
Possibility add outside airflow
Wired remote standard RCWV01
–drain height up to 600 mm(from the ceiling)
Document title 22
K7 600 x 600Air velocity distribution
Cooling mode
Heating mode
Document title 23
K7 900 x 900Air velocity distribution
Cooling mode
Heating mode
Document title 24
Wall
• wall:
HAV IDU 7
HAV IDU 9
HAV IDU 12
HAV IDU 18
HAV IDU 24
Possibility connect wired remote
–DC fan motor
– Updated design
– Infra red remote control
–Update electronic card withnew function
Document title 25
FAV unit Floor and Ceiling
• FAV unit Floor and Ceiling:
FAV IDU 12
FAV IDU 18
FAV IDU 24
Only 199mm
Wired remote standard
Document title 26
Floor Ceiling
Air velocity distribution console (heating)
Air velocity distribution ceiling (cooling)
Document title 27
Console
– 1 size 12 – Cooling cap 3.6 KW– Heating cap 4 KW– Air supplying from top or bottom of the unit body for fast temperature adjustment–Slim – Integrated EEV– Actual Design– infra red control
28
HRV
HRV heat recovery
• Two possibility of using air flow with differentsproducts :800 et 1000 m3/h
• modes : auto/récupération de chaleur/collatéral• Four fan speed• Option timer 24h
Taille 0800 800/900m3/h - 120Pa
Taille 1000 850/1000m3/h - 100Pa
29
RCWV01
Maintenance Functions
- Display actual default plus one historical default
-Display of running parameters of the unit
( Temp’s sensor, EEV position)
-Reading physical and centralized address
-Display filter dirty
30
Note: Câblage commande 3 fils polarisés
RWV01
Possible installation in :
- Display of set point or ambiance
- Function « I Feel » ( sensor from controller)
-Master and slave (« Va et vient ») - Group commands
(up to 16 units)Compatible with the followingindoor units:
- K7 C B V et C C V.- Ducted units D A V et D B V.- Floor ceiling F A V /HAV
31
RWV03
Compatible with the following indoor units :
- K7 C B V et C C V.
- Ducted D A V et D B V.
- Floor / Ceiling F A V /HAV
Installation possibility on :
- Master / slaves - Group command
(up to 16 units)
- Information for preheating and defrost
32
RWV03
Basic functions :
-ON / OFF ;-Fan speed selection-Selection mode ;-temperature setting.-Swing setting
Maintenace function:
- Display actual default and one historical default
Type RW V 0 3
Code 7ACELH 008
33
RCV01
Type RC V 01Code 7ACELH 001
Basic functions :
-ON / OFF ; Fan speed selectionSelection mode ; temperature setting ; Swing setting
-timer function ( ON ; OFF ; ON/OFF) , Horloge( time display)
Annexe functions:
-Back light ( manual activation)
-Screen and keypad lock
-Information of low battery
34
RCV01
Compatible with the following indoor units:
- Wall H A V.- Console E A V .
35
RCV01
Type REC 01Code 7ACELH 009
Type RC V 01Code 7ACELH 001
For ducted:Compatible with RCV 01
VRF AIRWELL RESIDENTIAL
BMS
Document title 37
BMS control (BMV01)
Airwell Residential :
Touch screen
Airwell Residential
Wired remote:
RWV02 ADV01
BACNET :
(BMV03)
Airwell
Residential
Modbus :
ADV03
ADV02 :
ADV02:
+
+
+
Document title 38
Software AIRWELL
RESIDENTIAL
b. Protocol convertor
RS
-23
2
RS-485
Ma
x. 3
2x
AD
V0
2
ADV02
……
Max. 40x indoor units
……
……
……
BMV01
homeBUS
……
……
KWh meter
1. RS-485 lengh max est 1000m.
Document title 39
Touch screen
Code 7ACELH 003 + Code 7ACELH 004
RWV 02
-Management up to 128 ODU-16 Idoor unit per group -Max wired Length = 1000 ml
Command global functions throughtouch screen :
.Individual control
.Zone control
.Weekly timer
.Default reading
.Central lock….
Mandatory gateway ADV01
+
Document title 40
Touch screen
RWV 02
Electrical power 230V, N , 50Hz
ADV 01
Bus
Ma
xi
32
AD
V 0
1
16 Units maxi per group command
128 groups maxi
64 units maxi per
link system
Group N°1 Group N°2 Group N°8
Document title 41
RS-485
ADV01 MAXIMUM 64 Indoor units
……
RWV02
homebus
… …
No.1 Group No..2 Group
No..128 group
Ma
x.
32
AD
V0
1
No.1
No..2
No..32
AC single phase
220-240V,50/60Hz
~
Max. 16 sets indoor units
Document title 42
Weekly timer
1. Lengh maximum : 600m.
2. Possibility connect :16.
3. Connect to indoor PCB directly.
RCWV04
Document title 43
Modbus ADV03
Document title 44
BMS BVM 01
Code 7ACELH 005 + Code 7ACELH 007
ADV 02
Document title 45
Document title 46
BMS Bacnet
ADV 02
IPC Module
Code 7ACELH 006 + Code 7ACELH 007
Document title 47
ADV03Protocol Translator
LonWorks Converter can control up to 32 indoor units
No.1 No..2 No..32
RS
-48
5 m
ax
. 1
00
0m
Lon
Wo
rks
AIRWELL
Net Control
Engine
One LonWorks ADV03 Converter can Only work with ONE
Protocol Translator ADV04
AIRWELL
Metasys
TC
P/I
P
Max.32 indoor units under one IGU06(one modular or
combination outdoor system)
ADV04
SOLUTION LONWORKS
Document title 48
Bacnet BMV03+ADV02
49
Software selection program
50
Project Data
Information to be obtained from the customer (to re alize a nice offer) :
1) Drawings or schemas of the related job 2) Selection conditions (ext / int)3) Kind of (internal units) 4) Kind of controls5) Estimated thermal needs 6) Specific constraints :
1) Outdoor units implantation,2) Way and length piping 3) Available heigth of the ceiling
51
Project Data
What we are able to return back to the customer :
1) Precise recap of indoor unit per room with repere
2) Table data with cooling and heating capacities for all the units
3) Complete refrigerant schema tubing with unitary swit ching
4) Electrical connection schema
5) Product offer (from the Led or excel file) + start up
6) Product documentation – VRF Catalog
52
Software selection program
• File the project name
• File the customer name
The major steps:
• Information on the rooms to be traited
– Surface– Thermal load au M2 or direct load (calculated by the job engineer)
• Selection of the indoor units
• Selection of the outdoor units
• Edition of the refrigerant schema and filled the pi ping length
• Selection of the global control
• Selection of what we want to print on the final rep ort
• Print the report (Word, PDF,Autocad)
• LED importation and price price calculation
• Send the offer to the customer
53
Software selection program
Room configuration
IDU Definition
Validate
Escape
Steps of the selection
54
Information for the rooms
55
Indoor units selection
56
Outdoor unit selectiondétails
ODU with color code
Associated IDU
Alert message
57
Outdoor unit selectiondétails
58
refrigerant schema piping
Unit details
Tubing Length