The air we breathe is important for our life!
One can live 3 weeks without food, 3 days without water, 3 minutes without air!
People in industrialized countries spend indoor, on average about 90% of the year. Modern buildings and systems do not
allow natural ventilation. This is a major precondition for creation of mechanical ventilation.
The fresh air must be heated in winter and chilled in
summer, and this is related with significant energy
costs. There is a preliminary trend for growing of the
price of energy resources for the last 10 years:
Energy consumption leads to environmental pollution and exhausting of resources of the
planet. It is our duty to protect it for future generation.
Quickly return on investments using heat recovery systems:
Human health and productivity are closely connected with the air quality. Our children
need fresh air even more than us it could help to avoid illnesses and allergies.
The data shown are not universal. These parameters are valid
for the following conditions:
- Bulgaria, Sofia;
- Indoor temperature 22oC;
- Air flow 3000m3/h;
- Installation working time 10 of 24h.
- Installation life time 10 years;
- Energy price 0.1 Euro/kWh;
- 8% annual maintenance costs;
- Energy price growth 12% per year;
- The initial expenses are average;
Your lost money!
HEAT RECOVERY UNITS
-
8/12/2019 Recuperator de Caldura Presiune Inalta
2/7
2
Heat recovery systems are the proper technical and economically acceptable solution:
Applications of heat recovery units:
Ventilation and air-conditioning systems, which provide fresh air supply in:
- Office and residential buildings;
- Hotels, restaurants, cafes, nightclubs;
- Sports halls, gyms and swimming pools;
- Hospitals, schools, laboratories;
- Cinemas, theaters, concert halls;
- Food industries bakeries;
- Technological systems;- Industrial ventilation.
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
-15 -10 -5 0 5 10
Q ,kWh
text ,
ENERGY CONSUMPTION PER YEAR, kWh
AHU - A
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
-15 -10 -5 0 5 10
Q ,kWh
text ,
ENERGY CONSUMPTION PER YEAR, kWh
AHU - A
AHU - B
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
-15 -10 -5 0 5 10
Q ,kWh
text ,
ENERGY CONSUMPTION PER YEAR, kWh
AHU - A
AHU - C
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
-15 -10 -5 0 5 10
Q ,kWh
text ,
ENERGY CONSUMPTION PER YEAR, kWh
AHU - A
AHU - D
,
,
AHU - A
RECAHU - B
AHU - C REC REC
AHU - D
System without
recuperation
E=0%
System with plate
heat exchanger
E=45 58%
System with high-
efficiency plate heat
exchanger
E=65 70%
System with rotary
heat exchanger
E=70 83%
E - % percentage of recovered energy
HEAT RECOVERY UNITS
-
8/12/2019 Recuperator de Caldura Presiune Inalta
3/7
3
Standard range EVB-AL
Middle range low pressure - EVB-CBM
Middle range, high pressure - EVB-CBP
High efficiency range EVB-TOP/ PLUS
Rotary regenerative exchanger range - EVB-ROT
Note: For flow rate higher than mentioned, see Section 6 Air handling units.
HEAT RECOVERY UNITS
= 45 57%
= 52 58%
= 52 56%
= 65 70%
= 70 83%
-
8/12/2019 Recuperator de Caldura Presiune Inalta
4/7
23
HEAT RECOVERY UNITS MIDDLE RANGE HIGH PRESSURE 05.03-01EVB AL-CBP
EVB ALCBP HEAT RECOVERY UNITS
MIDDLE RANGE HIGH PRESSURE
Description
Units for secondary use of energy of the exhaust air in
ventilation and air-conditioning systems.
Operation temperatures from -20C to +50C. Designed to work with clean air in non-aggressive and
non-sparkling environment.
Construction
Supporting construction, made by anodized aluminum
profiles
Thermo- and sound insulated panels, powder coated
RAL7035: Sandwich panels 25 mm with XPS insulation
class M1 or fiberglass class M0.
Cross ow aluminum plate heat exchanger with ecien-
cy up to 55%
Double inlet belt driven centrifugal fans 380V, 50 Hz
Air lters class G4 EN 779:2002
Rectangular duct connector
Drain tray with connection
Service doors from the side
By-pass with multiple leaf damper - on request
Heating/cooling coil on request
Support frame or basic steps on request
Roof panels for outdoor installation on request
Control and management systems - see section 7
-
8/12/2019 Recuperator de Caldura Presiune Inalta
5/7
24
05.03-02 HEAT RECOVERY UNITS MIDDLE RANGE HIGH PRESSUREEVB AL-CBP
Overall and joined dimensions
EVB AL-CBP, Standard version vertical installation
EVB AL-CBP, V Vertical installation
Model FanHeating/cooling
coil
B
[mm]
H
[mm]
L
[mm]
L1
[mm]
b
[mm]
h
[mm]
c
[mm]
d
[mm]
VB AL-41 CBP CBP 10/10 800/500 2R 1150 1350 1900 1500 335 290 600 400
VB AL-61 CBP CBP 12/9 800/800 2R/ 4R 1050 2000 2500 1600 310 340 500 600
VB AL-81 CBP CBP 15/15 1000/800 2R/ 4R 1250 2000 3000 1800 470 400 600 600
Model FanRecuperative
exchangerB [mm] H [mm] L [mm] b [mm] h [mm] c [mm] d [mm]
VB AL-41 CBP CBP 10/10 RECAL-600/5-040 1150 1350 1900 335 290 600 400
VB AL-61 CBP CBP 12/9 RECAL-1200/9-060 850 2000 2500 400 340 500 600
VB AL-81 CBP CBP 15/15 RECAL-1200/9-080 1050 2000 3000 470 400 600 600
-
8/12/2019 Recuperator de Caldura Presiune Inalta
6/7
25
HEAT RECOVERY UNITS MIDDLE RANGE HIGH PRESSURE 05.03-03EVB AL-CBP
Aerodynamic characteristics
Externalpressure
[Pa
]
Air flow [m3/h]
EVB AL-41 CBP
Externa
lpressure
[Pa]
Air flow [m3/h]
EVB AL-61 CBP
Externalpressure
[Pa]
Air flow [m3/h]
EVB AL-81 CBP
Note: - - - - - - the curve is valid for EVB-CBP with incorporated water heating coil COT 2R
-
8/12/2019 Recuperator de Caldura Presiune Inalta
7/7
26
Sound pressure level on frequency bands [dB]
Model min-1 Hz 63 125 250 500 1000 2000 4000 8000
EVB AL-41 CBP
1400 min-1Inlet 66 66 69 67 67 60 52 45
Outlet 66 68 72 71 79 78 69 64
Rad. 64 59 60 54 54 48 37 30
1500 min-1Inlet 67 67 70 68 68 61 53 46
Outlet 67 69 73 72 80 79 70 65
Rad. 65 60 61 55 55 49 40 32
1600 min-1Inlet 68 68 71 69 69 62 54 47
Outlet 68 70 74 73 81 80 71 66
Rad. 66 61 62 56 56 50 42 34
1700 min-1Inlet 69 69 72 70 70 63 55 49
Outlet 69 71 75 74 82 81 72 67
Rad. 67 62 63 57 57 51 44 36
EVB AL-61 CBP
1000 min-1Inlet 68 68 70 69 69 62 54 47
Outlet 68 70 73 74 81 80 71 64
Rad. 66 61 62 56 56 50 42 34
1200 min-1Inlet 70 70 72 71 71 64 56 49
Outlet 70 72 75 76 83 82 73 66
Rad. 68 63 64 58 58 52 44 36
1400 min-1Inlet 72 72 74 73 75 69 58 51
Outlet 72 74 77 78 85 87 75 68
Rad. 70 65 66 60 58 57 46 38
EVB AL-81 CBP
800 min-1Inlet 69 67 69 68 67 61 54 42
Outlet 69 69 72 72 77 77 67 60
Rad. 67 60 61 55 52 46 40 30
1000 min-1Inlet 70 68 70 69 68 62 55 43
Outlet 70 70 73 73 78 78 68 61
Rad. 68 61 62 56 53 47 42 32
1200 min-1Inlet 75 73 75 74 73 68 60 48
Outlet 75 75 78 78 83 83 73 66
Rad. 72 65 63 61 58 55 47 39
Note: Measured in free field conditions at a distance 1,5 m.
05.03-04 HEAT RECOVERY UNITS MIDDLE RANGE HIGH PRESSUREEVB AL-CBP
EVB AL - 41/1600 CBP
Model/Speed
Heat recovery unit
Order designation