Laporan Kajian Dan Proposal HOTEL
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
Confidentiality Statement
Copyright © 2012 PT Sinar Thompson. All rights reserved. Neither this documentation nor any part thereof may be passed on to others, copied or reproduced in any form or by any means, or translated into another language, for any purpose without the express prior consent in writing of PT Sinar Thompson. The information contained in this documentation is subject to change and supplementation without prior notice.
This document is the property of PT Sinar Thompson. It contains confidential and proprietary information of PT Sinar Thompson and is not to be disclosed outside of your organization. Any use or reproduction of this document, in whole or in part, other than for evaluation purposes, is strictly prohibited without the express prior written consent of PT Sinar Thompson. In the event you do not accept this proposal, you agree to return all copies of this document to PT Sinar Thompson together with written confirmation that no copies of this document or any of its contents have been retained
2
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
3
Harga yang dibayar untuk sesuatu pencahayaan bukanlah dari pembelian harga lampu itu sendiri, tetapi dihitung dari berapa besar biaya untuk memperoleh cahaya tersebut.
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
LATAR BELAKANG
4
Permasaalahan Energi Global Permasalahan energi adalah permasalahan global yang di seluruh dunia, sebab sampai saat ini belum ada solusi yang tepat untuk menggantikan sumber energi yang berasal dari tambang seperti minyak bumi, gas dan batu bara. Walaupun orang sudah berfikir untuk menggunakan energi alternatif seperti tenaga suria masih saja ada kendala iaitu dari segi investasi awal. Salah satunya memanfaatkan energi matahari menjadi energi listrik iaitu dengan memakai teknologi Solar Panel yang memerlukan investasi yang besar dan perawatan yang intensif khususnya untuk baterai. Seperti yang kita ketahui sumber energi tambang tidak dapat diperbaharui. Otomatis semakin lama, energi tersebut dipakai maka stoknya akan makin terus berkurang dan semakin tinggilah harganya. Padahal mahu tidak mahu kita akan bergantung kepada energi tersebut. Disetiap pembicaraan di media masa sering dibicarakan tentang bagaimana menghadapi krisis energi pada saat ini dan persiapan untuk masa mendatang, jadi secara keseluruhan masalah energi adalah masalah sehari hari yang dihadapi oleh setiap individu di dunia.
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
5
Permasalahan Energi Di Indonesia Di Indonesia sendiri masalah energi bahan bakar sudah menjadi masalah utama yang di hadapi oleh pemerintah. Presiden Indonesia sendiri pernah berbicara agar setiap individu, perusahaan, instansi pemerintah harus membatasi penggunaan energibahan bakar dan energi listrik.
Yang jadi pertanyaan bagaimana cara meminimalisir penggunaan listrik untuk penerangan? Apakah kita akan kembali kepada zaman dahulu atau membatasi penggunaan lampu? Kalau untuk individu rumah tangga mungkin sedikit banyak dapat dibatasi. Tetapi bagi kalangan pengusaha yang sangat bergantung pada pencahayaan, bagaimana? Hal ini pasti menjadi delima karena kurangnya pencahayaan akan mempengaruhi kekutaan bisnis usaha mereka. Contohnya, bisnis jasa perhotelan karena cahaya punya daya tarik yang besar untuk menarik pengunjung. Untuk pengusaha hotel, cahaya adalah seumpama’make-up’ bagi seorang wanita. Hal yang biasa biasa saja bisa menjadi sesuatu yang luar biasa kerana pencahayaan, dan tentunya harus tahu cara pemakaian dan penggunaannya.
Salah satu pemakaian energi yang dominan adalah energi listrik. Dimana energi listrik presentase terbesar diambi l dari bahan bakar yang dipergunakan dalam kehidupan sehari hari. Salah satunya energi listrik digunakan untuk penerangan (lighting), dimana penerangan adalah kebutuhan yang sangat pokok untuk manusia apalagi di zaman modern saat ini yang dialami di Indonesia
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
6
Permasalahan Energi Bagi Pengusaha Hotel Salah satu bisnis yang merasa sangat terpengaruh dengan krisis energi terutama energi listrik adalah pengusaha perhotelan dimana permakaian lighting sangat berpengaruh terhadap keputusan yang diambil agar bisa bersaing dengan kompetitor karena semakin bertambahnya populasi penduduk dan berkembangnya kemajuan zaman, kebutuhan akan jasa ini semakin meningkat dari tahun ke tahun. Kita bisa buktikan bahawa tahun ke tahun bisnis pehotelan di Indonesia semakin menjamur, sehingga menimbulkan persaingan dalam bisnis ini semakin ketat. Masing masing hotel menawarkan jasa dalam berbagai bentuk, apakah itu dengan diskaun atau perlayanan extra untuk menarik pengunjung. Seiring dengan itu pengunjung sendiri akan lebih selektif dalam memilih hotel yang akan dikunjungi. Selain dari penawaran tarif dan pelayanan yang menarik, adalagi salah satu aspek yang harus dipertimbangkan yaitu aspek keindahan hotel. Karena ada sebahagian pengunjung memilih sesuatu hotel yang sesuai dengan status dia. Dari sudut keindahan hotel ada perbedaan di siang hari dan di malam hari. Hotel itu akan berbeda terlihat antara malam dan siang hari jika diberi penekanan dari sudut pencahayaan. Bisa jadi waktu siang sebuah hotel terlihat biasa biasa saja dan sangat luar biasa dilihat di waktu malam. Kuncinya adalah pencahayaan.
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
7
Dengan kenaikan tarif dasar listrik dari tahun ke tahun akan menjadi dilema untuk memperindah pencahayaan di waktu malam karena akan menambah biaya listrik yang berdampak pada bertambahnya cash-flow hotel tersebut. Keindahan dalam hotel juga mempengaruhi daya tarik dan performance hotel itu sendiri. Masalahnya tetap sama yaitu masalah penghematan energi listrik untuk menekan biaya. Bagaimana cara menyingkapi masalah ini? Dan apa solusinya?
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
8
Latar Belakang Thompson Lighting and PT Sinar Thompson Keberadaan Thompson Lighting sudah mencakup hingga se Asia Tenggara. Kantor Pusat kami terletak di Hong Kong dan lokasi pabrikan terletak di Philiphines, Taiwan, China dan Italy. Kami juga memiliki beberapa distributor di seluruh Asia Tenggara dan Kantor Principal di Philiphines, Taiwan, Hong Kong, China, Malaysia dan Indonesia (PT Sinar Thompson).Kami memberikan jasa sekaligus memenuhi keperluan se Asia Tenggara. Thompson Lighting memberikan servis lengkap yang merangkumi pabrikan, penyalur, pemasangan dan perawatan kepada klien.
Thompson Lighting Philippine and SV-LED Factory 1 Mandaluyung City, Manila
Thompson Lighting SV-LED Factory 2 Jhonghe City, Taipei
Thompson Lighting SV-LED Factory 3 Shenzhen, China
Partner: FORMA Factory Forma Lighting, Italy
Thompson Lighting (M) Sdn Bhd Kuala Lumpur
Thompson Lighting (Sabah) Sdn Bhd Kota Kinabalu
Thompson Lighting Marketing and Distribution Hub Hong Kong
PT Sinar Thompson Jakarta
GDO Hong Kong, Kuala Lumpur
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
9
Misi Dan Visi PT Sinar Thompson Kami dari PT Sinar Thompson sebagai Principal Agent dari Thompson Lighting mencoba menjalani bisnis lighting khususnya di Indonesia. PT Sinar Thompson adalah perusahaan yang bergerak dibidang lighting baik itu produksi, penjualan, konsultasi dan design lighting untuk interior dan exterior. Untuk lighting sendiri, apa yang ditawarkan oleh PT Sinar Thompson adalah penggunaan produk LED (Light Emitting Diode) yang hemat energi. Dengan penggunaan lampu LED merupakan solusi yang paling tepat bagi kami PT Sinar Thompson, dengan pembuktian yang realistis, di mana akan menghemat energi 50% - 70%. Selain itu kami juga akan mengarahkan bagaimana penempatan cahaya yang benar sehingga menimbulkan daya tarik bagi yang melihat. Dengan perhitungan pencahayaan yang tepat. Hal ini menjadi tujuan utama kami dengan menggabungkan teknologi lighting dan seni pencahayaan, karena pencahayaan yang bagus dan tepat akan mempunyai nilai tersendiri dan kami akan memberikan perbandingan bagaimana sebelum dan sesudah menggunakan LED dengan hitungan yang matang.
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
OBJEKTIF KAJIAN DAN PROPOSAL
10
Kajian yang dilakukan kepada beberapa hotel di Bandung dan Semarang dengan menggunakan teknologi LED. Kajian untuk memperbaiki suasana pencahayaan pada hotel Bandung dan Semarang yang akan digunakan pada bangunan hotel (Façade Lighting) permukaan tembok dan siling (Interior Lighting) area lobi, kamar dan landskap (Landscape Lighting) yang terdapat di area hotel dengan teknologi lampu LED
Proposal pencahayaan yang ditawarkan kepada hotel Bandung dan Semarang menggunakan LED merangkup 3 aspek dasar:
1. Nilai Astetika yang memberikan nuansa yang menjurus kepada penempatan dan penggunaan cahaya yang tepat dan sesuai.
2. Nilai Ergonomic yang mengukur penggunaan cahaya yang sesuai 3. Nilai Efesiensi yang digunakan secara maksimal dalam hal
pencahayaan dan meminimalisasikan penggunaan energi itu sendiri
Setiap lampu LED yang ditawarkan akan memberikan 3 elemen yang mencakup:
1. Penampilan Visual – Level pencahayaan yang sesuai dengan kebutuhan
2. Kenyamanan Visual – Pencahayaan yang merata 3. Keindahan Visual – Pemilihan warna pencahayaan yang tepat
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
11
PENEMUAAN DAN DAMPAK DI HOTEL DI BANDUNG DAN SEMARANG
Hasil study memperoleh kesimpulan sebagai berikut:
Penemuan 1: Hotel di Bandung dan Semarang telah melakukan upaya untuk mengurangi penggunaan energi listrik dengan menurunkan pemakaian ‘wattage’ pada tiap titik lampu. Tetapi masih menggunakan teknologi lampu yang sama yaitu CFL (Compact Fluorescent Light). Dampak: W a l a u p u n H o t e l b e r h a s i l m e n u r u n k a n penggunaan’wattage’ tetapi mengorbankan qualitas dan quantitas cahaya (lux level and color temperature) Solusi: PT Sinar Thompson menawarkan solusi dengan menggunakan LED yang meberikan pengurangan ‘wattage’ sekaligus mengembalikan tahap pencahayaan ( lux level) yang dan warna ( color temperature ) yang sesuai.
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
12
Penemuan 2: Di setiap titik tidak ada keselarasan ‘wattage’ sebagai contoh satu ruangan memakai beberapa jenis bohlam yang ‘wattage’nya berbeda beda. Hal tersebut terjadi karena pada saat beberapa bohlam mati, stok yang ada ternyata tidak sesuai ‘wattage’nya yang akan diganti. Dampak: Tiada keselarasan pencahayaan dalam ruangan Solusi: PT Sinar Thompson menawarkan jasa ‘Outsourcing’ untuk perawatan keseluruhan lampu dimana kami akan menjaga ‘Inventory’ lampu pada setiap ruangan. Kami juga akan memastikan ‘wattage’ dan ‘lux level’ dan ‘color temperature’ akan tetap selaras.
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
13
Penemuan 3: Banyak titik titik lampu yang tidak diaktifkan kerana ingin menekan biaya listrik. Dampak: Titik titik tertentu terlihat suram sehingga menimbulkan ketidakselarasan pencahayaan Solusi: PT Sinar Thompson memberikan solusi dimana menggunakan ‘wattage’ LED yang sesuai secara maksimal tanpa membebani biaya penggunaan listrik dan mengorbankan keselarasan pencahayaan di setiap area yang seharusnya memerlukan pencahayaan.
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
14
Penemuan 4: Penggunaan bohlam yang tidak selaras dengan ‘fitting’ sebagai contoh, fitting yang berukuran tinggi 5 inci dengan meletakkan lampu yang berukuran di bawah 5 inci. Ini terjadi kerana keinginan untuk mengurangi ‘wattage’ tanpa mempertimbangkan dampak lampu kepada ‘reflector fitting’ yang sudah ada. Dampak: Sudut pencahayaan ( light angle beam) tidak maksimal yang menyebabkan berkurangnya intensitas cahaya dan ruang lingkup cahaya. Solusi: PT Sinar Thompson menemukan solusi yang tepat dengan menggunakan lampu LED tanpa mengubah ‘fitting’ yang sudah ada tanpa mengorbankan sudut pencahayaan (light angle beam) dan ruang lingkup cahaya.
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
15
Penemuan 5: Di Hotel di Bandung, pencahayaan luar gedung (Façade Lighting) dan lanskap (Landscape Lighting) tidak adanya daya tarik dari segi pencahayaan. Hal ini terjadi karena tidak ada model lampu yang ber’wattage’ rendah dan sesuai dengan struktur area, karena itu terpaksa diminimalisir penggunaan lampu untuk mengurangi biaya listrik. Dampak: Gedung dan halaman terlihat suram dari luar sehingga mengurangi daya tarik Solusi: PT Sinar Thompson mempunyai berbagai macam lampu LED yang ber’wattage’ rendah dan disesuaikan dengan struktur area. Kita akan mendesign area area tertentu yang dianggap menjadi pusat perhatian pengunjung agar t e r l i h a t l e b i h m e n a r i k d e n g a n t i d a k mengeyampingkan penghematan ‘wattage’.
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
16
Penemuan 6: Hotel di Bandung dan Semarang sudah mulai mencoba untuk menggunakan LED. Penjual di Indonesia sebenarnya sudah cukup lama masuk pangsa pasar dan dijual retail, di pusat pusat pasar yang menjual lampu. Pengusaha hotel sendiri sudah tahu kelebihan LED dari segi hemat energinya. Tetapi apakah mereka tahu LED yang mana yang berkualitas baik? Rata rata pengetahuan mereka terbatas pada keinginan untuk memakai LED dengan harga murah tanpa memperhutungkan kualitas LED itu sendiri dan penggunaan LED itu dari sudut penempatan cahaya yang dihasilkan. Dampak: Dampak yang dihasilkan dari pembelian LED yang tidak berkualitas dan kurangnya pengetahuan tentang pengunaan LED dan teknologi yang sebenarnya akan merugikan investment sekaligus timbulnya persepsi bahawa LED itu tidak mempunyai kelebihan. Solusi: PT Sinar Thompson dan Thompson Lighting masuk ke Indonesia dengan salah satu visinya iaitu memperkenalkan teknologi LED lebih dalam dari segala aspek baik itu aspek kualitasnya dan aspek penggunaannya. Sehingga LED sendiri menjadi lampu yang efektif digunakan. Dan akhirnya pengguna LED akan tahu manfaat LED baik dari segi financial dan artistiknya.
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
17
ANALISA PENGGUNAAN LISTRIK UNTUK KONSUMSI LAMPU HOTEL DI BANDUNG
HORISON'BANDUNG'-'ESTIMATES'FOR'ROOMSNo Location Horison'Bandung No'of Total' Total' Total Proposed'Light Prop %
Sub-Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Deluxe Philip'Genie 167 1 x 1 1 1 167 5 w 835'''''''''' w SV-E27B-4WWPP 4 w 167 668''''''''''' w 167'''''''''' w 20%Philip'Essential 167 1 x 1 1 3 501 8 w 4,008''''''' w SV-E27-6WWHB 6 w 501 3,006'''''''' w 1,002''''''' w 25%Halogen'-'Bed'Head 167 1 x 1 1 2 334 40 w 13,360'''' w SV-MR16-3W-WW 3 w 334 1,002'''''''' w 12,358''''' w 93%T8-4Feet 167 1 x 1 1 2 334 46 w 15,364'''' w SV-T8224-18W4C 18 w 334 6,012'''''''' w 9,352''''''' w 61%T8-2Feet 167 1 x 1 1 1 167 28 w 4,676''''''' w SV-T888-9W2C 9 w 167 1,503'''''''' w 3,173''''''' w 68%
1503 38,243'''' w 1503 12,191'''''' w 26,052''''' w 68%2 Executive'Suite Philip'Essential 39 1 x 1 1 7 273 8 w 2,184''''''' w SV-E27-6WWHB 6 w 273 1,638'''''''' w 546'''''''''' w 25%
Halogen'-'Bed'Side 39 1 x 1 1 2 78 20 w 1,560''''''' w SV-MR16-3W-WW 3 w 78 234''''''''''' w 1,326''''''' w 85%T8-4Feet 39 1 x 1 1 2 78 46 w 3,588''''''' w SV-T8224-18W4C 18 w 78 1,404'''''''' w 2,184''''''' w 61%T8-2Feet 39 1 x 1 1 5 195 28 w 5,460''''''' w SV-T888-9W2C 9 w 195 1,755'''''''' w 3,705''''''' w 68%Chili'Bulb'-'Table'Top 39 1 x 1 1 1 39 25 w 975'''''''''' w SV-E14B-4WWCB 4 w 39 156''''''''''' w 819'''''''''' w 84%
663 13,767'''' w 663 5,187'''''''' w 8,580''''''' w 62%3 Presidential'Suite Philip'Genie 1 1 x 1 1 38 38 5 w 190'''''''''' w SV-E27B-4WWPP 4 w 38 152''''''''''' w 38'''''''''''' w 20%
Philip'Essential 1 1 x 1 1 9 9 8 w 72'''''''''''' w SV-E27-6WWHB 6 w 9 54''''''''''''' w 18'''''''''''' w 25%PL-S7W 1 1 x 1 1 1 1 7 w 7'''''''''''''' w SV-E27-6WWHB 6 w 1 6''''''''''''''' w 1'''''''''''''' w 14%PL-S9W 1 1 x 1 1 23 23 9 w 207'''''''''' w SV-E27-6WWHB 6 w 23 138''''''''''' w 69'''''''''''' w 33%T8-4Feet 1 1 x 1 1 1 1 46 w 46'''''''''''' w SV-T8224-18W4C 18 w 1 18''''''''''''' w 28'''''''''''' w 61%T8-2Feet 1 1 x 1 1 4 4 28 w 112'''''''''' w SV-T888-9W2C 9 w 4 36''''''''''''' w 76'''''''''''' w 68%
76 634'''''''''' w 76 404''''''''''' w 230'''''''''' w 36%207 2242 52,644((( w 2242 17,782((((( w 34,862(((( w 66%
LightFittingSetup DifferenceWattageper'
Wattageper'Bulb
EstimatedWattage
TotalWattage
Total'Proposed'Wattage
Proposed
Bulb
TOTAL(FOR(ROOMS
Estimate'Total'Lighting'Config'for'Deluxe
Estimate'Total'Lighting'Config'for'Executive
Estimate'Total'Lighting'Config'for'Presidential
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
18
HORISON'BANDUNG'-'ESTIMATES'FOR'ROOM'CORRIDORSNo Location Horison'Bandung No'of Total' Total' Total Proposed'Light Prop %
Sub-Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Room'Corridors Philips'Genie 8 1 x 1 1 55 440 5 w 2,200''''''' w SV-MR18-3W 3 w 440 1,320'''''''' w 880'''''''''' w 40%Philips'Essential 8 1 x 1 1 14 112 8 w 896'''''''''' w SV-E27-6WWHB 6 w 112 672''''''''''' w 224'''''''''' w 25%
552 3,096''''''' w 552 1,992'''''''' w 1,104''''''' w 36%
2 Floor'Station T8-4Feet 8 1 x 1 1 2 16 46 w 736'''''''''' w SV-T8224-18W4C 18 w 16 288''''''''''' w 448'''''''''' w 61%T8-2Feet 8 1 x 1 1 1 8 28 w 224'''''''''' w SV-T888-9W2C 9 w 8 72''''''''''''' w 152'''''''''' w 68%
24 960'''''''''' w 24 360''''''''''' w 600'''''''''' w 63%
3 Staircase'-'1 T8-4Feet 1 1 x 1 1 10 10 46 w 460'''''''''' w SV-T8224-18W4C 18 w 10 180''''''''''' w 280'''''''''' w 61%Philip'18W 1 1 x 1 1 10 10 18 w 180'''''''''' w SV-E27-12WWHB 12 w 10 120''''''''''' w 60'''''''''''' w 33%
20 640'''''''''' w 20 300''''''''''' w 340'''''''''' w 53%
4 Staircase'-'2 T8-4Feet 1 1 x 1 1 10 10 46 w 460'''''''''' w SV-T8224-18W4C 18 w 10 180''''''''''' w 280'''''''''' w 61%Philip'18W 1 1 x 1 1 10 10 18 w 180'''''''''' w SV-E27-12WWHB 12 w 10 120''''''''''' w 60'''''''''''' w 33%
20 640'''''''''' w 20 300''''''''''' w 340'''''''''' w 53%616 5,336&&&&&& w 616 2,952&&&&&&& w 2,384&&&&&& 45%
Note:1.'Room'Corridors'-'Philips'Genie'is'used'for'downlight'for'display'boxes'on'the'corridor'wall
Wattage DifferenceBulb
Setup
Light Wattage Total Proposed Total' EstimatedFitting per' Wattage Wattage Proposed' Wattage
per'Bulb
HORISON'BANDUNG'-'ESTIMATES'FOR'2nd'FLOOR
No Location Horison'Bandung No'of Total' Total' Total Proposed'Light Prop %
Sub-Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 2nd'Floor' Philip'Essential 1 1 x 1 1 60 60 8 w 480'''''''''' w SV-E27-6WWHB 6 w 60 360''''''''''' w 120'''''''''' w 25%CorridorChandalier'
60 480'''''''''' w 60 360''''''''''' w 120'''''''''' w 25%
2 2nd'Floor' Philip'Essential 1 1 x 1 1 45 45 8 w 360'''''''''' w SV-E27-6WWHB 6 w 45 270''''''''''' w 90'''''''''''' w 25%Corridor Philip'Genie 1 1 x 1 1 13 13 5 w 65'''''''''''' w SV-E27B-4WWPP 4 w 13 52''''''''''''' w 13'''''''''''' w 20%
T8-4Feet 1 1 x 1 1 8 8 46 w 368'''''''''' w SV-T8224-18W4C 18 w 8 144''''''''''' w 224'''''''''' w 61%66 793'''''''''' w 66 466''''''''''' w 327'''''''''' w 41%
3 2nd'Floor T8-4Feet 1 1 x 2 2 32 64 46 w 2,944''''''' w SV-T8224-18W4C 18 w 64 1,152'''''''' w 1,792''''''' w 61%Office T8-4Feet 1 1 x 1 1 6 6 46 w 276'''''''''' w SV-T8224-18W4C 18 w 6 108''''''''''' w 168'''''''''' w 61%
Philips'Essential 1 1 x 1 1 1 1 8 w 8'''''''''''''' w SV-E27-6WWHB 6 w 1 6''''''''''''''' w 2'''''''''''''' w 25%71 3,228''''''' w 71 1,266'''''''' w 1,962''''''' w 61%
4 Meeting'Rooms T8-4Feet 2 1 x 2 2 34 136 36 w 4,896''''''' w SV-T8224-18W4C 18 w 136 2,448'''''''' w 2,448''''''' w 50%PL-S9W 2 1 x 1 1 16 32 9 w 288'''''''''' w SV-E27-6WWHB 6 w 32 192''''''''''' w 96'''''''''''' w 33%Incandescent 2 1 x 1 1 9 18 25 w 450'''''''''' w SV-E27-6WWHB 6 w 18 108''''''''''' w 342'''''''''' w 76%
186 4,896''''''' w 0 w 186 2,748'''''''' w 2,148''''''' w 44%
383 9,397&&&&&& w 383 4,840&&&&&&& w 4,557&&&&&& 48%
Difference
Estimated
Fitting per' Wattage Wattage Proposed' Wattage
Light Wattage Total Proposed Total'
BulbSetup Bulb per' Wattage
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
19
HORISON'BANDUNG'-'ESTIMATES'FOR'GROUND'FLOORNo Location Horison'Bandung No'of Total' Total' Total Proposed'Light Prop %
Sub-Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Ground'Floor Philips'Essential 1 1 x 1 1 39 39 8 w 312'''''''''' w SV-E27-6WWHB 6 w 39 234''''''''''' w 78'''''''''''' w 25%Lift'Landing MR16-LED 1 1 x 1 1 4 4 50 w 200'''''''''' w SV-MR16-3W-WW 3 w 4 12''''''''''''' w 188'''''''''' w 94%
43 512'''''''''' w 43 246''''''''''' w 266'''''''''' w 52%2 Ground'Floor T8-4Feet 1 1 x 2 2 14 28 46 w 1,288''''''' w SV-T8224-18W4C 18 w 28 504''''''''''' w 784'''''''''' w 61%
Reception T8-4Feet 1 1 x 1 1 8 8 46 w 368'''''''''' w SV-T8224-18W4C 18 w 8 144''''''''''' w 224'''''''''' w 61%Philips'Essential 1 1 x 1 1 10 10 8 w 80'''''''''''' w SV-E27-6WWHB 6 w 10 60''''''''''''' w 20'''''''''''' w 25%MR16'Halogen 1 1 x 1 1 3 3 50 w 150'''''''''' w SV-MR16-3W-WW 3 w 3 9''''''''''''''' w 141'''''''''' w 94%
49 1,886''''''' w 49 717''''''''''' w 1,169''''''' 62%3 Ground'Floor Philip'Essential 1 1 x 1 1 130 130 8 w 1,040''''''' w SV-E27-6WWHB 6 w 130 780''''''''''' w 260'''''''''' w 25%
Malabar'Coffee130 1,040''''''' w 130 780''''''''''' w 260'''''''''' w 25%
4 Ground'Floor Philip'Essential 1 1 x 1 1 50 50 8 w 400'''''''''' w SV-E27-6WWHB 6 w 50 300''''''''''' w 100'''''''''' w 25%Center'Lobby'Roof
50 400'''''''''' w 50 300''''''''''' w 100'''''''''' w 25%5 Ground'Floor Philip'Essential 1 1 x 1 1 91 91 8 w 728'''''''''' w SV-E27-6WWHB 6 w 91 546''''''''''' w 182'''''''''' w 25%
Lobby91 728'''''''''' w 91 546''''''''''' w 182'''''''''' w 25%
6 Ground'Floor Philips'Essential 1 1 x 1 1 22 22 8 w 176'''''''''' w SV-E27-6WWHB 6 w 22 132''''''''''' w 44'''''''''''' w 25%Puteri'Lounge Philip'PLCE 1 1 x 1 1 3 3 20 w 60'''''''''''' w SV-E27-12WWHB 12 w 3 36''''''''''''' w 24'''''''''''' w 40%
MR16'Halogen 1 1 x 1 1 10 10 50 w 500'''''''''' w SV-MR16-3W-WW 3 w 10 30''''''''''''' w 470'''''''''' w 94%35 736'''''''''' w 35 198''''''''''' w 538'''''''''' w 73%
7 Ground'Floor Philip'Essential 1 1 x 1 1 20 20 8 w 160'''''''''' w SV-E27-6WWHB 6 w 20 120''''''''''' w 40'''''''''''' w 25%Toilets
20 160'''''''''' w 20 120''''''''''' w 40'''''''''''' w 25%8 Arrival'Porch Philip'Essential 1 1 x 1 1 40 40 8 w 320'''''''''' w SV-E27-6WWHB 6 w 40 240''''''''''' w 80'''''''''''' w 25%
Main40 320'''''''''' w 40 240''''''''''' w 80'''''''''''' w 25%
9 Arrival'Porch Philip'Essential 1 1 x 1 1 37 37 8 w 296'''''''''' w SV-E27-6WWHB 6 w 37 222''''''''''' w 74'''''''''''' w 25%Second
37 296'''''''''' w 37 222''''''''''' w 74'''''''''''' w 25%495 6,078)))))) w 495 3,369))))))) w 2,709)))))) w 45%
Setup DifferenceBulb
EstimatedFitting per' Wattage Wattage Proposed' WattageLight Wattage Total Proposed Total'
Bulb per' Wattage
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
20
HORISON'BANDUNG'-'ESTIMATES'FOR'KRAKATAU'CONVENTION'CENTERNo Location Horison'Bandung No'of Total' Total' Total Proposed'Light Prop %
Sub-Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Krakatau'Conv Philips'Essential 1 1 x 1 1 125 125 8 w 1,000''''''' w SV-E27-6WWHB 6 w 125 750''''''''''' w 250'''''''''' w 25%Outside
125 1,000''''''' w 125 750''''''''''' w 250'''''''''' w 25%
2 Krakatau'Conv Philips'Essential 1 1 x 1 1 294 294 8 w 2,352''''''' w SV-E27-6WWHB 6 w 294 1,764'''''''' w 588'''''''''' w 25%Inside
294 2,352''''''' w 294 1,764'''''''' w 588'''''''''' w 25%419 3,352(((((( w 419 2,514((((((( w 838((((((((( w 25%
LightFitting
Differenceper' Wattage Wattage Proposed' Wattage
Wattage Total Proposed Total' Estimated
BulbSetup Bulb per' Wattage
HORISON'BANDUNG'-'ESTIMATES'FOR'PARAHYAGAN'CONVENTION'AND'POOL'AREANo Location Horison'Bandung No'of Total' Total' Total Proposed'Light Prop %
Sub-Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Suspended' T8-4Feet 1 1 x 1 1 19 19 46 w 874'''''''''' w SV-T8224-18W4C 18 w 19 342''''''''''' w 532'''''''''' w 61%Walkway'toParahyagan'Conv
19 874'''''''''' w 19 342''''''''''' w 532'''''''''' 61%
2 Parahyagan'Conv Philip'Essential 1 1 x 1 1 153 153 8 w 1,224''''''' w SV-E27-6WWHB 6 w 153 918''''''''''' w 306'''''''''' w 25%T8-4Feet 1 1 x 2 2 7 14 46 w 644'''''''''' w SV-T8224-18W4C 18 w 14 252''''''''''' w 392'''''''''' w 61%T8-4Feet 1 1 x 1 1 16 16 46 w 736'''''''''' w SV-T8224-18W4C 18 w 16 288''''''''''' w 448'''''''''' w 61%
183 1,868''''''' w 183 1,458'''''''' w 410'''''''''' 22%
3 Parahyagan'Lobby Philip'Essential 1 1 x 1 1 47 47 8 w 376'''''''''' w SV-E27-6WWHB 6 w 47 282''''''''''' w 94'''''''''''' w 25%47 376'''''''''' w 47 282''''''''''' w 94'''''''''''' w 25%
4 Parahyagan'Lobby Philip'Essential 1 1 x 1 1 28 28 8 w 224'''''''''' w SV-E27-6WWHB 6 w 28 168''''''''''' w 56'''''''''''' w 25%Pool'Area
28 224'''''''''' w 28 168''''''''''' w 56'''''''''''' w 25%277 3,342&&&&&& w 277 2,250&&&&&&& w 1,092&&&&&& w 33%
Difference
EstimatedFitting per' Wattage Wattage Proposed' WattageLight Wattage Total Proposed Total'
BulbSetup Bulb per' Wattage
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
21
HORISON'BANDUNG'-'ESTIMATES'FOR'POLE'LIGHT'-'LANDSCAPENo Location Horison'Bandung No'of Total' Total' Total Proposed'Light Prop %
Sub-Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Pole'Light Philip'PLCE 1 1 x 3 3 35 105 20 w 2,100''''''' w SV-E27-12WWHB 12 w 105 1,260'''''''' w 840'''''''''' w 40%105 2,100''''''' w 105 1,260'''''''' w 840'''''''''' 40%
Setup Bulb per' Wattage DifferenceBulb
Light Wattage Total Proposed Total' EstimatedFitting per' Wattage Wattage Proposed' Wattage
HORISON'BANDUNG'-'ESTIMATES'FOR'SHADED'PARKING
No Location Horison'Bandung No'of Total' Total' Total Proposed'Light Prop %Sub-Location Current'Light Similar Bulb Fitting Bulbs Setting Total' Diff
Setting Rooms/ per' per' BulbAreas Fitting Rooms/
Areas
1 Shaded'Parking T8-4Feet 1 1 x 1 1 5 5 46 w 230'''''''''' w SV-T8224-18W4C 18 w 5 90''''''''''''' w 140'''''''''' w 61%5 230'''''''''' w 5 90''''''''''''' w 140'''''''''' 61%
Bulb
Light Wattage Total Proposed Total' EstimatedFitting per' Wattage Wattage Proposed' WattageSetup Bulb per' Wattage Difference
HORISON'BANDUNG'-'ESTIMATES'FOR'GYM
No Location Horison'Bandung No'of Total' Total' Total Proposed'Light Prop %Sub-Location Current'Light Similar Bulb Fitting Bulbs Setting Total' Diff
Setting Rooms/ per' per' BulbAreas Fitting Rooms/
Areas
1 Gym T8-4Feet 1 1 x 1 1 60 60 46 w 2,760''''''' w SV-T8224-18W4C 18 w 60 1,080'''''''' w 1,680''''''' w 61%60 2,760''''''' w 60 1,080'''''''' w 1,680''''''' 61%
Setup Bulb per' Wattage DifferenceBulb
Light Wattage Total Proposed Total' EstimatedFitting per' Wattage Wattage Proposed' Wattage
HORISON'BANDUNG'-'ESTIMATES'FOR'SPANo Location Horison'Bandung No'of Total' Total' Total Proposed'Light Prop %
Sub-Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Spa Philip'Essential 1 1 x 1 1 47 47 8 w 376'''''''''' w SV-E27-6WWHB 6 w 47 282''''''''''' w 94'''''''''''' w 25%T8-4Feet 1 1 x 1 1 12 12 46 w 552'''''''''' w SV-T8224-18W4C 18 w 12 216''''''''''' w 336'''''''''' w 61%
59 928'''''''''' w 59 498''''''''''' w 430'''''''''' 46%
Bulb
Fitting per' Wattage Wattage Proposed' WattageSetup Bulb per' Wattage Difference
Light Wattage Total Proposed Total' Estimated
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
22
HORISON'BANDUNG'-'ESTIMATES'FOR'OKOH'JAPANESE'RESTAURANT
No Location Horison'Bandung No'of Total' Total' Total Proposed'Light Prop %Sub-Location Current'Light Similar Bulb Fitting Bulbs Setting Total' Diff
Setting Rooms/ per' per' BulbAreas Fitting Rooms/
Areas
1 OKOH'Restaurant Philips'Essential 1 1 x 1 1 98 98 8 w 784'''''''''' w SV-E27-6WWHB 6 w 98 588''''''''''' w 196'''''''''' w 25%T8-4Feet 1 1 x 1 1 50 50 46 w 2,300''''''' w SV-T8224-18W4C 18 w 50 900''''''''''' w 1,400''''''' w 61%MR16'Halogen 1 1 x 1 1 121 121 50 w 6,050''''''' w SV-MR16-3W-WW 3 w 121 363''''''''''' w 5,687''''''' w 94%
269 9,134''''''' w 269 1,851'''''''' w 7,283''''''' 80%
2 Sanggabuana Philip'Essential 1 1 x 1 1 150 150 8 w 1,200''''''' w SV-E27-6WWHB 6 w 150 900''''''''''' w 300'''''''''' w 25%Chandeliar-Philips'Ess 1 1 x 1 1 36 36 8 w 288'''''''''' w SV-E14B-4WWCB 4 w 36 144''''''''''' w 144'''''''''' w 50%
186 1,488''''''' w 186 1,044'''''''' w 444'''''''''' 30%
3 Bidadari Philip'Essential 1 1 x 1 1 150 150 8 w 1,200''''''' w SV-E27-6WWHB 6 w 150 900''''''''''' w 300'''''''''' w 25%Chaneliar-Philip'Ess 1 1 x 1 1 36 36 8 w 288'''''''''' w SV-E14B-4WWCB 4 w 36 144''''''''''' w 144'''''''''' w 50%
186 1,488''''''' w 186 1,044'''''''' w 444'''''''''' w 30%
641 12,110''' w 641 3,939''''''' w 8,171'''''' w 67%
5302 98,277'' w 5302 40,574''' w 57,703'' 59%
Bulb
ESTIMATE'GRAND'TOTAL
EstimatedFitting per' Wattage Wattage Proposed' WattageSetup Bulb per' Wattage Difference
Light Wattage Total Proposed Total'
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
23
HORISON'SEMARANG','ESTIMATES'FOR'ROOMSNo Location Horison'Semarang No'of Total' Total' Total Proposed'Light Prop %
Sub,Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Deluxe Philips'Genie/Panasonic 50 1 x 1 1 5 250 5 w 1,250''''''' w SV,E27B,4WWPP 4 w 250 1,000''''''' w 250''''''''''' w 20%Philips'PLC 50 1 x 1 1 2 100 13 w 1,300''''''' w SV,E27,6WWHB 6 w 100 600'''''''''' w 700''''''''''' w 54%MR16'Halogen 50 1 x 1 1 1 50 50 w 2,500''''''' w SV,MR16,3W,WW 3 w 50 150'''''''''' w 2,350'''''''' w 94%T8,4Feet 50 1 x 1 1 1 50 46 w 2,300''''''' w SV,T8224,18W4C 18 w 50 900'''''''''' w 1,400'''''''' w 61%Chilli'Bulb 50 1 x 1 1 1 50 2.5 w 125'''''''''' w LED'Strip 1 w 50 50'''''''''''' w 75''''''''''''' w 60%
500 7,475''''''' w 500 2,700''''''' w 4,775'''''''' w 64%
2 Horison'Club Philips'Genie/Panasonic 19 1 x 1 1 6 114 5 w 570'''''''''' w SV,E27,6WWHB 4 w 114 456'''''''''' w 114''''''''''' w 20%Philips'PLC 19 1 x 1 1 2 38 13 w 494'''''''''' w SV,E27,6WWHB 6 w 38 228'''''''''' w 266''''''''''' w 54%MR16'Halogen 19 1 x 1 1 1 19 50 w 950'''''''''' w SV,MR16,3W,WW 3 w 19 57'''''''''''' w 893''''''''''' w 94%T8,4Feet 19 1 x 1 1 1 19 46 w 874'''''''''' w SV,T8224,18W4C 18 w 19 342'''''''''' w 532''''''''''' w 61%T8,2Feet 19 1 x 1 1 2 38 28 w 1,064''''''' w SV,T888,9W2C 9 w 38 342'''''''''' w 722''''''''''' w 68%Chili'Bulb 19 1 x 1 1 1 19 2.5 w 48'''''''''''' w LED'Strip 1 w 19 19'''''''''''' w 29''''''''''''' w 60%
247 4,000''''''' w 247 1,444''''''' w 2,556'''''''' w 64%
3 Executive Philips'Genie/Panasonic 10 1 x 1 1 5 50 5 w 250'''''''''' w SV,E27,6WWHB 4 w 50 200'''''''''' w 50''''''''''''' w 20%Philips'PLC 10 1 x 1 1 6 60 13 w 780'''''''''' w SV,E27,6WWHB 6 w 60 360'''''''''' w 420''''''''''' w 54%MR16'Halogen 10 1 x 1 1 1 10 50 w 500'''''''''' w SV,MR16,3W,WW 3 w 10 30'''''''''''' w 470''''''''''' w 94%T8,4Feet 10 1 x 1 1 1 10 46 w 460'''''''''' w SV,T8224,18W4C 18 w 10 180'''''''''' w 280''''''''''' w 61%Chili'Bulb 10 1 x 1 1 1 10 2.5 w 25'''''''''''' w LED'Strip 1 w 10 10'''''''''''' w 15''''''''''''' w 60%
140 2,015''''''' w 140 780'''''''''' w 1,235'''''''' w 61%
4 Horison'Suite Philips'Genie/Panasonic 4 1 x 1 1 5 20 5 w 100'''''''''' w SV,E27B,4WWPP 4 w 20 80'''''''''''' w 20''''''''''''' w 20%Philips'PLC 4 1 x 1 1 7 28 13 w 364'''''''''' w SV,E27,6WWHB 6 w 28 168'''''''''' w 196''''''''''' w 54%T8,4Feet 4 1 x 1 1 4 16 46 w 736'''''''''' w SV,T8224,18W4C 18 w 16 288'''''''''' w 448''''''''''' w 61%Chilli'Bulb 4 1 x 1 1 1 4 2.5 w 10'''''''''''' w LED'Strip 1 w 4 4'''''''''''''' w 6''''''''''''''' w 60%
68 1,210''''''' w 68 540'''''''''' w 670''''''''''' w 55%
5 Royal Philips'Genie/Panasonic 1 1 x 1 1 5 5 5 w 25'''''''''''' w SV,E27B,4WWPP 4 w 5 20'''''''''''' w 5''''''''''''''' w 20%Philips'PLC 1 1 x 1 1 7 7 13 w 91'''''''''''' w SV,E27,6WWHB 6 w 7 42'''''''''''' w 49''''''''''''' w 54%T8,4Feet 1 1 x 1 1 4 4 46 w 184'''''''''' w SV,T8224,18W4C 18 w 4 72'''''''''''' w 112''''''''''' w 61%Chilli'Bulb 1 1 x 1 1 1 1 2.5 w 3'''''''''''''' w LED'Strip 1 w 1 1'''''''''''''' w 2''''''''''''''' w 60%
17 303'''''''''' w 17 135'''''''''' w 168''''''''''' w 55%
6 Junior'Suite Philips'Genie/Panasonic 6 1 x 1 1 5 30 5 w 150'''''''''' w SV,E27,6WWHB 4 w 30 120'''''''''' w 30''''''''''''' w 20%Philips'PLC 6 1 x 1 1 3 18 13 w 234'''''''''' w SV,E27,6WWHB 6 w 18 108'''''''''' w 126''''''''''' w 54%T8,4Feet 6 1 x 1 1 2 12 46 w 552'''''''''' w SV,T8224,18W4C 18 w 12 216'''''''''' w 336''''''''''' w 61%T8,2Feet 6 1 x 1 1 2 12 28 w 336'''''''''' w SV,T888,9W2C 9 w 12 108'''''''''' w 228''''''''''' w 68%Chili'Bulb 6 1 x 1 1 1 6 2.5 w 15'''''''''''' w LED'Strip 1 w 6 6'''''''''''''' w 9''''''''''''''' w 60%
78 1,287''''''' w 78 558'''''''''' w 729''''''''''' w 57%
7 Superior Philips'Genie/Panasonic 74 1 x 1 1 5 370 5 w 1,850''''''' w SV,E27,6WWHB 4 w 370 1,480''''''' w 370''''''''''' w 20%Philips'PLC 74 1 x 1 1 2 148 13 w 1,924''''''' w SV,E27,6WWHB 6 w 148 888'''''''''' w 1,036'''''''' w 54%MR16'Halogen 74 1 x 1 1 1 74 50 w 3,700''''''' w SV,MR16,3W,WW 3 w 74 222'''''''''' w 3,478'''''''' w 94%T8,4Feet 74 1 x 1 1 2 148 46 w 6,808''''''' w SV,T8224,18W4C 18 w 148 2,664''''''' w 4,144'''''''' w 61%Chili'Bulb 74 1 x 1 1 1 74 2.5 w 185'''''''''' w LED'Strip 1 w 74 74'''''''''''' w 111''''''''''' w 60%
814 14,467''''' w 814 5,328''''''' w 9,139'''''''' w 63%
164 1864 30,756**** w 1864 11,485*** w 19,271***** w 63%
Light Wattage Total Proposed Total' Estimated
Setup Bulb per' Wattage DifferenceBulb
Fitting per' Wattage Wattage Proposed' Wattage
Estimate'Total'Lighting'Config'for'Deluxe
Estimate'Total'Lighting'Config'for'Harison'Cllub
TOTAL*FOR*ROOMS
Estimate'Total'Lighting'Config'for'Executive
Estimate'Total'Lighting'Config'for'Harison'Suite
Estimate'Total'Lighting'Config'for'Royal
Estimate'Total'Lighting'Config'for'Junior'Suite
Estimate'Total'Lighting'Config'for'Superior
ANALISA PENGGUNAAN LISTRIK UNTUK KONSUMSI LAMPU HOTEL DI SEMARANG
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
24
HORISON'SEMARANG','ESTIMATES'FOR'ROOMSNo Location Horison'Semarang No'of Total' Total' Total Proposed'Light Prop %
Sub,Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Deluxe Philips'Genie/Panasonic 50 1 x 1 1 5 250 5 w 1,250''''''' w SV,E27B,4WWPP 4 w 250 1,000''''''' w 250''''''''''' w 20%Philips'PLC 50 1 x 1 1 2 100 13 w 1,300''''''' w SV,E27,6WWHB 6 w 100 600'''''''''' w 700''''''''''' w 54%MR16'Halogen 50 1 x 1 1 1 50 50 w 2,500''''''' w SV,MR16,3W,WW 3 w 50 150'''''''''' w 2,350'''''''' w 94%T8,4Feet 50 1 x 1 1 1 50 46 w 2,300''''''' w SV,T8224,18W4C 18 w 50 900'''''''''' w 1,400'''''''' w 61%Chilli'Bulb 50 1 x 1 1 1 50 2.5 w 125'''''''''' w LED'Strip 1 w 50 50'''''''''''' w 75''''''''''''' w 60%
500 7,475''''''' w 500 2,700''''''' w 4,775'''''''' w 64%
2 Horison'Club Philips'Genie/Panasonic 19 1 x 1 1 6 114 5 w 570'''''''''' w SV,E27,6WWHB 4 w 114 456'''''''''' w 114''''''''''' w 20%Philips'PLC 19 1 x 1 1 2 38 13 w 494'''''''''' w SV,E27,6WWHB 6 w 38 228'''''''''' w 266''''''''''' w 54%MR16'Halogen 19 1 x 1 1 1 19 50 w 950'''''''''' w SV,MR16,3W,WW 3 w 19 57'''''''''''' w 893''''''''''' w 94%T8,4Feet 19 1 x 1 1 1 19 46 w 874'''''''''' w SV,T8224,18W4C 18 w 19 342'''''''''' w 532''''''''''' w 61%T8,2Feet 19 1 x 1 1 2 38 28 w 1,064''''''' w SV,T888,9W2C 9 w 38 342'''''''''' w 722''''''''''' w 68%Chili'Bulb 19 1 x 1 1 1 19 2.5 w 48'''''''''''' w LED'Strip 1 w 19 19'''''''''''' w 29''''''''''''' w 60%
247 4,000''''''' w 247 1,444''''''' w 2,556'''''''' w 64%
3 Executive Philips'Genie/Panasonic 10 1 x 1 1 5 50 5 w 250'''''''''' w SV,E27,6WWHB 4 w 50 200'''''''''' w 50''''''''''''' w 20%Philips'PLC 10 1 x 1 1 6 60 13 w 780'''''''''' w SV,E27,6WWHB 6 w 60 360'''''''''' w 420''''''''''' w 54%MR16'Halogen 10 1 x 1 1 1 10 50 w 500'''''''''' w SV,MR16,3W,WW 3 w 10 30'''''''''''' w 470''''''''''' w 94%T8,4Feet 10 1 x 1 1 1 10 46 w 460'''''''''' w SV,T8224,18W4C 18 w 10 180'''''''''' w 280''''''''''' w 61%Chili'Bulb 10 1 x 1 1 1 10 2.5 w 25'''''''''''' w LED'Strip 1 w 10 10'''''''''''' w 15''''''''''''' w 60%
140 2,015''''''' w 140 780'''''''''' w 1,235'''''''' w 61%
4 Horison'Suite Philips'Genie/Panasonic 4 1 x 1 1 5 20 5 w 100'''''''''' w SV,E27B,4WWPP 4 w 20 80'''''''''''' w 20''''''''''''' w 20%Philips'PLC 4 1 x 1 1 7 28 13 w 364'''''''''' w SV,E27,6WWHB 6 w 28 168'''''''''' w 196''''''''''' w 54%T8,4Feet 4 1 x 1 1 4 16 46 w 736'''''''''' w SV,T8224,18W4C 18 w 16 288'''''''''' w 448''''''''''' w 61%Chilli'Bulb 4 1 x 1 1 1 4 2.5 w 10'''''''''''' w LED'Strip 1 w 4 4'''''''''''''' w 6''''''''''''''' w 60%
68 1,210''''''' w 68 540'''''''''' w 670''''''''''' w 55%
5 Royal Philips'Genie/Panasonic 1 1 x 1 1 5 5 5 w 25'''''''''''' w SV,E27B,4WWPP 4 w 5 20'''''''''''' w 5''''''''''''''' w 20%Philips'PLC 1 1 x 1 1 7 7 13 w 91'''''''''''' w SV,E27,6WWHB 6 w 7 42'''''''''''' w 49''''''''''''' w 54%T8,4Feet 1 1 x 1 1 4 4 46 w 184'''''''''' w SV,T8224,18W4C 18 w 4 72'''''''''''' w 112''''''''''' w 61%Chilli'Bulb 1 1 x 1 1 1 1 2.5 w 3'''''''''''''' w LED'Strip 1 w 1 1'''''''''''''' w 2''''''''''''''' w 60%
17 303'''''''''' w 17 135'''''''''' w 168''''''''''' w 55%
6 Junior'Suite Philips'Genie/Panasonic 6 1 x 1 1 5 30 5 w 150'''''''''' w SV,E27,6WWHB 4 w 30 120'''''''''' w 30''''''''''''' w 20%Philips'PLC 6 1 x 1 1 3 18 13 w 234'''''''''' w SV,E27,6WWHB 6 w 18 108'''''''''' w 126''''''''''' w 54%T8,4Feet 6 1 x 1 1 2 12 46 w 552'''''''''' w SV,T8224,18W4C 18 w 12 216'''''''''' w 336''''''''''' w 61%T8,2Feet 6 1 x 1 1 2 12 28 w 336'''''''''' w SV,T888,9W2C 9 w 12 108'''''''''' w 228''''''''''' w 68%Chili'Bulb 6 1 x 1 1 1 6 2.5 w 15'''''''''''' w LED'Strip 1 w 6 6'''''''''''''' w 9''''''''''''''' w 60%
78 1,287''''''' w 78 558'''''''''' w 729''''''''''' w 57%
7 Superior Philips'Genie/Panasonic 74 1 x 1 1 5 370 5 w 1,850''''''' w SV,E27,6WWHB 4 w 370 1,480''''''' w 370''''''''''' w 20%Philips'PLC 74 1 x 1 1 2 148 13 w 1,924''''''' w SV,E27,6WWHB 6 w 148 888'''''''''' w 1,036'''''''' w 54%MR16'Halogen 74 1 x 1 1 1 74 50 w 3,700''''''' w SV,MR16,3W,WW 3 w 74 222'''''''''' w 3,478'''''''' w 94%T8,4Feet 74 1 x 1 1 2 148 46 w 6,808''''''' w SV,T8224,18W4C 18 w 148 2,664''''''' w 4,144'''''''' w 61%Chili'Bulb 74 1 x 1 1 1 74 2.5 w 185'''''''''' w LED'Strip 1 w 74 74'''''''''''' w 111''''''''''' w 60%
814 14,467''''' w 814 5,328''''''' w 9,139'''''''' w 63%
164 1864 30,756**** w 1864 11,485*** w 19,271***** w 63%
Light Wattage Total Proposed Total' Estimated
Setup Bulb per' Wattage DifferenceBulb
Fitting per' Wattage Wattage Proposed' Wattage
Estimate'Total'Lighting'Config'for'Deluxe
Estimate'Total'Lighting'Config'for'Harison'Cllub
TOTAL*FOR*ROOMS
Estimate'Total'Lighting'Config'for'Executive
Estimate'Total'Lighting'Config'for'Harison'Suite
Estimate'Total'Lighting'Config'for'Royal
Estimate'Total'Lighting'Config'for'Junior'Suite
Estimate'Total'Lighting'Config'for'Superior
HORISON'SEMARANG','ESTIMATES'FOR'CORRIDORS'AND'EXIT'STAIRSNo Location Horison'Semarang No'of Total' Total' Total Proposed'Light Prop %
Sub,Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Corridor Philips'Genie/Panasonic 1 1 x 1 1 44 44 5 w 220'''''''''' w SV,E27B,4WWPP 4 w 44 176'''''''''' w 44''''''''''''' w 20%9th'Floor MR16'Halogen 1 1 x 1 1 2 2 50 w 100'''''''''' w SV,MR16,3W,WW 3 w 2 6'''''''''''''' w 94''''''''''''' w 94%
46 320'''''''''' w 46 182'''''''''' w 138''''''''''' w 43%2 Corridor Philips'Genie/Panasonic 1 1 x 1 1 70 70 5 w 350'''''''''' w SV,E27,6WWHB 4 w 70 280'''''''''' w 70''''''''''''' w 20%
6th'Floor70 350'''''''''' w 70 280'''''''''' w 70''''''''''''' w 20%
3 Corridors Philips'Genie/Panasonic 10 1 x 1 1 5 50 5 w 250'''''''''' w SV,E27,6WWHB 4 w 50 200'''''''''' w 50''''''''''''' w 20%Others MR16'Halogen 10 1 x 1 1 1 10 50 w 500'''''''''' w SV,MR16,3W,WW 3 w 10 30'''''''''''' w 470''''''''''' w 94%
60 750'''''''''' w 60 230'''''''''' w 520''''''''''' w 69%4 Exit'Stairs T8,4Feet 3 1 x 1 1 24 72 46 w 3,312''''''' w SV,T8224,18W4C 18 w 72 1,296''''''' w 2,016'''''''' w 61%
72 3,312''''''' w 72 1,296''''''' w 2,016'''''''' w 61%248 4,732''''''' w 248 1,988'''''' w 2,744''''''' w 58%
Light Wattage Total Proposed Total' Estimated
Setup Bulb per' Wattage DifferenceBulb
Fitting per' Wattage Wattage Proposed' Wattage
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
25
HORISON'SEMARANG','ESTIMATES'FOR'OFFICE'6TH'FLOORNo Location Horison'Semarang No'of Total' Total' Total Proposed'Light Prop %
Sub,Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Office'6th'Floor Philips'PLC 1 1 x 1 1 11 11 13 w 143'''''''''' w SV,E27,6WWHB 6 w 11 66'''''''''''' w 77''''''''''''' w 54%11 143'''''''''' w 11 66'''''''''''' w 77''''''''''''' w 54%
Light Wattage Total Proposed Total' EstimatedFitting per' Wattage Wattage Proposed' WattageSetup Bulb per' Wattage Difference
Bulb
HORISON'SEMARANG','ESTIMATES'FOR'BOROBUDUR'LOUNGENo Location Horison'Semarang No'of Total' Total' Total Proposed'Light Prop %
Sub,Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Borobudur'Lounge Philips'PLC 1 1 x 1 1 9 9 13 w 117'''''''''' w SV,E27,6WWHB 6 w 9 54'''''''''''' w 63''''''''''''' w 54%MR16'Halogen 1 1 x 1 1 12 12 50 w 600'''''''''' w SV,MR16,3W,WW 3 w 12 36'''''''''''' w 564''''''''''' w 94%T8,4Feet 1 1 x 1 1 3 3 46 w 138'''''''''' w SV,T8224,18W4C 18 w 3 54'''''''''''' w 84''''''''''''' w 61%
24 855'''''''''' w 24 144'''''''''' w 711''''''''''' w 83%
Light Wattage Total Proposed Total' Estimated
Setup Bulb per' Wattage DifferenceBulb
Fitting per' Wattage Wattage Proposed' Wattage
HORISON'SEMARANG','ESTIMATES'FOR'LOBBY'AND'RECEPTIONNo Location Horison'Semarang No'of Total' Total' Total Proposed'Light Prop %
Sub,Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Lobby'and'Reception Philips'Genie/Panasonic 1 1 x 1 1 4 4 5 w 20'''''''''''' w SV,E27B,4WWPP 4 w 4 16'''''''''''' w 4''''''''''''''' w 20%Philips'PLC 1 1 x 1 1 2 2 13 w 26'''''''''''' w SV,E27,6WWHB 6 w 2 12'''''''''''' w 14''''''''''''' w 54%MR16'Halogen 1 1 x 1 1 40 40 50 w 2,000''''''' w SV,MR16,3W,WW 3 w 40 120'''''''''' w 1,880'''''''' w 94%Chilli'Bulb 1 1 x 1 1 28 28 25 w 700'''''''''' w SV,E14B,4WWCB 4 w 28 112'''''''''' w 588''''''''''' w 84%
74 2,746''''''' w 74 260'''''''''' w 2,486'''''''' w 91%
EstimatedFitting per' Wattage Wattage Proposed' WattageLight Wattage Total Proposed Total'
Setup Bulb per' Wattage DifferenceBulb
HOTEL&SEMARANG&-&ESTIMATES&FOR&PUTERI&BARNo Location Horison&Semarang No&of Total& Total& Total Proposed&Light Prop %
Sub-Location Current&Light Similar Bulb Fitting Bulbs Setting Total& DiffSetting Rooms/ per& per& Bulb
Areas Fitting Rooms/Areas
1 Puteri&Bar MR16&Halogen 1 1 x 1 1 46 46 50 w 2,300&&&&&&& w SV-MR16-3W-WW 3 w 46 138&&&&&&&&&& w 2,162&&&&&&&& w 94%46 2,300&&&&&&& w 46 138&&&&&&&&&& w 2,162&&&&&&&& w 94%
Light Wattage Total Proposed Total& Estimated
Bulb
WattageSetup Bulb per& Wattage DifferenceFitting per& Wattage Wattage Proposed&
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
26
HOTEL&SEMARANG&-&ESTIMATES&FOR&2ND&FLOOR&LOBBYNo Location Horison&Semarang No&of Total& Total& Total Proposed&Light Prop %
Sub-Location Current&Light Similar Bulb Fitting Bulbs Setting Total& DiffSetting Rooms/ per& per& Bulb
Areas Fitting Rooms/Areas
1 2nd&Floor&Lobby Philips&PLCE 1 1 x 1 1 23 23 13 w 299&&&&&&&&&& w SV-E27-6WWHB 6 w 23 138&&&&&&&&&& w 161&&&&&&&&&&& w 54%MR16&Halogen 1 1 x 1 1 17 17 50 w 850&&&&&&&&&& w SV-MR16-3W-WW 3 w 17 51&&&&&&&&&&&& w 799&&&&&&&&&&& w 94%T8-4Feet 1 1 x 1 1 1 1 46 w 46&&&&&&&&&&&& w SV-T8224-18W4C 18 w 1 18&&&&&&&&&&&& w 28&&&&&&&&&&&&& w 61%
41 1,195&&&&&&& w 41 207&&&&&&&&&& w 988&&&&&&&&&&& w 83%
Light Wattage Total Proposed Total&
Setup Bulb per& Wattage DifferenceBulb
EstimatedFitting per& Wattage Wattage Proposed& Wattage
HOTEL&SEMARANG&-&ESTIMATES&FOR&PAPANDAIAN&HALLNo Location Horison&Semarang No&of Total& Total& Total Proposed&Light Prop %
Sub-Location Current&Light Similar Bulb Fitting Bulbs Setting Total& DiffSetting Rooms/ per& per& Bulb
Areas Fitting Rooms/Areas
1 Papandaian&Hall Philips&Genie/Panasonic 1 1 x 1 1 80 80 5 w 400&&&&&&&&&& w SV-E27B-4WWPP 4 w 80 320&&&&&&&&&& w 80&&&&&&&&&&&&& w 20%Philips&PLC 1 1 x 1 1 17 17 13 w 221&&&&&&&&&& w SV-E27-6WWHB 6 w 17 102&&&&&&&&&& w 119&&&&&&&&&&& w 54%T8-4Feet 1 1 x 1 1 96 96 46 w 4,416&&&&&&& w SV-T8224-18W4C 18 w 96 1,728&&&&&&& w 2,688&&&&&&&& w 61%
193 5,037&&&&&&& w 193 2,150&&&&&&& w 2,887&&&&&&&& w 57%
Fitting per& Wattage Wattage Proposed& WattageLight Wattage Total Proposed Total& Estimated
Setup Bulb per& Wattage DifferenceBulb
HOTEL&SEMARANG&-&ESTIMATES&FOR&GOLDEN&DRAGON&RESTAURANTNo Location Horison&Semarang No&of Total& Total& Total Proposed&Light Prop %
Sub-Location Current&Light Similar Bulb Fitting Bulbs Setting Total& DiffSetting Rooms/ per& per& Bulb
Areas Fitting Rooms/Areas
1 Golden&Dragon&Rest Philips&PLC 1 1 x 1 1 58 58 13 w 754&&&&&&&&&& w SV-E27-6WWHB 6 w 58 348&&&&&&&&&& w 406&&&&&&&&&&& w 54%MR16&Halogen 1 1 x 1 1 5 5 50 w 250&&&&&&&&&& w SV-MR16-3W-WW 3 w 5 15&&&&&&&&&&&& w 235&&&&&&&&&&& w 94%T8-4Feet 1 1 x 1 1 87 87 46 w 4,002&&&&&&& w SV-T8224-18W4C 18 w 87 1,566&&&&&&& w 2,436&&&&&&&& w 61%T8-2Feet 1 1 x 1 1 2 2 28 w 56&&&&&&&&&&&& w SV-T888-9W2C 9 w 2 18&&&&&&&&&&&& w 38&&&&&&&&&&&&& w 68%
152 5,062&&&&&&& w 152 1,947&&&&&&& w 3,115&&&&&&&& w 62%
Light Wattage Total Proposed Total& Estimated
Setup Bulb per& Wattage DifferenceBulb
Fitting per& Wattage Wattage Proposed& Wattage
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
27
HOTEL&SEMARANG&-&ESTIMATES&FOR&MURIA&ROOMNo Location Horison&Semarang No&of Total& Total& Total Proposed&Light Prop %
Sub-Location Current&Light Similar Bulb Fitting Bulbs Setting Total& DiffSetting Rooms/ per& per& Bulb
Areas Fitting Rooms/Areas
1 Muria&Room Philips&Genie/Panasonic 1 1 x 1 1 64 64 5 w 320&&&&&&&&&& w SV-E27B-4WWPP 4 w 64 256&&&&&&&&&& w 64&&&&&&&&&&&&& w 20%MR16&Halogen 1 1 x 1 1 36 36 50 w 1,800&&&&&&& w SV-MR16-3W-WW 3 w 36 108&&&&&&&&&& w 1,692&&&&&&&& w 94%T8-4Feet 1 1 x 1 1 44 44 46 w 2,024&&&&&&& w SV-T8224-18W4C 18 w 44 792&&&&&&&&&& w 1,232&&&&&&&& w 61%
144 4,144&&&&&&& w 144 1,156&&&&&&& w 2,988&&&&&&&& w 72%
EstimatedFitting per& Wattage Wattage Proposed& WattageLight Wattage Total Proposed Total&
Setup Bulb per& Wattage DifferenceBulb
HOTEL&SEMARANG&-&ESTIMATES&FOR&STAFF&ROOMNo Location Horison&Semarang No&of Total& Total& Total Proposed&Light Prop %
Sub-Location Current&Light Similar Bulb Fitting Bulbs Setting Total& DiffSetting Rooms/ per& per& Bulb
Areas Fitting Rooms/Areas
1 Staff&Room Philips&Genie/Panasonic 1 1 x 1 1 34 34 5 w 170&&&&&&&&&& w SV-E27B-4WWPP 4 w 34 136&&&&&&&&&& w 34&&&&&&&&&&&&& w 20%T8-4Feet 1 1 x 1 1 8 8 46 w 368&&&&&&&&&& w SV-T8224-18W4C 18 w 8 144&&&&&&&&&& w 224&&&&&&&&&&& w 61%
42 538&&&&&&&&&& w 42 280&&&&&&&&&& w 258&&&&&&&&&&& w 48%
Light Wattage Total Proposed Total& Estimated
Setup Bulb per& Wattage DifferenceBulb
Fitting per& Wattage Wattage Proposed& Wattage
HOTEL&SEMARANG&-&ESTIMATES&FOR&BOTTOM&PARKINGNo Location Horison&Semarang No&of Total& Total& Total Proposed&Light Prop %
Sub-Location Current&Light Similar Bulb Fitting Bulbs Setting Total& DiffSetting Rooms/ per& per& Bulb
Areas Fitting Rooms/Areas
1 Bottom&Parking T8-4Feet 1 1 x 1 1 21 21 46 w 966&&&&&&&&&& w SV-T8224-18W4C 18 w 21 378&&&&&&&&&& w 588&&&&&&&&&&& w 61%21 966&&&&&&&&&& w 21 378&&&&&&&&&& w 588&&&&&&&&&&& w 61%
Fitting per& Wattage Wattage Proposed& WattageLight Wattage Total Proposed Total& Estimated
Setup Bulb per& Wattage DifferenceBulb
HOTEL&SEMARANG&-&ESTIMATES&FOR&TOP&PARKINGNo Location Horison&Semarang No&of Total& Total& Total Proposed&Light Prop %
Sub-Location Current&Light Similar Bulb Fitting Bulbs Setting Total& DiffSetting Rooms/ per& per& Bulb
Areas Fitting Rooms/Areas
1 Top&Parking Philips&Genie/Panasonic 1 1 x 1 1 24 24 5 w 120&&&&&&&&&& w SV-E27B-4WWPP 4 w 24 96&&&&&&&&&&&& w 24&&&&&&&&&&&&& w 20%T8-4Feet 1 1 x 1 1 50 50 46 w 2,300&&&&&&& w SV-T8224-18W4C 18 w 50 900&&&&&&&&&& w 1,400&&&&&&&& w 61%
74 2,420&&&&&&& w 74 996&&&&&&&&&& w 1,424&&&&&&&& w 59%
Light Wattage Total Proposed Total& Estimated
Setup Bulb per& Wattage DifferenceBulb
Fitting per& Wattage Wattage Proposed& Wattage
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
28
HOTEL&SEMARANG&-&ESTIMATES&FOR&EDELWIS&ROOMNo Location Horison&Semarang No&of Total& Total& Total Proposed&Light Prop %
Sub-Location Current&Light Similar Bulb Fitting Bulbs Setting Total& DiffSetting Rooms/ per& per& Bulb
Areas Fitting Rooms/Areas
1 Edelwis&Room Philips&PLCE 1 1 x 1 1 10 10 8 w 80&&&&&&&&&&&& w SV-E27B-4WWPP 4 w 10 40&&&&&&&&&&&& w 40&&&&&&&&&&&&& w 50%10 80&&&&&&&&&&&& w 10 40&&&&&&&&&&&& w 40&&&&&&&&&&&&& w 50%
Fitting per& Wattage Wattage Proposed& WattageLight Wattage Total Proposed Total& Estimated
Setup Bulb per& Wattage DifferenceBulb
HOTEL&SEMARANG&-&ESTIMATES&FOR&OFFICENo Location Horison&Semarang No&of Total& Total& Total Proposed&Light Prop %
Sub-Location Current&Light Similar Bulb Fitting Bulbs Setting Total& DiffSetting Rooms/ per& per& Bulb
Areas Fitting Rooms/Areas
1 Office Panasonic&PLCE 1 1 x 1 1 39 39 8 w 312&&&&&&&&&& w SV-E27-6WWHB 4 w 39 156&&&&&&&&&& w 156&&&&&&&&&&& w 50%Panasonic&PLCE 1 1 x 1 1 18 18 18 w 324&&&&&&&&&& w SV-E27-6WWHB 6 w 18 108&&&&&&&&&& w 216&&&&&&&&&&& w 67%T8-2Feet 1 1 x 1 1 1 18 28 w 504&&&&&&&&&& w SV-T888-9W2C 9 w 18 162&&&&&&&&&& w 342&&&&&&&&&&& w 68%
75 1,140&&&&&&& w 75 426&&&&&&&&&& w 714&&&&&&&&&&& w 63%
Light Wattage Total Proposed Total& Estimated
Setup Bulb per& Wattage DifferenceBulb
Fitting per& Wattage Wattage Proposed& Wattage
HOTEL&SEMARANG&-&ESTIMATES&FOR&SWIMMING&POOLNo Location Horison&Semarang No&of Total& Total& Total Proposed&Light Prop %
Sub-Location Current&Light Similar Bulb Fitting Bulbs Setting Total& DiffSetting Rooms/ per& per& Bulb
Areas Fitting Rooms/Areas
1 Swimming&Pool Philips&Genie/Panasonic 1 1 x 1 1 19 19 5 w 95&&&&&&&&&&&& w SV-E27B-4WWPP 4 w 19 76&&&&&&&&&&&& w 19&&&&&&&&&&&&& w 20%Philips&PLC 1 1 x 1 1 9 9 13 w 117&&&&&&&&&& w SV-E27-6WWHB 6 w 9 54&&&&&&&&&&&& w 63&&&&&&&&&&&&& w 54%MR16&Halogen 1 1 x 1 1 30 30 50 w 1,500&&&&&&& w SV-MR16-3W-WW 3 w 30 90&&&&&&&&&&&& w 1,410&&&&&&&& w 94%T8-4Feet 1 1 x 1 1 51 51 46 w 2,346&&&&&&& w SV-T8224-18W4C 18 w 51 918&&&&&&&&&& w 1,428&&&&&&&& w 61%T8-2Feet 1 1 x 1 1 30 30 28 w 840&&&&&&&&&& w SV-T888-9W2C 9 w 30 270&&&&&&&&&& w 570&&&&&&&&&&& w 68%PAR&38&Halogen 1 1 x 1 1 5 5 80 w 400&&&&&&&&&& w SV-PAR38-12W 12 w 5 60&&&&&&&&&&&& w 340&&&&&&&&&&& w 85%
144 5,298&&&&&&& w 144 1,468&&&&&&& w 3,830&&&&&&&& w 72%
Setup Bulb per& Wattage DifferenceBulb
EstimatedFitting per& Wattage Wattage Proposed& WattageLight Wattage Total Proposed Total&
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
29
HOTEL&SEMARANG&-&ESTIMATES&FOR&KRAKATAU&BALL&ROOMNo Location Horison&Semarang No&of Total& Total& Total Proposed&Light Prop %
Sub-Location Current&Light Similar Bulb Fitting Bulbs Setting Total& DiffSetting Rooms/ per& per& Bulb
Areas Fitting Rooms/Areas
1 Krakatau&Ball&Room Philips&Genie/Panasonic 1 1 x 1 1 256 256 5 w 1,280&&&&&&& w SV-E27B-4WWPP 4 w 256 1,024&&&&&&& w 256&&&&&&&&&&& w 20%Philips&PLC 1 1 x 1 1 34 34 13 w 442&&&&&&&&&& w SV-E27-6WWHB 6 w 34 204&&&&&&&&&& w 238&&&&&&&&&&& w 54%Panasonic&PLCE 1 1 x 1 1 10 10 8 w 80&&&&&&&&&&&& w SV-E27-6WWHB 6 w 10 60&&&&&&&&&&&& w 20&&&&&&&&&&&&& w 25%MR16&Halogen 1 1 x 1 1 4 4 50 w 200&&&&&&&&&& w SV-MR16-3W-WW 3 w 4 12&&&&&&&&&&&& w 188&&&&&&&&&&& w 94%T8-4Feet 1 1 x 1 1 89 89 46 w 4,094&&&&&&& w SV-T8224-18W4C 18 w 89 1,602&&&&&&& w 2,492&&&&&&&& w 61%T8-2Feet 1 1 x 1 1 61 61 28 w 1,708&&&&&&& w SV-T888-9W2C 9 w 61 549&&&&&&&&&& w 1,159&&&&&&&& w 68%Mercury&High&Bay 1 1 x 1 1 30 30 80 w 2,400&&&&&&& w SV-FL-50A 50 w 30 1,500&&&&&&& w 900&&&&&&&&&&& w 38%
484 10,204&&&&& w 484 4,951&&&&&&& w 5,253&&&&&&&& w 51%
WattageSetup Bulb per& Wattage Difference
Light Wattage Total Proposed Total& EstimatedFitting per& Wattage Wattage Proposed&
Bulb
HORISON'SEMARANG','ESTIMATES'FOR'OUTSIDE'HOTELNo Location Horison'Semarang No'of Total' Total' Total Proposed'Light Prop %
Sub,Location Current'Light Similar Bulb Fitting Bulbs Setting Total' DiffSetting Rooms/ per' per' Bulb
Areas Fitting Rooms/Areas
1 Outside'Hotel Philips'Genie/Panasonic 1 1 x 1 1 11 11 5 w 55'''''''''''' w SV,E27B,4WWPP 4 w 11 44'''''''''''' w 11''''''''''''' w 20%Philips'PLC 1 1 x 1 1 7 7 13 w 91'''''''''''' w SV,E27,6WWHB 6 w 7 42'''''''''''' w 49''''''''''''' w 54%PAR'38 1 1 x 1 1 3 3 80 w 240'''''''''' w SV,PAR38,12W 12 w 3 36'''''''''''' w 204''''''''''' w 85%MR16'Halogen 1 1 x 1 1 7 7 50 w 350'''''''''' w SV,MR16,3W,WW 3 w 7 21'''''''''''' w 329''''''''''' w 94%Philips'Spotlight 1 1 x 1 1 5 5 100 w 500'''''''''' w SV,FL,308 30 w 5 150'''''''''' w 350''''''''''' w 70%Philips'Spotlight 1 1 x 1 1 1 1 80 w 80'''''''''''' w SV,FL,308 30 w 1 30'''''''''''' w 50''''''''''''' w 63%Philips'Spotlight 1 1 x 1 1 1 1 400 w 400'''''''''' w SV,FL,162A 162 w 1 162'''''''''' w 238''''''''''' w 60%
35 1,716''''''' w 35 485'''''''''' w 1,231'''''''' w 72%3,682&&&& 79,332&& w 3,682& 28,565&& w 50,767&&& w 64%ESTIMATE&GRAND&TOTAL
Light Wattage Total Proposed Total'
Setup Bulb per' Wattage DifferenceBulb
EstimatedFitting per' Wattage Wattage Proposed' Wattage
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
30
Kesimpulan Dari Analisa Pengunaan Listrik Dengan Teknologi LED 1. Dari analisa yang dibuat, jelas terlihat perbedaan konsumsi listrik
antara CFL (Compact Fluorescent Light) dengan LED yaitu selisih penghematan wattage berkisar antara 50% sampai 60%.
2. Penggantian CFL dengan LED selain memastikan penurunan
pemakaian wattage juga memastikan ‘Lux Level’ dan ‘Color Temperature’ sesuai dengan jenis area dan jenis kegunaanya.
3. Penggantian CFL dengan LED tidak akan merubah ‘fitting’ yang
digunakan sebelumnya yang disebut istilah ‘retrofitting’ sehingga tidak menambah biaya untuk fitting.
4. Dengan pemakaian LED tidak mempengaruhi kenaikan temperatur
suhu suatu ruangan yang berdampak pengurangan terhadap energi air-conditioner di ruangan tersebut. Secara tidak langsung akan mengurangi kinerja air-conditioner
5. Teknologi LED adalah termasuk salah satu produk ‘Green Technology’
yang saat ini sedang digalakan oleh pemerintah sekaligus industri perhotelan adalah menjadi salah satu hotel yang mendukung ‘Green Building Index’ (GBI).
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
ANALISA PELABURAN
31
Technology*ComparisonNo
1 1 w
2 PTST$Thompson$LED$ 1 w
Compariosn*6**Estimated*Wattage*UsedNo
30 infor Bulbs for*
1 w w w pcs w hrs 30 w Kw2 w w w pcs w hrs 30 w kw1,000* 6,000********** days 4,320,000**********
Philip*PL6S13W 13 0 134,320******************
Used Used 1000 1000 Bulbs
9,360******************1,000*
Total*Watt Total*KiloWattWattage*per in days
6
9,360,000**********
per*Bulb Fittings 1000 Fittings
unit(s) 1,000********** untis 1,000********** units
Bulb*Type Wattage Wattage
Retrofit*to*existing*fittingThompson*SV6PLC66W
EstimatedTotal Estimated Total Estimated*
Indoor
13,000******** 24 days
daysby*Ballast
Hours Days 30per*Bulb Consumed Wattage No*of*
per*Bulb
Thompson*SV6PLC66W 6 0 6 24
Conventional$Light Indoor
Remarks Fitting*Type*and* No*of*Bulb* No*of*Fittings No*of*Fittings Wattage*Fitting*Usage per*Fitting per*Fitting
unit(s) 1,000********** units 1,000********** units 13Philip*PL6S13W
Estimated)Monthly)Lighting)BillNo
1 Kw2 Kw
Lighting)Cost)Savings)Per)Month
pcspcs
Thompson)SVAPLCA6W 4,320))))))))))))))))))
Estimated)PLN)Electical)Tariff
IDR)2,000.00IDR)2,000.00
EstimatedMonthly)Bill
IDR)18,720,000.00IDR)8,640,000.00
Kw)Used
Philip)PLAS13W 9,360))))))))))))))))))
Savings)per)year)for
%)Savings 53.85%
1,000) IDR)120,960,000.00
Savings IDR)10,080,000.00
Savings)per)month)for 1,000) IDR)10,080,000.00
Philip)PLAS13W IDR)18,720,000.00Thompson)SVAPLCA6W IDR)8,640,000.00
Bulb)Type Estimated
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
32
No
0 Memberikan-Dukungan Tempo-Dukungan-= Tahun
1 Unit-Pembelian unit unit Perbandingan-Antara-Lampu-Biasa/Umum-Dengan-Lampu-LED-Thompson1 Lampu-Biasa =2 Lampu-LED-SV-Thompson-=-
2 Harga-untuk units Harga-SV/unit-=Harga-Lampu-Biasa/unit-=Kenyataan:-Bujet-awal-pembelian-lampu-LED-ternyata-lebih-mahal-dari
--pembelian-lampu-biasa
3 Garansi-Produk-dan Asumsi: Product.SV.ThompsonDukungan 1 tahun-garansi 2 tahun-garansi-dan Total-------------= 5 tahun
3 tahun-'Comprehensive DukunganMaintenance'-P-Com.Main
Lampu.Biasa1 tahun-garansi
13w 6w
1000
1000 1000
IDR-28,000,000.00 IDR-310,000,000.00
Proposal.PTST
Item Lampu-Biasa/UmumPhilip-PLPS13W
Lampu-LED-SV-ThompsonThompson-SVPPLCP6W
Kalkulasi-dan-Analisa
Philip.PL:S13W
IDR-28,000.00IDR-310,000.00
Thompson.SV:PLC:6W
5
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
33
No
4 Biaya(penggantian(lampu(dalam5 tahun Produk'SV'Thompson
1 Dalam 2 tahun(garansi,(PTST(menggantikan(produk(SV(Thompson(jikaterdapat(kerosakan(pabrikan
2 Biaya(dikeluarkan(untuk(Com.Main(oleh(klien(sebesar per(tahunkepada(PTST(untuk(perawatan unit(produk(SV(Thompson.Segalan(kerusakan(pabrikan(akan(di(tanggung(oleh(PTSTKontrak(Setahun(Com.Main(=
3 Klien(menandatangani(kontrak(selama( tahun(untuk(program(Com.Main(yang(prediksikan(sebesar
Normal'Product1 Estimasai(harga(per(lampu(untuk(penggantian2 Dalam(kurun 5 tahun,(klien(akan(mendapat( 1 tahun(garansi(dan(
4 tahun(kemudian,(klien(menanggung(penggantian(dan(perawatan(sendiri3 Dalam(setahun,(estimasi(penggantian(lampu(adalah unit.((Rujuk(
kembali(Item(Nomor(8)4 Biaya(penggantian(lampu(per(tahun5 Biaya(penggantian(lampu(dalam( adalah6 Biaya(penggantian(lampu(dalam( adalah
Kalkulasi(dan(AnalisaPhilip(PLQS13W Thompson(SVQPLCQ6W
Lampu(Biasa/Umum Lampu(LED(SV(Thompson
13w 6w
IDR(28,000.00
400
54 IDR(44,800,000.00
IDR(11,200,000.00
IDR(44,800,000.00
IDR(44,800,000.00 IDR(186,000,000.00
Item
20%1000
3IDR(186,000,000.00
IDR(62,000,000.00
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
34
No
5 Total(Penggantian
6 Bisa(di(perbaiki
7 Penghematan(biaya(energi Produk'SV'Thompsondalam( 5 tahun Penghematan/Bulan unit(SV(
Penghematan/Tahun unit(SV(Penghematan(dalam tahun(untuk( unit(SV(adalah
(Lihat(kalkulasi(Saving)
Lampu'BiasaTidak(ada(penghematan
8 Biaya(tenaga(kerja(dalam Asumsi:tahun 1.(Setiap(3(bulan( lampu(rusak,(jadi(dlm(1(thn lampu(rusak
2.(Estimasi(biaya(tenaga(kerja(utk(mengganti(satu(lampu3.(Estimasi(biaya(tenaga(kerja(untuk(satu(tahun4.(Estimasi(biaya(tenaga(kerja(untuk tahun
IDR(20,000,000.00
Tidak(ada(penghematan IDR(604,800,000.00
Sudah(termasuk(di(dalam(biaya
13w 6w
IDR(10,080,000.00IDR(120,960,000.00
5
Items Lampu(Biasa/Umum Lampu(LED(SV(Thompson
Biaya(tetap(sebanyak
Bisa
Biaya(maintenance
Bila(rusak,(dibuang
IDR(186,000,000.00
Philip(PLSS13W Thompson(SVSPLCS6W
meningkat(dari(tahun(ke(tahuntanpa(biaya(lain
Calculation(and(Analysis
10001000
1000IDR(604,800,000.00
5 Com.MainIDR(10,000.00
400100
IDR(4,000,000.005 IDR(20,000,000.00
PT SINAR THOMPSON Laporan Kajian & Proposal Untuk Hotel
Copyright © 2012 PT Sinar Thompson. Private and Confidential
Analisa Penggunaan Listrik Untuk Konsumsi Lampu
35
No
9 Total&Biaya&dalam 5 tahun Produk&SV&ThompsonTotal(Biaya/Tahun(=
Total(Harga(Beli: Total(Harga(Beli: Total(Biaya/Tahun/Unit
+(Biaya(Penggantian(: +(Com.(Maintenance: Lampu&BiasaTotal(Biaya/Tahun
+(Biaya(Tenaga(Kerja: @(Penghematan: Total(Biaya/Tahun/Unit(=
Total(Biaya: Total(Biaya:
10 Kesimpulan
Items Lampu(Biasa/Umum Lampu(LED(SV(Thompson Calculation(and(AnalysisPhilip(PL@S13W Thompson(SV@PLC@6W
IDR(44,800,000.00
IDR(20,000,000.00
IDR&92,800,000.00 AIDR&108,800,000.00
panjang
Tingginya(Investasi(Awal
jangka(panjang
Rendahnya(Investasi(Awal
@IDR(21,760,000.00
IDR(28,000,000.00
IDR(92,800,000.00
IDR(604,800,000.00
@IDR(108,800,000.00
13w 6w
@IDR(21,760.00
dan(tingginya(investasi(jangka dan(sangat(rendah(investasi
UntungRugi
IDR(18,560,000.00IDR(18,560.00
IDR(310,000,000.00
IDR(186,000,000.00