CERTIF'IED TRUE COPY
SETSCO SERVICES PTE tTD
18 Teban Gardens CrescentSingapore 608925Tel : (65) 65667777Fax: (65) 65667718Website: www.setsco.comBusiness Reg. No.
.196900269D
Your Ref: -
Subject
Tested For
Method of Test
Specification
Description ofSamples
I
TEST REF6HTT.26454ISLDate= 2410112014
Page I of3(This Repod is issued subject to the terms & conditions set out below)
Testing of "EVERLUX MlRROR" submitted by PT Alamkaca Prabawa lndonesiaon 1111212013.
PT ALAMKACA PRABAWA INDONESIAJalan Raya Mauk Km 2Desa Pabuaran TumpengTangerang 15112lndonesiaAttn: Ms Riah / Sutjahyo
CopperAccelerated Salt Spray (120 Hours) : ISO 9227 : 06Condensation in Constant Atmosphere (480 Hours) : EN 1036 : 1999 AnnexA
BS EN 1036 - Glass in building - Mirrors from silver-coated float glass forinternal use
8 pieces of approximately 100mm width x 100mm length x 5 mm thickness clearmirror were received(Refer to Photograph 1)
Results 1) 'EVERLUX MIRROR" has met BS EN 1036 acceptance level for the above 2tests requested.
2) Refer to Page 2 for detailed test results
SamuelTan Yu Yang Shirley Lim SuidiTesting Officer.. _ Engineer (CMTD)
Construction Technology Division
Terms & conditions:
(3) TheReportmaynotbeusedinanypublicitymaterialwithoutthewrittenconsentofSETSCO
(4) The Heport may not be reproduced in part or in full unless approval in writing has been given by SETSCO.
damage suffered by the Client, its agents, servants or representati\/e hows0ever arising or whether connected with the Services provided by SETSC0 hereln