    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    1of27

    1.0 SCOPE

    1.1 The specification covers design, engineering, manufacture, testing & supply deliveryat site/stores of Control & relay and protection panels inclusive of internal wiring and witharrangement for external connection to various Switchyard equipments and Control roombuilding equipments as necessary. The Contractor has to design the Schematics for protectionand Control of all equipments including monitoring indications, visual and audible alarm,interlocking schemes between different equipment. Any other requirement which are notspecifically covered here but which are necessary for successful commissioning of the Sub-station are also within the scope of the Contract.

    1.2 The equipment manufactured should conform to the relevant standards and of highest quality ofengineering design and workmanship. The equipment manufactured shall ensure satisfactoryand reliable performance throughout the service life.The Schedule of requirement of the Panel is furnished separately in details.

    2.0 STANDARDS :

    2.1 Unless otherwise specified all equipment and material shall conform to the latest IS applicablestandards. Equipment complying with other internationally recognised standards will also beconsidered if it ensures performance equivalent or superior to Indian standards. In the event ofsupply of equipment conforming to any international \ internationally recognised standards otherthan the standard listed below, the salient features of comparison shall be brought out and

    furnished along with the bid. One copy of such standard specification in English language shallbe enclosed with the tender.

    2.2 The equipment provided shall also comply with the latest revisions of Indian Electricity act andIndian Electricity rules and any other applicable Statutory provisions, rules and regulations

    2.3 All equipment provided under the specification shall generally conform to the latest issue of thefollowing:

    IS 3231 & IEC-255 Electrical relays for power system protection

    IS 1248 & IS 2419 Indicating Instrument

    IEC 337 &337-1 Control Switches (LV Switching devices forcontrol and auxiliary circuit)

    IS 2705 Current Transformers

    IS 3156 Voltage Transformer

    IS 375 Marking and arrangement for Switchgear Busbars, main connection and auxiliary wiring.

    IS 8686 Specification for static protective relays

    3.0 SYSTEM DETAILS :

    a) Nominal System Voltage 33KV

    b) Highest System Voltage 36KV

    c) Number of Phases

    d) Frequency

    e) Grounding Grounded through Earthing Transformer

    4.0 CT & PT RATIO AND TRANSFORMER DETAILS

    CIRCUIT 33KV CT RATIO

    Feeder 400-200/1 A, 2 core

    33kv side of 33/11kv transformer 400-200/1-1-1A, for 10 MVA and 200-100/1-1A for6.3 MVA Tr.

    11KV side CT for 6.3MVA & 10MVATransformer

    600-400/1-1-1A at phase side (Indoor Panel)

  • 7/29/2019 spec for 33kv system

    2/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    2of27

    11KV transformer Bushing CT for REFProtection

    600/1A for 10 MVA 33/11KV transformer for bothPhase & neutral.400/1A for 6.3 MVA 33/11KV transformer for onlyneutral.

    PT RATIO Voltage-class 33KV

    Electro-magnetic PT Ratio 33KV/3, 2 core110V/3

    TRANSFORMER DETAILS 33/11KV,6.3/10 MVA, Dy11

    5.0 AUXILIARY SUPPLY :

    D.C.Supply voltage shall be normally fed from Battery charger and battery connected inparallel which is 30V +/- 10%. In case of failure of the AC supply to battery charger, DCSupply voltage will be available automatically from lead acid Battery. The D.C Supplyvoltage may vary from -10% to + 10%. The D.C. system shall be 2 wire with necessaryearth fault annunciation scheme.

    AC Auxiliary supply voltage for the C&R panel shall be 230V, 1-phase, 50Hz grounded with+/- 10% voltage variation.

    6.0 STANDARD DRAWINGS:

    Tender purpose drawing for 33 KV C.B Schematic and different C&R panels with bus wiredetails for 33 KV system as per Annex-II of specification shall be followed for reference. Whiledesigning the control and protection schematic for various control & relay panels by theContractor, the above standard drawings, are to be followed by the contractor after checking itssuitability for satisfactory operation.

    7.0 CONTROL AND RELAY BOARD

    The Control and Relay Board shall be of Simplex and the access door shall be provided at the backof each Panel where no instruments or relays shall be mounted. The indicating and signalingdevices etc. shall be mounted on the front side and the auxiliaries which shall be inside the Panel.

    In front of Panel where relays and instruments are to be mounted shall be stretcher leveled steelplate 3 mm. Thick and side panel, doors and top covers shall be of 2mm. Thick steel plate. Lightsections of structural steel shall be used for switch-board frame.

    The individual panel shall be 2250 mm. In height with Channel base, 610 mm. In depth and ofsuitable width limited to 1000mm to accommodate the equipment at a suitable height, suitablegaps to facilitate easy workability as specified hereafter. Individual piece of Channel base of C&RPanel is to be provided to obtain the flexibility of inter-changing the Panel in the Board formation,if any. The access door shall at the back side and be of double door type of height 1900 mm.

    The complete panel shall incorporate all necessary instruments, meters, relays, auxiliary relays,control switches, indicating lamps, mimic, annunciators, audible alarms, horizontal and verticalwiring trough, wiring supports, interior lighting system, terminal blocks fuses and links etc.

    7.1 Constructional features

    a) The Control and Relay board frame shall be suitable for erection of flush concrete floor andsecured to it by means of evenly spaced grout bolt projecting through the base channels frommembers of the frame.

    b)The tenderer shall ensure that the equipment specified and such unspecified complementaryequipment required for completeness of protection/control scheme be properlyaccommodated in the panels without congestion and if necessary to provide panels withlarger width. No price increase at a later date on this account shall be allowed.

    c) Panels shall be completely metal enclosed and shall be dust, moisture and vermin prooffor tropical use. The enclosure shall provide a degree of protection not less that IP-31 inaccordance with IS-2147.

    d) Panels shall be free standing, floor mounting type and shall comprise structural

  • 7/29/2019 spec for 33kv system

    3/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    3of27

    frames enclosed completely with specially selected smooth finished, cold rolled sheet steel ofthickness not less than 3 mm for weight bearing members of panels such as base frame, frontsheets and door frames and not less than 2mm for sides, door, top & bottom portions. Thereshall be sufficient reinforcement to provide level surfaces, resistance to vibration and rigidity

    during transportation and installation.

    e) Design, material selection and workmanship shall be such as to result in neat appearance,inside and outside with no welds, rivets or bolt head apparent front outside, with all exteriorsurfaces tune and smooth.

    f) All holes and extension windows in the Panel shall be blanked and access doors shall be linedwith compressible liners at the edges. The purchaser will shut off the bottoms crevices withcream cement, the Cable Entry holes with weak concrete and the cable trench with present R.C.Slabs or checker plate. All control and supply cables will be laid in a distribution trench runningunder the panel board. The Cable will branch off into each cubicle through entry holes in theconcrete floor opening in the bottom cubicles. Necessary Drawings for concrete floor and trenchonly shall be supplied by the contractor to enable the purchaser to construct the foundation floorfor these boards. The drawings shall show details of the distributing trench, cable entry holes,glands and positions of grouting bolts. The purchaser will prepare foundation with pocket forgrouting bolts. The Contractor shall supply channel base, suitable grouting bolts, nuts lock andwashers.

    g) Cable entries to the panel shall be from the bottom. The bottom plates of the panel shall befitted with removable gland plates and fixed with cable glands.

    7.2 NAME OF IDENTITY PLATES :

    a) All instruments, relays and such other similar electrical devices mounted on thecontrol and relay panel shall be provided with name plates bearing the manufacturer's name,serial identifying number and the Electrical rating data.

    b) 25 mm wide plastic plates bearing suitable identification marks shall be fixed underthe terminal wiring at the test blocks, at the fuse blocks and at the cable terminals. Similarplates shall be fixed on the exterior of the switch board in appropriate places to indicate functionof control switches, push button etc. such as isolator control switch, breaker control switch,

    DC fail test, accept reset etc. Suitable identification marks shall be provided for individual casingpart of the relays and other equipment.

    c) 50mm wide plastic plate bearing suitable circuit description (which will be furnishedafter order is placed) etched in 30 mm size letters shall be provided for each panel and mountedon the top of both outer and inner sides of the front and rear panels. These plates shall beremovable type.

    d) Each unit of control and relay panel shall be provided with a label located at thebottom on the front and shall contain the following details :

    i) Manufacturer's nameii) P.O.no. and dateiii)Drg. ref. no. that pertains to the panel.

    8.0 Mounting

    a) All equipment on and in side the panels shall be mounted and completely wired to the

    terminal blocks ready for external connection. The equipment of panel shall be mounted flush.

    b) Equipment shall be mounted such that removal and replacement can be accomplishedindividually without interrupting of service to adjacent devices and are readily accessiblewithout use of special tools.Terminal marking shall be clearly visible and of permanent nature.

    c)The contractor shall carry out cutout, mounting and wiring of the bought out items which are tobe mounted in the panel in accordance with the corresponding equipment manufacturer'sdrawings.

    d) The centre line of switches, push buttons and indicating lamps shall be not less than 750

  • 7/29/2019 spec for 33kv system

    4/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    4of27

    mm from the bottom of the panel. The centre line of relays and meters and recorders shall benot less than 450 mm from the bottom of the panel.

    e) The centre lines of switches, push buttons and indicating lamps shall be matched to give a

    neat and uniform appearance. Likewise the top of all meters, relays and recorders etc. shall be inone line.

    f) The control switches for circuit breakers and isolators shall be located on the mimic diagramcorresponding to their exact position of the controlled equipment in the single line drawing. Thelocation of the switches shall be within working height from the floor level for easy andcomfortable operation.

    g) No equipment shall be mounted on the doors.

    h) All the panels in the control room shall be matched with the other panels of the same C&Rboard in respect of dimension, colour and appearance. Control equipment on front side ofthe panel shall be similarly placed.

    i) All the equipment connections and cabling shall be designed and arranged to minimise therisk of fire and damage.

    9 PAINTING

    9.1 Panel painting shall be done by the modern process of painting. All unfurnished surface of thesteel panel and frame work shall be sand blasted or suitable cured to remove rust, scale, foreignadhering matter or grease. A suitable rust resisting primer shall be applied on the interior andexterior surface of steel, which shall be followed by application of an undercoat suitable to serveas base and binder forth finishing coat.

    The panel shall be finished to enamel deep Grey for exterior and enamel light Grey for the interior.The Panel shall be given a plastic durable covering coat for protection of the finish during thetransshipment, which shall be capable being pealed off after installation. Additionally, a smallquantity of finished paint shall be supplied with each Consignment of the Panel to enable thepurchasers Store at Site for any finish which may get damaged during the transshipment.

    10 SMALL WIRING:

    10.1 All wiring shall be switch-board type, single core stranded tinned enameled Copper Wires, suitablefor 660 Volts service, polyvinyl chloride insulation which has provided its utility in tropical regionagainst hot and moist climate and vermin (Misc. white ant and cockroaches etc.) Rubber insulatedwiring will not be accepted.

    10.2 The sizes of wiring in different circuit shall not be less than these specified below:

    TABLE-I

    Circuit Minimum permissible size of wire

    Metering and Relaying Circuits connectedCurrent Transformer

    2.5 mm

    Potential Circuits for metering and Relaying,Control, Visual Audible Alarms and Signaling

    Circuit.

    2.5 mm

    10.3 The following colour schemes shall be used for the Wiring:

    TABLE II

    Circuit where used Colour of Wire & Ferruule

    Red Phase of Instrument Transformer Circuits Red

    Yellow Phase of Instrument Transformer Circuits Yellow

    Blue Phase of Instrument Transformer Circuits Blue

  • 7/29/2019 spec for 33kv system

    5/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    5of27

    Neutral connection, earthed or not earthed in theinstrument

    Black

    Transformer Circuit

    A.C. Control Wiring Circuits using auxiliary supply andcubical lighting

    Black

    D.C. Control Wiring Circuit using Battery Supply GreyEarth Connection Green

    10.4 a) All internal wiring shall be securely supported, neatly arranged, readily accessible andconnected to equipment terminals and terminal blocks. Wiring gutters & trough shall be used forthis purpose.

    b) Longitudinal troughs extending throughout the full length of the panel shall be used forinter panel wiring. Inter connections to adjacent panels shall be brought out to a separate setof terminal blocks located near the slot or holes meant for taking the interconnectingwires. All bus wiring for inter panel connection shall preferably be provided near the top of thepanels running through out the entire length of the panels.

    c) Wiring connected to the space heaters in the cubicles shall have porcelain beaded insulationover a safe length from the heater terminals.

    d) Wire termination shall be made with solder less crimping type and tinned copper lugs whichfirmly grip the conductor and insulation. Insulated sleeves shall be provided at all the wire

    terminations. Engraved core identification plastic ferrules marked to correspond with panelwiring diagram shall be fitted at both ends of each wire. Ferrules shall fit tightly on the wire andshall not fall off when the wire is disconnected for any purpose. Termination shall be such that nostrand of a conductor shall left loose or overhanging. Conductor termination shall be secured tothe holding nuts/screws, terminal blocks etc. with washers interposed between theterminals/holding nuts/screw heads. The terminals shall be so connected that no conductorferrule code gets masked due to overlay of conductors.

    e) All spare contacts of relays shall be wired up to terminal blocks.10.5 Each wire shall be continuous from end to end and shall not have any joint within itself Individual

    Wires shall be connected only at the connection terminals or studs of the terminal blocks, meters

    relays instruments and other switch board devices.

    10.6 Terminals Ends of all wires shall be provided with numbered Ferrules suitably coloured (Ref.Table-II above) for phase identification. At point of inter-connection where a change of number is

    necessary, duplicate Ferrules shall be provided with the appropriate numbers on the changingend.

    10.7 At the terminal connection, washers shall be interposed between terminals, wire terminals andthe holding nuts. All holding nuts shall be secured by locking nuts. The connection stud shallproject at least 6 mm from the lock nut surface. Wire ends shall be so connected at the terminals

    studs that no wire terminal number ferruled gets masked due to succeeding connections. Allwires shall be suitable for bending to meet the terminal stud at right angles with the stud axis,and they shall not be skewed.

    10.8 All studs, nuts, bolts screws etc. shall be threaded according to the British Standard practiceunless purchasers prior approval to any other practice of threading is obtained. Spare quantitiesof nuts, lock and washers of all varieties used on the panel board shall be supplied to the extent of

    10% of the used quantities.

    11.0 TERMINAL BLOCK CONNECTION:

    11.1 Terminal Block Connections built from coils of moulded die-electric and brass stud inserts shall be

    provided for terminating the outgoing ends of the cubicle wiring and the corresponding incomingtail ends of the control cables. Provision shall be made on each pillar, for holding 10% extraconnection (5% incoming + 5% outgoing). All blocks shall be shrouded by easily removablesarouds moulded of transparent die-electric materials.

  • 7/29/2019 spec for 33kv system

    6/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    6of27

    The terminal blocks shall be suitable for 660 V service and connection with both Aluminium andCopper Wires.

    12.0 SPACE FOR CONTROL CABLES AND CABLE GLANDS:

    Sufficient space for receiving the Control Cables inside the Board at the bottom of the cubicles andmounting arrangement for the terminal cable glands shall be provided. Removable type separatecable entry plate ( may be two) shall be fixed with bottom plate. The specification does not coversupply of control cables and cable glands for which the Purchaser will make separatearrangement.

    13.0 SPACE HEATERS:

    60W, 230 V, 50 HZ Tubular Space Heaters suitable for connection to the Single Phase A.C. Supplycomplete with On-Off Switches located at convenient position shall be provided at the bottom ofthe Switch Board to prevent condemnation of moisture. The Watt loss per Unit surface of heatershall be low enough to keep surface temperature well below sensible heat. The wattage of heatershall be such as to keep 10 deg C above average ambient temp in rainy season but the temp. shallnot under any circumstances damage the insulation of the wiring of the panel.

    14.0 DISTRIBUTION AND CONTROL OF AUX. POWER CIRCUIT:

    14.1 D.C. CIRCUIT

    There shall be only one 30V D.C. for the entire Control and Relay Board fed from a D.C.Distribution Board. A continuous D.C. Bus shall be provided in the Control and Relay Board andD.C. supply for control, protection, indication and supervision of circuit breaker and otherequipment shall be teed off from D.C. bus through a set of 16 Amp. H.R.C. Fuse on positive andnegative side. D.C. supply to be teed off shall be distributed within the Panel as below:

    (a) C.B. remote and protection tripping circuit- 1, C.B. local operation and protective relaycircuit without any fuse.

    (b) C.B. remote closing circuit through a 10A HRC Fuse on the positive side only.(c) C.B. remote and protection tripping circuit, TC-2, through 10A fuse both at +ve andve

    side with trip circuit supervision relay.

    (d) Indication Circuit through a set of 6 Amp. HRC Fuse and link.In addition to the above, one circuit common to the board shall be teed off for an AlarmAnnunciation Circuit from the above incomer D.C. Bus through a set of 6 Amps. HRC Fuse and link.

    1) C.B. remote and protection tripping circuit, TC-1, through 16A fuse both at +ve andve side with trip circuit supervision relay.

    2) C.B. remote and protection tripping circuit, TC-2, through 16A fuse both at +ve andve side with trip circuit supervision relay.

    3) C.B. local operation remote closing circuit through a 10 Amp HRC fuse on + ve and ve side.

    4) Protective relay circuits through 6A fuse both at +ve and ve side with DCsupervision relay.

    Alarm Bus shall be run throughout the Control and Relay Board & Alarm Circuit shall be teed off ateach Panel through a set of links.

    A D.C. operated no-volt auxiliary relay provided with hand reset type reverse flag with inscription

    Panel D.C. Fail and two sets of self-reset N/C contact shall be provided at each C&R Panel tosupervise the 18 Amp. HRC Fuse, through which D.C. Supply for control, protection and

    supervision of C.B. and other equipment has been teed off in each panel. One N/C contact shall beused for visual alarm and the other N/C contact shall be used for audible alarm. One Push buttonhaving N/C Contact used in Series with the above relay for D.C. Fall Test purpose. Both contactsshall be connected to D.C. Fail Non-Trip Alarm scheme.

    14.2 A.C. CIRCUITS :230 Volts, Single Phase A.C. Aux. Supply to the Control and Relay Board will be fed from A.C.Distribution Board through a suitable Fuse Switch Unit provided there. A continuous A.C. Busshall be provided to the Control and Relay Board where from A.C. Supply to each Panel shall be

  • 7/29/2019 spec for 33kv system

    7/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    7of27

    teed off through a set of links. One 16 Amps. Rated HRC Fuse shall be provided at the Control &Relay Board for the Incoming A.C. Supply. An A.C. operated no volt auxiliary relay rated for 230Vare provided with hand reset reverse flag with inscription A.C. Fail and two sets of self reset N/CContacts shall be provided in the Panel having common equipment (One N/C contact shall be used

    in Annunciation Circuit and other N/C contact shall be kept as spare. One push button having N/CContact used in Series with above relay for A.C. Fail Test purpose .

    14.3 P.T. SECONDARY CIRCUIT;There may be two nos 33KV bus PT, one in each bus section.P.T. supply shall be available from either of the two 33 KV Bus P.T.Two sets of Fuse and link of suitable rating shall be provided for the Incoming P.T supplies andtwo sets of 3 nos. LED indicating lamps having coloured top covers for Red, Yellow and Bluephases, shall be provided for supervision of the Fuse. Lamps shall be connected betweenrespective phases and neutral. The arrangement of distribution of P.T. Secondary Circuit shall beas follows:(a) Potential supply to the protective relay circuit for Feeder where necessary shall be fed fromrespective Bus P.T. supply bus.(b) Potential supply to meters, Energy meters and indicating instrument of each panel shall befed from respective Bus P.T. supply bus.c) Selected V.T. secondary supply to the protective relays of each panel shall be fed through 3pole - MCB and link in neutral in each panel where necessary with annunciation contact .d) Selected V.T. secondary supply to metering and indicating instruments of each

    panel shall be fed through fuse in each phase and link in neutral in each panel of 33KV systemvoltage.e) Two position (PT-1/PT-2), minimum 4(four) way PT selector switch (stay put type), minimum16A rating shall be provided in each panel for metering ckt. Additional 4 way in PT selector switchis required for protection wherever applicable. The no. of way may increase during detailedengineering.

    14.4 FUSE AND LINKFuses shall be of cartridge type. Carrier and base for the fuss and links for all D.C. and A.C.Circuits shall have imprint of rating, voltage and circuit designation.

    15 MIMIC DIAGRAMS;Provision shall be made for 10 mm. wide painted and overall drawing mimic diagram by thepurchaser on the exterior of the front panel board to represent the single line arrangement of thestation equipment. Provision shall be made in such a way that centre line of the mimic bus shall

    be at a suitable height from the bottom of the C&R Panel.c) Colour scheme for mimic diagram.

    KV Class C o l o u r Shade Index as per ISS-------- ----------- ----------------------66 KV Golden Brown 41433 KV Brilliant green 22111 KV Air Craft blue 108400/230 V Black 309Earth White -110 V Canary yellow -

    d) In 33 KV simplex type C&R panels, Symbol marking for the position indication ofisolators, earth switches etc, ON/OFF indication for Circiut breaker, PT supplyindication, CB spring charge, auto trip, trip ckt healthy etc. shall be mounted along

    the mimic diagram at appropriate location.e) Property label WBSEDCL shall be fixed at the front top corner of 33KV C&R panel.

    16 CONTROL SWITCH:

    PISTOL GRIP TYPE;Control Switches for Circuit Breakers shall be of three position spring return type with pistol griphandle and sequence device to ensure that manual pumping of closing solenoid not possible. Theswitches shall be robust construction and shall have four effective contact positions. At afterClose position the switches shall have a maintained contact for using with Circuit Breaker Auto -Trip Indication Lamp Circuit.

  • 7/29/2019 spec for 33kv system

    8/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    8of27

    INDICATING LAMPS:L.E.D. Type Indicating Lamps shall be provided on the Control Panel to indicate the following:

    17 Functions Quantity Colour of Lens

    1 C.B. Spring charged indication 1 No. Blue

    2 C.B. Spring Circuit healthy indication 1 No. White

    3 C.B. Auto tripped indication (where necessary) 1 No. Amber

    4 Panel D.C. Fall indication (for Common EquipmentPanel) 1 No. Amber

    5 P.T. Supply indicating Lamp (where necessary) 2 sets Red/Yellow/Blue

    6 C.B. ON indication 1 No. Red7 C.B. OFFindication 1 No. Green

    No indicating lamps under (1) & (2) shall be provided with push button control. All the lampsshall be connected to the auxiliary D.C. supply of the Sub-Station except Sl. No. (4) & Sl. No. (5)which should be connected to the auxiliary A.C. supply and P.T. Secondary supply resp0ectively.The Lamp shall be suitable for Switch Board purpose and shall be Low Watt consumption. TheLamps shall be of cluster LED type of normal colour, this shall be provided with screwed colouredglass covers made translucent to diffuse light. The Lamps should be provided with suitableseries resistance. In the initial supply 20% of the lamps actually used on the Switch Board and10% of the lamps covers used shall be supplied in excess to serve as spares.

    18 TEST BLOCKS:1. Terminal Blocks for D.C. Circuit and C.T., P.T. & A.C. Circuit should be located on the left

    hand side and right hand side of the wall of the Panel seen from back side respectively.

    2. Switch Board Type, back connected test terminal blocks with contacts shall be providedwith Link type shorting terminals of C.T. leads before interrupting the normal circuit forinjection from an external source, or for inserting testing instruments in the circuitwithout causing open circuit of the C.T. The potential testing studs shall preferably behoused in narrow recesses of the block moulding insulation to prevent accidental shortcircuit across the studs. All Test Terminal Block for meters, relays etc. shall be placed asclose to the respective equipment as possible.

    3. 3-Phase, 4-Wire Link type Test Terminal Block having sealing provision shall be providedin Metering Circuit of each Panel.

    19 NAME OF IDENTITY PLATES:

    1. All instruments, relays and such other similar electrical devices mounted on the ControlPanels shall be provided with Name Plates bearing the Manufacturers Name, SerialNumber and the Electrical Rating Data.

    2. 10mm. wide plastic plates bearing suitable identification marks shall be fixed under theterminal wiring at the test blocks, at the Fuse Blocks and at the Cable Terminals.Similar Plate shall be fixed on the exterior of the Switch Board in appropriate places toindicate functions of Control Switches, push buttons and equipment numbers etc.Suitable identification marks shall be provided for relays and other instruments. Platesshould screwed and riveted to the Panel Board.

    3. 50 mm. wide brass or plastic plates shall be provided in order to enable the purchaserto engrave suitable circuit description in 30 mm. size letters for each circuit andmounted in a sheet on the top of each Panel. These plates shall be removable type.

    4. SCHEMATIC DIAGRAM OF CT,PT,CB CIRCUITRY & AC,DC CKT, IND and ANNUN CKTALONG WITH PROTECTION CIRCUITRY GIVING THE TERMINAL NOS AND BUSWIREDETAILS SHALL BE PRINTED IN DURABLE STICKERS AND PASTED INSIDE THE PANELDOOR PAGE WISE OF THE RESPECTIVE PANEL.

    20 SAFETY EARTHING:1. Earthing of metallic parts or metallic bodies of the equipment on the Switch Board shall

    be done with soft drawn single conductor bare Copper Tail connections shall haveminimum area of 16 sq, mm. and the main earthing connection 60 sq.mm. These wiresshall be connected by suitable terminals and clamps junction. Soldered connectionsshall not be employed.

  • 7/29/2019 spec for 33kv system

    9/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    9of27

    2. The neutral point of star connected LV winding of instrument transformers and onecorner of the open delta connected LV side of instrument transformers shall be similarlyearthed by tail connected with main earth wire of Switch Board Earthing System.Multiple earthing of any instrument transformer circuit shall be avoided.

    21 PANEL BOARD LIGHTING:01 The Panel Board interior shall be illuminated by CFL lamps connected to 230 Volt Single

    Phase A.C. The illumination of the interior shall be free from shadows and shall beplanned to avoid any strain or fatigue to the wireman likely to be caused due to sub-normal or non-uniform illumination. One emergency D.C. light shall be provided foreach panel with individual switch with proper identification mark.

    02 A toggle switch or door operated switch shall be provided for control of A.C. lighting ineach panel.

    03 One combined 15 Amps. 3-Pin and 5 Amps. 2-Pin Power Socket outlet together with PlusPins shall be provided at convenient points in each Panel Board for A.C. Supply.

    22 ANNUNCIATOR:ELECTRONIC ANNUNCIATOR

    01 Suitable Multi-way (Minm. eight way for feeder and twelve way for Tr. Panel, this mayincrease according to scheme requirement during detailed engineering.) Microprocessorbased electronic annunciator shall be provided in each panel to indicate over currentand earth fault protection operated. In addition to above, each electronic annunciatorof Transformer Control Panel shall have provision to indicate Transformer troubletrip/alarm function operated. Also one window of the Annunciator shall have to be usedfor Non-Trip A.C. Fail Alarm Indication and one window for Trip Circuit unhealthyindication. Each Electronic Annunciator shall have provision for connection withaccept/reset/lamp test/mute Push buttons for proper functions. Electronic annunciatorshall have provision for connection with Electronic Buzzer/Electronic Bell for Trip &Non-Trip Audio Alarm of common annunciation scheme. Electronic Annunciation shallhave provision for flushing illuminating display with inscription for operation ofrespective Protection Relay. The Micro-Processor based Electronic Annunciator shouldhave separate coloured windows for Trip & Non-Trip Annunciation for easy detection.Electronic Annunciator shall have first Fault Indication Facilities & System Watch Dog.

    The MAKE of Annunciators shall preferably be ofALAN,INSTALARMandMINILEC make.

    02 ALARM SCHEMESTRIP & NON-TRIP ALARM SCHEMES:Each Control & Relay Board assembly shall be provided with one Multi way Micro-

    processor based Electronic Annunciator for Trip Alarm & Non-Trip Alarm. The AlarmScheme shall comprise of separate D.C. operated common buzzer/alarm bell mountedinside the panel for Trip Alarm & another for Non-Trip Alarm.

    The wiring shall be such that single set of buzzer/bell will be sufficient and cover incommon with all the alarm actuating device. Alarm Scheme shall have facility for bell

    and shall be suitable for self reset as well as hand reset type initiating contact. Thealarm Scheme operative as above shall be considered to be within the scope of theTender.

    03 PANEL D.C. FAIL ALARM SCHEMEControl & Relay Panel Board shall have a common Panel D.C. Fail Alarm Scheme

    operated by 230 V Single phase A.C. Aux. Supply for audible as well as visual alarm incase of failure of D.C. incoming supply to the Board.. The Scheme shall comprise of 2nos. single element Aux. Relays. One number having a reverse flag with inscription

    Panel D.C. Fail with 2 nos. self-reset type N/C contacts.

    Another Single Element Relay without Flag and 1 no. self-reset type N/O & 1 no. N/Ccontact having inscription Panel D.C. fail alarm accept Relay. Besides above 1 no.Indicating Lamp 1 no. A.C. Operated Electric Hooter and 2 nos. Push Button, one having1 no. N/C contact other having 1 no. N/O contact shall also be provided for successfuloperation of the scheme. All auxiliary relays required to render Annunciation Systemoperative and shall be considered to be within the scope of the tender.

  • 7/29/2019 spec for 33kv system

    10/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    10of27

    AC fail DC fail scheme shall be operated by relay not contactor.

    23 INDICATING INSTRUMENT AND METERS:01 All instruments shall be Switch Board Type, back connected suitable for semi-flush

    mounting and provided with dust tight cases for tropical use with dull black enamelfinish. All fixing screws, nuts and threaded parts shall be designed to IndianStandards. The dials shall be made of such materials as to ensure freedom fromwarping, fading, discoloring etc. during full life of instruments. Marking of Scale shallbe black on white background. Spring controlled instruments shall be provided withfront-of board. Zero adjuster capable of being safely handled while the instrument isin service. The adjustments above mark and below the zero point shall not be less than3% of the full scale length and need not exceed 6%. It shall have sufficient friction tokeep the adjustment in position.

    All instruments shall have a practicable laboratory means of adjustment of accuracy.The limits of error shall be of class 1.0 type. The calibration of the instruments shallfunction satisfactorily when mounted on steel panels or alternatively magneticallyshielded instruments shall be used.

    Instruments shall be capable of indicating freely when operated continuous at anytemperature from 0 to 50 degree C.

    All circuits of instruments shall be capable of withstanding applied load of 20% greaterthan the rated capacity for a period of eight hours.

    The instruments shall be capable of withstanding the effect of shock vibration and a di-electric test of 2000 Volts r.m.s. to ground for one minute as per relevant ISS.

    02 Ammeters:All ammeters shall be provided with direct reading scale. Full Scale Value of theAmmeters shall be 100% of the nominal current of maximum C.T. ratio.The ammetersshall be connected to measuring C.T. Core. Ammeters shall be of 96 mm sq. m& 90degree scale suitable for R.Y.B. Phase measurements. Ammeter shall be provided one

    in each phase.

    03

    VoltmetersAll Volt Meters shall be provided with direct reading scale. The maximum value of thevolt-scale be 15% in excess of the normal Circuit Voltage. The rated voltage of theVolt Meter shall be 110V A.C. superceded Zero Scale with suppression of 20% of thefull scale value may be provided. Volt Meter shall be of 96 mm. sq. and 90 degreescale.

    The MAKE of Indicating instruments shall preferably be of AE/Rishav make.04 Energy Meters

    Tariff Metering Equipments:(a) Three/Two element Tri-vector Meters with MDI projected mounting type shall be

    provided in the Panels as specified in the schedule of requirement and schedule ofequipment of Panels under this Specification. Meters shall be supplied by thepurchaser. But Panel Wiring for the Meters along with Test Terminal Block andspace or the Tri-vector Meters are to be provided for the Panels.

    24. RELAYS:GENERAL REQUIREMENT :

    The main protective relays eg. Scada Compatible Numerical Directional/NonDirectional O/C & E/F Relays shall be of panel manufacturers own make. However,multinational company manufacturing panel in India may import required/desiredrelays from their foreign counterpart with same brand name at their own risk, cost andresponsibility without hampering the stipulated delivery schedule as stated in thetender notification.Credential for offered relays shall also to be furnished along with C&R panel in tenderdocuments as pre-requisites of tender.

  • 7/29/2019 spec for 33kv system

    11/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    11of27

    All numerical relays shall be provided with Relay Failure Annunciation contact.

    Live demonstration of any offered relay has to be arranged by the Party at the laboratory ofDistribution Testing Department of WBSEDCL, if felt necessary by WBSEDCL before finalisation

    of bid.

    24.1 SCADA COMPATIBLE NUMERICAL DIRECTIONAL/NON DIRECTIONAL O/C & E/F RELAYS

    The primary requirements of the relays are to protect the respective single circuit or double

    circuit feeders and 33/11KV Power TRs in the event of fault. The Directional/Non Directional E/Frelays shall provide suitable sensitivity for limited earth fault current.

    The relay should be suitable for substation automation, primary circuit breaker operationthrough SCADA from remote control room.

    THE DETAILED SPECIFICATION OF RELAY IS AS PER ANNEXURU-I OF SPECIFICATION.

    24.2 OTHER PROTECTIVE RELAYS:

    Differential relay shall be of static or numerical (with proprietary protocol) type

    REF relay etc may be of electro-magnetic/ static type

    24.3 OTHER PARTICULARS RELATED TO ALL RELAYS

    1) All shall conform to the requirement of IS:3231 / IEC 255 and shall be suitable for operationwithin a temperature range 0C to 55C and 95% relative humidity. Relays shall be suitable forflush / semi flush mounting on the panel with connections from the rear, protected with dusttight cases for tropical use and with transparent cover removable from the front.

    2) All protective relays shall be in draw out case or plug-in/modular cases with proper built intesting facilities. If testing devices are not incorporated in the relay itself separate test block andswitches shall be provided. The adjusting devices shall be accessible with the relay mounted onthe panel board. Flag type operating indicators and flag indicator reset devices shall be providedwhich shall be suitable for operation from the front of the relay case without opening the cover.

    3) All A.C.relays shall be suitable for operation at 50Hz.The current coils shall be rated for a

    continuous current of 1 amp and the voltage coil for 110V normal. The contacts of the relaysshall be properly designed to prevent or minimise damage due to arcs which have to bebroken successfully against 30V +/- 10% volt DC. When open the contacts shall withstand avoltage of 115% of the normal circuit voltage. The relays shall be designed for satisfactoryoperation between 70% t0 110% of rated D.C.voltage of the sub-station. The voltageoperated relays shall have adequate thermal capacity for continuous operation.

    4) Timers shall be of static type. Pneumatic timers are not acceptable.

    5) Relays shall be suitable for semi-flush mounting, back connected on the Panel Board. Allnumerical relays shall be provided with Relay Failure Annunciation contact. The Relays shallpreferably be provided with suitable Seal-in-Devices.Relays should be immuned to all types of external influences like Electro static, Electro

    magnetic, Radio interference, shock etc.

    5) All the numerical relay should have provision for setting all the features available inthe relay and viewing those setting as well as different other parameters throughboth built in display unit as well as through PC. All numerical relays shall have selfmonitoring feature with watch dog contact. The supply of relay should be inclusiveof necessary software and hardware for interfacing with a PC, to be supplied by thebidder.

  • 7/29/2019 spec for 33kv system

    12/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    12of27

    25 PROTECTION SCHEMES01 PROTECTION SCHEMES FOR 33 KV LINES

    (A-1) NON-DIRECTIONAL PROTECTION;

    NON-DIRECTIONAL OVER CURRENT PROTECTION : (As detailed in clause no. 24.1)

    This relay shall be used for 33/11 KV transformer & 33KV feeder,. The relay shall-a) be three element type.b) have non directional IDMT characteristics with time current characteristics of 3 secs at

    10 times current setting.c) have variable current setting of 50% to 200% of rated current and adjustable time dial

    setting.d) have high set unit with current setting 500%-2000% for 33/11KV transformer

    protection and 33 KV feeder protection, with very low transient overreach.

    e) Definite Time Sensitive Earth Fault Protection shall have a variable current setting rangeminm 1% to 40% in very small steps of CT secondary current and wide range of definitetime setting range minm. 0.1 to 10 Sec. This relay shall be used in 33 KV feeder fordetection of line to ground fault current of both very low and high magnitude where the33 KV system is grounded through Earthing Transformer limiting the earth faultcurrent.

    f) LED indication for numerical relays of different type of faults including phase identification.

    B-1 PROTECTION SCHEMES FOR 33 KV PARELLEL LINES AT RECEIVING ENDSDIRECTIONAL PROTECTION

    Directional O/C & Directional Instantaneous E/F Relays shall be required for 33 KV parallelLines as specified in the schedule of requirement. The relay shall be as per clause 24.1 of thisspec. Each Feeder shall be provided with 3 elements IDMT Voltage polarized O/C Relays andsingle element voltage polarized E/F Relay. The O/C Relays shall be IDMT type with high setelement. The E/F Relay shall have directional sensitive E/F setting having wide range of setting(1-40%) & wide range of definite time setting range minm. 0.1 to 10 Sec. The relay shall alsohave instantaneous unit.The relay shall have necessary P.T. fuse failure monitoring scheme. Ratio and phase angle

    correction may be inbuilt feature of numerical relays.

    Characteristics:-

    O/C Element:IDMT with High SetUnit

    Current Settings& Operatingtime

    IDMT-50-200%, 0-3 sec,Inst.- 500-2000%or 400-1600%

    MTA 30 Degree to 45 Degree Lead

    Polarized P.T. Voltage 110 V A.C.

    E/F Element

    Current Setting 1-40%(minm.) in very small steps

    Operating Time of Relay Instantaneous

    Operating Time of Timer 0.1 to 10 Sec in very small steps

    MTA 10 Degree to 14 Degree Lag

    Open Delta P.T. Voltage 63.5 V A.C.

    In order to obtain required Polarized Voltage for Directional Earth Fault Relay, 3 Nos. Single Phase

    Interposing P.Ts shall be provided either in the Relay Block or in Control & Relay Panel having followingTechnical Parameters:

    1 Insulation Level : 1.1KV

    2 Over Voltage Factor : 1.2 Cont./1.9 for 8 Hrs.

    3 Transformation Ratio : 110 V/3 / 110/34 VA Burden/Phase : 15

    5 Accuracy Class : 3P

    6 No. of Phase : ONE

    7 Type : Epoxy Cast Resin Indoor Single Phase Voltage

  • 7/29/2019 spec for 33kv system

    13/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    13of27

    Transformer

    8 Formation : 3 nos. Single Phase P.T. shall be connected inprimary as Star and Secondary as Open Deltawith neutral of Primary and one end of OpenDelta earthed.

    C) PROTECTION OF 33 KV INDIVIDUAL & GROUP CONTROL TRANSFORMERSFor protection of H.V. Side of the Transformers, following main protective relays are required

    (i) Numerical O/C protection as per cl. 24.1(ii) 2 sets Restricted E/F Relay shall be provided for HV and LV side of individual control

    transformer panel.(iii) and 3 sets Restricted E/F Relay shall be provided for HV and 2 nos LV side of group

    control transformer panel.(iv) 1 set Differential Relay in addition to above, shall be provided for 10 MVA 33/11KV

    transformer panel.

    C-1 For protection of 10 MVA 33/11 KV Transformer, Differential Relay in addition to above protectionshall be provided:Differential shall be

    a) Provided at the HV side panel of the transformers to be protected. It shall be fully static or

    numerical/microprocessor based adjustable/variable percentage biased type differentialrelay.Necessary software, cables, connectors and other accessories as required for download,

    analyze data etc. shall be within the scope of successful bidder.b) The relay shall be very fast in operation with an operating time less than 30 millisecond at

    5 times setting.c) The relays shall be inherently stable for external through fault conditions without affecting

    the speed of operation for internal faults.

    d) The relay shall have either a built in facility of ratio and phase angle correction ornecessary interposing Auxiliary current transformers of universal type, shall be provided inthe respective panel.

    e) The relay shall be provided with 2nd harmonic restraint or any other inrush proof feature toprevent operation due to magnetizing in rush current when the transformer is charged eitherfrom HV or LV side. But this shall not affect the speed of operation for internal fault.

    f) It shall be provided with 5th harmonic restraint features to prevent operation due to

    possible over excitation of the transformer. This shall also not affect the speed of operationfor internal fault.

    g) The relay shall have adjustable bias setting range 20% to 50% and adjustable operatingsetting range of 10% to 50% at zero bias.

    h) It shall have three instantaneous high set over current units for clearing heavy internal fault.i) The relay shall be with 2-bias winding.j) The relay shall be such that there will not be any necessity of changing the setting of the

    relay whenever the transformer taps are changed.k) The bidder has to furnish the type test report from CPRI/NABL accredited; Govt. recognized

    Test House and performance certificate from Power Utilities in India.

    In case of numerical/ microprocessor based relays, necessary hardware and software fordownloading the data captured by disturbance recorder to the personal computer available in thesubstation shall be included in the scope.

    C-2 RESTRICTED EARTH FAULT PROTECTION :

    The above protection shall be provided 33/11 KV transformers at HV and LV side.The Relay shall be :

    a) Single pole type.b) Current/voltage operated high impedance type with a suitable setting to cover the

    maximum portion of transformer winding. Necessary calculation to prove theabove winding coverage shall be furnished along with the tender.

    c) tuned to the system frequency.d) have suitable nonlinear resistor to limit the peak voltage without detriment to the

  • 7/29/2019 spec for 33kv system

    14/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    14of27

    scheme.e) operating time shall be less than 20 ms.f) shall be standalone type.g) have suitable stabilizing resistor to prevent mal operation during external faults if

    necessary.

    C-3 A set of D.C. Voltage Operated Aux. Relays shall be provided for each Transformer for(a) Buchhoiz Alarm(b) Buchhoiz Trip(c) Winding Temp. Trip(d) Oil Temp. Alarm & Winding Temp. Alarm(e) Low Oil Level Alarm(f) Pressure Release Device Trip

    C-4 Each Transformer Panel shall be provided with a lockout Tripping Relay having sets of TripContacts & one set of Alarm Contacts. One set of Trip Contract shall be provided for inter-trippingcorresponding 11 KV Incoming Switchgear(s).

    D) AUXILIARY RELAYS, TRIP RELAYS and TRIP CIRCUIT SUPERVISION RELAYS

    D-1 Auxiliary Relays- D.C. Voltage operated auxiliary relays provided with mechanically operated handreset indicator and sufficient no of hand reset contacts shall be provided for protection and

    supervision against transformer internal trouble/faults. No of elements and number of relays shallbe as per requirement of individual trafo.

    D-2 For Trip Circuit Supervision Relays - All Panels should be provided with D.C. Voltage operated TripCircuit Supervision Relay having provisions for pre & post close supervision of Trip Circuit with set ofself-reset contacts provided for Trip Circuit Healthy Indication and Trip Circuit unhealthy indication& Alarm in respect of Trip Coils of respective Breakers.

    D-3 Tripping Relays- All Panels should be provided with D.C. Voltage operated High Speed TrippingRelays having self reset contacts capable to make, carry and break trip coil current. Sets of TripContacts shall be provided for Inter-tripping function of corresponding 11 KV Incoming Switchgearand closing blocking function of 33 KV & 11 KV Breakers in respect of Transformer Control Panels.Each set of trip relay shall have minimum two nos. NO and 1No. NC contact as SPARES. Theoperating time of master trip relay shall be less than 15 ms.

    D-5 All auxiliary relays, trip relays , trip circuit supervision relays etc. shall also be ofbidders own make,if not available, it can be M/s AREVA, M/s Easun Reyrolle/ABB MAKE.

    26 CO-ORDINATION WITH CIRCUIT BREAKER AND OTHER EQUIPMENT

    01 The Circuit Breakers, Transformers, Isolators, C.Ts, P.Ts, etc. will be purchased separately.Details of the Control Circuits closing and tripping currents etc. will be furnished to the successful

    bidder of the Panels. The Control Panel supplier shall have to supply the Control Panel Equipmentadequately matched for the duty which it is expected to perform. The supplier of the Control & RelayPanel shall have to prepare complete wiring diagram including the Control Circuit of the CircuitBreaker, Transformer, Isolator etc. as required. Wiring nos., bus wire nos. etc shall be in line withtender purpose drawing ( given along with tender doc.).However the drawings will be finalized during detailed engineering. If any additional equipment befound necessary for proper operation, match and co-ordination with the existing panel, the same shallalso to be provided by the bidder without any extra price.

    27 AUXILIARY A.C AND D.C. SUPPLYThe purchaser will make separate arrangement for providing low tension A.C. and D.C. supply. A.C.

    supply will be 230 + 5% Volts, Single Phase, 50 Cycles per Second or 400/230 + 5% Volts, 3-Phase: 4Wire as the case may be. D.C. supply will be 30 Volts.

    28 TENDER DRAWING & LITERATURE

    Triplicate copies of the following drawings and literature shall be submitted along with the Tenders:-(a) Principal dimension details of each unit cubicles, complete assembly of panel Board and

    proposed arrangement of the Panel Board in a Control Room.(b) Front and rear views of the Panel Board with instrument and device positions marked.(c) Pictorial views of the Control Switches Terminal Blocks, Indication Instruments, Test Blocks

  • 7/29/2019 spec for 33kv system

    15/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    15of27

    and exploded views of draw out type instructions and Fuse Blocks.(d) Schematic Wing Diagram for Test Terminal Block.(e) Illustrative, descriptive literature, General Technical Data & Specification of Devices.f) MAKE, TYPE , PARTICULARS, LITERATURES OF EACH AND EVERY RELAY( PROTECTIVE &

    AUXILIARY), METERS, ANNUNCIATORS, SWITCHES, LAMPS, TBS, TTBS ETC. ALONGWITH BILL OFMATERIAL IN LINE WITH TENDER SPECIFICATION.

    29 CONTRACT DRAWINGS & LITERATURE

    O1 In the event of an order materializing, the Supplier also submit four prints ofeach drawing for approval of the purchaser along with 2 sets of literature as mentioned in thespec.

    The Contract drawings shall cover the followings:-(a) Details of construction and dimensions of a cubicle and of the complete Panel Board.(b) Template for foundation and details of Cable Trench and Cable Entry Holes in the Foundation

    Platform.(c) Elementary diagrams of all controls, metering, protection annunciation and other circuits. All

    devices shall be numbered according to ASA or international usage, which shall be separatelycoded.

    (d) Cabling and wiring diagram of the cubicles and inter-connections between them. Ferrulenumbers, device number and grouping for cable take off shall be distinctly shown.

    (e) Dimensional outline drilling diagram and special mounting arrangement if any, of such type ofvarious devices on the Control Board.

    (f) Inter-connection diagram between Control Board and C.B. power and instrument transformeretc.

    (g) Wiring Schedule for Control & Relay Panel.(h) Internal wiring diagram of all devices and elementary wiring diagram of relays where internal

    wiring is in triplicate. Construction details of switches, terminal blocks and test blocks etc.After approval 10 sets of the final contract drawing for each set of Control & Relay Boards are tobe supplied by the contractor. One set reproducible tracing of the above drawings shall also besupplied.

    O2 In the event of contract being awarded 4 copies of the following literatures shallbe supplied along with the drawings as mentioned(a) Literature describing construction, operation, adjustment and rating specifications of all the

    protective and auxiliary relays, recording instruments, metering instruments and controlswitches.

    (b) Literature giving rating data, details and adjustments for calibration of the indicatinginstruments.

    (c) Calibration instruments for the metering instruments.(d) List of spare parts, identification number of renewable parts of relays, instruments and

    switches etc. with the help of which the purchaser will be able to procure spare parts fromthe contractor at any subsequent time.

    30. Type Test & Routine test Report and credential to be submitted along with tender documents:i) The bidder has to furnish the type test report, including functional tests for all protective

    relays from CPRI/NABL accredited, Govt. recognized Test House carried out within fiveyears .

    ii) routine test Report carried out within five years signed by any PSU, reputed power utilityetc. for similar type C&R panels ( with same type protective and auxiliary relays) alongwith tender documents

    iii) Credential for supply&delivery and performance certificate from Power Utilities inIndia(with same type protective and auxiliary relays) along with tender documents.

    31 TEST FACTORY

    The following tests shall be carried out and 6 copies of test certificates shall be submitted forapproval. The equipment shall only be dispatched after approval of the test certificates.

    1. Checking of wiring of Circuits and the continuity.2. One minute applied voltage test. All equipment on Panel and small Wiring shall be tested for

    a withstand voltage of 2000 Volts to earth & between different Voltage Circuits.3. Insulation resistance of the complete wiring, circuit by circuit with all equipment mounted on

    the Board before and after H.V. test mentioned under 2 above.4. Routine tests according to the relevant national standard are on the instruments, relays and

    other devices.

  • 7/29/2019 spec for 33kv system

    16/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    16of27

    32 TEST WITNESS(a) Tests shall be performed at ManufacturersWorks in presence of purchasers representative

    shall be carried out. The Supplier shall give at least 15 (fifteen) days advance notice of thedate when the tests are to be carried out.

    (b) Purchaser shall have the right to select any quantity of the itemwise offered lot for testing,offered for inspection and in the event of failure in test(s), the purchaser shall have the rightto reject the offered equipment(s).

    (c) All Relays, Meters & Annunciators provided in the Control & Relay Panel are to be acceptedonly after successful hundred percent performances testing at Testing Department ofWBSEDCL.

    33 SPARES:The tenderer shall quote item-wise Unit Prices for all type of relays and other consumable sparesrecommended by him for three years operation. Such spare shall include Fuse Holders, Fuses,Indicating Lamps, essential spare parts of Relays, Instrument, extra Control Switches etc.

    The price quoted for such items must be Firm and Nett.

    34 PRICEThe Price quoted by the tenderer for Control & Relay Board shall be FIRM.The Unit Price of items as per Annexure must be Firm. During detailed engineering, if it is found that

    some items are required to be incorporated in the Panels under procurement, the purchaser shall not

    pay any extra amount over the quoted Firm Price of these items for Control & Relay Boards.35 DELIVIERY & TRANSPORTATIONThe minimum delivery period offered by the tenderer shall be essence of this Tender.The Panel Board shall be delivered to different destination by Road Transport in suitable crateswithout instruments, relays & meters but with other devices mounted in positions and wired.Similarly instruments, relays, meters of the associated Panel Board shall be delivered by RoadTransport in separates crates to the Testing Laboratory of WBSEDCL as per Despatch Instruction.Each crate shall accompany detailed packing, list with mention of schedule of equipment/device indetails.TRANSPORTATIONThe panel board shall be transported in suitable crates without instruments, protective relays andmeters but other devices mounted in positions and wired. Instruments, protective relays, meters ofthe panel shall be separately crated and transported as per despatch instruction.

    Prior to dispatch three copies of detailed packing schedule of each panel board shall be submitted. In

    the schedule items accompanying the control panel and items separately crated shall be clearlymentioned.

    36 GUARANTEED TECHNICAL PARTICULARS:Tenderers shall furnish Guaranteed Technical Particulars of equipment offered mentioning thereonMake & Technical particulars of each device as per schedule specified. Performance Guarantee will bebased on the Guaranteed Technical Particulars.

    37 VALIDITY PERIOD:Validity period of the offer shall be reckoned from the date of Opening of Tender provided it istechnically and commercially complete one, otherwise it will be counted from the date of receipt ofcomplete information.

    38 PERFORMANCE CERTIFICATE;Copies of performance Certificate of similar equipment supplied to various Organizations shall have tobe furnished in triplicate along with the Tender.

    39 CREDENTIAL as Pre-requisites of Tenderer- shall furnish document in support of manufacture, supply

    and deliviery of similar supplied along with the Tender.

    40.0 Bus Configuration and Bill of material40.1 33/11KV and 66/11KV delta star individual control transformer panel having HV side control and

    protection. Single main bus with bus section isolator scheme.

    Two Circuit label engraved suitably at front and inner sideOne Section of painted and overlaid mimic diagram.One Circuit breaker control switch.Six Indicating lamps for circuit breaker ON/OFF, spring charged, trip circuit 1

    & 2 healthy and auto trip indication.

  • 7/29/2019 spec for 33kv system

    17/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    17of27

    Two Trip circuit supervision relay to supervise the TC 1 & 2 bothunder pre close and post close condition.

    Three 96 mm x 96 mm 2400 scale, moving coil taut band type ammeterscaled suitably.

    One Suitable space and wiring for non-tariff TVM for energymanagement.

    One Three phase 4 wire test terminal block for above.One Auxiliary relay with test push button for panel DC supervision

    relay.12 way Facia window type annunciator complete with accept reset and

    test PB but without audible bell.One Triple pole, IDMTL, non-directional over current relay with

    setting range 50% - 200% for IDMTL units and 500% - 2000% forhigh set unit.

    Two Restricted earth fault relay current operated having setting range10% - 40% both for HV side and LV side of the transformer.

    One High speed master tripping relay with contacts as required withlock out and coil supervision scheme complete.

    One set Two bias Transformer differential relay (for 10 MVA only) with Interposingauxiliary CTs (universal type) where ever necessary.

    One PT selector switch, Two position PT-1/PT-2 switch,stay put type.One Three element DC operated auxiliary relay with hand reset

    contacts for transformer Buchhlz trip and winding temp. tripfunction. Each element with 4NO+2NC Contact.

    One Three element DC operated auxiliary relay with hand resetcontacts for transformer Buchholz, winding and oil level low alarmfunction. Each element with 4NO+2NC Contact.

    One Space heater with On/OFF switch and thermostat.One DC operated emergency lamp with switch.One Cubicle illumination lamp operated from door switch.One 5A, 3 phase plug & socket with switch.One set Panel accessories as necessary.One set Other equipment, relays etc. as required to fulfill the scheme

    Requirement

    40.2 33/11KV and 66/11KV delta-star group control transformer panel having HV side control andprotection.The panel shall be equipped with the similar items stated above under Sl.No.40.1.01 with theadditional of the followings :

    One Two element DC operated auxiliary relay with hand reset contactsfor transformer Buchholz trip and winding trip function. Each element with4NO+2NC Contact.

    One Three element DC operated auxiliary relay with hand resetcontacts for transformer Buchholz, winding and low oil level alarm contact.Each element with 4NO+2NC Contact.

    One Restricted earth fault relay for LV side of the 2nd transformer.

    6 way Additional 6 way ( total 16/18 way) Facia

    40.3 33KV single feed line C&R Panel with Non directional O/C & E/F protection and 33KV parellel feederline C&R Panel with directional O/C & E/F protection. Single main bus with bus section isolator scheme.

    Two Circuit label engraved suitably at front and inner sideOne Section of painted and overlaid mimic diagram.One Circuit breaker control switch.Six Indicating lamps for circuit breaker ON/OFF, spring charged, trip circuit

    1 & 2 healthy and auto trip indication

  • 7/29/2019 spec for 33kv system

    18/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    18of27

    Two Trip circuit supervision relay to supervise the TC 1 & 2 both under pre closeand post close condition.

    Three 96 mm x 96 mm 2400 scale, moving coil taut band type ammeterscaled suitably.

    One Suitable space and wiring for non-tariff TVM for energymanagement.

    One Three phase 4 wire test terminal block for above.One Auxiliary relay with test push button for panel DC supervision relay.12 way Facia window type annunciator complete with accept reset and

    test PB but without audible bell.One Triple pole, IDMTL, non-dir- over current relay as per clause 24.1One Single pole definite time sensitive E/F relay current operated having wide

    setting range for single circuit line.

    One Triple pole, IDMTL, directional over current relay withsetting range 50% - 200% for IDMTL units and instanteneous high set unit

    -500% - 2000% applicable for parellel line feeder as per schedule

    one Single pole directional definite time sensitive E/F relay current operatedhaving wide setting range for single circuit line.NECESSARY IPTs ARE WITHIN THE SCOPE OF BIDDER

    One High speed master tripping relay with contacts as required withlock out and coil supervision scheme complete.

    One PT selector switch, Two position PT-1/PT-2 switch,stay put type.

    One Space heater with On/OFF switch and thermostat.One DC operated emergency lamp with switch.One Cubicle illumination lamp o9perated from door switch.One 5A, 3 phase plug & socket with switch.One set Panel accessories as necessary.One set Other equipment, relays etc. as required to fulfill the scheme

    Requirement40.4 Common items :( where ever mentioned)

    One 96 mm x 96 mm 2400 scale moving coil taut band type voltmeterscaled suitably.

    Six PT supply Indicating lamps, red-yellow-blue.One Voltmeter selector switch, 4-position, RYYBBROFF.One set Audible bell and hooter for trip and non-trip facia annunciation

    common for the entire C&R board.One AC operated single element, auxiliary relay having only self reset

    contacts and with reverse flag for incoming AC supplysupervision with test push button.

    One DC operated, two element, auxiliary relay having only self resetcontact and with reverse flag for incoming DC and alarm bus DCfail supervision.

    Two Test push button for above.One Single element AC operated auxiliary relay having self reset

    contact only for incoming DC and alarm bus DC fail alarmcancellation.

    One Push button for incoming DC and alarm bus DC fail alarmaccept.One Indicating lamp for incoming DC and Alarm bus DC fail

    indication.One AC operated buzzer for incoming DC and Alarm bus DC fail

    audible alarm.

    NOTE: THE BIDDERS MUST HAVE TO SUBMIT SEPARATE BILL OF MATERIAL FOR DIFFERENT TYPE OFPANELS WITH THE GUIDELINE AS MENTIONED ABOVE, FURNISHING THE TYPE AND MAKE OFEACH ITEM

  • 7/29/2019 spec for 33kv system

    19/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    19of27

    DETAILS OF RELAYS, METERS, EQUIPMENT& DEVICES AS OFFERED IN SCHEDULE OF 33 KV SIMPLEX TYPECONTROL AND RELAYS PANEL TO BE FILLED UP BY THE BIDDERS ALONGWITH SUBMISSION OF

    SUPPORTING DOCUMENTS

    Sl.No.

    Description Make AndCountry OfManufacture

    Type( Catalogueto beenclosed)

    Brief Description, withCT/PT details, contactconfiguration,Input/Output details,characteristics, range,suitability etc. for clearperspective.

    A SURFACE MOUNTING DEVICES

    1 Circuit Level

    2 Mimic Diagram

    3 Circuit Breaker Control Switch Springreturn lost motion type

    4 Ammeter 96 mm sq. 90 Deg Scale DualScale for C.T. Secondary rated Current 1AScale 0-100/0-200A Scale 0-200A / 0-400

    5 Voltmeter 96 mm Sq. 90 Deg Scale for P.T.

    Secondary 110 VAC (L/L) Scale 0-40 KV

    6 Voltmeter Selector Switch 6 way & off

    position having break before make contact

    7 Test Terminal block suitable for 3 phase 4wire system with wire rear connecting

    studs having provision of sealingarrangement

    8 Multi way micro processor basedElectronic Annunciator with building-system watchdog first fault indicationsand red & yellow coloured windows withinscription for Trip & Non Trip Alarm

    functions

    9 Indicating Lamps led type 63.5 VAC forP.T. Supply indication with coverRED/YELLOW/ BLUE Colours

    10 Indicating Lamp LED type 230 VAC forPanel D.C. Fail Common Indication withcover

    11 Indicating Lamp LED type 30 VDC for CBON/OFF Auto up Spring Charge Trip CircuitHealthy Indication with RED/GREEN/AMBER /BLUE Colours

    12 Push Button for Panel DC fail test

    13 Push Button for including AC fail test

    14 Push Button for non trip Panel DC failAlarm Accept

    15 Push Button for Annunciator Alarm Test /Mute/Accept Reset

    16 3 Element normal IDMTL over currentRelay with instantaneous high set unit

    17 Single Element Instantaneous sensitiveEarth Fault Relay with Timer

  • 7/29/2019 spec for 33kv system

    20/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    20of27

    Sl.No.

    Description Make AndCountry OfManufacture

    Type( Catalogueto beenclosed)

    Brief Description, withCT/PT details, contactconfiguration,Input/Output details,

    characteristics, range,suitability etc. for clearperspective.

    18 Triple Pole Directional Voltage polarizedOver Current Relay with DirectionalisedHigh Set Unit on all Element

    19 Single Pole Directional Voltage polarizedInstantaneous sensitive E/F Relay withtimer

    20 High Impedance Circulatory Currentbalance Instantaneous Restricted Each

    Fault Relay(a) HV side of Power Trf.(b) LV side of Power Trf.

    21 Single Element High Speed Tripping Relay

    with H/R Contact & H/R flag/indicationwith required numbers of contracts

    22 Two Element 30 V DC Voltage ActuatedAuxiliary Relay with HR Contacts &HR/LED Flag/indication for TransformerInternal Trouble functions(a) Buchholz Trip & Winding Temp. Tripfunction

    (b) Buchholz Non-Trip & Winding/OilTemp. Non-Trip Alarm function

    23 Two Element 30 V DC Voltage ActuatedAuxiliary Relay with HR Contacts & HR,Fag indication for

    (i) Transformer Low Oil Level Alarmfunction

    (ii) Pressure release Device Tripfunction

    24 Single Element 30V DC Voltage ActuatedAuxiliary Relay with self Reset Contact &Reverse Flag indication for Panel DCSupply fail function

    25 Single Element 230V AC Voltage ActuatedAuxiliary Relay with self Reset Contacts &Reverse Flag indication for incoming ACSupply fail function

    26 30 V DC Voltage operated Relay for TripCircuit supervision purpose with self reset

    contact27 Single Element 230V AC Voltage Actuated

    Auxiliary Relay with self Reset Contactswithout Flag indication for panel DC failAlarm, Accept

    28 Additional Involvement of Single Element30V DC Voltage Actuated Auxiliary Relaywith self Reset Contacts without Flag forLV side breaker closing blocking function

    for Transformers internal fault

  • 7/29/2019 spec for 33kv system

    21/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    21of27

    Sl.No.

    Description Make AndCountry OfManufacture

    Type( Catalogueto beenclosed)

    Brief Description, withCT/PT details, contactconfiguration,Input/Output details,

    characteristics, range,suitability etc. for clearperspective.

    29 Extra Involvement of Auxiliary Relay fornot having sufficient contacts to achieverequired functions

    30 Space & wiring for housing purchasersprojection mounting type Energy meter(not within the scope of bidder

    31 Common Electronic DC bell/Buzzer Trip &Non-Trip Alarm functions

    32 Common Electronic AC Ball for Panel DCfail Alarm functions

    33 Biased differential relay for 10 MVA Trf.Control & Relay Panel

    B Inside Mounting Devices

    1 230V AC Cubicle illuminating lamp with

    door operated Switch/Toggle Switch

    2 30V DC Emergency Lamp with ToggleSwitch

    3 230C AC 60W space heater withthermostat & Toggle Switch

    4 15A Double V AC Combined 2/3 pin plugand socket with Switch

    5 15A Double Pole MCB for Incoming ACSupply

    6 Fuse

    7 Links

    8 Board Terminals

    9 Earthing Arrangement

    10 Interposing P.T. for Directional Relay ifrequired

    11 Interposing Universal type CT forDifferential Relay if required

    Note: All surface mounting devices excepting Energy meter,TTB & Belts are flush mounting typeAs per Schedule requirement

    Seal and Signature of Bidder

    ANNEXURE-I

  • 7/29/2019 spec for 33kv system

    22/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    22of27

    Technical Specification for SCADA Compatible Numerical Directional And Non Directional Relays

    The offered item should meet minimum following requirements:-

    Sl. No Feature and Function Technical requirement

    1 Purpose and application It is intended to automate the Switchgears specified in the scope of supply and use

    Communicable Numeric relays for Protection, Control, Metering and Statusmonitoring. This specification is based on the understanding that an integrated

    Automation System along with protections shall be provided and same shall haveprovisions for Integration with SCADA system. All the feeders shall be remotecontrolled from Employers SCADA and from the local console of the numerical relays.

    Numerical multifunctional combined Microprocessor based Feeder protection andmanagement relay to protect the 33 kV Parallel Feeder from all electrical and otherfaults along with reporting system, Disturbance record for fault analysis. Bidder shouldcomply with any especial requirement or feature asked for retrofitting the relays.Relay should be IEC 61850 compliant. Relay should have 4 CT input for O/C and E/Fprotection 4 voltage input for directional O/C protection with internally derivedresidual voltage for E/F protection. There should be option for derivation of E/Finternally.

    2.(a) Main Protection Featurefor Directional O/C & E/Frelay.

    1. Relay should have minimum two group of setting. Setting group changeoverrequired from digital status input.2. Electrical over load protection with selectable IEC curves with two stage, first

    stage to be used as Definite Time / IDMT and second stage to be used ashigh set for short circuit protection.

    3. Earth fault protection in two stages with IEC characteristics. First stage to beused as IDMT/Definite Time and second stage to be used as instantaneouselements. Earth fault element should be suitable for both CBCT and residualtype CT connection.

    4. Negative phase sequence Protection with IEC Curves.5. CB Fail Protection & time settable as per user.6. The relay should be immune to DC switching while carrying current i.e. no

    spurious trip should be generated if relay DC is made On and Off7. The relay should conform to the IEC255-4 or BS 142 for Inverse time

    characteristics.8. VT fuse fail detection on NPS current/NPS Voltage based logic and blockingof under voltage protection by VT fuse fail detection.

    9. Three phase VT fuses fail detection on current based logic.10. The relay should have features to monitor for broken conductor and CB

    opening time.11. The relay shall be designed for application in WBSEDCLs distribution

    network where the system is non-effectively earthed through earthingtransformer at emanating 33 kV bus of 132/33 kV substation.

    2(b) Main Protection Featurefor non Directional O/C &E/F relay.

    1) Relay should have minimum two group of setting. Setting group changeoverrequired from digital status input.

    2) Electrical over load protection with selectable IEC curves with two stage, firststage to be used as Definite Time / IDMT and second stage to be used as

    high set for short circuit protection.3) Earth fault protection in two stages with IEC characteristics. First stage to beused as IDMT/Definite Time and second stage to be used as instantaneouselements. Earth fault element should be suitable for both CBCT and residualtype CT connection.

    4) Negative phase sequence Protection with IEC Curves.5) CB Fail Protection & time settable as per user.6) The relay should be immune to DC switching while carrying current i.e. no

    spurious trip should be generated if relay DC is made On and Off7) The relay should conform to the IEC255-4 or BS 142 for Inverse time

  • 7/29/2019 spec for 33kv system

    23/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    23of27

    characteristics.8) The relay should have features to monitor for broken conductor and CB

    opening time.9) The relay shall be designed for application in WBSEDCLs distribution network

    where the system is non-effectively earthed through earthing transformer atemanating 33 kV bus of 132/33 kV substation.

    3. Processor feature Relay shall be completely Numerical with protective elements having softwarealgorithm based on sampling of analog inputs. Sampling Rate of Analog Signal: Thesampling rate should be 1000 Hz for 50 Hz signal or better for each analog channel.Hardware based measurements shall not be acceptable.

    4. Operational Philosophy The operation of Relay shall be possible from both locally from the Switchgear andremote and Local Work station. The local position shall be displayed in remote / localworkstation and remote operation shall be blocked if the switch is in Local. Clearcontrol priorities shall prevent initiation of operation of a single switch at the sametime from more than one of the various control levels and there shall be interlocksamong various control levels. The priority shall always be with the lowest enabledcontrol level. Relay accuracy shall not be affected by system frequency fluctuation.

    5. Status/Optical

    Inputs/Digital inputs

    1. Minimum 8 number status inputs are required2. All status inputs should be 30 V to 110 VDC(site selectable)3. Setting group is required to be changed with any Digital input status.4. Trip circuit supervision with DI status5. The digital inputs shall be acquired by exception with 1ms resolution.

    Contact bouncing in digital inputs shall not be assumed as change of state.6. Relay should have comprehensive self diagnostic feature with remote

    indication of relay failure and alarm shall be generated without tripping ofcircuit

    7. Provision of Testing output relays without any current injection.8. No. of programmable LEDs- at least 4 nos. with latching option.

    6. Main measuring andreporting feature

    All measurements should be in primary quantities. Minimum following displays arerequired in alpha numeric:-

    1. Three phase (Positive sequence) current, Three phase voltage2. Neutral (zero sequence) current, MW, MVAR, Frequency, Pf, MVA etc.3. All the trips should have clear indication on the relay terminals4. Resetting should be selectable as hand reset or auto reset.

    7. Memory and RecordingFeature

    1. The relay setting and programming should be stored in EEPROM so thatduring Aux. Power failure the said data is not lost.

    2. Relay should have event log, trip log and DR record. All logs should go in tohistory.

    3. All tripping of relay should initiate DR in auto without extra binary input.Triggering of DR with binary input should be user configurable.

    4. The last 2 fault DR records should be in flash memory and DR will not erasein case of DC supply fail for more than 2 days.

    5. Should be able to record at least 5 Oscillographic disturbances and 5 faultrecords and 250 event records.

    6. Minimum Four no. of latest trip log with cause of trip should be stored inmemory along with date and time stamping. The memory should not be lostwith the switching off of DC.

    7. The relay should have fault-recording feature with current waveform andDigital Input status. The fault waveform should consist of minimum fourcurrent waveforms of three phase current and zero sequence current and DIstatus. Triggering time for Pre and Post should have user selectable. Thisrecord should be in flash memory for minimum 7 days even after switchingoff the DC supply.

    8. The fault should be date and time stamped.9. Communication protocol IEC 61850.

  • 7/29/2019 spec for 33kv system

    24/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    24of27

    10. The relay firmware shall be stored in flash memory and new firmware can bedownloaded by user. All flash software for downloading firmware shall beprovided at no extra cost.

    8. Auxilliary Supply 30 V to 110 VDC(site selectable) to - 25% to + 10%, 2 wire unearthed system.Necessary software shall be in-built for proper shutdown and restart in case of power

    failure. Auxilliary supply burden will be around 20Watt.9. Rated CT/PT secondary 5/1 Amp(site selectable) , CTs used to be protection class.

    3PT input rated 110 Volt (L-L)

    10. Rated frequency 50 HZ +/- 5%

    11. Ambient condition 1. Operating ambient temperature up to 55 Deg C2. Operating Humidity up to 100 %3. Relay shall meet the requirement for withstanding electromagnetic

    interference according to relevant parts of IEC 61850. Failure of singlecomponent within the equipment shall neither cause unwanted operation norlead to a complete system breakdown.

    12. Module and Mounting 1. Relay should be flush mounted type2. If module is draw out type then it should have CT shorting facility of make

    before break type.3. Mounting in C&R Panel/switchgears located in non AC rooms.4. Galvanic isolation between field connection and relay hardware should bethere.

    13. Watchdog and selfmonitoring

    The relay should have facility to monitor the healthiness of its circuits andcomponents by own monitoring system. In case of any problems, the alarm should begenerated by one of the output contacts. The alarm as soft signal to be sent toSCADA system as well. Necessary support documentation explaining the selfdiagnostic feature shall be furnished.

    14. Settings Approximate settings possible should be as follows:-1. Nominal Feeder current 2% to 110 %2. CT Ratio setting 10-1000(approx.)3. Earth fault current 1% to 40% with time delay IEC Curves, 2nd stage for

    instantaneous trip(less than 50 ms)4. Over current trip- 50% to 200% of 1/5 Amp with time delays as per IEC

    Curves.

    5. High set with delay 200% to 2000%6. IEC Curves for all O/C and E/F have user selectable.7. Selectable MTA for Directional features for O/C relay will be 30/45/60

    deg(Lag with respective phase voltage) and 45 deg(lag with internallyderived zero sequence voltage)

    15. Output Relays Minimum 7 number output relays are required out of which1. One potential free change over contact should be provided for start inhibit of

    relay.2. All o/p contact should be freely programmable.3. Atleast 4 nos. DPDT type contacts are required for close and open operation.

    Rest of the contacts may be changeover type.4. Rating of trip contacts:-

    a) Contact durability>10K operationb) 15 Amp make and carry for 3 sec for trip contactc) Make and carry for trip contacts L/R

  • 7/29/2019 spec for 33kv system

    25/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    25of27

    is to be issued for WBSEDCL, if required.

    4. Bidder has to supply communication hardware for relay setting, DRdownloading from front port. This device should be compatible toUSB/Ethernet port.

    5. It shall be possible to transfer the data stored in the DFR to computer onIEEE/COMTRADE format. The data format shall be compatible for dynamicprotection relay testing on relay test kit. COMTRADE Data viewer software isto be provided.

    6. Corporate license for installation on unlimited number of PCs.17. Date and time Date and Time stamping with faults and record. The clock should be powered from

    internal cell and should not required setting after every DC switching. The internal celllife minimum 5 years. Time synchronization by IRIG-B or SNTP. For timesynchronization through SNTP is to be provided from clock signal coming from RTU.In case of IRIG-B, time synchronization will be done with GPS clock signal from GPSreceiver located at substation.

    18. Lugs and terminators All CT and PT terminals shall be provided as fixed (screwed) type terminals on therelay to avoid any other any hazard due to loose connection leading to CT opening orany other loose connection. Necessary amount of lugs should be supplied along witheach relay for CT connection and control wiring.

    19. Manuals, Drawings andLiterature

    1. The relays should be supplied with manuals with all technical and operatinginstructions.2. All the internal drawings indicating the logics and block diagram details

    explaining principle of operation should be given at the time of supply.3. Mapping details shall be submitted in IEC format.

    20. Demonstration/assistance in commissioning

    Mounting-Retrofitting of relay will be carried out by WBSEDCL. The party shoulddepute competent technical person during commissioning at least to 30% location ofthe offered item. The sites may be across the state of West Bengal. Those sites are tobe commissioned with the assistance of Commissioning Engineer of the Bidder forwhich incidental charges is to be borne by the Bidder. He will explain various featuresof relay and assist for finalizing the settings, generation of *.icd files etc. As peravailability of shutdown of equipment, the commissioning may be done in differentphases. Bidder shall have to arrange for his boarding or lodging. This should beintegral part of the offer and the Bidder should include this in offer. 10% payment will

    be released only after successful completion of the above job. As part of this offer,Bidder shall have to provide necessary support during integration of relays with thethird party SCADA system which will be commissioned in future.

    21. Standarddocumentation perRelay, according to IEC61850

    1. MICS document (model implementation conformance statement)2. PICS(protocol implementation conformance statement3. Conformance Test certificate by KEMA4. ICD file5. SCD file6. PIXIT Document.

    22. Extendibility in Future The Bidder shall provide all necessary software tools along with source codes toperform addition of bays in future and complete integration with SCADA by theUser. These software tools shall be able to configure relay, add analog variable,alarm list, event list, modify interlocking logics etc. for additional bays/equipments which shall be added in future.

    23. Lifespan The supplier should mention following:-1. Product maturity: The Bidder should mention the time period for which the

    product is in the market2. Expected production life3. Hardware/Firmware change notification process. Upgrades to be provided

    free of cost within the warranty period, if needed.4. Lifespan of standard tools and processes for relay configuration, querying

    and integration

    24. Standards The relay should conform to the IEC255-5 or equivalent BS / ANSI for following:-

  • 7/29/2019 spec for 33kv system

    26/27

    TECHNICAL SPECIFICATION FOR 33KV CONTROL RELAY AND METERINGPANEL FOR WBSEDCL SYSTEM

    26of27

    1. Overload withstand test2. Dielectric withstand: 2kV in common, 1 kV in differential mode3. Impulse Voltage: 5kV in common, 1kV in differential mode4. Insulation resistance>100 Mohm5. Vibration: Shock and bump and Seismic6. Storing and transportation7. Radio Interference: IEC 61000 for high frequency disturbance, Transientdisturbance, Electrostatic discharge8. KEMA Certification for the particular model offered with respect to IEC61850

    Protocol

    25. Communication Port 1. Two nos. IEC 61850 protocol compliant Ethernet RJ45/F.O port forcommunication with SCADA system through two managed Ethernet Switchesoperating in redundant mode. The communication shall be made in 1+1mode between individual IED to Switch, such that failure of one set of LANshall not affect the normal operation of SCADA. However, it shall be alarmedin SCADA.

    2. Functioning of Relay shall not hamper to fault occurring any interconnectedrelay.

    3. One Front port Ethernet RJ45/USB 2.0 for relay parameterization andconfiguration etc. with the help of PC.

    4. Relay should generate GOOSE message as per IEC 61850 standard forinterlocking and also ensure interoperability with third party relays.26. Name Plate and marking Each IED shall be clearly marked with manufacturers Name, type, serial no.

    and electrical rating data. Name plates shall be made of anodized aluminiumwith white engrav