Keravent smoke control system Natural smoke and heat exhaust ventilation systems (NSHEV) Kera Group Oy RT 38831 en 324.2 Talo 2000 427.3 Talo 90 X37 SfB Product Information October 2016 1 (8) SV/Grano Oy/Rakennustieto Oy www.rakennustieto.fi © Rakennustietosäätiö RTS 2016 RT tuotetieto RT CAD/BIM PURPOSE OF SMOKE CONTROL In a fire situation, smoke and heat exhaust ventilation systems create and maintain a smoke free layer above the floor by remo- ving smoke, to assist people in evacuation, and faciliate access for firefighting. NSHEVS consists five main components: 1. NSHEV 2. Air inlet 3. Smoke barrier 4. Power supply 5. Control panel HARMONISED EN STANDARDS Performances for NSHEV in normal situati- on, when no fire, are under scopes: EN 14351-1 wall mounted EN 1873 individual rooflights of plastics prEN 1873-2 individual rooflights of glass prEN 1873-3 roof hatches, and EN 14963 Continuous rooflights of plas- tics. Performances in fire situation for NSHEV are under scope of EN 12101-2. Require- ment levels for all smoke control products in Finland are in NAS standards (SFS 7000 serie). Orivent 01 230VAC in Khimky, Moscow Orivent 51 in Itella, Pennala Orivent 01 in Oriville factory, Orimattila Control panel of train depot in Helsinki Power supply of a swimming bath in Espoo Download Orivent BIM objects from ProdLib product library

Upload: others

Post on 26-Dec-2019

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RT 38831 en Keravent smoke control system Natural smoke and … · 2018-09-19 · − EN 14351-1 wall mounted − EN 1873 individual rooflights of plastics − prEN 1873-2 individual

SV/Grano Oy/Rakennustieto Oy www.rakennustieto.fi © Rakennustietosäätiö RTS 2016

RT 38831 en 1

Keravent smoke control systemNatural smoke and heat exhaust ventilation systems (NSHEV)Kera Group Oy

RT 38831 en324.2 Talo 2000427.3 Talo 90 X37 SfB

Product InformationOctober 2016

1 (8)

SV/Grano Oy/Rakennustieto Oy www.rakennustieto.fi © Rakennustietosäätiö RTS 2016

RT tuotetietoRT CAD/BIM

PURPOSE OF SMOKE CONTROL

In a fire situation, smoke and heat exhaust ventilation systems create and maintain a smoke free layer above the floor by remo-ving smoke, to

− assist people in evacuation, and − faciliate access for firefighting.

NSHEVS consists five main components:1. NSHEV2. Air inlet3. Smoke barrier4. Power supply5. Control panel

HARMONISED EN STANDARDS

Performances for NSHEV in normal situati-on, when no fire, are under scopes:

− EN 14351-1 wall mounted − EN 1873 individual rooflights of plastics − prEN 1873-2 individual rooflights of glass − prEN 1873-3 roof hatches, and − EN 14963 Continuous rooflights of plas-tics.

Performances in fire situation for NSHEV are under scope of EN 12101-2. Require-ment levels for all smoke control products in Finland are in NAS standards (SFS 7000 serie).

Orivent 01 230VAC in Khimky, Moscow

Orivent 51 in Itella, Pennala

Orivent 01 in Oriville factory, Orimattila

Control panel of train depot in HelsinkiPower supply of a swimming bath in Espoo

Download Orivent BIM objects from ProdLib product library

Page 2: RT 38831 en Keravent smoke control system Natural smoke and … · 2018-09-19 · − EN 14351-1 wall mounted − EN 1873 individual rooflights of plastics − prEN 1873-2 individual

SV/Grano Oy/Rakennustieto Oy www.rakennustieto.fi © Rakennustietosäätiö RTS 2016

RT 38831 en 2

ORIVENT 51 AND ORIVENT GLASS

Structure − Visible surfaces of color coated sheet metal

− standard colors white, light gray, gray, dark gray and black

− stone wool or PIR insulation 100 mm

Glazing − safety glass, 3K argon filling and selecti-ve coating

Average U values − Orivent 51: 0,58W/m²K (PIR insulated) − Orivent 51: 1,22W/m²K (stone wool) − Orivent 51 Glass: 1,26 W/m²K

Upstand heights– standard 750 mm, 400 or 900 by order

Actuators 24 VDC, 48 VDC or 230 VACA. gas spring operatedthermal fuse + 100 °C, permanent magnet (manual closing from roof )B. motor operatedmotor actuators (controlled from floor le-vel, also suitable for comfort ventilation)

Accessories − burglary protection, fall protection, flashing, limit switch (information to building automation system)

ORIVENT 01 AND ORIVENT 01 DUAL

Structures − acrylic dome or pyramid, single, double or triple layer

Upstands − MAR upstand with wood frame, 8 mm silicate board inside, plywood outside, thermal insulation of stone wool 70 mm or PIR 70 mm by order. Standard height 750 (alternative height 400).

− TAR upstand of Zn sheet metal, insulati-on and heights as in MAR

− Insulated mid beam 300/400 mm in Dual ventilators

Average U values − Orivent 01: U value 0.81 W/m²K (3-layer-dome)

Actuators 24 VDC, 48 VDC or 230 VACA. gas spring operatedthermal fuse + 100 °C, permanent magnet (manual closing from roof )B. motor operatedmotor actuators (controlled from floor le-vel, also suitable for comfort ventilation)

Alternative mountingSolid wood frame SAR h 145 mm may be mounted for structural upstand build at site

Accessories − burglary protection, fall protection, flashing, limit switch (information to building automation system)

Nominal size V1 mm x mm

Weight kg

Current consumption A Aa m² (Cv 0,74)

gas spring motor

1000 x 1000 135 0,4 2,0 0,74

1000 x 2000 195 0,4 2,0 1,48

1200 x 1200 170 0,4 2,0 1,07

1200 x 1800 205 0,4 2,0 1,6

1200 x 2400 250 0,4 2,0 * 2,13

Resistance to heat B 30030, wind load WL 1500, snow load SL 500 with gas spring and SL 750 with motor*no pyramids

Nominal size V1 mm x mm

Weight kg

Current consumption A 24/48 VDC

Aa m² (Cv 0,70...0,64)

gas spring motor

Ø 900 75 0,4 3,0/1,5 0,45 Solo

Ø 1000 95 0,4 3,0/1,5 0,55

Ø 1200 95 0,4 3,0/1,5 0,79

Ø 1500 125 - 3,0/1,5 1,24

900 x 1200 90 0,4 3,0/1,5 0,77

900 x 1800 115 0,4 3,0/1,5 1,13

900 x 2100 125 0,4 3,0/1,5 1,32

1000 x 1000 90 0,4 3,0/1,5 0,70

1000 x 2000 125 0,4 3,0/1,5 1,40

1200 x 1200 105 0,4 3,0/1,5 1,01

1200 x 1800 130 0,4 3,0/1,5 1,51

1200 x 2100 240 - 3,0/1,5 1,76

1200 x 2400 160 - 3,0/1,5 2,02

1500 x 1500 135 - 3,0/1,5 1,58

1800 x 1800 195 0,8 5,0/2,5 2,14 * Dual

2100 x 2100 260 0,8 6,0/3,0 2,91

2400 x 2400 320 0,8 6,0/3,0 3,80 *

Resistance to heat B 60030, wind load WL 1500, snow load SL 500* in glazed hatch 2,8 A

Page 3: RT 38831 en Keravent smoke control system Natural smoke and … · 2018-09-19 · − EN 14351-1 wall mounted − EN 1873 individual rooflights of plastics − prEN 1873-2 individual

SV/Grano Oy/Rakennustieto Oy www.rakennustieto.fi © Rakennustietosäätiö RTS 2016

RT 38831 en 3

ORIVENT 21 (wood structure) ORIVENT 23 (metal structure) ORIVENT 21 AND 23 DUAL ORIVENT 23PC Structures

− exterior and interior surfaces Zn sheet metal, by order color coated sheet metal

− stone wool insulation, 70 mm in upstand and 100 mm in lid

− Orivent 23 PC lid of translucent PC mul-tiwall sheet.

− Dual models with insulated mid-beam, width 300...400 mm.

− alternative ridged lid, recommended when installation on surface without slope.

Average U values − Orivent 21: 0,5 W/m²K − Orivent 23: 0,92 W/m²K − Orivent 23PC: 0,85W/m²K

Upstand heights − standard 750 mm, 400 mm by order

Actuators 24 VDC, 48 VDC or 230 VACA. gas spring operatedthermal fuse + 100 °C, permanent magnet (manual closing from roof )B. motor operatedmotor actuators (controlled from floor le-vel, also suitable for comfort ventilation)

Alternative mountingSolid wood frame SR h 145mm or TR 200 mm may be mounted for structural up-stand build at site

Accessories − burglary protection, fall protection, flashing, limit switch (information to building automation system)

ORIVENT 31 (non-transparent lid) AND ORIVENT 41 (translucent lid)Structures

− exterior and interior surfaces Zn sheet metal, by order color coated sheet metal

− stone wool insulation, 70 mm in upstand and 100 mm in lid

− Orivent 41 PC lid of translucent PC mul-tiwall sheet.

Average U values − Orivent 31: 1,27 W/m2K (PIR insulated) − Orivent 41: 0,85 W/m2K (stone wool)

Upstand heights − lower side 600 mm, higher side 800, 820 and 860 mm

Actuators 24 VDC, 48 VDC or 230 VACA. gas spring operatedthermal fuse + 100 °C, permanent magnet (manual closing from roof )B. motor operatedmotor actuators (controlled from floor le-vel, also suitable for comfort ventilation)

Accessories − burglary protection, fall protection, flashing, limit switch (information to building automation system)

Nominal size V1 mm x mm

Weight kg

Current consumption A 24/48 VDC

Aa m² (Cv 0,73)

gas spring motor

900 x 1200 130 0,4 3,0/1,5 0,79

900 x 1800 151 0,4 3,0/1,5 1,18

900 x 2400 170 0,4 3,0/1,5 1,57

1000 x 1000 121 0,4 3,0/1,5 0,73

1000 x 2000 167 0,4 3,0/1,5 1,46

1000 x 2500 204 0,4 3,0/1,5 1,82

1200 x 1200 144 0,4 3,0/1,5 1,05

1200 x 1800 167 0,4 3,0/1,5 1,57

1200 x 2100 186 0,4 3,0/1,5 1,83

1200 x 2400 204 0,4 5,0/2,5 2,10

Resistance to heat of Orivent 41: B 30030 and Orivent 31: B 60030, wind load WL 1500, snow load SL 500

Nominal size V1 mm x mm

Weight kg

Current consumption A 24/48 VDC

Aa m² (Cv 0,71...0,64)

gas spring motor

900 x 1200 90 0,4 3,0/1,5 0,77 Solo

900 x 1800 110 0,4 3,0/1,5 1,15

1000 x 1000 120 0,4 3,0/1,5 0,71

1000 x 2000 140 0,4 3,0/1,5 1,42

1200 x 1200 130 0,4 3,0/1,5 1,02

1200 x 1800 140 0,4 3,0/1,5 1,53

1200 x 2100 150 - 3,0/1,5 1,79

1200 x 2400 160 - 3,0/1,5 2,04

1500 x 1500 140 - 3,0/1,5 1,51

1800 x 1800 180 0,8 5,0/2,5 2,17 Dual

2100 x 2100 190 0,8 6,0/3,0 2,45

2400 x 2400 210 0,8 6,0/3,0 3,86

Resistance to heat Orivent 21: B 30030, Orivent 23: B 60030, wind load WL 1500, snow load SL 500 with gas spring and SL 750 with motor

Page 4: RT 38831 en Keravent smoke control system Natural smoke and … · 2018-09-19 · − EN 14351-1 wall mounted − EN 1873 individual rooflights of plastics − prEN 1873-2 individual

SV/Grano Oy/Rakennustieto Oy www.rakennustieto.fi © Rakennustietosäätiö RTS 2016

RT 38831 en 4

ORIVENT T2

Structures − sandwich panel with stone wool or PIR insulation

− standard colors: interior white, exterior dark gray

− upstand sandwich panel 70 mm, lid 100 mm PIR insulated.

Average U values − U value 0,45 W/m2K

Upstand heights − standard 800 mm, by order 200 or 400 mm

Actuators − 24 VDC, 48 VDC or 230 VAC motor

Accessories − burglary protection, fall protection, flashing, limit switch (information to building automation system)

ORIVENT T1

Structures − sandwich panel with stone wool or PIR insulation

− standard colors: interior white, exterior dark gray

− Upstand panel 70 mm, lid 100 mm.

Average U values − U value 0,45 W/m2K

Upstand heights − standard 800 mm, by order 200 or 400

Actuators − 24 VDC, 48 VDC or 230 VAC motor

Accessories − burglary protection, fall protection, flashing, limit switch (information to building automation system)

Nominal size V1 mm x mm

Weight kg

Current consumption A 24/48 VDC

Aa m² (Cv 0,74)

900 x 1200 160 3,0/1,5 0,80

900 x 1800 220 3,0/1,5 1,20

1000 x 1000 150 3,0/1,5 0,74

1000 x 2000 270 3,0/1,5 1,48

1200 x 1200 180 3,0/1,5 1,07

1200 x 1800 240 3,0/1,5 1,60

1200 x 2100 280 3,0/1,5 1,86

1200 x 2400 300 3,0/1,5 2,13

Resistance to heat B60030, wind load WL 1500 and snow load SL500

Resistance to heat B 60030, wind load WL 1500, snow load SL 500

Nominal size V1 mm x mm

Weight kg

Current consumption A 24/48 VDC

Aa m² (Cv 0,73)

900 x 1200 160 3,0/1,5 0,79

900 x 1800 220 3,0/1,5 1,18

1000 x 1000 150 3,0/1,5 0,73

1000 x 2000 270 3,0/1,5 1,46

1200 x 1200 180 3,0/1,5 1,05

1200 x 1800 240 3,0/1,5 1,58

1200 x 2100 280 3,0/1,5 1,84

1200 x 2400 310 3,0/1,5 2,10

Page 5: RT 38831 en Keravent smoke control system Natural smoke and … · 2018-09-19 · − EN 14351-1 wall mounted − EN 1873 individual rooflights of plastics − prEN 1873-2 individual

SV/Grano Oy/Rakennustieto Oy www.rakennustieto.fi © Rakennustietosäätiö RTS 2016

RT 38831 en 5

ORIVENT 70 SI AND ORIVENT 70 SL

Casing and opening frameA. Aluminium profile (for warm buildings)

− Purso LK78 profile, thermal break, pow-der coated in RAL colour of choice

B. Schüco, Sapa and Nokia profiles are also included in Keravent’s tested systems. More information about cascading part-ners in Finland: www.keravent.fiC. Aluminium profile system

Average U values − Orivent 70 SI: 1,0 W/m2K − Orivent 70 SL: 0,9 W/m2K

Glazing/steel sheets − 70 SI: 3K triple glazing, argon filling and selective coating

− 70 SL: galvanized steel sheets powder coated in RAL color, PIR insulation board 56 mm

Actuators − Chain drives or rack actuators 24 VDC or 230 VAC, operated from floor level

− Dual purpose ventilators: suitable also for comfort ventilation

Accessories − burglary protection, limit switch (for building automation)

Nominal size, mm

Exterior dimensionwidth x length, mm

Weight, kg

Current consumption A

Aa m²(Cv 0,48...0,56)

U valueW/m²K

1010 990 x 990 21,9 1,0 0,55 0,9

1209 1190 x 890 23,1 1,0 0,59 0,8

1212 1190 x 1190 28,3 1,0 0,68 0,8

2010 1990 x 990 36,6 1,0 1,1 0,8

Orivent 70 SL (Purso LK78, 56 mm PIR insulation)

Nominal size, mm

Exterior dimensionwidth x length, mm

Weight, kg

Current consumption A

Aa m²(Cv 0,48...0,56)

U valueW/m²K

1010 990 x 990 40,4 1,0 0,55 1,0

1209 1190 x 890 44,1 1,0 0,59 0,9

1212 1190 x 1190 38,1 1,0 0,68 1,0

2010 1990 x 990 95,1 1,0 1,1 0,9

Orivent 70 SI (Purso LK78, 3K glazing)

SERVICE AND MAINTENANCE OF NSHEV

According national regulation owner of the building has responsibility to arrange ser-vice for all fire safety systems installed. In Finland this is covered by Rescue Act.

NSHEVS must be maintained according instructions of manufacturer once a year of more often. In this service the system is inspected and minimum 20 % of venti-lators are test relesed, The NSHEVS must have a log book for maintenance, where arr actions done are recorded. According maintenance instructions of Keravent the cycle of whole system is test released in maximum five years.

It is recommended that the building has a named person in charge of maintenance, and to organize contract with specialized service company. The person in charge should maintain the log book.

Annual service and maintenance should be done by a specialized experts who are trained for these actions.

All Keravent power supplies of NSHEVS are equipped with service timer, which re-minds of service needs in case maintenan-ce is not done in time.

Page 6: RT 38831 en Keravent smoke control system Natural smoke and … · 2018-09-19 · − EN 14351-1 wall mounted − EN 1873 individual rooflights of plastics − prEN 1873-2 individual

SV/Grano Oy/Rakennustieto Oy www.rakennustieto.fi © Rakennustietosäätiö RTS 2016

RT 38831 en 6

SMOKE EXHAUST SYSTEM IN A BUILDING

The scheme of a building above shows how two decentralized control panels and a cent-ralized button control the smoke exhaust system. This solution offers optimized cable costs.

Design, installation and maintenance of smoke exhaust systems

RIL 232-2012, Design, installation and main-tenance of smoke exhaust systems, comple-ments the European standard EN 12101 and provides guidelines for functional recom-mendations and calculation methods for smoke exhaust ventilation systems. Details

of recommendations and calculation met-hods for smoke and heat exhaust ventilati-on systems can be found in CEN/TR 12101-5 Smoke and Heat Control Systems. Regu-lations RakMk E1, E2 and E4A can be used for the design of smoke exhaust ventilation systems for staircases, basements, produc-tion buildings and garages. Another simple method is using a design scheme where the building is divided into four categories based on smoke production in the area. In areas, where personal safety is of high impor-tance, calculations are based on steady state or developing fire simulations, and these fire simulations are carried out by a qualified en-gineer. According to RIL 232, the installation

and maintenance of smoke exhaust systems must be carried out by personnel trained and skilled for the expertise. Fire safety and personal safety can be guaranteed, when installation, testing and regular maintenance is carried out by trained personnel.

Installation and maintenance

The supplier of the smoke exhaust system tests the system and signs the installation re-port along with other handover documenta-tion, when installation carried out by system supplier. The installation report is to be pre-sented to the building inspection authority and/or rescue authority if so required.

Ventilation button

Smoke vent button

Power supply

Weather sensor

CABLES1. Input FRH 230 VAC2. Cables to ventilators FRH 24 VDC, 48 VDC or 230 VAC3. Instrumentation cable, fireproof4. Instrumentation cable

ORIVENT SMOKE EXHAUST SHAFT

Orivent shaft is manufactured by robot cutting machinery of sandwich panel. Sandwich structure gives finishing featu-res; finished surfaces, finished insulation, fire and smoke compartmentation, option to install ladder for access to shaft and in-tegrated NSHEV of same finished materials on top of shaft. Sandwich shaft is constant, warm and air tight structure.

Structure − sandwich panel of stone wool or PIR in-sulation

− thickness 100 or 70 mm − selection of colors available

Thermal transmittance − U value with stone wool 0,44 W/m²K − U value with PIR insulation 0,22 W/m²K

Dimensions − width and length by order, maximum horizontal section opening area 1200 x 2400 mm

Heights − heights by order, panels connected with female and male joints

Fire resistance − EI 30-90

Page 7: RT 38831 en Keravent smoke control system Natural smoke and … · 2018-09-19 · − EN 14351-1 wall mounted − EN 1873 individual rooflights of plastics − prEN 1873-2 individual

SV/Grano Oy/Rakennustieto Oy www.rakennustieto.fi © Rakennustietosäätiö RTS 2016

RT 38831 en 7

SMOKE EXHAUST IN APARTMENT BUILDINGS (Finnish Building Code E1: Fire safety of buildings, 11.4 2011 Smoke extraction)

Basement smoke ventilator ORI 23 (hand operated)

Motor equipped ventilator

Motor operated system1. Orivent ventilator2. ORI 70 SI/SL replacement air inlet ventilator3. Power supply RZN 4503 with battery back-up 72 h4. Ventilation button LT 84 (optional)5. Sign ”Smoke vent, manual operation” in entrance door

Smoke exhaust in starircases

Cable wire ventilator

Orivent 01 NSHEV with optional use for roof access, mountend on top of Orivent smoke exhaust shaft

Accessories − external safety hasp (for padlock), doorstay, burglary protection

Means shall be designed and con-structed in a building for adequate smo-ke extraction suitable for the different premises of the building.

Means shall be provided for the extrac-tion of smoke from, and for the flow of replacement air to fire-separated exits and fire-separated lift shaft.

Means shall be provided for smoke extraction from the spaces of the ba-sement storey, so that it will not be necessary to use fireseparated exits or fire-separated extinguishing routes for smoke extraction.

In buildings of classes P2 and P3 with two storeys means for smoke extracti-on from the second floor exit shall be arranged through a window or hatch with an area of at least 0,5 m² and which is simple to open or break. In buildings of not more than 8 storeys means for smoke extraction from the upper part of the exits shall be arranged through a window or hatch with an area of at least 1,0 m². When designing smoke ex-traction from the exits in buildings with more than 8 storeys it must be ensured that smoke and combustion gases will not endanger the evacuation from the premises connected with the exits. The arrangements concerning smoke ex-traction shall be negotiated with the local rescue authorities.

Smoke ventmanual operation

manual operationSmoke vent

Page 8: RT 38831 en Keravent smoke control system Natural smoke and … · 2018-09-19 · − EN 14351-1 wall mounted − EN 1873 individual rooflights of plastics − prEN 1873-2 individual

SV/Grano Oy/Rakennustieto Oy www.rakennustieto.fi © Rakennustietosäätiö RTS 2016

RT 38831 en 8

MANUFACTURING, SALES, INSTALLATION AND MAINTENANCE

Kera Group OyKäkeläntie 41FI-16300 ORIMATTILA, FINLANDTel. +358 3 544 [email protected]

CONTROL SYSTEMS

Control panels 24 VDC, 48 VDC and 230 VACControl panels have a built-in battery back-up unless the building’s power systems (230 VAC) have generators as a secondary power supply. The control system must have a battery back-up for 72 hours in case of incidents such as a power failure.

The standard EN 12101-10 (Power Supply Equipment PSE) is applied to primary and secondary power supplies, and they requi-re a CE marking.

Power supply devices are divided into two categories

− class A devices are suitable for use with all systems

− class B devices are suitable for use with systems that are fail-safe.

The power supply equipment for natural smoke and heat exhaust ventilation sys-tems belongs to category A as it is not fail-safe.

Smoke control systems that are not fail-sa-fe must have at least two power supplies: primary and secondary power supply. The primary power supply must be designed to use the power grid or similar. The seconda-ry power supply, such as battery or gene-rator, must be functional at all times and it must be tested and maintained regularly.

Each power source, on its own, shall be capable of operating those parts of thes-moke and heat control system for which it is intended.

If the primary power source fails, then the PSE shall be automatically switched over to a secondary power source. When the primary power source is restored, the PSE shall be automatically switched back.

The capacity of the power supply depends on the total current load of hatches. Hat-ches are opened in groups as smoke reser-voirs. Each room is a single reservoir. Large rooms are divided by smoke barriers into smaller reservoirs so that the area of one smoke reservoir does not exceed 2,000 m². In larger buildings control panels that operate as power supplies should be de-centralised to ensure a reasonable cable thickness. Smoke vent buttons are usually located at the main entrance and/or near the fire control panel, where the scheme of the smoke exhaust system is also located.

Buttons Dimensions (W x H x D), mm

WSK 320 1-os. 24 VDC 125 x 125 x 36

Model Lines Output voltage, VDC Load capacity, A Dimensions (W x H x D), mm

SVM 24V-5A 1 24 5 286 x 238 x 113

SVM 24V-8A 1 24 8 286 x 238 x 113

SV 24V-24A-ds 2 24 24 343 x 450 x 178

SV 24V-30A-ds 2 24 30 343 x 450 x 178

SV 24V-32A-ds 2 24 32 343 x 450 x 178

SV 48V-8A-ds 2 48 8 343 x 450 x 178

SV 48V-24A-ds 2 48 24 343 x 450 x 178

SV 48V-30A-ds 2 48 30 343 x 450 x 178

SV 48V-32A-ds 2 48 32 343 x 470 x 178

RZN control panels

Buttons Dimensions (W x H x D), mm

RT 45 1 part 24 VDC 129 x 138 x 39

RT 45-2 2 part 24 VDC 129 x 138 x 39

RT 45-3 3 part 24 VDC 129 x 138 x 39

Model Lines Output voltage, VDC Load capacity, A Dimensions (W x H x D), mm

RZN 4503-T 1 24 3 155 x 235 x 85

RZN 4402-K 1 24 2 310 x 310 x 100

RZN 4404-K 1 24 4 310 x 310 x 100

RZN 4404-M 2 24 4 310 x 310 x 100

RZN 4408-K 1 24 8 310 x 310 x 100

RZN 4408-M 2 24 8 310 x 310 x 100

RZN 4416-M 2 24 16 600 x 600 x 210

RZN 4300-E as required 24 8A - 64A from 600 x 600 x 210

RZN 4308E max. 15 230 VAC as required from 600 x 600 x 210

EN 12101-10 CE marked control panels

EN 12101-10 CE marked control panels

Control panels