    GSecGas-insulated switch-disconnector

    Product presentation

  • 8/10/2019 SL_GSEC(EN)-_1VCP000480.pdf

    2/15

    SF6-insulated switch-disconnector

    3 positions: LINE OPEN EARTHED(separate slots for opening and earthing)

    Suitable for metal-enclosed secondary

    distribution switchgear

    (incoming/outgoing, with CB and fuses)

    Safety

    Lower part in stainless steel for partition

    metallic (PM) classified panels

    Interlocks to prevent incorrect operations

    Plug&play accessories to cover a wide range

    of applications

    Reduced maintenance

    Compact design

    GSecMain feature

    Month DD, Year | Slide 2

    ABB Group

  • 8/10/2019 SL_GSEC(EN)-_1VCP000480.pdf

    3/15

    GSec

    Standards:

    IEC 60694,

    IEC 62271-102,

    IEC 62271-105,

    IEC 60265-1.

    Operating

    temperature:

    -5C +40C (5)

    Max installation

    altitude:

    3000 m (6)

    Phase distance:

    230mm

    SF6pressure:

    1,48 bar

    (absolute)

    (5) According to IEC 62271

    (6) Ka correction factor

    needed according to

    62271-1

    Main data and ratings

    Month DD, Year | Slide 3

    ABB Group

    Electrical characteristics

    Rated voltage kV 12 17,5 24

    Withstand voltage (50/60 Hz, 1 min)- Phase-phase and phase-earth kV 28 38 50

    - Between open contacts kV 32 45 60

    Impulse withstand voltage (BIL 1.2/50 s)

    - Phase-phase and phase-earth kVp 75 95 125

    - Between open contacts kVp 85 110 145

    Rated frequency Hz 50-60 50-60 50-60

    Rated current A 800 (1) 800 (1) 630

    Rated short-time withstand current kA 25(2s) (2) 20(3s) (2) (3) 16(3s) - 20(3s) (2) (3)

    Rated short-time making capacity kAp 63 52,5 40 - 52,5

    Breaking capacity

    - Active load A 800 (1) 800 (1) 630

    - No-load transformers A 16 16 16

    - No-load lines A 25 25 25

    - No-load cables A 50 50 50

    - Ring circuit A 800 (1) 800 (1) 630

    (1)up to 630A for GSec/T2

    (2)

    up to 16kA(3s) for GSec/T2(3)For 21 kA (3s) please contact ABB

    Electrical and mechanical performance

    Line electrical endurance class E3 - up to 5 makings and 100 breaking of rated current

    Earth electrical endurance class E2 - up to 5 makings

    Line mechanical endurance with 1S - Single spring actuator class M2 - up to 5000 mechanical operations

    Line mechanical endurance with 2S - Double spring actuator class M1 - up to 1000 mechanical operations

    Earth mechanical endurance class M0 - up to 1000 mechanical operations

  • 8/10/2019 SL_GSEC(EN)-_1VCP000480.pdf

    4/15

    GSec/T1 Three positions switch disconnector

    1S Single spring mechanism

    Incoming/outgoing panels

    Typical unitsGSec/T1 and GSec/T2

    Month DD, Year | Slide 4

    ABB Group

    GSec/T2 Three positions switch disconnector

    2S Double spring mechanism (stored energy)

    Incoming/outgoing panels

  • 8/10/2019 SL_GSEC(EN)-_1VCP000480.pdf

    5/15

    GSec/T2F

    Three positions switch disconnector

    2S Double spring mechanism

    Fuse tripping system

    Earthing switch with transmission

    Fuse base

    Fuse blown indicator

    Typical unitsGSec/T2F and GSec/IB

    Month DD, Year | Slide 5

    ABB Group

    GSec/IB

    Three positions switch disconnector

    1S Single spring mechanism

    Earthing switch with transmission

    For panels with removable circuit breakers

  • 8/10/2019 SL_GSEC(EN)-_1VCP000480.pdf

    6/15

    GSecMain components and dimensions

    Month DD, Year | Slide 6

    ABB Group

    In Line

    Open

    Earth

  • 8/10/2019 SL_GSEC(EN)-_1VCP000480.pdf

    7/15

    Lower part in stainless steel:

    PM classified (metallic partition)

    No leakage currents

    Maximum personnel safety

    Panel classified LSC2A Compact design:

    Upper part in epoxy resin

    Capacitive sockets integrated in the apparatus

    lower insulators

    Cable connection directly to the lower bushings

    Granted Sealed for life for 30 years

    according to IEC 60694

    Gas exhaust valve

    ComponentsPower part Enclosure

    Month DD, Year | Slide 7

    ABB Group

  • 8/10/2019 SL_GSEC(EN)-_1VCP000480.pdf

    8/15

    Components

    1SSingle Spring 2SDouble Spring

    Closing/

    Opening

    Operating energy is provided by

    charging a spring (lever or motor),

    which, when released, causes the

    contacts to open or close

    - Springs charging (with lever or motor)

    - Using the stored energy for closing and

    opening operations (with pushbuttons or shunts)

    Speed of the

    operationIndependent Independent

    Manual

    operation Lever Lever and pushbutton

    Automatic

    operationMotor Motor and coils

    Earthing

    switch

    function

    - Operating energy is provided by charging a spring (with a lever),

    which, when released, causes the contacts to open or close

    - Independent speed

    Safety

    - Separate lever insertion point for line and earth operation- Operating lever with anti-reflex function

    - For motor operated actuators, in case of emergency, it is always possible to operate

    manually the actuators

    Note

    - In combination with fuses, opening can be

    triggered by the fuse striker

    - Possibility to discharge springs once loaded

    Actuators

    Month DD, Year | Slide 8

    ABB Group

  • 8/10/2019 SL_GSEC(EN)-_1VCP000480.pdf

    9/15

    ComponentsActuators diagrams

    Month DD, Year | Slide 9

    ABB Group

    Position of line contact (0 = open, 1 = closed)

    Spring status (0% = discharged, 100% = charged)

    Spring charging time

    - manual operation: depend on operator

    - automatic operation with motor = 3-4 s.

    Tc Opening or closing time of the contact < 0,3 s.

    Tclose Total closing time < 5 s.

    Topen Total opening time < 5 s.

    Ts1

    Position of line contact (0 = open, 1 = closed)

    Springs status (0% = discharged, 100% = charged)

    Springs charging time

    - manual operation: depend on operator

    - automatic operation with motor = 3-4 s.

    Tc Opening or closing time of the contact < 0,3 s.

    Tclose Total closing time < 0,3 s.

    Topen Total opening time < 0,3 s.

    Ts2

    1S

    Single Spring 2S

    Double Spring

    timetime

  • 8/10/2019 SL_GSEC(EN)-_1VCP000480.pdf

    10/15

    Components

    1. Line operating slot

    2. Earth operating slot

    3. Line diagram with indicators

    (mounted directly on the

    operating shaft)

    4. Pushbuttons (for 2S actuator)

    5. Voltage indicators6. Spring charged signal

    7. Fuse blown signal

    Front cover

    Month DD, Year | Slide 10

    ABB Group

  • 8/10/2019 SL_GSEC(EN)-_1VCP000480.pdf

    11/15

    ComponentsAccessories 1/4

    ABB Group3th May Slide 11

    Auxiliary contacts

    4 line + 4 earth

    Each can be a make

    contact or a break contact

    250 VAC - 16A

    250 VDC - 0,3A

    Spring charging motor

    For 1S and 2S actuators

    AC (50Hz): 48, 110 and 220 V

    DC: 24, 48, 110 and 220 V

    Voltage indicators

    VPIS type

    Capacitive dividers

    integrated in the apparatus

    bottom isolators

    Possibility to perform phase

    concordance

  • 8/10/2019 SL_GSEC(EN)-_1VCP000480.pdf

    12/15

    ComponentsAccessories 2/4

    ABB Group3th May Slide 12

    Key locks type: standard, Ronis and Profalux

    Possibility to use up to 3 padlocks

    Fuse blown signaling contact

    Make or break contact

    In addition to the mechanical indicator

    For GSec/T2F

    Key locks and padlocking

  • 8/10/2019 SL_GSEC(EN)-_1VCP000480.pdf

    13/15

    ComponentsAccessories 3/4

    ABB Group3th May Slide 13

    Shunt opening release (MBO)

    and shunt closing release (MBC)

    DC: 24, 48, 60, 110-132, 220-250

    AC (50-60Hz): 48, 60, 110-127, 220-250

    For GSec/T2 and /T2F

    Undervoltage release (MBU)

    DC: 24, 48, 60, 110-132, 220-250

    AC (50Hz): 48, 60, 110-132(*), 220-250(*) For GSec/T2 and /T2F

    (*) available also for 60Hz

  • 8/10/2019 SL_GSEC(EN)-_1VCP000480.pdf

    14/15

    ComponentsAccessories 4/4

    ABB Group3th May Slide 14

    Temperature-compensated pressure switch Manometer

    Analogic indication

    Temperature-compensated scale

    Possibility to have also an electrical output of

    the pressure

    Temperature-compensated device

    Possibility to have also an electrical output of

    the pressure